SAUDI ARAMCO ID/PID - 18-May-05 -REV 0 (Standards Cutoff - March 2013) Rev 7 30-Apr-13

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Grease Filter Installation SAIC-K-4030 30-Apr-13 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Type I hoods shall be equipped with approved grease filters designed
for the specific purpose.Listed grease filters, baffles or other SAES-K-100
A1
approved grease removal devices for use with commercial cooking Para. 508.5.11
equipment shall be provided. (UMC, para. 509.1)
Filters shall be placed at the location indicated on the Construction
A2 IFC DRAWING
Drawings
Grease collecting equipment shall be accessible for cleaning.Listed
SAES-K-100
A3 grease filters shall be tested in accordance with UL 1046. Mesh filters
Para. 508.5.11
shall not be used. (UMC, para. 509.1)

The lowest edge of a grease filter located above the cooking surface
shall be at least the height set forth in Table 5-D below.The distance
between the grease removal device and the cooking surface shall be SAES-K-100
as great as possible but not less than eighteen (18) inches (457 mm). Para. 508.5.11
(UMC, para. 509.2.1)

A4
Table 5-D Where grease removal devices are used in conjunction
with charcoal-type broilers, including gas or electrically heated
SAES-K-100
charbroilers, a minimum vertical distance of four (4) feet (1,219 mm)
Para. 508.5.11
shall be maintained between the lower edge of the grease removal
device and cooking surface. (UMC, para. 509.2.2)

Grease Filter units shall be installed in frames or holders with


handles by which they may be readily removed without the use of
tools, unless designed and installed to be cleaned in placeGrease
SAES-K-100
A5 filters shall be listed and constructed of steel or listed equivalent
Para. 508.5.11
material ans shall be of rigid construction that will not distort or crush
under normal operation, handling and cleaning conditions. (UMC,
para. 509.2.4)

Grease Filters shall be of such size, type and arrangement as will


permit the required quantity of air to pass through such units at rates
not exceeding those for which the filter or unit was designed or SAES-K-100
A6
approved.Grease filters shall be tight fitting and firmly held in place Para. 508.5.11
and so arranged so that all exhaust air passes through the grease
filters. (UMC, para. 509.2.4.1)

Grease Filter units shall be installed in frames or holders with


handles by which they may be readily removed without the use of SAES-K-100
A7
tools, unless designed and installed to be cleaned in place and the Para. 508.5.1
system is equipped for such cleaning in place.

Grease Filter shall be sized and made removable so they may be


passed through a dishwashing machine or cleaned in a pot sink and
so arranged in place or provided with drip intercepting devices as to SAES-K-100
A8
avoid grease or other condensate from dripping into food or on food Para. 508.5.11
preparation surfaces.Grease filters shall be easily accessible and
removable for cleaning. (UMC, para. 509.2.4.2)

Grease Filters shall be installed at an angle greater not less than SAES-K-100
A9
forty-five (45) degrees from the horizontal. (UMC, para. 509.2.4.3) Para. 508.5.11

Page 1 of 3
Grease Filters shall be equipped with a drip tray beneath the lower
SAES-K-100
A10 edge of the filters and drip tray shall be pitched to drain into an
Para. 508.5.11
enclosed metal container. (UMC, para. 509.2.5)

Page 2 of 3
SAUDI ARAMCO ID/PID - 18-May-05 -REV 0 (Standards Cutoff -March 2013) Rev 7 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Grease Filter Installation SAIC-K-4030 30-Apr-13 HVAC
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

REMARKS:

REFERENCE DOCUMENTS:
1-SAES-K-100 Saudi Aramco Mechanical (HVAC) code -- 20 October 2012
2-Uniform Mechanical Code (UMC) -- 19972009

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 3 of 3

You might also like