DEVELOPED BY : ROYCE AGA

PROJECT NAME : Rev.01: 2016


PROJECT LOCATION : Rev.02: 2017

Check Maximum Shear Around Column Perimeter (PUNCHING SHEAR)

U = punching perimeter (1.5d from face of the column)


Uo = Column Perimeter
d = Effective depth of Slab EXTRA BARS
Vu = Ultimate Column Load/Reactions Bar Diam = 0
Column b = 250 mm Spacing = 200
Column hc = 400 mm 0
Uo = 1300 mm 3.1416
ØDb = 6 mm 6.66667
Slab Thk h = 250 mm b
d = 227 mm hc
Vu = 275 KN (Ultimate)
Bar Spacing = 150
Bar Diam = 16 mmØ
Vu
As = 1340.416 mm²
fcu = 20.6 Mpa
fy = 248 Mpa

vmax = Vu < .8√fcu = 3.63 N/mm² (BS Code Sec 3.4.5.12)


Uod

vmax = 275,000 = 0.93 N/mm²


295,100

Calculated Shear Capacity,vmax = 0.93 < 3.63 N/mm² OK!!!

>>Thus, If OK, The slab thickness is adequate

Calculate Shear Stress at Shear Perimeter 1.5d from the column face

U = 4024 mm

v = V = 275000 = 0.301 N/mm²


Uxd 4024 x 227

Calculate Vc

Vc = 0.79 {100 As/bvd}^1/3 x (400/d)^1/4


Ym
Vc = 0.65985392

v = 0.301 < 0.6599 No Shear Reinforcement is required

clause 3.7.7.5 of the code for slabs over 200 mm thick.


if, vc<v≤ 2vc, shear reinforcement is required

Notes:
Input data in Blue caption
Don't erase any cell

Ref: Reinforced Concrete : Design Theory and Examples


3Rd Ed.
Bhatt, P.; MacGinley, T. J.; Choo, B. S.
DEVELOPED BY : ROYCE AGABAS
Rev.01: 2016
Rev.02: 2017

A BARS
mm
mm 5

Punching Perimeter

134041.6
227000
0.590492

400
227

fcu
25