Manual Transmisores Yokogawa AJX PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 57

User’s

Manual EJX and EJA-E Series


Differential Pressure and
Pressure Transmitters
Installation Manual

IM 01C25A01-01E

Contents
1. Introduction
1.1 For Safe Use of Product...............................................2
1.2 Warranty.......................................................................4
1.3 ATEX Documentation...................................................5
2. Handling Cautions
2.1 Model and Specifications Check..................................7
2.2 Selecting the Installation Location...............................7
2.3 Pressure Connection...................................................7
2.4 Installation of an Explosion-Protected Instrument.......7
2.5 EMC Conformity Standards...................................... 27
2.6 Pressure Equipment Directive (PED)....................... 28
2.7 Safety Requirement Standards................................. 29
3. Installation
3.1 Mounting................................................................... 30
3.2 Mounting the Diaphragm Seals.......................................30
3.3 Diaphragm Seals Installation Consideration............. 31
3.4 Mounting the Flushing Connection Ring................... 32
3.5 Affixing the Teflon Film.............................................. 33
3.6 Rotating Transmitter Section..................................... 34
3.7 Changing the Direction of Integral Indicator............. 34
4. Installing Impulse Piping
4.1 Impulse Piping Installation Precautions.................... 35
4.2 Impulse Piping Connection Examples...................... 37
4.3 Process Piping Installation Precautions (EJ115).38
5. Wiring
5.1 Wiring Precautions.................................................... 40
5.2 Connections of External Wiring to Terminal Box....... 40
5.3 Wiring........................................................................ 43
5.4 RTD Cable Connection (EJX910A/EJX930A).......... 45
5.5 Grounding................................................................. 47
5.6 Power Supply Voltage and Load Resistance............ 47
6. Operation
6.1 Preparation for Starting Operation............................ 48
6.2 Zero Point Adjustment............................................... 48
6.3 Local Parameter Setting........................................... 49
7. Errors and Countermeasures

IM 01C25A01-01E
12th Edition
<1. Introduction> 1

1. Introduction
This installation manual provides the basic guidelines [EJX series Communication Manual]
for installation and wiring procedures of the DPharp EJX Models Document No. Style
series and EJA-E series transmitters with BRAIN and DPharp HART 5/HART 7
HART protocols and is composed of the information IM 01C25T01-06EN —
Communication Type
extracted from the product users’ manuals as listed in DPharp FOUNDATION Fieldbus
IM 01C25T02-01E —
Table 1.1. It does not provide the information including Communication Type
wiring procedures of the transmitters with FOUNDATION DPharp BRAIN Communication
IM 01C25T03-01E —
Fieldbus, Profibus and Modbus protocols, product Type
DPharp PROFIBUS PA
specific functional specifications and explanations, IM 01C25T04-01EN —
Communication Type
operation, maintenance and trouble-shooting.
EJX910A and EJX930A HART
IM 01C25R02-01E —
For EJXC40A Digital Remote Sensor, as this Installation Communication Type
Manual does not cover the product, please refer to the EJX910A and EJX930A
IM 01C25R03-01E —
Fieldbus Communication Type
dedicated manual for EJXC40A.
EJX910A and EJX930A Modbus
IM 01C25R05-01E —
Communication Type
WARNING
[EJA-E series Hardware Manual]
To ensure correct and safe use of the instrument,
Models Document No. Style
obtain the manuals applicable to designated models EJA110E, EJA120E
and specifications as listed Table 1.1, read them EJA130E, EJA310E, EJA430E IM 01C25B01-01E S1
thoroughly and fully understand how to operate the and EJA440E
instrument before operating it. EJA210E IM 01C25C01-01E S1
EJA510E and EJA530E IM 01C25F01-01E S1
EJA118E and EJA438E IM 01C25H01-01E S1
Users’ manual for each product consists of a hardware
EJA115E IM 01C25K01-01E S1
manual describing installation, wiring, operation,
EJAC80E and EJAC50E IM 01C25W01-01EN —
maintenance and specification including detailed model
and suffix code information, and a communication
manual describing information specific to each [EJA-E series Communication Manual]
communication protocol type, including safety manual for Models Document No. Style
safety instrumented system. DPharp HART 5/HART 7
IM 01C25T01-06EN —
Communication Type
These manuals can be downloaded from the website DPharp FOUNDATION Fieldbus
of Yokogawa or purchased from the Yokogawa IM 01C25T02-01E —
Communication Type
representatives. DPharp BRAIN Communication
IM 01C25T03-01E —
Type
Website address: http://www.yokogawa.com/fld/
DPharp PROFIBUS PA
IM 01C25T04-01EN —
Communication Type

Table 1.1 PDF Manual List and Applicable Style Code Note: An exclusive User’s Manual might be attached for the
products whose suffix codes or optional codes contain
[EJX series Hardware Manual] code “Z”. Please read it along with the standard manuals.
Models Document No. Style
EJX110A S3
EJX120A S1
IM 01C25B01-01E
EJX130A, EJX310A, EJX430A
S2
and EJX440A
EJX210A IM 01C25C01-01E S2
EJX510A and EJX530A S2
IM 01C25F01-01E
EJX610A and EJX630A S1
EJX118A and EJX438A IM 01C25H01-01E S2
EJX115A IM 01C25K01-01E S1
EJX910A S2
IM 01C25R01-01E
EJX930A S1
EJXC80A and EJXC50A IM 01C25W01-01EN —
EJXC40A IM 01C25W05-01EN —

12th Edition: Feb. 2017 (YK) IM 01C25A01-01E


All Rights Reserved, Copyright © 2009, Yokogawa Electric Corporation
<1. Introduction> 2
 Regarding This Manual
IMPORTANT
• This manual should be passed on to the end user.
Indicates that operating the hardware or software in
• The contents of this manual are subject to change
this manner may damage it or lead to system failure.
without prior notice.
• All rights reserved. No part of this manual may be
reproduced in any form without Yokogawa’s written
permission. NOTE
• Yokogawa makes no warranty of any kind with regard
Draws attention to information essential for
to this manual, including, but not limited to, implied
understanding the operation and features.
warranty of merchantability and fitness for a particular
purpose.
Direct current
• If any question arises or errors are found, or if any
information is missing from this manual, please inform
the nearest Yokogawa sales office. Functional grounding terminal
• The specifications covered by this manual are limited
to those for the standard type under the specified Caution
model number break-down and do not cover custom- This symbol indicates that the operator must
made instruments. refer to an explanation in the user’s manual
in order to avoid the risk of injury or death of
• Please note that changes in the specifications,
personnel or damage to the instrument.
construction, or component parts of the instrument
may not immediately be reflected in this manual at
the time of change, provided that postponement of 1.1 For Safe Use of Product
revisions will not cause difficulty to the user from a
functional or performance standpoint. For the protection and safety of the operator and the
instrument or the system including the instrument, please
• Yokogawa assumes no responsibilities for this
be sure to follow the instructions on safety described
product except as stated in the warranty.
in this manual when handling this instrument. In case
• If the customer or any third party is harmed by the use the instrument is handled in contradiction to these
of this product, Yokogawa assumes no responsibility instructions, Yokogawa does not guarantee safety.
for any such harm owing to any defects in the product Please give your attention to the followings.
which were not predictable, or for any indirect
damages. (a) Installation
• When describing the model name like EJ110
in this manual, it shows the applicability for both
EJX110A and EJA110E. The same representations WARNING
are used for the other models, too.
• The instrument must be installed by an expert
• The following safety symbol marks are used in this engineer or a skilled personnel. The procedures
manual: described about INSTALLATION are not permitted
for operators.
• In case of high process temperature, care should
WARNING be taken not to burn yourself because the surface
of body and case reaches a high temperature.
Indicates a potentially hazardous situation which, if not
• The instrument installed in the process is under
avoided, could result in death or serious injury.
pressure. Never loosen the process connector
bolts to avoid the dangerous spouting of process
fluid.
CAUTION • During draining condensate from the pressure
detector section, take appropriate care to avoid
Indicates a potentially hazardous situation which, if not contact with the skin, eyes or body, or inhalation
avoided, may result in minor or moderate injury. It may of vapors, if the accumulated process fluid may be
also be used to alert against unsafe practices. toxic or otherwise harmful.
• When removing the instrument from hazardous
processes, avoid contact with the fluid and the
interior of the meter.
• All installation shall comply with local installation
requirement and local electrical code.

IM 01C25A01-01E
<1. Introduction> 3
(b) Wiring (e) Explosion Protected Type Instrument

WARNING WARNING
• The instrument must be installed by an expert • Users of explosion proof instruments should refer
engineer or a skilled personnel. The procedures first to section 2.4 (Installation of an Explosion
described about WIRING are not permitted for Protected Instrument) of this manual.
operators. • For TIIS flameproof type instruments, be sure
• Please confirm that voltages between the power to read “INSTALLATION AND OPERATING
supply and the instrument before connecting the PRECAUTIONS FOR TIIS FLAMEPROOF
power cables and that the cables are not powered EQUIPMENT” at the end of this manual.
before connecting. • The use of this instrument is restricted to those
who have received appropriate training in the
device.
(c) Operation • Take care not to create sparks when accessing the
instrument or peripheral devices in a hazardous
location.
WARNING
• Wait 5 min. after power is turned off, before
(f) Modification
opening the covers.
• Do not open the cover in wet weather or humid
environment. If the cover is opened, stated WARNING
enclosure protection is not applicable.
• Yokogawa will not be liable for malfunctions or
damage resulting from any modification made to
(d) Maintenance this instrument by the customer.

WARNING (g) Product Disposal


• Please do not carry out except being written The instrument should be disposed of in accordance with
to maintenance descriptions. When these local and national legislation/regulations.
procedures are needed, please contact nearest
(h) Authorized Representative in EEA
YOKOGAWA office.
• Care should be taken to prevent the build up of In relation to the CE Marking, The authorized
drift, dust or other material on the display glass representative for this product in the EEA (European
and name plate. In case of its maintenance, soft Economic Area) is:
and dry cloth is used. Yokogawa Europe B.V.
Euroweg 2, 3825 HD Amersfoort,The Netherlands

IM 01C25A01-01E
<1. Introduction> 4
(i) Control of Pollution Caused by the Product
This is an explanation for the product based on “Control of Pollution caused by Electronic Information
Products” in the People’s Republic of China. The information is valid only in China.

有害物质或元素
产品中有 素的名称及含
含量
有害物质


型号 部件名称
称 铅 汞 镉 六价铬 铬 多溴联苯苯 多溴二苯醚醚
(P b) (Hg
g) (Cd)
) (Cr(VI))) (PBB) (PBDE)
壳体 × ○ ○ ○ ○ ○
EJX/E
EJA-E/ 膜盒组件
件 × ○ ○ ○ ○ ○
EJA/EJA
A-A Series
差压/压
压力变送器 基板组件
件 × ○ ○ × ○ ○
电源连接线
线 × ○ ○ ○ ○ ○
壳体 × ○ ○ ○ ○ ○
FVX
X110
基板组件
件 × ○ ○ × ○ ○
现场总线网
网段指示器
电源连接线
线 × ○ ○ ○ ○ ○
○:表
表示该部件的所
所有均质材料
料中的有害物质
质的含量均在
在 GB/T26572 标准中所规
规定的限量以下
下。

×:表
表示至少该部件
件的某些均质
质材料中的有害
害物质的含量
量均在 GB/T26
6572 标准中 所规定的限量
量以上。

环保使用期限:

识适用于 SJ /T
该标识 T11364 中所述
述,在中华人民共和国销售
售的电子电气
气产品的环保使
使用期限。

注)该
该年数为“环保
保使用期限” ,并非产品的质量保证期
期。

1.2 Warranty - Failure or damage due to improper handling, use


or storage which is out of design conditions.
• The warranty shall cover the period noted on the - Use of the product in question in a location
quotation presented to the purchaser at the time of not conforming to the standards specified by
purchase. Problems occurred during the warranty Yokogawa, or due to improper maintenance of the
period shall basically be repaired free of charge. installation location.
• In case of problems, the customer should contact the - Failure or damage due to modification or repair
Yokogawa representative from which the instrument by any party except Yokogawa or an approved
was purchased, or the nearest Yokogawa office. representative of Yokogawa.
- Malfunction or damage from improper relocation of
• If a problem arises with this instrument, please inform
the product in question after delivery.
us of the nature of the problem and the circumstances
- Reason of force majeure such as fires,
under which it developed, including the model
earthquakes, storms/floods, thunder/lightening,
specification and serial number. Any diagrams,
or other natural disasters, or disturbances, riots,
data and other information you can include in your
warfare, or radioactive contamination.
communication will also be helpful.
• Responsible party for repair cost for the problems  Trademarks:
shall be determined by Yokogawa based on our • ‘DPharp’, ‘EJX’, ‘EJA’, ‘FieldMate’ and ‘BRAIN
investigation. TERMINAL’ are registered trademarks of Yokogawa
• The Purchaser shall bear the responsibility for Electric Corporation. Company names and product
repair costs, even during the warranty period, if the names used in this material are registered trademarks
malfunction is due to: or trademarks of their respective owners.
• In this manual, trademarks or registered trademarks
- Improper and/or inadequate maintenance by the are not marked with ™ or ®.
purchaser.

IM 01C25A01-01E
<1. Introduction> 5
1.3 ATEX Documentation
This is only applicable to the countries in European Union.

GB SK

CZ
DK

I LT

E LV

EST
NL

PL

SF

SLO
P

BG

RO

S
M

GR

IM 01C25A01-01E
<2. Handling Cautions> 6

2. Handling Cautions
When the transmitter is delivered, visually check them EJ110 B
to make sure that no damage occurred during shipment. EJ120 1 D
Also check that all transmitter mounting hardware shown EJ130 2 G
-   - 
EJ310 3 J
in Figure 2.1 is included. If the transmitter was ordered
EJ430 4 K
without the mounting bracket or without the process EJ440 M
connector, the transmitter mounting hardware is not
included. 1
B
2
Table 2.1 Applicable Model Code for Mounting 1 D
3
Hardware EJX910A 2 G
4
-   -  J
EJX930A 3
Applicable B
Suffix code Part name Qty 4 K
model C
M
D
EJ110 Process connector bolt 4
1
EJ120 Process Process connector 2
2
EJ130 connections EJ210 -   - 
Process connector 3
EJX910A 1,2,3 and 4 2
gasket 4
EJX930A
EJ510
EJ210 Process connector bolt 2
Process EJ530 F
EJ310 Process connector 1 -  - 
connections EJX610A L
EJ430 Process connector EJX630A
1,2,3 and 4 1
EJ440 gasket
EJ110 EJ118 B
-  - 
EJ120 U-bolt 1 EJ438 J
EJ130
EJ310 B
U-bolt nut 2 D
EJ430 Mounting bracket EJ115 -  - 
EJ440 B,D,G,J,K and J
EJ118 M* Mounting bracket K
1
EJ438 (L or flat type) F0201.ai

EJ115
EJX910A Transmitter mounting Cable gland and RTD cable
4 (EJX910A and EJX930A only)
EJX930A bolt

Mounting U-bolt 1 Bolt


bracket M (For U-bolt nut 2 Process connector
EJ110 measurement Mounting bracket 1 Process connector
span code other Transmitter mounting Gasket
than F) 2
bolt U-bolt
EJ510 U-bolt (L and S) 1 ea.
EJ530 Mounting bracket U-bolt nut (L and S) 2 ea.
EJX610A F and L
EJX630A Mounting bracket 1

External Mounting bracket


temperature input (Flat type)
B, C and D RTD cable 1
EJX910A Mounting bracket
EJX930A External (L type)
temperature input U-bolt nut
Cable gland 2 Transmitter mounting bolt
1, 2, 3 and 4
Teflon film 1 U-bolt nut (L)
EJ210
Option code /TF1
EJ438 Fluorinated oil 1 Teflon film
Teflon film 2
EJ118 Option code /TF1
Fluorinated oil 2 Fluorinated oil
*: For measurement span code F.
Mounting bracket

U-bolt nut (S)

U-bolt (S)

U-bolt (L)
F0202.ai

Figure 2.1 Transmitter Mounting Hardware

IM 01C25A01-01E
<2. Handling Cautions> 7
2.1 Model and Specifications 2.3 Pressure Connection
Check
The model name and specifications are indicated on the WARNING
name plate attached to the case.
• Never loosen the process connector bolts when an
instrument is installed in a process. The device is
under pressure, and a loss of seal can result in a
sudden and uncontrolled release of process fluid.
• When draining toxic process fluids that have
condensed inside the pressure detector, take
appropriate steps to prevent the contact of such
fluids with the skin or eyes and the inhalation of
vapors from these fluids.

The following precautions must be observed in order to


F0203.ai
safely operate the transmitter under pressure.
Figure 2.2 Name Plate
(a) Make sure that the process connector bolts are
tightened firmly.
2.2 Selecting the Installation (b) Make sure that there are no leaks in the impulse
Location piping.
(c) Never apply a pressure higher than the specified
The transmitter is designed to withstand severe maximum working pressure.
environmental conditions. However, to ensure that it will
provide years of stable and accurate performance, take
the following precautions when selecting the installation 2.4 Installation of an Explosion-
location. Protected Instrument
(a) Ambient Temperature If a customer makes a repair or modification to an
Avoid locations subject to wide temperature variations intrinsically safe or explosionproof instrument and the
or a significant temperature gradient. If the location is instrument is not restored to its original condition, its
exposed to radiant heat from plant equipment, provide intrinsically safe or explosionproof construction may be
adequate thermal insulation and/or ventilation. compromised and the instrument may be hazardous to
(b) Ambient Atmosphere operate. Please contact Yokogawa before making any
Do not install the transmitter in a corrosive repair or modification to an instrument.
atmosphere. If this cannot be avoided, there must be
adequate ventilation as well as measures to prevent CAUTION
the leaking of rain water and the presence of standing
water in the conduits. This instrument has been tested and certified as
being intrinsically safe or explosionproof. Please
(c) Shock and Vibration
note that severe restrictions apply to this instrument’s
Although the transmitter is designed to be relatively
construction, installation, external wiring, maintenance
resistant to shock and vibration, an installation site
and repair. A failure to abide by these restrictions could
should be selected where this is kept to a minimum.
make the instrument a hazard to operate.
(d) Installation of Explosion-protected Transmitters
An explosion-protected transmitters is certified for
installation in a hazardous area containing specific
gas types. See subsection 2.4 “Installation of an
WARNING
Explosion-Protected Instrument.”
Maintaining the safety of explosionproof equipment
requires great care during mounting, wiring, and
piping. Safety requirements also place restrictions on
maintenance and repair. Please read the following
sections very carefully.

IM 01C25A01-01E
<2. Handling Cautions> 8

WARNING
The range setting switch must not be used in a
hazardous area.

IMPORTANT
For combined approval types
Once a device of multiple approval type is installed,
it should not be re-installed using any other approval
types. Apply a permanent mark in the check box of
the selected approval type on the certification label on
the transmitter to distinguish it from unused approval
types.

2.4.1 FM Approval

a. FM Intrinsically Safe/Nonincendive for


HART/BRAIN Protocol Type (Except for
EJX90A)

Note 1. EJX/EJA-E Series pressure transmitters with


optional code /FS1 are applicable for use in
hazardous locations.
• Applicable Standard:
Class 3600:2011, Class 3610:2010,
Class 3611:2004, Class 3810:2005
ANSI/ISA-60079-0:2009, ANSI/ISA-60079-11:2009
NEMA 250:1991
• Rating
Intrinsically Safe for
Class I, II, III Division 1,
Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Nonincendive for
Class I, II, III Division 2
Groups A, B, C, D, F, G T4
Class I, Zone 2 Group IIC T4
• Ambient temperature: –60 to 60°C
• Enclosure: Type 4X
Note 2. Installation
Installation should be in accordance with Control
Drawing IFM022-A12.
Note 3. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Factory Mutual Intrinsically safe and
Nonincendive Approval.

IM 01C25A01-01E
<2. Handling Cautions> 9
b. FM Intrinsically Safe/Nonincendive for
Fieldbus Type (Except for EJX90A)
EJX/EJA-E Series pressure transmitters with optional
code /FS15 are applicable for use in hazardous
locations.
Note 1.
• Applicable Standard:
Class 3600:2011, Class 3610:2010,
Class 3611:2004, Class 3810:2005
ANSI/ISA-60079-0:2009, ANSI/ISA-60079-11:2009
NEMA 250:1991
• Rating
Intrinsically Safe with Entity/FISCO for
Class I, II, III Division 1,
Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Nonincendive field wiring/FNICO for
Class I, II Division 2
Groups A, B, C, D, F, G T4
Class III Division 1 T4
Class I, Zone 2 Group IIC T4
• Ambient temperature: –40 to 60°C
• Enclosure: Type 4X
• Electrical Connection:
1/2 NPT female, M20 female
Note 2. Installation
Installation should be in accordance with Control
Drawing IFM024-A12.

IM 01C25A01-01E
<2. Handling Cautions> 10

c. FM Intrinsically Safe/Nonincendive for


Fieldbus Type for EJX90A
EJX multivariable transmitter with optional code
/FS15 are applicable for use in hazardous locations.
Note 1.
• Applicable Standard:
Class 3600:2011, Class 3610:2010,
Class 3611:2004, Class 3810:2005
ANSI/ISA-60079-0:2009, ANSI/ISA-60079-11:2009,
ANSI/ISA-60079-27:2006
NEMA 250:1991
• Rating
Intrinsically Safe with Entity/FISCO for Class I, II, III
Division 1 Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Nonincendive field wiring/FNICO for Class I, II
Division 2 Groups A, B, C, D, F, G T4
Class III Division 1 T4
Class I, Zone 2 Group IIC T4
• Ambient temperature: –40 to 60°C
• Enclosure: Type 4X
• Electrical Connection: 1/2 NPT female, M20
female
Note 2. Installation
Installation should be in accordance with Control
Drawing IFM026-A12.

IM 01C25A01-01E
<2. Handling Cautions> 11

IM 01C25A01-01E
<2. Handling Cautions> 12
d. FM Explosionproof
Caution for FM explosionproof type.
Note 1. EJX/EJA-E Series pressure transmitters with
optional code /FF1 or /V1F are applicable for
use in hazardous locations.
• Applicable Standard: FM3600, FM3615, FM3810,
ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups B, C
and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Enclosure: Type 4X
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
9 to 30 V dc, 250 mW (RS485 Modbus
Communication Type)
• Output signal: 4 to 20 mA
15 mA (FOUNDATION Fieldbus and PROFIBUS PA
type)
1 to 5 V (Low Power type)
RS485 Modbus (RS485 Modbus Communication
Type)
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NFPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY SEALED,
CONDUIT SEAL NOT REQUIRED.”
• Wiring connection for output signal code Q (Low
Power type) shall follow the diagram below.
Pressure Transmitters
SUPPLY +
Voltmeter
A Power Supply
+ +

– –

SUPPLY –

Three-Wire Connection
Pressure Transmitters
SUPPLY +
Voltmeter
A Power Supply
+ +

– –

SUPPLY –

Four-Wire Connection
F0218.ai

IM 01C25A01-01E
<2. Handling Cautions> 13
Note 3. Operation • Intrinsically Safe for Class I, Division 1, Groups
• Keep the “WARNING” nameplate attached to the A, B, C & D, Class II, Division 1, Groups E, F & G,
transmitter. Class III, Division 1
WARNING: OPEN CIRCUIT BEFORE • Nonincendive for Class I, Division 2, Groups A, B,
REMOVING COVER. FACTORY SEALED, C & D, Class II, Division 2, Groups F & G, Class III,
CONDUIT SEAL NOT REQUIRED. INSTALL IN Division 1
ACCORDANCE WITH THE USERS MANUAL IM • Enclosure: Type 4X
01C25. • Temp. Code: T4
• Take care not to generate mechanical sparking • Amb. Temp.: –50* to 60°C
when accessing to the instrument and peripheral * –15°C when /HE is specified.
devices in a hazardous location. • Process Temperature: 120°C max.
[For CSA E60079]
Note 4. Maintenance and Repair • Applicable Standard: CAN/CSA E60079-11,
• The instrument modification or parts replacement CAN/CSA E60079-15, IEC 60529:2001
by other than authorized representative of • Ex ia IIC T4, Ex nL IIC T4
Yokogawa Electric Corporation is prohibited and • Ambient Temperature: –50 to 60°C
will void Factory Mutual Explosionproof Approval. • Max. Process Temp.: 120°C
e. FM Intrinsically Safe and Explosion Proof • Enclosure: IP66/IP67
Combination for HART/BRAIN Protocol Note 2. Entity Parameters
Type • Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
EJX/EJA-E Series pressure transmitters with
Maximum Input Current (Imax/Ii) = 200 mA
optional code /FU1 or /V1U1 can be selected the
Maximum Input Power (Pmax/Pi) = 0.9 W
type of protection (FM Intrinsically Safe or FM
Maximum Internal Capacitance (Ci) = 10 nF
Explosionproof) for use in hazardous locations.
Maximum Internal Inductance (Li) = 0 µH
Note 1. For the installation of this transmitter, once a • Type "n" or Nonincendive ratings are as follows:
particular type of protection is selected, any Maximum Input Voltage (Vmax/Ui) = 30 V
other type of protection cannot be used. The Maximum Internal Capacitance (Ci) = 10 nF
installation must be in accordance with the Maximum Internal Inductance (Li) = 0 µH
description about the type of protection in this • Installation Requirements
instruction manual. Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Note 2. In order to avoid confusion, unnecessary Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
marking is crossed out on the label other Voc ≤ Vmax, Isc ≤ Imax,
than the selected type of protection when the Ca ≥ Ci + Ccable, La ≥ Li + Lcable
transmitter is installed. Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
2.4.2 CSA Certification
Note 3. Installation
• In any safety barreir used output current must
a. CSA Intrinsically Safe for HART/BRAIN
be limited by a resistor 'R' such that Io=Uo/R or
Protocol Type (Except for EJX90A)
Isc=Voc/R.
Caution for CSA Intrinsically safe and nonincendive • The safety barrier must be CSA certified.
type. (Following contents refer to “DOC No. ICS013- • Input voltage of the safety barrier must be less
A13”) than 250 Vrms/Vdc.
• Installation should be in accordance with Canadian
Note 1. EJX/EJA-E Series pressure transmitters with
Electrical Code Part I and Local Electrical Code.
optional code /CS1 are applicable for use in
• Dust-tight conduit seal must be used when
hazardous locations.
installed in Class II and III environments.
Certificate: 1606623
• The instrument modification or parts replacement
[For CSA C22.2]
by other than authorized representative of
• Applicable Standard: C22.2 No.0, C22.2 No.0.4,
Yokogawa Electric Corporation and Yokogawa
C22.2 No.25, C22.2 No.94, C22.2 No.157,
Corporation of America is prohibited and will
C22.2 No.213, C22.2 No.60079-0,
void Canadian Standards Intrinsically safe and
C22.2 No.61010-1 , C22.2 No.61010-2-030
nonincendive Certification.

IM 01C25A01-01E
<2. Handling Cautions> 14
[Intrinsically Safe]  Caution for CSA Intrinsically Safe Type.
Hazardous Location Nonhazardous Location (Following Contents Refer to “DOC. No.
Group IIC, Zone 0 ICS018)
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
General Installation Diagram for Intrinsically Safe
Purpose (Division 1 Installation)
Pressure Transmitters Safety Barrier Equipment
+ + + + Terminator
Supply – – – –
+ Pressure
– Transmitter
F0206.ai

+
[Nonincendive] – Field Instruments
Hazardous Location Nonhazardous Location
Group IIC, Zone 2
Class I, II, Division 2, +
CSA Certified – Field Instruments
Groups A, B, C, D, F, G Equipment
Class III, Division 1. ([nL] or
Pressure Transmitters nonincendive) Hazardous Location
+ + Non-Hazardous Location
Terminator
Supply – –
Not Use
Safety Barrier + –
F0207.ai
Safety Barrier
+ – F0229.ai

b. CSA Intrinsically Safe for Fieldbus Type


(Except for EJX90A) Note 1. The safety barrier must be CSA certified.

EJX/EJA-E Series pressure transmitters with optional Note 2. Input voltage of the safety barrier must be less
code /CS15 are applicable for use in hazardous than 250Vrms/Vdc.
locations.
Note 3. Installation should be in accordance with
• Certificate: 1689689
Canadian Electrical Code Part I and local
• Applicable standard: C22.2 No.0, C22.2 No.0.4,
Electrical Code.
C22.2 No.25, C22.2 No.94, C22.2 No.157,
C22.2 No.213, C22.2 No.61010-1, Note 4. Do not alter drawing without authorization from
C22.2 No.61010-2-030, C22.2 No.60079-0, CSA.
CAN/CSA E60079-0, CAN/CSA E60079-11,
Electrical Data:
CAN/CSA E60079-15, IEC 60529
• CSA Intrinsically Safe Approval • Rating 1 (Entity)
Class I, Division 1, Groups A, B, C, & D; Class II, For Groups A, B, C, D, E, F, and G or Group IIC
Division 1, Groups E, F & G; Class III; Ex ia IIC T4 Ui (vmax) = 24 V dc
Ambient Temperature: –40* to 60°C (–40* to Ii (Imax) = 250 mA
140°F) Encl. Type 4X, IP66/IP67 Pi (Pmax) = 1.2 W
* –15°C when /HE is specified. Ci = 3.52 nF
• CSA Nonincendive Approval Li = 0 μH
Class I, Division 2, Groups A, B, C, & D; Class II, or
Division 2, Groups F & G; Class III; Ex nL IIC T4 • Rating 2 (FISCO)
Ambient Temperature: –40* to 60°C (–40* to For Groups A, B, C, D, E, F, and G or Group IIC
140°F) Encl. Type 4X, IP66/ IP67 Ui (vmax) = 17.5 V dc
* –15°C when /HE is specified.
Ii (Imax) = 380 mA
Pi (Pmax) = 5.32 W
Ci = 3.52 nF
Li = 0 μH
or

IM 01C25A01-01E
<2. Handling Cautions> 15
• Rating 3 (FISCO) c. CSA Explosionproof Type
For Groups C, D, E, F, and G or Group IIB
Caution for CSA explosionproof type.
Ui (vmax) = 17.5 V dc
Ii (Imax) = 460 mA Note 1. EJX/EJA-E Series pressure transmitters with
Pi (Pmax) = 5.32 W optional code /CF1 or /V1F are applicable for
Ci = 3.52 nF use in hazardous locations.
Li = 0 μH • Certificate: 2014354
Installation requirements; • Applicable Standard: C22.2 No.0,
Po ≤ Pi Uo ≤ Ui Io ≤ Ii, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25,
Co ≥ Ci + Ccable Lo ≥ Li + Lcable C22.2 No.30, C22.2 No.94, C22.2 No.61010-1,
Vmax ≥ Voc Imax ≥ Isc C22.2 No.61010-2-030, C22.2 No.60079-0,
Ca ≥ Ci + Ccable La ≥ Li + Lcable C22.2 No.60079-1
Uo, Io, Po, Co, Lo,Voc, Isc, Ca and La are parameters • Explosion-proof for Class I, Groups B, C and D.
of barrier. • Dustignition-proof for Class II/III, Groups E, F and
G.
 Caution for CSA Non-incendive Type.
• Enclosure: Type 4X
(Following contents refer to “DOC. No. • Temperature Code: T6...T4
ICS018) • Ex d IIC T6...T4
Installation Diagram for Non-incendive or Type of • Enclosure: IP66/IP67
protection “n” (Division 2 Installation) • Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
Terminator • Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
+
SUPPLY * –15°C when /HE is specified.

Pressure • Supply Voltage: 42 V dc max.
Transmitter
32 V dc max. (FOUNDATION Fieldbus and
+
PROFIBUS PA type)
Transmitter 9 to 28 V dc, 27 mW (Low Power type)

9 to 30 V dc, 250 mW (RS485 Modbus
Communication Type)
• Output Signal: 4 to 20 mA dc
+

Transmitter 15 mA (FOUNDATION Fieldbus and PROFIBUS PA
type)
1 to 5 V (Low Power type)
Hazardous location
RS485 Modbus (RS485 Modbus Communication
Non-Hazardous location Type)
Terminator Note 2. Wiring
• All wiring shall comply with Canadian Electrical
+ – Code Part I and Local Electrical Codes.
CSA Certified • In hazardous location, wiring shall be in conduit as
Equipment [nL]
+ – shown in the figure.
• WARNING:
F0230.ai A SEAL SHALL BE INSTALLED WITHIN 50cm OF
THE ENCLOSURE.
Note 1. Installation should be in accordance with UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
Canadian Electrical Code Part I and local MOINS DE 50cm DU BOÎTIER.
Electrical Code. • WARNING:
Note 2. Dust-tight conduit seal must be used when WHEN INSTALLED IN CL.I, DIV 2, SEAL NOT
installed in class II and III environments. REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2, AUCUN
Note 3. Do not alter drawing without authorization from JOINT N'EST REQUIS.
CSA.

Electrical Data:
• Rating (including FNICO)
Ui or Vmax = 32 V
Ci = 3.52 nF
Li = 0 μH

IM 01C25A01-01E
<2. Handling Cautions> 16
Non-Hazardous Hazardous Locations Division 1 Note 3. Operation
Locations • WARNING:
Non-hazardous AFTER DE-ENERGIZING, DELAY 5 MINUTES
Location Equipment 50 cm Max.
BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5 MINUTES
AVANT D'OUVRIR.
42 V DC Max. Conduit • WARNING:
4 to 20 mA DC Sealing Fitting
Signal WHEN AMBIENT TEMPERATURE ≥ 65°C, USE
Transmitter THE HEAT-RESISTING CABLES ≥ 90°C.
F0208.ai
QUAND LA TEMPÉRATURE AMBIANTE ≥ 65°C,
Non-Hazardous Hazardous Locations Division 2 UTILISEZ DES CÂBLES RÉSISTANTES Á LA
Locations CHALEUR ≥ 90°C.
Non-hazardous • Take care not to generate mechanical sparking
Location Equipment
when accessing to the instrument and peripheral
devices in a hazardous location.
42 V DC Max. Note 4. Maintenance and Repair
4 to 20 mA DC Sealing Fitting • The instrument modification or parts replacement
Signal
Transmitter by other than authorized representative of
F0209.ai
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
• All wiring shall comply with local installation
Canadian Standards Explosionproof Certification.
requirements and local electrical code.
• In hazardous locations, the cable entry devices d. CSA Intrinsically Safe and Explosion-proof
shall be of a certified flameproof type, suitable for Combination for HART/BRAIN Protocol
the conditions of use and correctly installed. Type (Except for EJX90A)
• Unused apertures shall be closed with suitable
flameproof certified blanking elements. (The plug EJX/EJA-E Series pressure transmitters with
attached is flameproof certified.) optional code /CU1 or /V1U1 can be selected the
• Wiring connection for output signal code Q (Low type of protection (CSA Intrinsically Safe or CSA
Power type) shall follow the diagram below. Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter, once a
Pressure Transmitters
particular type of protection is selected, any
SUPPLY + other type of protection cannot be used. The
Voltmeter
A Power Supply installation must be in accordance with the
+ + description about the type of protection in this
instruction manual.
– –
Note 2. In order to avoid confusion, unnecessary
SUPPLY – marking is crossed out on the label other
Three-Wire Connection than the selected type of protection when the
Pressure Transmitters
transmitter is installed.

SUPPLY + 2.4.3 ATEX Certification


Voltmeter
A Power Supply
(1) Technical Data
+ +

– – a. ATEX Intrinsically Safe for HART/BRAIN


SUPPLY –
Protocol Type (Except for EJX90A)

Four-Wire Connection
Caution for ATEX Intrinsically safe type.
F0219.ai
Note 1. EJX/EJA-E Series pressure transmitters with
optional code /KS21 for potentially explosive
atmospheres.
• No. DEKRA 11ATEX0228 X
• Applicable Standard:
EN 60079-0:2012+A11:2013
EN 60079-11:2012

IM 01C25A01-01E
<2. Handling Cautions> 17
• Type of Protection and Marking code: Note 5. Special Conditions for Safe Use
Ex ia IIC T4 Ga
Ex ia IIIC T85 ºC T100 ºC T120 ºC Db
• Group: II
WARNING
• Category: 1G, 2D
• When the enclosure of the Pressure Transmitter
• Ambient Temperature for EPL Ga:
is made of aluminum, if it is mounted in an area
–50 to 60°C
where the use of category 1G equipment is
• Ambient Temperature for EPL Db:
required, it must be installed such, that, even in
–30* to 60°C
* –15°C when /HE is specified. the event of rare incidents, ignition sources due to
• Process Temperature (Tp.): 120°C max. impact and friction sparks are excluded.
• Maximum Surface Temperature for EPL Db: • Electrostatic charges on the coated parts of
T85°C (Tp.: 80°C) Pressure Transmitter shall be avoided.
T100°C (Tp.: 100°C) • Electrostatic charge may cause an exlosion
T120°C (Tp.: 120°C) hazard. Avoid any actions that cause the
• Enclosure: IP66 / IP67 generation of electrostatic charge, such as rubbing
To satisfy IP66 or IP67, apply waterproof glands to with a dry cloth on coating face of the product.
the electrical connection port. • In case of the enclosure of the Pressure
Transmitter with paint layers, if it is mounted in an
Note 2 Electrical Data area where the use of category 2D equipment is
• In type of explosion protection intrinsic safety Ex ia required, it shall be installed in such a way that the
IIC or Ex ia IIIC, only for connection to a certified risk from electrostatic discharges and propagating
intrinsically safe circuit with following maximum brush discharges caused by rapid flow of dust is
values: avoided.
Ui = 30 V
Ii = 200 mA
Pi = 0.9 W b. ATEX Intrinsically Safe for Fieldbus Type
(Linear Source) (Except for EJX90A)
Maximum internal capacitance; Ci = 27.6 nF
Maximum internal inductance; Li = 0 µH Caution for ATEX Intrinsically safe type.

When the lightning protector option is specified, Note 1. EJX/EJA-E series pressure transmitters with
the apparatus is not capable of withstanding the optional code /KS26 are applicable for use in
500V insulation test required by EN60079-11. This hazardous locations.
must be taken into account when installing the • No. KEMA 04ATEX1116 X
apparatus. • Applicable Standard:
EN 60079-0:2012+A11:2013
Note 3. Installation EN 60079-11:2012
• Refer to the control drawing. All wiring shall comply
with local installation requirements. Note 2. Ratings
Type of Protection and Marking Code:
[Control Drawing]
Ex ia IIC/IIB T4 Ga
Hazardous Location Nonhazardous Location Ex ia IIIC T85°C T100°C T120°C Db
Pressure Transmitters Group: II
+ + Category: 1G, 2D
Supply Safety Barrier *1 Ambient Temperature for EPL Ga: –40 to 60°C
– – Ambient Temperature for EPL Db: –30* to 60°C
* –15°C when /HE is specified.
Maximum Process Temperature (Tp.): 120°C
Maximum Surface Temperature for EPL Db.
F0210.ai T85°C (Tp.: 80°C)
*1: Any safety barriers must be a linear power source T100°C (Tp.: 100°C)
whose output current is resistively limited. T120°C (Tp.: 120°C)
Ambient Humidity:
Note 4. Maintenance and Repair
0 to 100% (No condensation)
• The instrument modification or parts replacement
Degree of Protection of the Enclosure:
by other than authorized representative of
IP66 / IP67
Yokogawa Electric Corporation is prohibited and
will void DEKRA Intrinsically safe Certification.

IM 01C25A01-01E
<2. Handling Cautions> 18
Electrical Data Note 6. Installation Instructions
• When combined with Trapezoidal and Rectangular [Installation Diagram]
output characteristic FISCO model IIC barrier
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W,
Terminator
Ci = 3.52 nF, Li = 0 μH
• When combined with Linear characteristic barrier
+ Pressure
Ui = 24 V, Ii = 250 mA, Pi = 1.2 W, − SUPPLY Transmitter
Ci = 3.52 nF, Li = 0 μH
• When combined with Trapezoidal or Rectangular +
− Transmitter
output characteristic FISCO model IIB barrier
Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W,
Ci = 3.52 nF, Li = 0 μH
+ Transmitter

Note 3. Installation
• All wiring shall comply with local installation
Hazardous Location
requirements. (Refer to the installation diagram)
Non-Hazardous Location
Note 4. Maintenance and Repair Terminator
• The instrument modification or parts replacement
by other than authorized representative of + −
Yokogawa Electric Corporation is prohibited and Safety Barrier
will void DEKRA Intrinsically safe Certification. + − F0231.ai

Note 5. Special Conditions for Safe Use • In the rating 1(*1), the output current of the barrier
must be limited by a resistor ‘Ra’ such that Io = Uo/
Ra.
WARNING • In the rating 2(*2), the output of the barrier must be
the characteristics of the trapezoid or the rectangle
• In the case where the enclosure of the Pressure
and this transmitter can be connected to Fieldbus
Transmitter is made of aluminium, if it is mounted
equipment which are in according to the FISCO
in an area where the use of category 1 G
model.
apparatus is required, it must be installed such,
• The terminators may be built in by a barrier.
that even in the event of rare incidents, ignition
• More than one transmitter may be connected to
sources due to impact and friction sparks are
the power supply line.
excluded.
• The terminator and the safety barrier shall be
• Electrostatic charge may cause an explosion
certified.
hazard. Avoid any actions that cause the
Electrical data:
generation of electrostatic charge, such as rubbing
with a dry cloth on coating face of the product. Maximum Input Voltage Ui: 24 V
• In the case where the enclosure of the Pressure Maximum Input Current Ii: 250 mA
*1:
Transmitter is made of aluminum, if it is mounted in Maximum Input Power Pi: 1.2 W
Rating 1
an area where the use of category 2D apparatus is Maximum Internal Capacitance Ci: 3.52 nF
required, it shall be installed in such a way that the Maximum Internal Inductance Li: 0 μH
risk from electrostatic discharges and propagating or
brush discharges caused by rapid flow of dust is Maximum Input Voltage Ui: 17.5 V
avoided. Maximum Input Current Ii: 380 mA
• To satisfy IP66 or IP67, apply waterproof glands to Maximum Input Power Pi: 5.32 W
the electrical connection port. Maximum Internal Capacitance Ci: 3.52 nF
• When the lightning protector option is specified, Maximum Internal Inductance Li: 0 μH
*2:
the apparatus is not capable of withstanding the or
Rating 2
500V insulation test required by EN60079-11. Maximum Input Voltage Ui: 17.5 V
This must be taken into account when installing Maximum Input Current Ii: 460 mA
the apparatus. Maximum Input Power Pi: 5.32 W
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH

IM 01C25A01-01E
<2. Handling Cautions> 19
c. ATEX Intrinsically Safe for Fieldbus Type Note 4. Maintenance and Repair
for EJX90A • The instrument modification or parts replacement
by other than authorized representative of
Caution for ATEX Intrinsically safe type.
Yokogawa Electric Corporation is prohibited and
Note 1. EJX multivariable transmitter with optional will void DEKRA Intrinsically safe Certification.
code /KS26 are applicable for use in hazardous
Note 5. Special Conditions for Safe Use
locations:
• No. KEMA 06ATEX0278 X
• Applicable Standard: WARNING
EN 60079-0:2012+A11:2013
EN 60079-11:2012 • In the case where the enclosure of the Pressure
Transmitter is made of aluminium, if it is mounted
Note 2. Ratings
in an area where the use of category 1G apparatus
Type of Protection and Marking Code:
is required, it must be installed such, that even in
Ex ia IIC/IIB T4 Ga
the event of rare incidents, ignition sources due to
Ex ia IIIC T85°C T100°C T120°C Db
impact and friction sparks are excluded.
Group: II
• Electrostatic charge may cause an explosion
Category: 1G, 2D
hazard. Avoid any actions that cause the
Ambient Temperature for EPL Ga:
generation of electrostatic charge, such as rubbing
–40 to 60°C
with a dry cloth on coating face of the product.
Ambient Temperature for EPL Db:
• In the case where the enclosure of the Pressure
–30* to 60°C
* –15°C when /HE is specified.
Transmitter is made of aluminum, if it is mounted in
Maximum Process Temperature (Tp.): 120°C an area where the use of category 2D apparatus is
Maximum Surface Temperature for EPL Db. required, it shall be installed in such a way that the
T85°C (Tp.: 80°C) risk from electrostatic discharges and propagating
T100°C (Tp.: 100°C) brush discharges caused by rapid flow of dust is
T120°C (Tp.: 120°C) avoided.
Ambient Humidity: • To satisfy IP66 or IP67, apply waterproof glands to
0 to 100% (No condensation) the electrical connection port.
Degree of Protection of the Enclosure: • When the lightning protector option is specified,
IP66/IP67 the apparatus is not capable of withstanding the
Electrical Data 500V insulation test required by EN60079-11.
• When combined with Trapezoidal or Rectanglar This must be taken into account when installing
output characteristic FISCO model IIC barrier the apparatus.
[Supply circuit (terminals + and -)]
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W,
Note 6. Installation instructions
Ci = 3.52 nF, Li = 0 µH
[Installation Diagram]
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
Co = 4.8 µF, Lo = 100 mH Terminator RTD
• When combined with Linear characteristic barrier Pt100.3wire
[Supply circuit (terminals + and -)] + Pressure
− SUPPLY Transmitter
Ui = 24 V, Ii = 250 mA, Pi = 1.2 W,
Ci = 3.52 nF, Li = 0 µH
+
[Sensor circuit] − Transmitter
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
Co = 4.8 µF, Lo = 100 mH
• When combined with Trapezoidal or Rectanglar + Transmitter

output characteristic FISCO model IIB barrier
[Supply circuit (terminals + and -)]
Hazardous Location
Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W,
Ci = 3.52 nF, Li = 0 µH Non-Hazardous Location
Terminator
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
+ −
Co = 4.8 µF, Lo = 100 mH Safety Barrier
Note 3. Installation + − F0232.ai

• All wiring shall comply with local installation


requirements. (Refer to the installation diagram)

IM 01C25A01-01E
<2. Handling Cautions> 20
• In the rating 1(*1), the output current of the barrier • Category: 2G, 2D
must be limited by a resistor ‘Ra’ such that Io = Uo/ • Enclosure: IP66 / IP67
Ra. • Temperature Class for gas-poof:
• In the rating 2(*2), the output of the barrier must be T6, T5, and T4
the characteristics of the trapezoid or the rectangle • Ambient Temperature for gas-proof:
and this transmitter can be connected to Fieldbus –50 to 75°C (T6), –50 to 80°C (T5), and
equipment which are in according to the FISCO –50 to 75°C (T4)
model. • Process Temperature (Tp.) for gas-proof:
• The terminators may be built in by a barrier. –50 to 85°C (T6), –50 to 100°C (T5), and
• More than one transmitter may be connected to –50 to 120°C (T4)
the power supply line. • Maximum Surface Temperature for dust-proof:
• The terminator and the safety barrier shall be T85°C (Tamb.: –30* to 75°C, Tp.: –30* to 85°C)
certified. * –15°C when /HE is specified.
Electrical data: Note 2. Electrical Data
Supply circuit • Supply voltage: 42 V dc max.
Maximum Input Voltage Ui: 24 V 32 V dc max. (FOUNDATION Fieldbus and
Maximum Input Current Ii: 250 mA PROFIBUS PA type)
*1:
Maximum Input Power Pi: 1.2 W 9 to 28 V dc, 27 mW (Low Power type)
Rating 1
Maximum Internal Capacitance Ci: 3.52 nF 9 to 30 V dc, 250 mW (RS485 Modbus
Maximum Internal Inductance Li: 0 μH Communication Type)
or • Output signal: 4 to 20 mA
Maximum Input Voltage Ui: 17.5 V 15 mA (FOUNDATION Fieldbus and PROFIBUS PA
Maximum Input Current Ii: 380 mA type)
Maximum Input Power Pi: 5.32 W 1 to 5 V (Low Power type)
Maximum Internal Capacitance Ci: 3.52 nF RS485 Modbus (RS485 Modbus Communication
Maximum Internal Inductance Li: 0 μH Type)
*2:
or Note 3. Installation
Rating 2
Maximum Input Voltage Ui: 17.5 V • All wiring shall comply with local installation
Maximum Input Current Ii: 460 mA requirement.
Maximum Input Power Pi: 5.32 W • Cable glands, adapters and/or blanking elements
Maximum Internal Capacitance Ci: 3.52 nF with a suitable IP rating shall be of Ex d IIC/Ex tb
Maximum Internal Inductance Li: 0 μH IIIC certified by ATEX and shall be installed so as
to maintain the specific degree of protection (IP
Sensor circuit Code) of the equipment.
Maximum Output Voltage Uo: 7.63 V • Wiring connection for output signal code Q (Low
Maximum Output Current Io: 3.85 mA Power type) shall follow the diagram below.
Maximum Output Power Po: 0.008 W Pressure Transmitters
Maximum Internal Capacitance Co: 4.8 μF
SUPPLY +
Maximum Internal Inductance Lo: 100 mH Voltmeter
A Power Supply
• RTD sensor is prepared by the user. + +
The sensor signal line must suited a test voltage of
– –
500Vac.
SUPPLY –
d. ATEX Flameproof Type
Three-Wire Connection
Caution for ATEX flameproof type.
Pressure Transmitters
Note 1. EJX/EJA-E Series pressure transmitters with
SUPPLY +
optional code /KF22 or /V1F are applicable for Voltmeter
use in hazardous locations. A Power Supply
• No. KEMA 07ATEX0109 X + +
• Applicable Standard:
– –
EN 60079-0:2012+A11:2013
EN 60079-1:2007, EN60079-31:2014 SUPPLY –
• Type of Protection and Marking Code:
Four-Wire Connection
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db F0220.ai

• Group: II

IM 01C25A01-01E
<2. Handling Cautions> 21
Note 4. Operation  ATEX Intrinsically Safe Ex ic
• Keep the “WARNING” label attached to the
Caution for ATEX intrinsically safe Ex ic
transmitter.
• Applicable Standard:
WARNING: AFTER DE-ENERGIZING, DELAY
EN 60079-0:2012+A11:2013
5 MINUTES BEFORE OPENING. WHEN THE
EN 60079-11:2012
AMBIENT TEMP.≥65°C, USE HEAT-RESISTING
• Type of Protection and Marking Code:
CABLE AND CABLE GLAND ≥90°C.
II 3G Ex ic IIC T4 Gc
• Take care not to generate mechanical sparking
• Ambient Temperature: –30* to +60°C
when accessing to the instrument and peripheral * –15°C when /HE is specified.
devices in a hazardous location. • Ambient Humidity:
Note 5. Specific Conditions of Use 0 to 100% (No condensation)
• Maximum Process Temperature: 120°C
• IP Code: IP66
WARNING • Ambient pollution degree: 2
• Overvoltage category: I
• Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the Note 1. Electrical Data
generation of electrostatic charge, such as rubbing Ui = 30 V
with a dry cloth on coating face of the product. Ci = 27.6 nF
• In the case where the enclosure of the Pressure Li = 0 µH
Transmitter is made of aluminium, if it is mounted Note 2. Installation
in an area where the use of category 2D apparatus • All wiring shall comply with local installation
is required, it shall be installed in such a way requirements. (refer to the control drawing)
that the risk from electrostatic discharges and • Cable glands, adapters and/or blanking elements
propagating brush discharges caused by rapid shall be of Ex “n”, Ex “e” or Ex “d” and shall be
flow of dust is avoided. installed so as to maintain the specified degree of
• The instrument modification or parts replacement protection (IP Code) of the transmitters.
by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and Note 3. Maintenance and Repair
will void the certification. • The instrument modification or parts replacement
• The fasteners used to fasten the transmitter by other than authorized representative of
enclosure onto the sensor capsule is special Yokogawa Electric Corporation is prohibited and
fastener, and the property class of it is will void ATEX intrinsically safe.
A2-50(A4-50) or more. [Control Drawing]

Hazardous Area Nonhazardous Area

e. ATEX Intrinsically Safe and ATEX


Pressure +
Flameproof Combination for HART/BRAIN Associated
Transmitters Apparatus
Protocol Type (Except for EJX90A) –

EJX/EJA-E Series pressure transmitters with optional


code /KU22 or /V1U1 can be selected the type of
protection ATEX Flameproof, Intrinsically Safe. Ex ia, F0212.ai

or Ex ic for use in hazardous area.


Note 4. Specific Conditions of Use
Note 1. For the installation of this transmitter, once a
particular type of protection is selected, any
other type of protection cannot be used. The WARNING
installation must be in accordance with the
• Electrostatic charge may cause an explosion
description about the type of protection in this
hazard. Avoid any actions that cause the
user’s manual.
generation of electrostatic charge, such as rubbing
Note 2. For combined approval types with a dry cloth on coating face of the product.
Once a device of multiple approval type is • When the lightning protector option is specified,
installed, it should not be re-installed using any the apparatus is not capable of withstanding the
other approval types. Apply a permanent mark 500V insulation test required by EN60079-11. This
in the check box of the selected approval type must be taken into account when installing the
on the certification label on the transmitter to apparatus.
distinguish it from unused approval types.

IM 01C25A01-01E
<2. Handling Cautions> 22
f. ATEX Intrinsically Safe Ex ic for Fieldbus Note 4. Specific Conditions of Use
Type (Except for EJX90A)
Caution for ATEX Intrinsically safe Ex ic. WARNING
EJX/EJA-E Series pressure transmitters with optional
code /KN26 are applicable for use in hazardous • Electrostatic charge may cause an explosion
locations. hazard. Avoid any actions that cause the
• Applicable Standard: gerenation of eletrostatic charge, such as rubbing
EN 60079-0:2012+A11:2013 with a dry cloth on coating face of the product.
EN 60079-11:2012 • When the lightning protector option is specified,
• Type of Protection and Marking Code: the apparatus is not capable of withstanding the
II 3G Ex ic IIC T4 Gc 500V insulation test required by EN60079-11. This
• Ambient Temperature: –30* to +60°C must be taken into account when installing the
* –15°C when /HE is specified. apparatus.
• Maximum Process Temperature: 120°C
• Ambient Humidity:
0 to 100% (No condensation) (2) Electrical Connection
• IP Code: IP66
A mark indicating the electrical connection type is
• Ambient pollution degree: 2
stamped near the electrical connection port. These
• Overvoltage category: I
marks are as followed.
Note 1. Electrical Data
Screw Size Marking
Ui = 32 V
Ci = 3.52 nF ISO M20 × 1.5 female M
Li = 0 µH ANSI 1/2 NPT female N or W
Note 2. Installation
• All wiring shall comply with local installation
requirements. (refer to the control drawing)
• When installing the transmitter in “ic” FISCO
system or FNICO system, follow the installation
requirements of each system. Location of the mark
• Cable glands, adapters and/or blanking elements
F0214.ai
shall be of Ex “n”, Ex “e” or Ex “d” and shall be
installed so as to maintain the specified degree of (3) Installation
protection (IP Code) of the transmitters.
Note 3. Maintenance and Repair
WARNING
• The instrument modification or parts replacement
by other than authorized representative of • All wiring shall comply with local installation
Yokogawa Electric Corporation is prohibited and requirements and the local electrical code.
will void ATEX intrinsically safe. • There is no need for conduit seal in Division 1
[Control Drawing] and Division 2 hazardous locations because this
Hazardous Area Nonhazardous Area product is sealed at the factory.

+
Associated
Transmitter
Apparatus (4) Operation

WARNING
F0233.ai
• OPEN CIRCUIT BEFORE REMOVING COVER.
• Above drawing shows the installation of Entity INSTALL IN ACCORDANCE WITH THIS USER’S
system. MANUAL
When installing the transmitters in “ic” FISCO • Take care not to generate mechanical sparking
system or FNICO system, follow the installation when access to the instrument and peripheral
requirements of each system. devices in a hazardous location.

IM 01C25A01-01E
<2. Handling Cautions> 23
(5) Maintenance and Repair  Tag plate for intrinsically safe Ex ia for Fieldbus
No. KEMA 04ATEX1116 X
Ex ia IIC/IIB T4 Ga Ta:-40 to 60°C

WARNING
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) to 60°C
MAX PROCESS TEMP.(Tp.):120°C
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Enclosure: IP66/IP67
FISCO field device(IIC/IIB)
Entity parameters Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0μH

The instrument modification or parts replacement by


other than an authorized Representative of Yokogawa *3 D

Electric Corporation is prohibited and will void the WARNING

certification.
POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

 Tag plate for intrinsically safe Ex ic for Fieldbus


(6) Name Plate Ex ic IIC T4 Gc
IP66
Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C
 Name plate Ui=32V, Ci=3.52nF, Li=0µH

WARNING

POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.

[EJX90A]
 Tag plate for flameproof type No. KEMA 07ATEX0109 X
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Enlcosure : IP66/IP67
 Tag plate for intrinsically safe Ex ia for Fieldbus
TEMP. CLASS T6 T5 T4
PROCESS TEMP.(Tp.) -50 TO 85 100 120 °C No. KEMA 06ATEX0278 X
Tamb. (for GAS) -50 TO 75 80 75 °C Ex ia IIC/IIB T4 Ga Ta: -40 to 60°C
T85°C(Tamb.: -30(-15) TO 75°C, Tp.:-30(-15) TO 85°C)(for Dust) Ex ia IIIC T85°C T100°C T120°C Db Ta: -30(-15) to 60°C
MAX PROCESS TEMP.(Tp.): 120°C
T85°C (Tp.: 80°C), T100°C (Tp.: 100°C), T120°C (Tp.: 120°C)
ENCLOSURE: IP66/IP67
Supply circuit
FISCO field device(IIC/IIB)
*3 D Entity Parameter Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µH
Sensor circuit
WARNING Uo=7.63V, Io=3.85mA, Po=0.008W, Co=4.8uF, Lo=100mH

*3
AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE
OPENING.
WHEN THE AMBIENT TEMP. ≥ 65°C, USE THE
HEAT-RESISTING CABLE & CABLE GLAND ≥ 90°C
POTENTIAL ELECTROSTATIC CHARGING HAZARD -SEE THE USER’S MANUAL

F0215-1.ai POTENTIAL ELECTROSTATIC CHARGING HAZARD-SEE USER'S MANUAL.

F0215-3.ai
[Except for EJX90A]
 Tag plate for intrinsically safe Ex ia for HART/BRAIN MODEL: Specified model code.
No. DEKRA 11ATEX 0228 X
Ex ia IIC T4 Ga Ta: -50 TO 60°C
STYLE: Style code.
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°C
IP66/IP67
MAX. PROCESS TEMP.(Tp.) 120°C
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
SUFFIX: Specified suffix code.
Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH
SUPPLY: Supply voltage.
OUTPUT: Output signal.
*3 D
MWP: Maximum working pressure.
WARNING
CAL RNG: Specified calibration range.
NO.: Serial number and year of production*1.
TOKYO 180-8750 JAPAN:
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
- SEE USER’S MANUAL

The manufacturer name and the address*2.


 Tag plate for intrinsically safe Ex ic for HART/BRAIN
Ex ic IIC T4 Gc
IP66
*1: The first number in the second block of “NO.” column
Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C
Ui=30V, Ci=27.6nF, Li=0µH
is the last one number of the production year.

WARNING
second block

POTENTIAL ELECTROSTATIC
NO. 91K819857 132 7
CHARGING HAZARD
- SEE USER’S MANUAL

F0215-2.ai The year 2011

*2: “180-8750” is a zip code which represents the


following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identification number of Notified Body.

IM 01C25A01-01E
<2. Handling Cautions> 24
2.4.4 IECEx Certification Note 3. Installation
• In any safety barrier used output current must be
Model EJX Series pressure transmitters with optional
limited by a resistor ‘R’ such that Io=Uz/R.
code /SU21 can be selected the type of protection
• The safety barrier must be IECEx certified.
(IECEx Intrinsically Safe Ex ia, Ex ic or flameproof) for
• Input voltage of the safety barrier must be less
use in hazardous locations.
than 250 Vrms/Vdc.
EJX Series pressure transmitters with optional code
/SS26 can be selected the type of protection (IECEx • The instrument modification or parts replacement
intrinsically safe Ex ia or Ex ic) for use in hazardous by other than authorized representative of
locations. Yokogawa Electric Corporation is prohibited and
EJX Series pressure transmitters with will void IECEx certification.
optional code /SU2 can be selected the type of [Ex ia]
protection (IECEx Intrinsically Safe/type n or Hazardous Location Nonhazardous Location
flameproof) for use in hazardous locations. Group IIC, Zone 0
Note 1. For the installation of this transmitter, once a EJX/EJA-E Series IECEx certified
particular type of protection is selected, any Pressure Transmitters Safety Barrier
other type of protection cannot be used. The + +
installation must be in accordance with the Supply – –
description about the type of protection in this
instruction manual.
(*1)
Note 2. For combined approval types, once a device of
*1: When using non isolation barrier,
multiple approval type is installed, it should not connect (*1) to IS barrier system. F0236.ai
be re-installed using any other approval types.
Apply a permanent mark in the check box of the Note 4. Specific Condition of Use
selected approval type on the certification label
on the transmitter to distinguish it from unused
approval types.
WARNING
a. IECEx Intrinsically Safe Ex ia for HART/ • Electrostatic charge may cause an explosion
BRAIN Protocol Type (Except for EJX90A) hazard. Avoid any actions that cause the
generation of electrostatic charge, such as rubbing
Caution for IECEx Intrinsically safe Ex ia. with a dry cloth on coating face of the product.
Note 1. EJX/EJA-E series pressure transmitters with • When the enclosure of the pressure transmitter
optional code /SU21 are applicable for use in is made of aluminum, if it is mounted in an area
hazardous locations where the use of EPL Ga equipment is required, it
• No. IECEx DEK 11.0081X must be installed such, that, even in the event of
• Applicable Standard: IEC 60079-0:2011, rare incidents, ignition sources due to impact and
IEC 60079-11:2011 friction sparks are excluded.
• Ex ia IIC T4 Ga • Electrostatic charges on the coated parts of
• Ambient Temperature: –50 to 60°C Pressure Transmitter shall be avoided.
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
To satisfy IP66 or IP67, apply waterproof glands to b. IECEx Intrinsically Safe Ex ic for HART/
the electrical connection port. BRAIN Protocol Type (Except for EJX90A)
Note 2. Electrical Data Caution for IECEx Intrinsically safe Ex ic.
Maximum Input Voltage (Ui) = 30 V Note 1. EJX/EJA-E series pressure transmitters with
Maximum Input Current (Ii) = 200 mA optional code /SU21 are applicable for use in
Maximum Input Power (Pi) = 0.9 W (linear source) hazardous locations
Maximum Internal Capacitance (Ci) = 27.6 nF • No. IECEx DEK 13.0061X
Maximum Internal Inductance (Li) = 0 μH • Applicable Standard: IEC 60079-0:2011,
When the lightning protector option is specified, the IEC 60079-11:2011
apparatus is not capable of withstanding the 500V • Ex ic IIC T4 Gc
insulation test required by IEC60079-11. This must be • Ambient Temperature: –30* to 60°C
* -15 °C when /HE is specified.
taken into account when installing the apparatus.
• Max. Process Temp.: 120°C
• IP Code: IP66
• Overvoltage Category: I

IM 01C25A01-01E
<2. Handling Cautions> 25
Note 2. Electrical Data Note 2. Electrical Data
Maximum Input Voltage (Ui) = 30 V • Intrinsically safe ratings are as follows:
Maximum Internal Capacitance (Ci) = 27.6 nF [Entity]
Maximum Internal Inductance (Li) = 0 μH Maximum Input Voltage (Ui) = 24 V
Maximum Input Current (Ii) = 250 mA
Note 3. Installation
Maximum Input Power (Pi) = 1.2 W
• The pressure transmitter is allowed to be installed
Maximum Internal Capacitance (Ci) = 3.52 nF
in “nL” systems, on condition that the output
Maximum Internal Inductance (Li) = 0 μH
parameters of “nL” source (associated energy-
[FISCO IIC]
limited apparatus) are suitable to the above
Maximum Input Voltage (Ui) = 17.5 V
mentioned input parameters of the pressure
Maximum Input Current (Ii) = 380 mA
transmitter and the cable parameters.
Maximum Input Power (Pi) = 5.32 W
• Cable glands, adapters and/or blanking elements
Maximum Internal Capacitance (Ci) = 3.52 nF
shall be of Ex “n”, Ex “e” or Ex “d” and shall be
Maximum Internal Inductance (Li) = 0 μH
installed so as to maintain the specified degree of
[FISCO IIB]
protection of the equipment.
Maximum Input Voltage (Ui) = 17.5 V
• The instrument modification or parts replacement
Maximum Input Current (Ii) = 460 mA
by other than authorized representative of
Maximum Input Power (Pi) = 5.32 W
Yokogawa Electric Corporation is prohibited and
Maximum Internal Capacitance (Ci) = 3.52 nF
will void IECEx certification.
Maximum Internal Inductance (Li) = 0 μH
[Ex ic]
Hazardous Location Nonhazardous Location Note 3. Installation
[Ex ia]
EJX/EJA-E Series Associated apparatus
Pressure Transmitters Terminator
+ +
Supply +
– – Pressure
– Transmitter

F0237.ai
+
– Field Instruments
Note 4. Specific Condition of Use

WARNING +
– Field Instruments

• Electrostatic charge may cause an explosion


Hazardous Location
hazard. Avoid any actions that cause the
Non-Hazardous Location
generation of electrostatic charge, such as rubbing Terminator
with a dry cloth on coating face of the product.
• The apparatus is not capable of dielectric strength + –
tests required by IEC 60079-11. Safety Barrier
This must be taken into account when installing + – F0238.ai

the apparatus.
• In the rating 1(*1), the output current of the barrier
must be limited by a resistor ‘Ra’ such that Io = Uo/
c. IECEx Intrinsically Safe Ex ia for Fieldbus Ra.
Type (Except for EJX90A) • In the rating 2(*2), the output of the barrier must be
Caution for IECEx Intrinsically safe Ex ia. the characteristics of the trapezoid or the rectangle
and this transmitter can be connected to Fieldbus
Note 1. EJX/EJA-E Series pressure transmitters with equipment which are in according to the FISCO
optional code /SS26 are applicable for use in model.
hazardous locations. • The terminators may be built in by a barrier.
• No. IECEx DEK 12.0016X • More than one transmitter may be connected to
• Applicable Standard: IEC 60079-0:2011, the power supply line.
IEC 60079-11:2011, IEC 60079-26: 2006 • The terminator and the safety barrier shall be
• Ex ia IIC/IIB T4 Ga certified.
• Ambient Temperature: –40 to 60°C
• Max. Process Temp.: 120°C

IM 01C25A01-01E
<2. Handling Cautions> 26
Electrical data: Note 2. Electrical Data
Maximum Input Voltage Ui: 24 V • Intrinsically safe ratings are as follows:
Maximum Input Current Ii: 250 mA Maximum Input Voltage (Ui) = 32 V
*1: Maximum Internal Capacitance (Ci) = 3.52 nF
Maximum Input Power Pi: 1.2 W
Rating 1 Maximum Internal Inductance (Li) = 0 μH
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH Note 3. Installation
or • The instrument modification or parts replacement
Maximum Input Voltage Ui: 17.5 V by other than authorized representative of
Maximum Input Current Ii: 380 mA Yokogawa Electric Corporation and will void IECEx
Maximum Input Power Pi: 5.32 W Intrinsically safe and type n certification.
Maximum Internal Capacitance Ci: 3.52 nF • The pressure transmitter is allowed to be installed
Maximum Internal Inductance Li: 0 μH in “nL” systems, on condition that the output
*2:
or parameters of “nL” source (associated energy-
Rating 2
Maximum Input Voltage Ui: 17.5 V limited apparatus) are suitable to the above
Maximum Input Current Ii: 460 mA mentioned input parameters of the pressure
Maximum Input Power Pi: 5.32 W transmitter and the cable parameters.
Maximum Internal Capacitance Ci: 3.52 nF • When installing the transmitter in “ic” FISCO
Maximum Internal Inductance Li: 0 μH system or FNICO system, follow the installation
requirements of each system.
Note 4. Specific Condition of Use • Cable glands, adapters and/or blanking elements
shall be of Ex “n”, Ex “e” or Ex “d” and shall be
WARNING installed so as to maintain the specified degree of
protection of the equipment.
• Electrostatic charge may cause an explosion • For multiple types of protection, the selected Ex
hazard. Avoid any actions that cause the marking on the marking plate shall be checked at
generation of electrostatic charge, such as rubbing the time of installation.
with a dry cloth on coating face of the product. [Ex ic]
• In the case where the enclosure of the pressure Hazardous Location Nonhazardous Location
transmitter is made of aluminum, if it is mounted
in an area where the use of EPL Ga equipment is EJX/EJA-E Series Associated apparatus
required, it shall be installed in such a way that , Pressure Transmitters
even in the event of rare incidents, ignition sources + +
due to impact and friction sparks are excluded. Supply
– –
• When the lightning protector option is specified,
the apparatus is not capable of withstanding the
F0237.ai
500 V insulation test required by IEC 60079-11.
This must be taken into account when installing • Above drawing shows the installation of entity
the apparatus. system. When installing the transmitter in “ic”
FISCO system or FNICO system, follow the
installation requirements of each system.
d. IECEx Intrinsically Safe Ex ic for Fieldbus Note 4. Specific Condition of Use
Type (Except for EJX90A)
Caution for IECEx Intrinsically safe Ex ic. WARNING
Note 1. EJX/EJA-E Series pressure transmitters with • Electrostatic charge may cause an explosion
optional code /SS26 are applicable for use in hazard. Avoid any actions that cause the
hazardous locations. generation of electrostatic charge, such as rubbing
• No. IECEx DEK 13.0064X with a dry cloth on coating face of the product.
• Applicable Standard: IEC 60079-0:2011, • When the lightning protector option is specified,
IEC 60079-11:2011 the apparatus is not capable of withstanding the
• Ex ic IIC T4 Gc 500 V insulation test required by IEC 60079-11.
• Ambient Temperature: –30* to 60°C This must be taken into account when installing
* -15 °C when /HE is specified.
the apparatus.
• Max. Process Temp.: 120°C
• IP Code: IP66
• Overvoltage Category: I

IM 01C25A01-01E
<2. Handling Cautions> 27
e. IECEx Flameproof Type Note 3. Operation
• WARNING:
Caution for IECEx flameproof type.
AFTER DE-ENERGIZING, DELAY 5 MINUTES
Note 1. EJX/EJA-E Series pressure transmitters with BEFORE OPENING.
optional code /SF2 or /SU21 are applicable for • WARNING:
use in hazardous locations: WHEN THE AMBIENT TEMP.≥65°C, USE HEAT-
• No. IECEx CSA 07.0008 RESISTING CABLE AND CABLE GLAND ≥90°C.
• Applicable Standard: IEC60079-0:2011, • Take care not to generate mechanical sparking
IEC60079-1:2007-4 when accessing to the instrument and peripheral
• Flameproof for Zone 1, Ex d IIC T6...T4 Gb devices in a hazardous location.
• Enclosure: IP66/IP67 • Electrostatic charge may cause an explosion
• Maximum Process Temperature: 120°C (T4), hazard. Avoid any actions that cause the
100°C (T5), 85°C (T6) generation of electrostatic charge, such as rubbing
• Ambient Temperature: –50 to 75°C (T4), with a dry cloth on coating face of the product.
–50 to 80°C (T5), –50 to 75°C (T6)
Note 4. Maintenance and Repair
• Supply Voltage: 42 V dc max.
• The instrument modification or parts replacement
32 V dc max. (FOUNDATION Fieldbus and
by other than authorized representative of
PROFIBUS PA type)
Yokogawa Electric Corporation is prohibited and
9 to 28 V dc, 27 mW (Low Power type)
will void IECEx Certification.
9 to 30 V dc, 250 mW (RS485 Modbus
• Electrical Connection
Communication Type)
A mark indicating the electrical connection type is
• Output Signal: 4 to 20 mA dc
stamped near the electrical connection port. These
15 mA (FOUNDATION Fieldbus and PROFIBUS PA
marks are as followed.
type)
1 to 5 V (Low Power type) Screw Size Marking
RS485 Modbus (RS485 Modbus Communication ISO M20 × 1.5 female M
Type)
ANSI 1/2 NPT female N or W
Note 2. Wiring
• In hazardous locations, the cable entry devices
shall be of a certified flameproof type, suitable for
the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable
flameproof certified blanking elements. Location of the mark
• Wiring connection for output signal code Q (Low
Power type) shall follow the diagram below. F0222.ai

Pressure Transmitters
SUPPLY +
A
Voltmeter 2.5 EMC Conformity Standards
Power Supply
+ + EN 61326-1 Class A, Table 2 (for use in industrial
locations)
– – EN 61326-2-3
SUPPLY –
EN 61326-2-5 (for Fieldbus)

Three-Wire Connection
Pressure Transmitters
CAUTION
SUPPLY + To meet EMC regulations, Yokogawa recommends
Voltmeter that customers run signal wiring through metal
A Power Supply
+ +
conduits or use shielded twisted-pair cabling when
installing EJX/EJA-E Series transmitters in a plant.
– –

SUPPLY –

Four-Wire Connection
F0221.ai

IM 01C25A01-01E
<2. Handling Cautions> 28
2.6 Pressure Equipment Model
Capsule PS*1
V(L)
PS.V
Category*2
code (bar) (bar.L)
Directive (PED) A, B, C 100 0.1 10 Article 4,
EJ510
Paragraph 3
EJX610A D 700 0.1 70
(1) General (SEP)
EJ510,
• EJX/EJA-E Series pressure transmitters are EJX610A
D 700 0.1 70 III
categorized as piping under the pressure accessories with code /
section of directive 2014/68/EU, which corresponds PE3
to Article 4, Paragraph 3 of PED, denoted as Sound A, B, C 100 0.1 10 Article 4,
EJ530,
Paragraph 3
Engineering Practice (SEP). EJX630A D 700 0.1 70 (SEP)
• EJX110A-MS, EJX110A-HS, EJ530,
EJX110A-VS, EJA110E with /HG, EJ130, EJX630A
D 700 0.1 70 III
EJ440, EJ510-D, EJ530-D, with code /
EJX610A-D, and EJX630A-D can be used above PE3
200 bar and therefore considered as a part of a L 160 0.01 1.6 Article 4,
EJX910A Paragraph 3
pressure retaining vessel where category III, Module M, H 250 0.01 2.5 (SEP)
H applies. These models with option code /PE3 EJX910A
conform to that category. with code / M, H 250 0.01 2.5 III
PE3
(2) Technical Data Article 4,
EJX930A M, H 500 0.01 5.0 Paragraph 3
• Models without /PE3 (SEP)
Article 4, Paragraph 3 of PED, denoted as Sound EJX930A
Engineering Practice (SEP). with code / M, H 500 0.01 5.0 III
• Models with /PE3 PE3
Module: H *1: PS is maximum pressure for vessel itself based on
Type of Equipment: Pressure Accessory-Vessel Pressure Equipment Directive 2014/68/EU. Refer to
General Specification for maximum working pressure of a
Type of fluid: Liquid and Gas
transmitter.
Group of fluid: 1 and 2 *2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 2014/68/EU.
Capsule PS*1 PS.V
Model V(L) Category*2
code (bar) (bar.L) (3) Operation
EJA110E M, H, V
160 0.01 1.6
EJ110 F, L
Article 4, CAUTION
EJX110A Paragraph 3
(SEP) • The temperature and pressure of fluid should
EJA110E M, H, V 250 0.01 2.5
with code be maintained at levels that are consistent with
/HG normal operating conditions.
EJ110 • The ambient temperature should be maintained
with code / M, H, V 250 0.01 2.5 III at a level that is consistent with normal operating
PE3
conditions.
Article 4,
• Please take care to prevent water hammer and the
EJ130 M, H 500 0.01 5.0 Paragraph 3
(SEP) like from inducing excessive pressures in pipes
EJ130 and valves. If phenomena are likely, install a safety
with code / M, H 500 0.01 5.0 III valve or take some other appropriate measure to
PE3 prevent pressure from exceeding PS.
Article 4, • Take appropriate measures at the device or
EJ310 L, M, A, B 160 0.01 1.6 Paragraph 3
(SEP) system level to protect transmitters if they are to be
Article 4, operated near an external heat source.
EJ430 H, A, B 160 0.01 1.6 Paragraph 3
(SEP)
Article 4,
EJ440 C, D 500 0.1 5.0 Paragraph 3
(SEP)
EJ440
with code / C, D 500 0.1 5.0 III
PE3

IM 01C25A01-01E
<2. Handling Cautions> 29
2.7 Safety Requirement
Standards
Applicable standard: EN 61010-1, EN 61010-2-30,
C22.2 No.61010-1, C22.2 No.61010-2-030

(1) Pollution Degree 2


"Pollution degree" describes the degree to which
a solid, liquid, or gas which deteriorates dielectric
strength or surface resistivity is adhering. " 2 " applies
to normal indoor atmosphere. Normally, only non-
conductive pollution occurs. Occasionally, however,
temporary conductivity caused by condensation must
be expected.

(2) Installation Category I


"Overvoltage category(Installation category)"
describes a number which defines a transient
overvoltage condition. It implies the regulation for
impulse withstand voltage. " I " applies to electrical
equipment which is supplied from the circuit when
appropriate transient overvoltage control means
(interfaces) are provided.

(3) Altitude of installation site:


Max. 2,000 m above sea level

(4) Indoor/Outdoor use

IM 01C25A01-01E
<3. Installation> 30

3. Installation
Vertical pipe mounting Vertical pipe mounting
IMPORTANT (Process connector upside) (Process connector downside)

• When welding piping during construction, take


care not to allow welding currents to flow through Mounting
the transmitter. bracket
• Do not step on this instrument after installation. 50 mm
(2-inch) pipe
• For EJ430, EJ440 and EJ438,
the atmospheric opening is located on the low U-bolt nut
U-bolt
pressure side cover flange. For EJ530 and
EJX630A whose capsule code is A, B, or C, the
pipe of the atmospheric opening is located on the Transmitter
pressure detecting section. These openings must mounting bolt
F0303.ai
not face upward.
Figure 3.3 Transmitter Mounting
(Vertical Impulse Piping Type)

Vertical pipe mounting Horizontal pipe mounting


Pipe
50 mm
(backside of the instrument) Zero-adjustment screw (2-inch) pipe
U-bolt nut (L)
Capsule code
 
6  F00301.ai

Figure 3.1 EJ530 and EJX630A Horizontal


Mounting Position
U-bolt
nut (S)
U-bolt (L)
Mounting
3.1 Mounting bracket U-bolt (S)
F0304.ai

■ The transmitter can be mounted on a nominal Figure 3.4 EJ510 and EJ530 Mounting
50 mm (2-inch) pipe using the mounting bracket
supplied, as shown in Figure 3.2 and 3.3. Tighten the
(four) bolts that hold the transmitter with a torque of
approximately 39 N·m {4 kgf·m}. 3.2 Mounting the Diaphragm Seals
IMPORTANT
Transmitter • Please use a gasket with an inside diameter (ød)
mounting bolt
that is greater than the diameter of the diaphragm
seal. If a gasket with a smaller inside diameter is
used, the diaphragm may not function correctly.
• During the diaphragm seal installation, ensure as
U-bolt nut far as possible that no seal liquid head pressure is
applied to the diaphragm seals.
Mounting bracket
U-bolt • Exercise care so as not to damage diaphragm
50 mm(2-inch) pipe surfaces. Since the diaphragm protrudes approx.
F0302.ai

Figure 3.2 Transmitter Mounting 1 mm from the flange surface, do not place the
(Horizontal Impulse Piping Type) pressure detector section face down on a surface
as this can damage the diaphragm.
• Do not sharply bend or twist capillary tube or apply
excessive stress to them.
• Never loosen the four bolts securing the cover
flange or the screws at the joints between the
capillary tube and cover flanges. If the seal liquid
leaks, the transmitter cannot be used.

IM 01C25A01-01E
<3. Installation> 31
3.2.1 EJ210 3.3 Diaphragm Seals Installation
The transmitter is mounted on a process using its Consideration
high pressure side flange as shown in Figure 3.5. The
customer should prepare the mating flange, gasket, stud IMPORTANT
bolts and nuts.
• When measuring the liquid level of the tank, the
minimum liquid level (zero point) must be set to a
Gasket level at least 50 mm above the center of the high
pressure side diaphragm seal (see Figure 3.7).
• Correctly install the diaphragm seals on the high
and low pressure sides of the process, checking
the label on each seal.
• To avoid measuring error duets temperature
Stud bolt
difference between the two diaphragm seals,
Nut F0305.ai capillary tube must be bound together. The
Figure 3.5 EJ210 Mounting capillary tube must be securely fixed to the tank
wall to prevent movement by wind or vibration.
If the capillary tube is too long, loosely coil the
3.2.2 EJ118 and EJ438 extra tube portion (coil diameter of 300 mm or
Mount the diaphragm seals using the flanges as shown in more) and secure the coiled tube with a clamp.
Figure 3.6. The mating flange, gasket, bolts and nuts are
to be procured by the customer. Low

Flange
IMPORTANT pressure
Nut side
Bolt Diaphragm Install the sealed diaphragm
so that the shank positions
downward.

ød Minimum
High liquid level
Gasket
pressure
The product is side 50 mm minimum
shipped with these Correctly install the diaphragm
parts assembled. seals on the high and low pressure
sides of the process (The label on
each diaphragm seal is marked
HIGH or LOW). F0306.ai The transmitter should
be installed as low as
Figure 3.6 Mounting the Diaphragm Seals
possible below the
position where the high
pressure side
diaphragm seal is
installed.
F0307.ai

Figure 3.7 Installing the Diaphragm Seals to a


Tank

IM 01C25A01-01E
<3. Installation> 32

Low pressure side


IMPORTANT
The transmitter should be installed at least 600 mm below
the high pressure (HP) process connection to ensure a P
positive head pressure of fill fluid. Pay special attention to h
High
vacuum applications. (+) pressure
side
If it can not be installed at least 600 mm below the HP
process connection, please use the equation below: 0

(P–P0) (–)
h= × 0.102 [mm]
ds

h: Vertical height between the HP process connection


and the transmitter (mm) F0308.ai

h≤0: Install the transmitter at least h (mm) below the Figure 3.8 Example of Installation to Tank
HP process connection (Caution on Installation)
h>0: Install the transmitter at most h (mm) above the
HP process connection
P: Pressure in the tank (Pa abs)
3.4 Mounting the Flushing
P0: Minimum working pressure limit of the transmitter (Pa
abs) See below table. Connection Ring
[For fill fluid code A, B, C, D, E]
Wetted parts Process connection size 3.4.1 Mounting to Pressure Detector
Capillary
material
length
code Section
code 2, 8 3 4,W
1 to 5m 6790 3190 The flushing connection ring is mounted to the pressure
SW
6 to 10m 10030 3520 detector section as shown in Figure 3.9.
1 to 5m 6790 3190 At the factory shipment, the flushing connection ring is
SE
6 to 10m 10030 3520
1 to 5m 3190 already assembled and attached to process detector
SY section.
6 to 10m 3520
1 to 5m 19150 6140
HW Pressure-detector section
6 to 10m 8290
1 to 5m 9620 3620
TW
6 to 10m 4210
1 to 5m 9540 4750 Ring
UW
6 to 10m 6050
[For fill fluid code 1, 2, 4]
Wetted parts Process connection size Spiral gasket
Capillary
material code
length Groove for
code 2, 8 3 4,W installing Ring holder
1 to 5m 2570 320 spiral gasket
SW
6 to 10m 4680 530
1 to 5m 2570 320 View from pressure Vent/Drain plug
SE detector section
6 to 10m 4680 530
1 to 5m 320 F0309.ai
SY
6 to 10m 530 Figure 3.9 Mounting to Pressure Detector Section
1 to 5m 10220 2050
HW
6 to 10m 3450
1 to 5m 4270 570 (1) Mount the ring holder on the ring and loosely tighten
TW
6 to 10m 960 the mounting screws.
ds: Specific gravity of fill fluid (at 25°C). See below table. (2) Place the spiral gasket in the ring groove. With the
ring correctly aligned and flush with the face of the
Fill fluid
A, 1, 4 B C, 2 D E pressure detector, securely tighten each ring holder’s
code
ds: Specific 1.90 to mounting screws.
1.07 0.94 1.09 1.09 (3) Position the ring so that the vent/drain plugs are
gravity 1.92
aligned straight up and down.

IM 01C25A01-01E
<3. Installation> 33
3.4.2 Mounting to Process Flange 3.5 Affixing the Teflon Film
Tighten the bolts to completely close the gap between the
ring and the pressure detector section. IMPORTANT
The mating flange, gasket, stud bolts and nuts are to
procured by the customer. The FEP Teflon option includes a teflon film and
fluorinated oil. Before mounting the transmitter to the
process flange, affix the teflon film as follows:

Spiral gasket 1) Position the diaphragm seal so that the diaphragm


Mating flange is in an upward position.
Ring 2) Pour the fluorinated oil on the diaphragm and
gasket area covering it completely and evenly. Be
careful not to scratch the diaphragm or change the
its shape.
3) Affix the teflon film over the diaphragm and gasket
area.
4) Next, carefully inspect the cover and try to identify
Diaphragm any entrapped air between the diaphragm and
Gasket Pressure-detector
the teflon film. The air must be removed to ensure
section optimum performance. If air pockets are present,
use your fingers to remove the air by starting at the
center of the diaphragm and work your way out.
5) Position the gasket on the Teflon film.
6) Mount the transmitter onto the process flange.

F0310.ai
Teflon film
Figure 3.10 Mounting to Process Flange PART No.
EJ210 F9347YD
2 inch EJ118
F9347YA
IMPORTANT EJ438
3 inch F9347XA
Fluorinated oil
• Confirm that there is no gap between the ring [PART No. : F9145YN]
and the process-detector section after they are Diaphragm
mounted on the process flange. A gap can lead to
a sudden, explosive release of process fluids. Gasket area
• When mounting or removing the ring, take care not F0311.ai
to tilt the pressure detector downward as the ring Figure 3.11 Affixing the Teflon Film
can slip off and cause injury.
• When re-mounting the ring, use the new spiral
gasket as shown in below table.

Table 3.1 Spiral Gasket for Pressure Detector


Section Side*
Part number Size Description
F9350SV ø100×ø120×t4.5 For 3-inch flange
F9970XF ø100×ø120×t4.5 For 3-inch flange**
F9350ST ø70×ø90×t4.5 For 2-inch flange
F9970XD ø70×ø90×t4.5 For 2-inch flange**
F9346ZH ø60×ø75×t4.5 For 1 1/2-inch flange
F9970XB ø60×ø75×t4.5 For 1 1/2-inch flange**
*: Material; 316SST (Hoop), PTFE Teflon (Filler)
**: For oil-prohibited use (Option code: /K1, /K2, /K5, /K6)

IM 01C25A01-01E
<3. Installation> 34
3.6 Rotating Transmitter Section 3.7 Changing the Direction of
The transmitter section can be rotated approximately Integral Indicator
360° (180° to either direction or 360° to one direction
from the original position at shipment, depending on the IMPORTANT
configuration of the instrument.) It can be fixed at any
angle within above range. Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area before
1) Remove the two setscrews that fasten the transmitter
disassembling and reassmbling an indicator.
section and capsule assembly, using the Allen
wrench.
An integral indicator can be installed in the following
2) Rotate the transmitter section slowly and stop it at
three directions.
designated position.
3) Tighten the two setscrews to a torque of 1.5 N·m.

IMPORTANT
Do not rotate the transmitter section more than the
F0313.ai
above limit.
Figure 3.13 Integral Indicator Direction
Vertical impulse piping type
IMPORTANT
Pressure-detector section
Stopper
The terminal box cover is locked by an Allen head
bolt (a shrouding bolt) on ATEX flameproof type
Rotate 0 to ±180° segments
transmitters. When the shrouding bolt is driven
clockwise by an Allen wrench, it is going in and cover
lock is released, and then the cover can be opened.
When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shrouding bolt
Conduit connection to a torque of 0.7 N·m.

1) Remove the cover.


Transmitter section
2) While supporting the integral indicator with one hand,
loosen its two mounting screws.
3) Dismount the LCD board assembly from the CPU
Horizontal impulse piping type
assembly. When doing this, carefully pull the LCD
board assembly straight forward so as not to damage
Transmitter section the connector pins between it and the CPU assembly.
Rotate 0 to ±180° segments 4) After rotating the LCD, align both the LCD board
assembly and CPU assembly connectors and engage
them.
5) Insert and tighten the two mounting screws.
6) Replace the cover.
Conduit connection
Zero-adjustment screw CPU assembly

Integral 90°
Pressure-detector section indicator 90°
F0312.ai

Figure 3.12 Rotating Transmitter Section


(Left Side High Pressure Type) LCD board assembly
Mounting screw

Amplifier cover
F0314.ai

Figure 3.14 Rotating Integral Indicator

IM 01C25A01-01E
<4. Installing Impulse Piping> 35

4. Installing Impulse Piping


4.1 Impulse Piping Installation (3) Tightening the Process Connector
Mounting Bolts
Precautions
After connecting an impulse line, tighten the process
The impulse piping that connects the process
connector mounting bolts uniformly.
outputs to the transmitter must convey the process
pressure accurately. If, for example, gas collects in (4) Removing the Impulse Piping Connecting
a liquid-filled impulse line, or the drain of a gas-filled Port Dustproof Cap
impulse line becomes plugged, it will not convey the
pressure accurately. Since this will cause errors in the The impulse piping connecting port on the transmitter is
measurement output, select the proper piping method covered with a plastic cap to keep out dust. This cap must
for the process fluid (gas, liquid, or steam). Pay careful be removed before connecting the line. (Be careful not
attention to the following points when routing the impulse to damage the threads when removing this cap. Never
piping and connecting the impulse piping to a transmitter. insert a screwdriver or other tool between the cap and
port threads to remove the cap.)
4.1.1 Connecting Impulse Piping to the
Transmitter (5) Connecting the Transmitter and 3-Valve
Manifold (for differential pressure
(1) Check the High and Low Pressure transmitters)
Connections on the Transmitter (Figure 4.1)
A 3-valve manifold consists of two stop valves to block
Symbols “H” and “L” have been placed on the capsule process pressure and an equalizing valve to equalize
assembly to indicate high and low pressure side. With
the pressures on the high and low pressure sides of the
differential pressure transmitters, connect the high
transmitter. Such a manifold makes it easier to disconnect
pressure side impulse line to the “H” side, and the low
pressure side impulse line to the “L” side. the transmitter from the impulse piping, and is convenient
when adjusting the transmitter zero point.
With gauge/absolute pressure transmitters, connect the
impulse line to the ‘H’ side. There are two 3-valve manifold typs: the pipe-mounting
type and the direct-mounting type; care should be taken
Differential Pressure Transmitter with respect to the following points when connecting the
manifold to the transmitter.
“H” and “L” are shown
Process
connection Process connection  Pipe-Mounting Type 3-Valve Manifold
Process connector
Impulse piping
Bolt F0401.ai Nipple
Vent plug 3-valve
Figure 4.1 “H” and “L” Symbols on a Capsule (optional)
Assembly manifold Ball head
Stop valve lock nut
(2) Changing the Process Connector Piping (low pressure side)
Pipe
Connections (for differential pressure Equalizing valve Pipes
transmitters) (balancing)
Ball head
The impulse piping connection distances can be changed
lock nut
between 51 mm, 54 mm and 57 mm by changing the Stop valve
orientation of the process connectors. (high pressure side) Nipple
This is convenient for aligning the impulse line with a Process
50 mm(2-inch) pipe
process connectors. Process connector
connector bolts
F0403.ai

Figure 4.3 3-Valve Manifold (Pipe-Mounting Type)

57 mm 54 mm 51 mm
F0402.ai

Figure 4.2 Process Connector Impulse Piping


Connection Distances

IM 01C25A01-01E
<4. Installing Impulse Piping> 36
1) Screw nipples into the connection ports on the 4.1.2 Routing the Impulse Piping
transmitter side of the 3-valve manifold, and into
the impulse piping connecting ports on the process (1) Process Pressure Tap Angles
connectors. (To maintain proper sealing, wind sealing
tape around the nipple threads.) If condensate, gas, sediment or other extraneous
2) Mount the 3-valve manifold on the 50 mm (2-inch) material in the process piping gets into the impulse
pipe by fastening a U-bolt to its mounting bracket. piping, pressure measurement errors may result. To
Tighten the U-bolt nuts only lightly at this time. prevent such problems, the process pressure taps must
3) Install the pipe assemblies between the 3-valve be angled as shown in Figure 4.5 according to the kind of
manifold and the process connectors and lightly fluid being measured.
tighten the ball head lock nuts. (The ball-shaped ends
of the pipes must be handled carefully, since they will NOTE
not seal properly if the ball surface is scratched or
otherwise damaged.) • If the process fluid is a gas, the taps must be
4) Now tighten the nuts and bolts securely in the vertical or within 45° either side of vertical.
following sequence: • If the process fluid is a liquid, the taps must be
Process connector bolts → transmitter-end ball head horizontal or below horizontal, but not more than
lock nuts → 3-valve manifold ball head lock nuts → 45° below horizontal.
3-valve manifold mounting bracket U-bolt nuts • If the process fluid is steam or other condensing
vapor, the taps must be horizontal or above
 Direct-Mounting Type 3-Valve Manifold horizontal, but not more than 45° above horizontal.
[Gas] [Liquid] [Steam]
1) Mount the 3-valve manifold on the transmitter. (When
Pressure 45° 45°
mounting, use the two gaskets and the four bolts
taps
provided with the 3-valve manifold. Tighten the bolts 45° 45°
evenly.)
Process 45° 45°
2) Mount the process connectors and gaskets on the top piping
of the 3-valve manifold (the side on which the impulse F0405.ai

piping will be connected.) Figure 4.5 Process Pressure Tap Angle


(For Horizontal Piping)
Bolts Impulse
piping
Process Stop valve
connector 3-valve
manifold
(2) Position of Process Pressure Taps and
Gasket Equalizing
valve
Transmitter
If condensate (or gas) accumulates in the impulse piping,
Stop valve it should be removed periodically by opening the drain
(or vent) plugs. However, this will generate a transient
disturbance in the pressure measurement, and therefore
it is necessary to position the taps and route the impulse
Equalizing valve
piping so that any extraneous liquid or gas generated in
Stop valve
the leadlines returns naturally to the process piping.
Impulse
piping • If the process fluid is a gas, then as a rule the
transmitter must be located higher than the process
Gasket Bolts
pressure taps.
Process Stop valve 3-valve
connector manifold • If the process fluid is a liquid or steam, then as a
F0404.ai rule the transmitter must be located lower than the
Figure 4.4 3-Valve Manifold (Direct-Mounting Type) process pressure taps.

(3) Impulse Piping Slope


NOTE The impulse piping must be routed with only an upward or
downward slope. Even for horizontal routing, the impulse
After completing the connection of the transmitter and piping should have a slope of at least 1/10 to prevent
3-valve manifold, be sure to CLOSE the low pressure condensate (or gases) from accumulating in the pipes.
and high pressure stop valves, OPEN the equalizing
valve, and leave the manifold with the equalizing valve
OPEN.
You must do this in order to avoid overloading the
transmitter from either the high or the low pressure
side when beginning operation.

IM 01C25A01-01E
<4. Installing Impulse Piping> 37
(4) Temperature Difference Between Impulse 4.2 Impulse Piping Connection
Piping (for differential pressure
transmitters)
Examples
Figure 4.6, 4.7, and 4.8 shows examples of typical
If there is a temperature difference between the high
impulse piping connections. Before connecting the
and low impulse lines, the density difference of the fluids
transmitter to the process, study the transmitter
in the two lines will cause an error in the measurement
installation location, the process piping layout, and
pressure. When measuring flow, impulse lines must be
the characteristics of the process fluid (corrosiveness,
routed together so that there is no temperature difference
toxicity, flammability, etc.), in order to make appropriate
between them.
changes and additions to the connection configurations.
(5) Condensate Pots for Steam Flow
Note the following points when referring to these piping
Measurement (for differential pressure examples.
transmitters)
• If the impulse line is long, bracing or supports should
If the liquid in the impulse piping repeatedly condenses be provided to prevent vibration.
or vaporizes as a result of changes in the ambient or • The impulse piping material used must be compatible
process temperature, this will cause a difference in the with the process pressure, temperature, and other
fluid head between the high pressure and low pressure conditions.
sides. To prevent measurement errors due to these head • A variety of process pressure tap valves (main valves)
differences, condensate pots are used when measuring are available according to the type of connection
steam flow. (flanged, screwed, welded), construction (globe, gate,
(6) Preventing Wind Speed Effects in Very Low or ball valve), temperature and pressure. Select the
Differential Pressure Measurement type of valve most appropriate for the application.
(for differential pressure transmitters)
Liguid Gas Steam

IMPORTANT Tap valve


Orifice Condensate pot
Union
When using a differential pressure transmitter to or flange
measure very low pressures (draft pressure), the low
pressure connection port is left open to atmospheric
pressure (the reference pressure).
Any wind around the differential pressure transmitter Tee
will therefore cause errors in the measurement. To
3-valve
prevent this, it will be necessary either to enclose the manifold
transmitter in a box, or to connect a impulse line to
the low pressure side and insert its end into a wind
excluding pot (cylindrical with a base plate). Drain valve
Drain plug
F0406.ai

(7) Preventing Freezing Figure 4.6 Impulse Piping Connection Examples


If there is any risk that the process fluid in the impulse (for differential pressure transmitters)
piping or transmitter could freeze, use a steam jacket or
heater to maintain the temperature of the fluid. Open Tank Closed Tank Tap valve
Union or flange

NOTE Vent plug

After completing the connections, close the valves on Tee


the process pressure taps (main valves), the valves at
the transmitter (stop valves), and the impulse piping
drain valves, so that condensate, sediment, dust and
other extraneous material cannot enter the impulse
piping.
Drain valve

Drain plug
Pipe (opened to atmosphere
at low pressure side) F0407.ai

Figure 4.7 Impulse Piping Connection Examples


(EJ210)
IM 01C25A01-01E
<4. Installing Impulse Piping> 38
Liquid Gas Steam (3) Removing the Process Connector Port
Dustproof Cap
Tap valve Union or flange The process connector port threads are covered with a
Union or flange plastic cap to exclude dust. This cap must be removed
Drain plug Tap valve before connecting the piping. (Be careful not to damage
the threads when removing this cap. Never insert a
Drain valve
screwdriver or other tool between the cap and port
threads to remove the cap.)
Union or
flange Tee 4.3.2 Routing the Process Piping
Tee Tee
(1) Relationship between Process Fluid
Union or flange and Manifold Locations (For the vertical
Tap valve impulse piping type)
Drain valve Drain valve If condensate (or gas) generated in the process piping
Drain plug were allowed to accumulate, then it would be necessary
Drain plug
F0408.ai to remove it periodically by opening the drain (or
Figure 4.8 Impulse Piping Connection Examples vent) plug. However, this would generate a transient
(for gauge/absolute pressure disturbance in the pressure measurement. Therefore, the
transmitters) process piping must be routed so that any condensate (or
gas) generated in the process piping will not accumulate
in the pressure-sensing assembly of the transmitter.
4.3 Process Piping Installation
Precautions (EJ115) NOTE
• If the process fluid is a gas, then as a rule the
4.3.1 Connecting Process Piping to the
manifold must be located at the downside of the
Transmitter
pressure-sensing assembly.
• If the process fluid is a liquid, then as a rule the
(1) Confirming the Process Fluid Flow
manifold must be located at the upside of the
Direction pressure-sensing assembly.
The mark “ ” on the manifold indicates the direction in
which the process fluid is flowed (from right to left). (2) Pipe Size for Process Piping
When connecting the process piping to the process Use a 15 mm (1/2-inch) pipe for process piping
connector, confirm the process fluid flow direction. connection to the process connector.
Flow direction (from right to left) Orifice name plate (3) Preventing Freezing
Process connection Manifold
Process connection If there is any risk that the process fluid in the transmitter
(outflow side) (inflow side)
pressure-sensing assembly could freeze or solidify, use
a steam jacket or heater to maintain the temperature of
the fluid.

(4) Process Piping Connection Examples


Process connector Process connector
(low pressure side) Figure 4.10 shows examples of typical process piping
(high pressure side)
F0409.ai
connections. Before connecting the transmitter to the
process, study the transmitter installation location, the
Figure 4.9 Manifold and Flow Direction Indication
process piping layout, and the characteristics of the
process fluid (corrosiveness, toxicity, flammability, etc.), in
(2) Tightening the Process Connector order to make appropriate changes and additions to the
Mounting Bolts connection configurations.
The transmitter is shipped with the process connector Note the following points when referring to these piping
mounting bolts only loosely tightened. After connecting examples.
the process piping, tighten these bolts uniformly to
• The process piping material used must be compatible
prevent leaks with a torque of 39 to 49 N·m {4 to 5 kgf·m}.
with the process pressure, temperature, and other
conditions.

IM 01C25A01-01E
<4. Installing Impulse Piping> 39
• A variety of process piping-mounted stop valves are
available according to the type of connection (flanged,
screwed, welded), construction (globe, gate, or ball
valve), temperature and pressure.
Select the type of valve most appropriate for the
application.

Gas flow measurement Union or flange

Stop valve

Manifold
Process piping

Liquid flow measurement


Manifold

Union or flange
Stop valve

Process piping
F0410.ai

Figure 4.10 Process Piping Connection Examples


(EJ115)

IM 01C25A01-01E
<5. Wiring> 40

5. Wiring
5.2 Connections of External
NOTE
Wiring to Terminal Box
For FOUNDATION Fieldbus, PROFIBUS PA, and Mod
bus communication types, please refer to each ● Terminal Configuration
communication manual.
RTD cable connection*

5.1 Wiring Precautions

IMPORTANT
Terminal 4 [B]*
• Lay wiring as far as possible from electrical noise
sources such as large capacity transformers,
motors, and power supplies. Terminal 1 Terminal 3 [A]
• Remove electrical connection dust cap before Terminal 2

wiring.
• All threaded parts must be treated with *For EJX9A only. F0527.ai

waterproofing sealant. (A non-hardening silicone


group sealant is recommended.) ● Terminal Wiring for 4 to 20 mA output
SUPPLY +
1
• To prevent noise pickup, do not pass signal and – 2
Power supply and output terminals
power cables through the same ducts.
CHECK +–
3
2
External indicator (ammeter) terminals*1*2
• Explosion-protected instruments must be wired or or
in accordance with specific requirements (and, ALARM –+ 3 Status contact output terminals*2
2 (when /AL is specified)
in certain countries, legal regulations) in order
Ground terminal
to preserve the effectiveness of their explosion-
protected features. *1: When using an external indicator or check meter, the
internal resistance must be 10 Ω or less. A check meter
• The terminal box cover is locked by an Allen head
or indicator cannot be connected when /AL option is
bolt (a shrouding bolt) on ATEX flameproof type specified.
transmitters. When the shrouding bolt is driven *2: Not available for FOUNDATION Fieldbus and PROFIBUS
clockwise using an Allen wrench, it gose in. The PA communication types.
cover lock can then be released and the cover can
be opened by hand. ● Terminal Wiring for 1 to 5 V output
When a cover is closed it should be locked by a SUPPLY +
1
Power supply terminals
– 2
shrouding bolt without fail. Tighten the shrouding + 3 1 to 5 V DC with HART communication
VOUT –
bolt to a torque of 0.7 N·m. 2 terminals
Ground terminal

Shrouding Bolt ● Terminal Wiring for 4 to 20 mA output


Shrouding Bolt [EJX9A]
F0501.ai

SUPPLY +
1
– Power supply and output terminals
2
Figure 5.1 Shrouding Bolt
CHECK +
3
External indicator (ammeter) terminals *1*2
– 2

• Plug and seal an unused conduit connection. PULSE + 4


Pulse or status contact output terminals *2
– 2

Ground terminal
*1: When using an external indicator or check meter, the
internal resistance must be 10Ω or less.
*2: Not available for FOUNDATION Fieldbus communication
type.
F0528.ai

Figure 5.2 Terminal

IM 01C25A01-01E
<5. Wiring> 41
5.2.1 Power Supply Wiring Connection 5.2.3 Status Output Connection
When option code /AL is specified, connect the external
IMPORTANT wiring as shown in Figure 5.7.
To configure and activate the process alarm function and
Connecting with the commercial AC power supply
status output, it is necessary to set some parameters.
will damage the device. Be sure to use the DC power
Refer to each communication manual for procedures.
supply in the predetermined range.
Transmitter
24V DC
terminal box Shielded cable
Connect the power supply wiring to the SUPPLY + and – +
Distributor
terminals. – 250Ω

Transmitter terminal box


+
Magnetic
Power supply valve
External power

supply 30V DC,
120mA max
Load resistance is not
necessary for 1 to 5 V output. F0502.ai Use two-wire separately shielded cables. AC power supply
F0504.ai
Figure 5.3 Power Supply Wiring Connection
Figure 5.7 Status Output Connection

5.2.2 Configuration Tool Connection

■ 4 to 20 mA output, BRAIN / HART


Connect the configuration tool to the SUPPLY + and –
terminals. (Use hooks.)

Transmitter terminal box Power supply


+
USB –
FieldMate Modem
Ignore the polarity since
the configuration tool is
AC-coupled to the
PC/FieldMate terminal box. F0503.ai

Figure 5.4 Configuration Tool Connection

■ 1 to 5 V output, HART
Connect the HART communicator or configuration tool to
the SUPPLY - and VOUT (+) terminals. (Use hooks.)

Power supply Transmitter terminal box Voltmeter


+ +
– USB –
FieldMate Modem

PC/FieldMate F0532.ai

Figure 5.5 Four wire connection

Transmitter terminal box Power supply


+
USB –
FieldMate Modem Voltmeter
+

PC/FieldMate F0533.ai

Figure 5.6 Three wire connection

IM 01C25A01-01E
<5. Wiring> 42
5.2.4 Connection Example for EJX910A and EJX930A
Table 5.1 The connection example for simultaneous analog and pulse and alarm, status output. (For HART protocol type)
Connection Description
Analog Output Transmitter Electrical Terminal
Distributor
In this case, + 24V DC
Communication is SUPPLY +
possible (up to a distance – 250Ω
of 2km when a CEV cable –
is used.) PULSE B* * Either B or +

Pulse Output Transmitter Electrical Terminal Use the Three-wire shielded cable.
Shielded Cable
In this case,
No communication is SUPPLY + E
possible.

* *1
PULSE B *2 R Electric counter
* Either B or +

Transmitter Electrical Terminal Use the Three-wire shielded cable.


Status Output
Shielded Cable
E
SUPPLY + Relay
In this case,
No communication is –
*
possible. PULSE B
Mognetic
* Either B or + valve
External Power supply
30V DC, 120mA max
(Contact Rating)
AC power supply

When analog and pulse output are used, the length of communication line is subjected to wiring conditions. Refer to
Simultaneous example 1 to 3.
Distributor (or communication medium : ex. EP card)
Analog
For the shielded cables in this example of
-Pulse Output *3 Shielded Cable
24V DC
flowmeter installation, use two-wire separately
Example 1 SUPPLY + shielded cables.
In this case, Communica – *2 R 250Ω
-tion is possible(up to a * E(10.5 to 30V DC) This supply voltage requires a power sourse
distance of 2km when a
PULSE B Counting input with a maximum output current of no less than
CEV cable is used). * Either B or + Common E/R.
Electric counter *1 (or communication medium : ex. EP card)
Transmitter Electrical Terminal
For the shielded cables in this
Example 2 Recorder or
example of flowmeter installation,
In this case, Communica Shielded Cable other instrument
use two-wire separately shielded
-tion is possible (up to a 250Ω cables.
distance of 200m when a
SUPPLY + *2
E(16.4 to 30V DC)
This supply voltage requires a power
CEV cable is used) and R
= 1kΩ). – R
Counting input sourse with a maximum output current
PULSE * of no less than E/R+25mA.
B Common
The supply voltage requires output
* Either B or +
Electric counter *1 impedance no more than 1/1000 of R
Transmitter Electrical Terminal (load resistance).
Recorder or
other instrument
Example 3 250Ω
In this case, No communi
-cation is possible (when SUPPLY + E(16.4 to 30V DC) This supply voltage requires
R*2 a power sourse with a
shielded cable is not used). – Counting input maximum output current of
* no less than E/R+25mA.
PULSE B Common
* Either B or + Electric counter *1
Transmitter Electrical Terminal

The load resistance of pulse output should be used to 1kΩ, 2W.


The range of load If no translation of the pulse output possible by the cable length or the frequency of the pluse output,
resistance R for the load resistance should be selected by calculation as shown below.
the pulse output. E (V) 0.1
≤ R (kΩ) ≤ Example of CEV cable capacitance
120 C ( µF ) × f ( kHz ) 0.1µF/km
2 Where
E (V) E = Supply voltage (V) C = Cable capacitance (µF)
P (mW) =
R (kΩ) f = Frequency of pulse output (kHz) P = Power ratio of the load resistance
R = Value of load resistance (kΩ) (mW)
F0531.ai
*1: To avoid the influence of external noise, use an electric counter which fits to the pulse frequency.
*2: Resistor is not necessary in case of an electric counter which can receive contact pulse signal directly.
*3: When using analog and pulse output simultaneously, the HART communication may be influenced by noise comparing analog output only. Take
countermeasure for noise shown above, e.g. use shield cable etc.

IM 01C25A01-01E
<5. Wiring> 43
5.2.5 External Temperature Connection • Pulse output and Alarm, Status Output or
(for EJX910A and EJX930A) Simultaneous Analog-Pulse Output
Connect the RTD cable assembly to the Juck Terminal. (for EJX910A and EJX930A)
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)

Receiver
F0505.ai
instrument
Figure 5.8 External Temperature Connection

5.3 Wiring
Receiver
5.3.1 Loop Configuration instrument

Since the DPharp uses a two-wire transmission system F0507.ai


for 4 to 20 mA output, signal wiring is also used as power Figure 5.10 Connection between Transmitter and
wiring. Distributor
DC power is required for the transmitter loop. The
transmitter and distributor are connected as shown below. (2) Intrinsically Safe Type (4 to 20 mA output)
For details of the power supply voltage and load
resistance, see Section 5.6. With the intrinsically safe type, a safety barrier must be
included in the loop.
For 1 to 5 V output, three or four wire system is used. See
(4). Hazardous Location Nonhazardous Location

(1) General-use Type and Flameproof Type (4 Transmitter terminal box


Distributor
to 20 mA output) (Power supply unit)
• Analog Output
Receiver
Hazardous Location Nonhazardous Location instrument
Transmitter terminal box
Distributor
(Power supply unit)
Safety barrier F0508.ai

Figure 5.11 Connection between Transmitter and


Receiver
instrument Distributor

F0506.ai
(3) Intrinsically Safe Type (for EJX910A and
Figure 5.9 Connection between Transmitter and EJX930A)
Distributor
• Analog Output
Hazardous Location Nonhazardous Location

Transmitter terminal box Receiver instrument


Safety barreir (and power supply)
(Isolation type)

Power
supply
Anaolg input

F0509.ai

IM 01C25A01-01E
<5. Wiring> 44
• Simultaneous Analog-Pulse Output • Four wire connection
Fasten the negative side wiring of both power supply
Hazardous Location Nonhazardous Location
and signal line to the SUPPLY - terminal.
Transmitter terminal box I/O module Hazardous Location Nonhazardous Location
Safety barrier
(Isolated type)
Transmitter terminal box
Distributor
Power (Power supply unit)
supply

Analog input

Power
supply

Receiver
Pulse input instrument
Safety barrier
(Isolated type)
F0510.ai F0530.ai

Figure 5.12 Connection between Transmitter, Figure 5.14 Connection between Transmitter,
barrier and receiver Distributor and Receiver

(4) 1 to 5 V output 5.3.2 Wiring Installation


Either three or four wire system can be used.
(1) General-use Type and Intrinsically Safe
Power supply line and 1 to 5 V signal line commonly use
Type
the SUPPLY - terminal.
With the cable wiring, use a metallic conduit or waterproof
NOTE glands.

With three wire connection, the cable length may • Apply a non-hardening sealant to the terminal box
affect the measurement accuracy of the output signal. connection port and to the threads on the flexible
In either three-wire or four-wire connection, metal conduit for waterproofing.
recommended wiring distance is 200 m or less, and
the use of shielded cable is recommended.

• Three wire connection


Flexible metal conduit
A negative wiring shall be commonly used for power
supply and signal line. Wiring metal Apply a non-hardening
conduit sealant to the threads for
Hazardous Location Nonhazardous Location waterproofing.

Transmitter terminal box Tee


Distributor
(Power supply unit)
Drain plug F0511.ai

Figure 5.15 Typical Wiring Using Flexible Metal


Conduit

Receiver
instrument

F0529.ai

Figure 5.13 Connection between Transmitter,


Distributor and Receiver

IM 01C25A01-01E
<5. Wiring> 45
(2) Flameproof Type • RTD connection components: EJX multivariable
transmitter, two cable glands, and RTD cable.
Wire cables through a flameproof packing adapter, or use
Two cable glands are attached.
a flameproof metal conduit.
Electrical connection
 Wiring cable through flameproof packing adapter.
• Apply a non-hardening sealant to the terminal box Cable gland
connection port and to the threads on the flameproof
packing adapter for waterproofing. RTD cable
with connector

Flameproof packing Detail of connector


adapter
Transmitter
Flexible metal conduit

Wiring metal F0514.ai


Apply a non-hardening
conduit
sealant to the threads for • Magnified view of the RTD connector in the
waterproofing.
transmitter's terminal box.
Tee

Drain plug
F0512.ai

Figure 5.16 Typical Cable Wiring Using Flameproof


Packing Adapter
M M
ALAR ALAR

 Flameproof metal conduit wiring


• A seal fitting must be installed near the terminal box
Protection Cap Connecting Port
connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of the F0515.ai
terminal box connection port, flexible metal conduit
The RTD cable connecting port is covered with a cap to
and seal fitting for waterproofing.
keep out dust. The cap should not be removed until you
Gas sealing device are ready to install the cable.
Non-hazardous area • Components for the cable gland
The cable gland assembly consists of an entry, seal,
Flameproof flexible running coupler, and backnut. Confirm that the seal is
metal conduit attached inside the entry and that the thread size of the
Hazardous area cable gland is the same as that for the RTD electrical
Flameproof Apply a non-hardening connection.
heavy-gauge sealant to the threads of
steel conduit these fittings for 1/2NPT Type
waterproofing
Running
Entry with Seal Coupler Backnut
Tee Seal fitting
Drain plug After wiring, impregnate the fitting
with a compound to seal tubing.
F0513.ai

Figure 5.17 Typical Wiring Using Flameproof Metal


Conduit
M20 Type
Running
Gasket Entry with Seal Coupler Backnut
5.4 RTD Cable Connection
(EJX910A/EJX930A)
Connection of the RTD cable is always required to
measure external temperature. Follow the procedures F0516.ai
below to connect a cable when a cable gland or a conduit
is used.
CAUTION
5.4.1 Connecting Shielded Cable with
Input/output signal is non-isolated.
Cable Gland (External temperature Do not turn on power supply until you complete all the
input code: -1, -2, -3, and -4) wiring work.

IM 01C25A01-01E
<5. Wiring> 46
Procedure (7) Rotate the running coupler another half turn to
securely tighten the seal on the RTD cable.
(1) Disassemble the cable gland: loosen the running
coupler to separate the backnut from the entry. (8) Use a protection conduit, if necessary.
(2) Remove the protection cap over the transmitter In this case, insert the cable through the conduit and
electrical connection and install the entry on the attach it to the Backnut.
electrical connection. Note that a non-hardening
sealant should be applied to the threads for a 1/2 NPT CAUTION
connection and a gasket should be used for an M20
connection. After the cable is secured as explained above, do not
tighten the running coupler any further; to do so could
damage the RTD connection.
Do not pull the cable or subject it to excessive
mechanical shock.

5.4.2 Connecting Shielded Cable for Con-


duit Use (External temperature input
F0517.ai code: -B, -C, and -D)
(3) Pass the RTD cable through the running coupler and • RTD connection components: EJX multivariable
backnut assembly. transmitter and RTD cable

F0518.ai

(4) Insert the RTD cable and firmly plug its connector into
the connecting port in the transmitter's terminal box.

F0522.ai

Procedure
(1) Remove the protection cap protecting the RTD
electrical connection and insert the RTD cable.

F0519.ai

(5) Align the running coupler on the entry.

F0523.ai

(2) Remove the cap protecting the connecting port. Then


insert the RTD cable and firmly plug the connector
into the connecting port in the transmitter's terminal
F0520.ai
box.
(3) Insert the cable through the conduit and attach it to
(6) Turn the running coupler until the seal in the entry
the RTD electrical connection.
comes into contact with the RTD cable.

CAUTION
Do not pull the cable or subject it to excessive
mechanical shock.

F0521.ai

IM 01C25A01-01E
<5. Wiring> 47
5.4.3 Cable Connection RTD Terminal Box 5.5 Grounding
Side
Grounding is always required for the proper operation of
EJX multivariable transmitter RTD I/F is for 3-wire Type transmitters. Follow the domestic electrical requirements
RTD, Pt100. as regulated in each country. For a transmitter with a
Heed the following when wiring an RTD of the 2- or 4-wire built-in lightning protector, grounding should satisfy
type. ground resistance of 10Ω or less.

NOTE Ground terminals are located on the inside and outside of


the terminal box. Either of these terminals may be used.
Please note that a temperature error will occur when
you use a 2-wire RTD because of wiring resistance.
Please do not ground the shield on the RTD side of
the cable.

Ground terminal
(inside)
CAUTION
Ground terminal
Please use only the cables provided with this (outside)
instrument.
When wiring, be sure not to damage the cable's
insulation or its core. F0525.ai

All the cable cores must have sufficient insulation Figure 5.19 Ground Terminals
around them.
Do not let the signal line contact the shield line.
Do not allow the shield line or the signal line to come 5.6 Power Supply Voltage and
the earth potential voltage.
Load Resistance
2-Wire 3-Wire 4-Wire For 4 to 20 mA output only.
When configuring the loop, make sure that the external
load resistance is within the range in the figure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.

A B A B b Aa B b 600
F0524.ai

Figure 5.18 The Method of Wiring for the RTD Side


External E–10.5
R= Communication
load 0.0244
applicable range
Table 5.2 The Method of Wiring for the RTD Side resistance BRAIN and HART
RTD Terminal R (Ω)

RTD Terminal A a B b
250
2-Wire White - Blue1 and Blue2 -
3-Wire White - Blue1 Blue2
4-Wire White open Blue1 Blue2

0 10.5 16.6 25.2 42


NOTE Power supply voltage E (V DC)
F0526.ai

Figure 5.20 Relationship between Power Supply


The color display in the table shows the white line of
Voltage and External Load Resistance
the cable.
The cable color could change depending on the cable
type.
Blue 1 and blue 2 allow changing places.
For 2-wire Type, connect either which is blue1 or
blue2, and give other side as OPEN.

IM 01C25A01-01E
<6. Operation> 48

6. Operation
NOTE Burnout direction switch

For FOUNDATION Fieldbus, PROFIBUS PA and Modbus BO H L


communication types and for the transmitter operating Slide switch WR E D
confirmation and zeroing by any communication
CPU assembly Write protection switch
method, refer to each communication manual.
Burnout direction switch (BO)

Burnout Direction H L H L
6.1 Preparation for Starting Switch Position

Operation Burnout Direction HIGH LOW

Hardware write protection switch (WR)


 Confirming that Transmitter is Operating
Write Protection H L H L
Properly Switch Position E D E D
On the integral indicator NO YES
Write Protection (Write enabled) (Write disabled)
• If the wiring system is faulty, the display stays blank. F0602.ai
• If the transmitter is faulty, an error code is displayed.
Figure 6.1 Burn-out Direction and Hardware Write
Protection Slide Switch

Self-diagnostic error
on the integral indicator
(Faulty transmitter) 6.2 Zero Point Adjustment
After completing preparations for operating the
F0601.ai
transmitter, adjust the zero point.

 Verify and Change Transmitter Zero point adjustment can be done by turning the
transmitter’s zero-adjustment screw or by using the
Parameter Setting and Values
communicator. This section describes the procedure
The parameters related to the following items are set at for the zero-adjustment screw. For the zero-adjustment
factory as specified in order. via communication, procedure, please refer to each
• Calibration range communication manual.
• Integral indicator display
• Output mode IMPORTANT
• Software damping (optional)
Other parameters like following are shipped with the Do not turn off the power to the transmitter
default setting. immediately after performing a zero point adjustment.
• Low-cut Powering off within 30 seconds of performing this
• Process alarm setting procedure will return the zero point to its previous
• Static pressure range setting.
• Signal characterizer
• Write protection
To confirm or change the values, please refer to each 6.2.1 Adjusting Zero Point for Differential
communication manual. Pressure Transmitters
Before adjusting zero point, make sure that the equalizing
 Output Status Setting at CPU Failure and valve is open.
Hardware Write Protection
Set the switches as shown in the figure below to set the
burn-out direction and write protection. The Burnout
switch is set to the H side for delivery (unless option code
/C1 or /C2 is specified in the order), and the hardware Zero-adjustment screw cover
write protection switch is set to E side except EJX910A F0603.ai
and EJX930A. The setting of the switches can be Figure 6.2 External Zero Adjustment Screw
confirmed via communication.
IM 01C25A01-01E
<6. Operation> 49
The zero-adjustment screw is located inside the cover. 6.3 Local Parameter Setting
Use a slotted screwdriver to turn the zero-adjustment
screw. Equalize the transmitter, then turn the screw
clockwise to increase the output or counterclockwise to WARNING
decrease the output. The zero point adjustment can be
made with a resolution of 0.01% of the setting range. The The local push button on the integral indicator must
degree of zero adjustments varies with the screw turning not be used in a hazardous area. When it is necessary
speed; turn the screw slowly to make a fine adjustment, to use the push button, operate it in a non- hazardous
quickly to make a rough adjustment. location.

When using differential pressure transmitters for level


measurement and if you cannot obtain the lower range
value from the actual measurement value of 0%, refer to IMPORTANT
subsection 6.2.2(2).
• Do not turn off the power to the transmitter
immediately after performing parameter setting.
6.2.2 Adjusting Zero Point for Gauge/
Powering off within 30 seconds of performing this
Absolute Pressure Transmitters procedure will return the parameter to its previous
setting.
(1) When you can obtain the Low Range Value
• The parameter of Ext SW must be“Enabled”
from the actual measured value of 0% to perform this configuration. See the user’s
(0 kPa, atmospheric pressure); manual IM 01C25T (HART/BRAIN) for the setting
For pressure measurement using gauge pressure procedure.
transmitters, follow the steps below before performing • The Local Parameter Setting function is available
zero point adjustment. with HART or BRAIN communication type.

1) Close the tap valve (main valve).


2) Loosen the fill plug so that the pressure applied to the 6.3.1 Local Parameter Setting (LPS)
transmitter is only the head of the seal liquid. Overview
3) Adjust the zero point at this status.
4) After the adjustment, close the fill plug and then Parameter configuration by the external adjustment
gradually open the tap valve. screw and push button (integral indicator code E) offers
easy and quick setup for parameters of Tag number, Unit,
Use a slotted screwdriver to turn the zero-adjustment LRV, URV, Damping,Output mode (linear/square root),
screw. Turn the screw clockwise to increase the output or Display out 1, and Re-range by applying actual pressure
counterclockwise to decrease the output. The zero point (LRV/URV). There is no effect on measurement signal
adjustment can be made with a resolution of 0.01% of the (analog output or communication signal) when Local
setting range. Since the degree of the zero adjustment Parameter Setting is carried out.
varies with the screw turning speed, turn the screw slowly
to make a fine adjustment and quickly to make a rough
adjustment.

(2) When you cannot obtain the Low Range


External adjustment screw cover
Value from the actual measured value of
0%; F0604.ai

Adjust the transmitter output to the actual measured Figure 6.3 External Adjustment Screw
value obtained by a digital manometer or a glass gauge.
Integral indicator
[Example]
The measuring range of 50 to 250 kPa; the actual
measured value of 130 kPa.

130–50
Actual measured value= x100=40.0% Push-button
250–50 F0605.ai
(=10.4mA)
Figure 6.4 Range –Setting Switch (push button)
Turn the screw to match the output signal to the actual
measured value.

IM 01C25A01-01E
<6. Operation> 50

screw

Process
Measurement Zero adjustment
Display push
Activate LPS mode
push
*
1. Tag Number Select Tag number Save/Cancel the value

*
2. Press Unit Edit Press unit Save/Cancel the value

push *
3. Press LRV Edit Press LRV Save/Cancel the value

*
4. Press URV Edit Press URV Save/Cancel the value

push *
5. Damping Time Edit Damping time Save/Cancel the value

*
6. Output Mode Select Output mode Save/Cancel the value

push *
7. Display Out1 Edit Display Out1 Save/Cancel the value

8. LRV-Apply Press Set LRV Save/Cancel the value

push
9. URV-Apply Press Set URV Save/Cancel the value

8, 9 : Re-range by applying actual pressure

10. Device Information

Process
Measurement
Display F0606.ai

*: Note that the above 1 to 7 parameter configurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a field communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for HART
parameter “Software rev” and IM 01C25T03 for BRAIN “SOFT REV”.

Figure 6.5

IM 01C25A01-01E
<7. Errors and Countermeasures> 51

7. Errors and Countermeasures


NOTE
For HART protocol revision 7, FOUNDATION Fieldbus, PROFIBUS PA and Modbus communication types, please refer to
each communication manual.

The table below shows a summary of error messages for BRAIN and HART (protocol revision 5) protocols.

Table 7.1 Alarm Message Summary (Except EJX910A and EJX930A)


Output Operation
Indicator Cause Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error keeps
CAP. ERR Capsule temperature sensor problem. Low) set with parameter. appearing even after restart.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor problem. Outputs the signal (Hold, High, or Replace amplifier.
AMP. ERR Amplifier EEPROM problem. Low) set with parameter.
Amplifier problem.
AL. 10 Input is outside measurement range Outputs high range limit value or low Check input or replace capsule when
PRESS limit of capsule. range limit value. necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside range Use heat insulation or make lagging
CAP. TMP (–50 to 130°C). to keep temperature within range.
AL. 13 Amplifier temperature is outside range
AMP. TMP (–50 to 95°C).
AL. 30 Output is outside upper or lower range Outputs high range limit value or low Check input and range setting, and
RANGE limit value. range limit value. change them as needed.
AL. 31 Static pressure exceeds specified Continues to operate and
SP. RNG range. output.
AL. 35 *1 Input pressure exceeds specified Check input.
P. HI threshold.
AL. 36 *1
P. LO
AL. 37 *1 Input static pressure exceeds specified
SP. HI threshold.
AL. 38 *1
SP. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI specified threshold.
AL. 40 *1
TMP. LO
AL. 50 Specified value is outside of setting Holds output immediately before error Check setting and change them as
P. LRV range. occurred. needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 54 Continues to operate and output Check setting and change them as
SP. RNG holding static pressure in %. needed.
AL. 55 Continues to operate and output. Check input.
SP. ADJ
AL. 60 Specified values or settings to define Check setting and change
SC. CFG signal characterizer function do not them as needed.
satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP
*1: These alarms may appear only when process alarm function is activated.

IM 01C25A01-01E
<7. Errors and Countermeasures> 52
Table 7.2 Alarm Message Summary (For EJX910A and EJX930A, HART protocol type)
Integral 4-20mA Output
Cause Countermeasure
indicator operation during error
AL. 01 Sensor problem. Outputs the signal (High or Low) set Replace capsule if the error recurs
CAP.ERR with burnout direction switch. after the transmitter is restarted.
Capsule temperature sensor problem. [status output: undefined] Replace capsule.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor problem. Replace amplifier.
AMP.ERR Amplifier EEPROM problem.
Amplifier problem.
A/D Converter problem.
AL. 03 External temperature sensor Check external temperature sensor.
ET.ERR disconnection.
— No device ID is found. Continues to operate and output. Replace amplifier.
AL. 10 Differential pressure is outside When PV is Pres Check input or replace capsule when
PRESS measurement range limit of capsule. Output AO upper limit or AO Lower necessary.
limit.
AL. 11 Static pressure exceeds limit. When PV is SP
ST. PRSS Output AO upper limit or AO Lower
limit.
AL. 12 Capsule temperature is outside range Continues to operate and output. Use heat insulation or make lagging
CAP.TMP (–50 to 130°C). to keep temperature within range.
AL. 13 Amplifier temperature is outside range
AMP.TMP (–50 to 95°C).
AL. 14 External temperature is outside range. When PV is ET
EXT. TMP Output AO upper limit or AO Lower
AL. 15 External temperature sensor resistance limit.
EXT. TMP is out specification.
AL. 16 PLS Pulse output is out specification. Continues to operate and output. Check settings and change them.
AL. 30 Differential pressure exceeds specified When PV is Pres. Check input and range setting, and
PRS.RNG range. Output AO upper limit or lower limit. change them as needed.
AL. 31 Static pressure exceeds specified When PV is SP
SP. RNG range. Output AO upper limit or lower limit.
AL. 32 Flow exceeds specified range. When PV is Flow
F. RNG Output AO upper limit or lower limit.
AL. 33 External temperature exceeds specified When PV is ET
ET. RNG range. Output AO upper limit or lower limit.
AL. 35 P.HI Input pressure exceeds specified Continues to operate and output. Check input.
AL. 36 P.LO threshold.
AL. 37 SP.HI Input static pressure exceeds specified
AL. 38 SP.LO threshold.
AL. 41 F.HI Input flow exceeds specified threshold.
AL. 42 F.LO
AL. 43 ET.HI Input external temperature exceeds
AL. 44 ET.LO specified threshold.
AL. 50 P. LRV Specified value is outside of setting Holds at the output value that existed Check settings and change them as
AL. 51 P. URV range. immediately before the error occurred. needed.
AL. 52 P. SPN
AL. 53 P. ADJ Continues to operate and output. Adjust settings and change them as
needed.
AL. 54 Holds at the output value that existed Check settings and change them as
SP. RNG immediately before the error occurred. needed.
AL. 55 Continues to operate and output. Adjust settings and change them as
SP. ADJ needed.
AL. 56 Holds at the output value that existed Check settings and change them as
ET. RNG immediately before the error occurred. needed.
AL. 57 Continues to operate and output. Adjust settings and change them as
ET. ADJ needed.
AL. 58 Holds at the output value that existed Check settings and change them as
FL. ADJ immediately before the error occurred. needed.
AL. 59 Specified value is outside of setting Normal calculation.
PLS.ADJ pulse output.
— Under Temperature Fix Mode. PV is ET Temp. Output Fix at 4mA. Leave from Temperature Fix Mode.

IM 01C25A01-01E
<7. Errors and Countermeasures> 53
Integral 4-20mA Output
Cause Countermeasure
indicator operation during error
AL. 79 Displayed value exceeds limit. Continues to operate and output. Check settings and change them as
OV. DISP needed.
AL.87 Flange temperature exceeds a preset It depends on the Diag Out Option Check the heater failure.
FLG. HI upper limit. setting.
AL.87 Flange temperature is below a preset Check the capsule temp. and
FLG. LO lower limit. Off: Continue to operate and output. Amplifier temp.
Burnout:Outputs AO upper limit or AO
lower limit. Adjust Flg Temp Coef.
Fall back:Outputs Diag Out Fixed Val.
AL.88 Differential pressure/pressure Continue to operate and output. Check process condition.
INVR.DP fluctuation does not reach the reference
level required to blockage detection so
that no blockage detection is carried
out.
AL.88 Low-pressure-side fluctuation does not
INVR.SL reach the reference fluctuation level
required to blockage detection.
AL.88 High-pressure-side fluctuation does not
INVR.SH reach the reference fluctuation level
required to blockage detection.
AL.88 BlkF can not be used for blockage
INVR.F detection for some reasons.
AL.89 Appointed the diagnosis range outside.
ILBD.OV
AL.89 B Blocking (both-side blockage) is It depends on the Diag Out Option Check process condition.
B BLK detected. setting.
AL.89 High-pressure-side blockage is
H BLK detected. Off: Continue to operate and output.
Burnout: Outputs AO upper limit or AO
AL.89 Low-pressure-side blockage is
lower limit.
L BLK detected.
Fall back: Outputs Diag Out Fixed Val.
AL.89 Pressure fluctuation amplitude of high-
H LRG pressure side is large.
AL.89 Pressure fluctuation amplitude of low-
L LRG pressure side is large.
AL.89 A Blocking (single-side blockage) is
A BLK detected.
AL. 90 SIM Under Simulation Mode for flow. Simulate input output. Check Simulation Mode.
AL. 91 F. SIM Under Simulation Mode for device Output the setting value of Simulate- Check Simulation Mode.
AL. 91 P. SIM variables. Value.
AL.91 SP. SIM
AL. 91
ET. SIM
AL. 91
TF. SIM
AL. 91
PCT. SIM
AL. 91
AO. SIM

IM 01C25A01-01E
54

Revision Information
 Title : EJX and EJA-E Series
Differential Pressure and Pressure Transmitters Installation Manual
 Manual No. : IM 01C25A01-01E

Edition Date Page Revised Item


1st Aug. 2009 New publication
2nd Apr. 2010 7 to 14 2.4 Add limitation of ambient temperature for/HE.
3rd Oct. 2010 1, 5 and 15 Add EJX610A and EJX630A.
1 1. Add HART 7 manual.
2 1. Add note for wet location in (c).
3 3. Add EJX630A.
30 to 31 5.4 Modify pictures of cable gland.
41 to 43 8. Add parameters for EJX900A (Dev.rev.2).
4th Aug. 2011 1 1. Modify Table 1.1.
14 2.4.3 Alter the note (*1) for name plate.
27 5.2.2 Change the picture of configuration tool.
28 5.2.4 Add note (*3).
36 7 Add HART protocol revision 7 to NOTE.
37 7 Modify Table 7.2.
40 8 Add HART protocol revision 7 and EJX910A/EJX930A to NOTE.
Delete the Menu Tree for EJX910A/EJX930A.
5th Mar. 2012 Revise CD-R (Ed5).
6th Aug.2012 ― Add EJA-E series.
1 Add table for EJA to Table 1.1. Add note for representation of model name.
10 to 15 Revise ATEX approval.
17 Add models to PED table.
42-46 Add parameters and notes.
7th Jun. 2013 ― Add PROFIBUS PA.
7 Add note for multiple approval option.
13 to 14 Replace ATEX type n by ATEX Ex ic.
16 and 17 Add EJA110E with /HG to PED table.
20 Modify note for installation height.
8th June 2014 2 1. Add note for symbols.
8 2.4.2 Revise category for CSA Nonincendive.
17 2.7 Update safety requirement standard.
28 to 34 5. Revise drawings and symbols for terminal.
28 5.2.1 Add note for power supply.
37 to 42 6.3 Add local parameter setting function.
9th Oct. 2014 8 2.4.1 Add information for 1 to 5 V output.
10 2.4.2 Add information for 1 to 5 V output.
13 2.4.3 Add information for 1 to 5 V output.
16 to 17 2.4.5 Add EPL code. Revise applicable standard. Add information for 1 to 5
V output. Add note for electro static charge. Add electrical connection.
17 2.5 Add standard for PROFIBUS.
29 5.2 Add Figure 5.2 Terminal.
30 5.2.1 Add information for 1 to 5 V output.
33 5.3.1 Add information for 1 to 5 V output.
36 5.6 Add applicability.
40 6.3.1 Add “10.Device information”
41 6.3.3 Add note in the figure. Add method of cancel/save. Delete 6.3.4 to
6.3.11
42 7. Correct AL31 output operation.

IM 01C25A01-01E
55

Edition Date Page Revised Item


10th Apr. 2015 Removal of CD-R.
1 1. Modify descriptions. Replace CD-ROM information by the
downloading information. Modify structure of Table 1.1.
2 Delete note about CD-ROM.
1.1 Add WARNING sign.
3 Add (g) and (h).
5 2. Modify Table 2.1.
6 2.1 Replace Figure 2.2.
2.4 Delete Note for CD-ROM.
7 to 28 Add Fieldbus intrinsically safe type.
(2.4.1 b and c, 2.4.2 b, 2.4.3 c, d and g, and 2.4.4 b.)
28 2.5 for Profibus → for Fieldbus
30 2.7 Add C22.2 standard.
41, 49, 52 5, 6 and 7 Modify note for CD-ROM.
51 Delete 6.3.2.
11th July 2015 26 to 31 2.4.4 Add SU21 and SS26. Add a, b, c and d.
26 Revise Note 2.
53 6.3.1 Delete note for 10. from Figure 6.5.
12th Feb. 2017 1 Add IM for Diaphragm Seal System and DRS. Add a note on User’s Manual
for code Z.
4 Add statement for Chinese ROHS.
6 Update the L-type bracket in Figure 2.1.
8 to 12 Delete descriptions and add Control Drawing for FM approval.
16 to 23 Update ATEX applicable standards.
16 Revise descriptions for item a.
17 Delete item “b.ATEX Intrinsically Safe for HART Protocol Type for EJX90A”
20 Revise notes for ATEX flameproof type.
23 Update the tag plate for ATEX flameproof. Delete tag plate for EJX90A
intrinsically safe for HART/BRAIN.
24 Update IECEx applicable standards. Revise notes for IECEx intrinsically
safe type.
27 Delete items “e. IECEx Intrinsically Safe / type n for HART/BRAIN Protocol
Type (Except for EJX90A)” and “f. IECEx Intrinsically Safe / type n for
Fieldbus Type (Except for EJX90A).
28 Update PED information.(97/23/EC →2014/68/EU)
30 Update the L-type bracket in Figure 3.3.

IM 01C25A01-01E
YOKOGAWA ELECTRIC CORPORATION
Headquarters
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPAN
Phone : 81-422-52-5555
Branch Sales Offices
Osaka, Nagoya, Hiroshima, Kurashiki, Fukuoka, Kitakyusyu

YOKOGAWA CORPORATION OF AMERICA


Head Office
12530 West Airport Blvd, Sugar Land, Texas 77478, USA
Phone : 1-281-340-3800 Fax : 1-281-340-3838
Georgia Office
2 Dart Road, Newnan, Georgia 30265, USA
Phone : 1-800-888-6400/ 1-770-253-7000 Fax : 1-770-254-0928

YOKOGAWA AMERICA DO SUL LTDA.


Praca Acapulco, 31 - Santo Amaro, Sáo Paulo/SP, BRAZIL, CEP-04675-190
Phone : 55-11-5681-2400 Fax : 55-11-5681-4434

YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
Phone : 31-88-4641000 Fax : 31-88-4641111

YOKOGAWA ELECTRIC CIS LTD.


Grokholskiy per 13 Building 2, 4th Floor 129090, Moscow, RUSSIA
Phone : 7-495-737-7868 Fax : 7-495-737-7869

YOKOGAWA CHINA CO., LTD.


3F Tower D Cartelo Crocodile Building, No.568 West Tianshan Road,
Shanghai 200335, CHINA
Phone : 86-21-62396262 Fax : 86-21-62387866

YOKOGAWA ELECTRIC KOREA CO., LTD.


(Yokogawa B/D, Yangpyeong-dong 4-Ga), 21, Seonyu-ro 45-gil, Yeongdeungpo-gu,
Seoul, 150-866, KOREA
Phone : 82-2-2628-6000 Fax : 82-2-2628-6400

YOKOGAWA ENGINEERING ASIA PTE. LTD.


5 Bedok South Road, Singapore 469270, SINGAPORE
Phone : 65-6241-9933 Fax : 65-6241-2606

YOKOGAWA INDIA LTD.


Plot No.96, Electronic City Complex, Hosur Road, Bangalore - 560 100, INDIA
Phone : 91-80-4158-6000 Fax : 91-80-2852-1442

YOKOGAWA AUSTRALIA PTY. LTD.


Tower A, 112-118 Talavera Road, Macquarie Park NSW 2113, AUSTRALIA
Phone : 61-2-8870-1100 Fax : 61-2-8870-1111

YOKOGAWA MIDDLE EAST & AFRICA B.S.C.(C)


P.O. Box 10070, Manama, Building 577, Road 2516, Busaiteen 225, Muharraq,
Kingdom of BAHRAIN
Phone : 973-17358100 Fax : 973-17336100
Apr. '15

Printed in Japan

You might also like