Professional Documents
Culture Documents
Modeling and Simulation in XENDEE: IEEE 34 Node Test Feeder
Modeling and Simulation in XENDEE: IEEE 34 Node Test Feeder
March 2, 2016
This document is one of several guides designed to support skills development in distribution
network modeling. It can be used during standard university curricula, a short industry course,
self-guided lessons, peer learning, or other training opportunities. Files resulting from the guide
can also be modified at the discretion of the user to pursue advanced topics of analysis. The IEEE
Test Feeders are used as examples given their wide recognition and use. Resulting power flow
analysis and short circuit analysis are presented in separate documents for each test feeder.
Each guide is developed through a partnership between Arizona State University researchers and
XENDEE. These training guides have been successfully used to train people individually, in small
and large classrooms, during interactive micro-grid boot camps, and during short sessions for
industry integrators and operators.
IEEE 34 Node Test Feeder is an existing feeder located in Arizona, with a nominal voltage of 24.9
kV. It is characterized by long and lightly loaded overhead transmission lines, two in-line
regulators, one in-line transformer for a short 4.16 kV section, a total number of 24 unbalanced
loads, and two shunt capacitors.
1
848
822 846
820 844
864
818 842
802 806 808 812 814 850 824 826 834 860 836
858 840
816
832 862
800 888 890
810
838
852
The below figure shows the one-line diagram of the IEEE 34 Node Test Feeder built in XENDEE.
OpenDSS, an open-source technology developed by the Electric Power Research Institute (EPRI),
is a powerful analytics engine capable of simulating complex multi-phase electrical power
distribution systems. XENDEE enhances EPRI OpenDSS with enterprise level features such as
visualization, design, simulation, and reporting automation. XENDEE is a web-based analytical
tool that runs in Mozilla Firefox using the Microsoft Silverlight add-on.
Table 1. List of XENDEE Files Along with Supporting Files for XENDEE Modeling.
The utility has been modeled as a 69 kV three phase source (Figure 1). All other parameters for
the utility were kept at their default value as shown in XENDEE.
Figure 1. Slack Bus with model (left) and power flow solution (right).
Modeling power flow along a transmission line requires data including (1) line length between two
nodes, (2) line parameters and pole construction data at a specific bus.
Line Data.xls – Line length between two nodes with the configuration for that specific line.
Line Configuration.xls – Line parameters including the Geometric Mean Ratio (GMR) of the
line and resistance per mile. Values pulled from the XENDEE overhead line catalogue.
XENDEE code words for a specific ACSR wire are present in this file (see Table 2). Pole
construction data is also included for the each type of configuration.
IEEE Test Feeder.pdf – All details summarized for the IEEE Test Feeder.
Transformers are modeled in XENDEE according to the winding connection provided in the Excel
file.
Figure 2. Transmission Line with model (left) and power flow solution (right).
𝑋𝑋
Transformer Data.xls – Transformer model data. XENDEE requires 𝑍𝑍% and 𝑅𝑅
% ratio for
Substation transformer impedances are provided but they are not used by IEEE for power flow
analysis. IEEE reports results that assume voltage begins at the substation bus at the designated
𝑋𝑋
voltage. To address this issue, a substation transformer in XENDEE has 𝑅𝑅% of 0.001% and �𝑅𝑅 � %
of 1.001%.
Figure 3. Transformer with model (left) and power flow solution (right).
A line voltage regulator is connected between two nodes or two buses. This regulator modifies the
line voltage in case of sudden addition or loss of load connected to the distribution network.
Regulator Data.xls – Contains line voltage regulator information.
IEEE_34_LVRauto.xpf – uses LVR with automatic tap control. This is used for modern
distribution system analysis rather than estimated tap control. Additional information required to
model the LVR in XENDEE is provided in the following table.
The LVR is modeled by a single phase transformer with a fixed tap setting. Similarly, a three phase
LVR is modeled by three single phase transformers each associated with an individual phase and
a fixed tap position.
IEEE_34_LVRtapsFixed.xls – uses single phase transformers with fixed tapping instead of LVR.
The fixed tap values are present in IEEE 34 Node Test Feeder.doc in the power flow results
section. Each LVR fixed tap setting is calculated using the following equation:
Figure 4. LVR with model (top) and power flow solution (bottom).
All spot loads have their respective load model (constant power, constant impedance, constant
current) type defined and are considered balanced across all three phases. These loads are modeled
as three phase with appropriate load model.
Figure 5. Spot loads with model (left) and power flow solution (right).
The power factor for the load is calculated in the Excel file. XENDEE requires the power factor
be given as a percentage of the load. See column heading “Power Factor (%)”.
Modeling a distributed load requires creating an additional node between the two nodes across
which the distributed load is applied. For example, the IEEE test case provides information for
distributed loads that can be connected between two nodes as shown in Figure 6a.
XENDEE / EPRI OpenDSS approach this scenario by inserting a middle node and modeling two
overhead wires of the same configuration but each having one-half the length of the original line.
Figure 6b shows this approach for the original line shown in Figure 6a.
In looking at an example from the actual IEEE 34 Node Test Feeder system, Figure 7 shows an
extra node created at the midpoint between nodes 802 and 806. That distributed load is connected
to that middle node.
Figure 7. Distributed loads with model (left) and power flow solution (right).
Figure 8. Shunt capacitors with model (left) and power flow solution (right).
Table 5. Comparison of Power and Losses between IEEE Results & XENDEE Simulation.
Table 6. Comparison of Phase Voltage Magnitude & Angle between IEEE Results & XENDEE Simulation.
The voltage profile at each node can be viewed within the annotation view in XENDEE. Moreover,
the professional report view in XENDEE can be used to check voltages at any node.
Table 7. Comparison of Phase Current Magnitude between IEEE Results & XENDEE Simulation.
The annotation view in XENDEE can also be used to view current values through individual lines
for each phase.
5 ADDITIONAL NOTES
We hope you have benefited from this step-by-step guide to creating an IEEE Test Feeder in
XENDEE. The full XENDEE results report can be generated by importing and simulating the
models referenced in this guide. The partnership with XENDEE has allowed our education and
research programs at Arizona State University to grow rapidly through the easy-to-use and
versatile user interface. You can find out more about our research, computational lab, micro-grid
test bed, and capacity building programs at http://faculty.engineering.asu.edu/nathanjohnson/