Electric Coils For Single Duct Terminals

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Single Duct Terminal Units

Electric Coils for


Single Duct Terminals
Product Information

General Information
Price offers factory supplied and mounted
electric coils for single duct terminal units.
The electric coils come standard as a
side-mounted unit (slide-in type) and are
specifically designed to suit Price terminal
units. The heating elements are low watt
density and designed to minimize hot spots
and thermal cutout. This allows for a more
compact assembly making field installation
much easier and reducing shipping costs.
Price heaters offer a full range of options
and accessories to meet all customers'
needs. SCR (Silicon Controlled Rectifier) and
the Price exclusive 'Electronic Modulat­ing
Control' are also available, offering numer­
TERMINAL UNITS

ous benefits over conventional duct heater


control.
Benefits of Electric Reheat
Electric coils offer an alternative to water
reheat coils as an optional accessory for
single duct terminal units.
Some of the benefits include:
• No requirement for water lines.
• Low pressure drop across the coil
elements, which reduces central fan
horsepower requirements.
• Operate using standard building
electrical power.
Features
• Extremely compact design – 35 in.
housing length.
• Specially designed elements allow
for installation with minimal clearance
between the terminal and coil, resulting • All heaters come with an Automatic • An air flow switch is provided as
in an extremely compact assembly. This Reset thermal cutout to protect from standard to ensure air is passing over
allows for easier field installation and overheating in case the minimum air the coil before it will energize. This
reduced shipping costs. flow requirements are not met. ensures that the coil will not energize
• A Manual Reset thermal cutout is when the system fan is shut-down or
• Heaters are factory wired and tested
standard on all heaters. fails.
ensuring a high level of quality.
• Terminal housing is lined with 1/2 in. • ETL certified to meet UL 1995 as an
• The heater controls can be specified
[13] thick, min. 1.5 lb density fiberglass assembly (n/a EMC option).
compatible with pneumatic, electronic,
or direct digital control. internal insulation ­­­which meets • A unique pressure sensing tap
requirements for NFPA90A and UL181. strategically located to ensure
• Heavy gauge zinc-coated steel electrical
Optional 3/4 in. [19] and 1 in. [25] also positive operation of the heater at low
enclosure and frame.
available. Heater section in not insulated downstream static pressure.
• Electric coil configuration and air flow is
unless requested. • For stable operation of heater controls
matched to eliminate hot spots, provide
• Magnetic contactors or Pneumatic- minimum discharge static pressure of
efficient heat transfer, and to maintain
Electric switches are provided as 0.2 in. w.g. is recommended
element life.
standard on staged heaters for de-
• Hinged access door for the electrical
energizing or disconnecting power to
enclosure.
the heating element.
• Heaters are provided with Low Watt
Density elements to prevent overheating
and nuisance tripping of the thermal
Product Information Index overload protectors.
Options.............................................. F141 • High grade nickel chrome elements
Electronic Heating Controls............. F141 provide maximum corrosion resistance
Coil Selection Charts............... F142-F143 and extended element life.
Selection Guidelines......................... F144 • When needed, a Class II (24VAC) control
Suggested Specification.................. F495 transformer is provided as standard
with heater controls.

F-142 All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
© Copyright Price Industries Limited 2011.
Price SilentGuard TM

SINGLE DUCT – HEATER CONTROL MODULE


The Price Silent Guard Heater Control Module (PSG) provides An all-in-one
efficient operation of duct heaters with a wide range of
features to cover all control, safety and troubleshooting
solution to duct
concerns. The complex internal wiring normally associated heater control.
with duct heater assemblies is eliminated and replaced with
the sleek and compact all-inclusive PSG circuit board.

Fast and reliable field hookup: Quiet long-life relays allow Automatic sensing between
Combo power/diagnostic
the unit simply snaps in up to three stages of on/ HOT and COMMON
LED blinks out status codes
to the duct heater off (digital) control switching controls

www.price-hvac.com for additional product


C
LISTED
US information, including product videos and brochures.
Single Duct Terminal Units
Electric Coils

Price Silent GuardTM

The Price Silent Guard Heater Control


Module provides efficient operation of duct PSG (Price Silent Guard)
heaters with a wide range of features to
cover all control, safety and troubleshooting
concerns. The on-board PCB relays provide
quiet and reliable operation to give the end
user peace of mind.
Benefits
• Quiet on-board relays
• Auto resetting 24VAC fuse
• On-board air flow switch
• Status LED to aid troubleshooting
General Information
The Price Silent Guard (PSG) is an all-in-one
TERMINAL UNITS

solution to duct heater control.The complex


internal wiring normally associated with
duct heater assemblies is eliminated and
replaced with the sleek and compact all-
inclusive PSG circuit board. Installing the
board is very straightforward: thanks to the
snap-in design and fully labeled on-board
connectors, wiring is quick and efficient.
Features Installation and Maintenance Safety
The Price Silent Guard incorporates many The design of the PSG greatly reduces The PSG has undergone rigorous testing
features on to the board to make it the safest installation time and increases convenience: and earned ETL approval giving the user
and most reliable product possible: the unit simply snaps in to the duct heater. comfort in the safe operation of the device.
Wiring connections for every possible Numerous innovative concepts were
• Accepts either switched HOT or switched
configuration are labeled on the board in a incorporated into the design of the circuit
COMMON input signals. straightforward manner.This reduces wiring board ensuring not only the safety of the
• Software averaging of input signal clutter and space required for assembly. building and its occupants, but also the
prevents relay chatter and extends safety and longevity of the fan and heater
Troubleshooting the unit is even easier. An
device life. on-board status LED sequentially blinks out components.
• Fan interlock option prevents coil from a troubleshooting code which indicates the
overheating. current status of the board. (For example:
• FR-4 rated circuit board complies with three blinks means 3 stages of heating
safety standards. are active, six blinks means auto reset
• PCB mounted air flow switch with has tripped, etc.) The indicator lights also
Intelliflow technology. show the user which individual circuits are
currently energized.
• Easy to use with One-Phase, Three-
Phase Y or Three-Phase Delta power
systems.
• Each stage handles up to 277VAC.
• Indicator lights show operation of each
stage of heat and fan output.
• Programmed time delay's prevent short
cycling of fan or heater stages.

F-144 All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
© Copyright Price Industries Limited 2011.
Single Duct Terminal Units
SPV, SDV Series
SPVLP, SDVLP Series
Electric Coils

Available Options

• SCR (Silicon Controlled Rectifier) SCR control plus a unique electronic sensitive applications. They may also be
option provides infinite heater control flow sensor for additional protection at used for applications, that have frequent
using a proportional signal. Element life low flows. (NRTL/C and CSA certified) reheat demands that cause the coil to
is extended and noise from contactors is • A Door-Interlocking Disconnect Switch is cycle repeatedly.
eliminated. This option may be specified available to disconnect the power when • Primary or Secondary Fusing for added
compatible with pneumatic, electronic, the electrical enclosure door is opened. safety or to meet local electrical codes.
or DDC controls. See description below. • Mercury contactors may be supplied (UL and CSA certified)
• EMC (Electronic Modulating Control) in place of standard magnetic contactors
option provides all of the benefits of to provide quiet operation for noise

Control Options
Conventional Staged Heater SCR and Electronic Modulating Control • Digital (DDC)
• Pneumatic Heater proportional, pulsed AC, or pulsed DC.

TERMINAL UNITS
• Digital (DDC) • Pneumatic
proportional (with the addition of a
pneumatic-electric transducer).

Electronic Heating Controls


SCR EMC SCR (Silicon Controlled Rectifier)
The Price SCR Controller is a Silicon The Electronic Modulating Control (EMC)
Controlled Rectifier that provides option is a Price exclusive feature which
proportional modulation to the output over provides all of the advantages and benefits
its full operating range. The SCR acts like of SCR control plus an electronic flow
an electronic switch that turns on and off sensor.
large amounts of power to the load (heater).
Benefits of Electronic Air Flow Sensor
The Price SCR uses a Zero Crossing feature
that allows a soft start of the electronic load, The air flow sensor responds to radiant
which eliminates power surges. heat of the heating element which, in turn,
is influenced by the air flowing through the
Features
heater to dissipate the heat. The patented
• Power requirements – 24 VAC, polarity air flow sensor and associated electronic
sensitive. controller modulate the power to the heater,
• Large, finned aluminum Heat Sink to adjusting the heater’s capacity to match
provide proper heat dissipation. the air flow available. This unique concept
• Load Power ranging from 120 VAC allows the heater to respond exactly to the
to 480 VAC, and a current rating quantity of air flowing through it as well
up to 25 or 45 amps (depending on as safely shut down in case of a total loss
model). Multiple Control Input signals of air flow. Electronic Modulating Controller
from stand alone controller or BAS (EMC)
Note: The air flow sensor overrides the
controller: 2-10 vdc signal, 4-20 mA
temperature control to match the heating
signal, 24 VAC Pulsed signal
capacity to the air flow available.
• LED indication for: Firmware Version,
Type of Input Signal, and Output Since the electronic flow sensor responds
Indication. to radiant heat as opposed to duct pressure,
• Factory or Field installable optional it eliminates the problem of low air flow or
Discharge Air Temperature (DAT) Probe duct static pressure switches, and ensures
safe operation of heaters at flows as low as
for maintaining outlet air temperature.
can be set by conventional controls.
Benefits of SCR
• Proportional modulation of the heater
maintains set-point more accurately
than on/off control, providing maximum
comfort in the space.
• Energy efficient by avoiding overshooting
and undershooting and reduces
operation costs.
• Quiet operation of solid state relays
compared to mechanical relay or
contactor pulling in and dropping out.
• SCR can be tied into existing BAS
controller, or can be used in a stand
alone application.

F-145
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
SPVLP, SDVLP Series
Electric Coils

Coil Selection Charts – Maximum kW


Conventional Staged Control
Allowable Maximum kW
1 Phase 3 Phase
Size cfm Range* L/s Range* Stages 120V 208V 240V 277V 480V 208V 480V 600V
4 100-225 47-106 1, 2 3.5 3.5 3.5 3.5 3.0 3.5 3.5 3.5
5 100-350 47-165 1, 2 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
6 100-450 47-212 1, 2 5.5 6.0 6.0 6.0 6.0 6.0 6.0 6.0
7 167-650 94-306 1, 2, 3 5.5 7.0 7.0 7.0 9.0 7.0 7.0 9.0
Notes:
8 167-800 94-377 1, 2, 3 5.5 10.0 11.0 11.0 11.0 11.0 11.0 11.0 1. Low watt density elements
9 243-1050 188-495 1, 2, 3 5.5 10.0 11.5 13.0 15.0 13.0 13.0 15.0 (Max 35w/in2)
10 243-1350 188-637 1, 2, 3 5.5 10.0 11.5 13.0 19.0 17.0 17.0 19.0 2. 1995 UL Certified as an assembly.
12 333-2100 283-991 1, 2, 3 5.5 10.0 11.5 13.0 23.0 17.0 30.0 30.0 3. Minimum kW
TERMINAL UNITS

- Single phase = 0.5 kW/stage


14 486-3000 424-1415 1, 2, 3 5.5 10.0 11.5 13.0 23.0 17.0 39.0 49.0
- Three phase = 1.5 kW
16 600-4000 566-1887 1, 2, 3 5.5 10.0 11.5 13.0 23.0 17.0 39.0 49.0 4. Min. based on air velocity of 200fpm
24 x 16 1200-8000 1415-3775 1, 2, 3 5.5 10.0 11.5 13.0 23.0 17.0 39.0 49.0 across the coil.


SCR
Allowable Maximum kW
1 Phase 3 Phase
Size cfm Range* L/s Range* 120V 208V 240V 277V 480V 208V 480V 600V
4 100-225 47-106 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
5 100-350 47-165 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
6 100-450 47-212 5.1 5.0 6.0 6.0 6.0 6.0 6.0 6.0
7 167-650 94-306 5.1 6.0 9.0 9.0 9.0 9.0 9.0 9.0
8 167-800 94-377 5.1 9.3 10.8 11.0 11.0 11.0 11.0 11.0
9 243-1050 188-495 5.1 9.3 10.8 12.4 14.0 15.0 15.0 15.0
10 243-1350 188-637 5.1 9.3 10.8 12.4 19.0 16.0 19.0 19.0
Notes:
12 333-2100 283-991 5.1 9.3 10.8 12.4 21.6 16.0 30.0 30.0 1. Low watt density elements (Max 35w/in2)
14 486-3000 424-1415 5.1 9.3 10.8 12.4 21.6 16.0 37.3 42.5 2. 1995 UL Certified as an assembly.
16 600-4000 566-1887 5.1 9.3 10.8 12.4 21.6 16.0 37.3 46.5 3. Minimum kW
24 x 16 1200-8000 1415-3775 5.1 9.3 10.8 12.4 21.6 16.0 37.3 46.5 - Single phase = 1.0 kW
- Three phase = 1.5 kW


Electronic Modulating Control
Allowable Maximum kW
1 Phase 3 Phase
Size cfm Range* L/s Range* 120V 208V 240V 277V 480V 208V 480V 600V
4 50-225 23-106 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
5 65-350 30-165 4.5 5.0 5.0 5.0 5.0 5.0 5.0 5.0
6 70-450 33-212 4.5 6.0 6.0 6.0 6.0 6.0 6.0 6.0
7 100-650 47-306 4.5 8.0 9.0 9.0 9.0 9.0 9.0 9.0
8 135-800 63-377 4.5 8.0 9.5 11.0 11.0 11.0 11.0 11.0
9 170-1050 80-495 4.5 8.0 9.5 11.0 15.0 14.0 15.0 15.0
10 225-1350 106-637 4.5 8.0 9.5 11.0 19.0 14.0 19.0 19.0 Notes:
12 305-2100 143-991 4.5 8.0 9.5 11.0 22.0 14.0 30.0 30.0 1. Low watt density elements (max 35w/in2)
14 440-3000 207-1415 4.5 8.0 9.5 11.0 22.0 14.0 33.0 41.5 2. NRTL/C and CSA certified coil
3. Minimum kW
16 570-4000 269-1887 4.5 8.0 9.5 11.0 22.0 14.0 33.0 41.5
- Single phase = 1.0 kW
24 x 16 1200-8000 566-3775 4.5 8.0 9.5 11.0 22.0 14.0 33.0 41.5 - Three phase = 1.5 kW
* Minimum air flow must be the greater of the minimum air volume listed or 70 cfm per kilowatt [33 L/s per kW].

F-146 All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
© Copyright Price Industries Limited 2011.
Single Duct Terminal Units
SPV, SDV Series
SPVLP, SDVLP Series
Electric Coils

Coil Selection Charts – Maximum kW


Price Silent Guard Control
Allowable Maximum kW
1 Phase 3 Phase
Size cfm Range* L/s Range* Stages 120V 208V 240V 277V 347V 208V 480V 600V
4 100-225 47-106 1, 2 3.0 3.0 3.0 3.0 -- 3.0 -- --
5 100-350 47-165 1, 2 3.4 5.0 5.0 5.0 -- 5.0 -- --
6 100-450 47-212 1, 2 3.4 6.2 6.0 6.0 -- 6.0 -- --
7 167-650 94-306 1, 2, 3 3.4 6.2 7.2 8.3 -- 9.0 -- --
Notes:
8 167-800 94-377 1, 2, 3 3.4 6.2 7.2 8.3 -- 10.5 -- -- 1. Low watt density elements
9 243-1050 188-495 1, 2, 3 3.4 6.2 7.2 8.3 -- 10.5 -- -- (Max 35w/in2)
10 243-1350 188-637 1, 2, 3 3.4 6.2 7.2 8.3 -- 10.5 -- -- 2. 1995 UL Certified as an
12 333-2100 283-991 1, 2, 3 3.4 6.2 7.2 8.3 -- 10.5 -- -- assembly.
3. Minimum kW

TERMINAL UNITS
14 486-3000 424-1415 1, 2, 3 3.4 6.2 7.2 8.3 -- 10.5 -- --
- Single phase = 0.5 kW/stage
16 600-4000 566-1887 1, 2, 3 3.4 6.2 7.2 8.3 -- 10.5 -- -- - Three phase = 1.5 kW
24 x 16 1200-8000 1415-3775 1, 2, 3 3.4 6.2 7.2 8.3 -- 10.5 -- -- 4. Min. based on air velocity of 200fpm
across the coil.

F-147
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
Single Duct Terminal Units
SPV, SDV Series
SPVLP, SDVLP Series
Electric Coils

Selection Guidelines

Electric Coil Selection 3. With the heating capacity known, 5. Static pressure loss of the coil elements
When selecting electric coils, the following confirm: is negligible, therefore minimum
points should be considered: a. Power Supply requirements from pressure is equal to the basic unit
coil selection charts. values.
1. Once the design air flow has been
determined refer to the appropriate b.
The minimum air flow 6. For stable operation of heater controls
air flow limits to select the size of unit requirements are met (at least 70 minimum discharge static pressure of
required to deliver the specified air flow. cfm/kW), and that the discharge 0.2 in. w.g. is recommended.
2. With size and air flow known, electric air temperature does not exceed
reheat capacity can be calculated. Refer 120 °F.
to the electric coil selection procedure 4. Select coil options.
below for details.
TERMINAL UNITS

How to Use the Chart


Electric Coil Selection Procedure Reheat Selection Chart
The selection of an electric coil for a single
duct terminal unit requires the determination
of the two components of the heat loss. One
component is the heat required to satisfy the
space load. The second component is the
heat required to raise the temperature of
the primary air to that of the space. This can
be determined as follows, using the Electric
Reheat Selection Chart and the equation as
given below.
1. Locate the room heat loss on the MBH
scale on the far left side of the chart.
Convert to kW by moving horizontally to
the right to the kW scale (1 kW = 3.413
MBH).
2. Calculate the kW required to heat the
primary air to room temperature using
the following equation:
kW = cfm x 1.08 x ∆T
3413
3. Add the kW value obtained in step 2
to the kW scale at the left side. Move
horizontally to the right to the point
where the kW value and the air flow
volume intersect.
4. With the point of intersection from step
three, the air temperature rise (ATR), can
be obtained by interpolating between
the air temperature rise lines on the
graph. Selection Example 5. Leaving air temperature = 58
5. To verify the selection, sum the air Select electric coil for a size 12 in. with a °F + 40 °F = 98 °F. Since the leaving
temperature rise and the temperature of minimum air flow of 700 cfm. Space heat air temperature is less than the
the primary air. The sum total should be loss is estimated at 20 MBH and space recommended maximum limit of 120 °F,
less than 120 °F. design temperature is 70 °F.The temperature the selection is satisfactory.
of the primary air flow is 58 °F. 6. Select a suitable power supply from the
1. Space heat loss (20 MBH) = 5.9 kW. Coil Selection Charts.
2. Heat required to raise the temperature 7. Verify minimum air flow requirements
of the primary air: are met. (Minimum 70 cfm/kW).
kW = 700 x 1.08 x 12 = 2.65 kW 700 cfm = 81 cfm/kW
3413 8.6 kW
3. Total heat required = 5.9 + 2.65 = 8.6 kW
4. Air temperature rise (ATR) = 40 °F

F-148 All Metric dimensions ( ) are soft conversion.


Imperial dimensions are converted to metric and rounded to the nearest millimetre.
© Copyright Price Industries Limited 2011.