EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A Receiving
The tag or name plate shall be located such that the information is SAES-K-001
A4
visible and can be read after equipment installation Para 4.8.1.2.3
SAES-K-001
A6 Number of rows per coil shall not exceed 10 rows.
Para 4.8.4.7
Fin spacing of condenser coils shall not be closer than 15 fins per
SAES-K-001
A7 inch*.Fin spacing of evaporator and condenser coils shall not be
Para 4.8.4.8
closer than 15 fins per inch.
Page 1 of 3
Copper fins on copper tubes shall be used for all condenser coils
within ½ km of sea or within an industrial area.*Copper fins on
copper tubes shall be used for all condenser SAES-K-001
A8
coils within ½ km of sea. Evaporator coils shall also have Para 4.8.4.9
copper fins on copper tubes when introducing 20% or more
outside air within ½ km of sea or within an industrial area.
Coil return bends shall have flux removed and be protected from SAES-K-001
A9
corrosion. Para 4.8.4.10
* Verification is required by checking the equipment submittal if verification is not possible by visual inspection
Page 2 of 3
SAUDI ARAMCO ID/PID - 18-May-05 -REV 0 (Standards Cutoff -March 2013) Rev 7 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Air Cooled Condenser Receiving and Storage SAIC-K-4037 30-Apr-13 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC) 5 July 2009 Design and Installation of Heating,
Ventilating and Air Conditioning Systems 05 December 2012