Especificaciones Técnicas Cable 132kv
Especificaciones Técnicas Cable 132kv
Especificaciones Técnicas Cable 132kv
1.0 General
1.1 Name of manufacturer
2
- conductor size mm
2.5 Rated impulse withstand voltage (Up) (at altitude <1000m) kV 1050
2.6 Rated short duration power frequency withstand voltage (at kV 460
altitude <1000m)
3.0 Ratings
3.1 Maximum continuous direct-buried current rating, assuming,
- Maximum Soil thermal resistivity of 2.7K.m/W
- Touching trefoil configuration
- Special bonding of metal sheaths
For,
Guaranteed Current Rating (Single Circuit in Trench) A
Guaranteed Current Rating (Double Circuit in one Trench, A
distance between middle phases, s = 1500 mm)
Calculation Method IEC 60287
Page 1 of 15
220kV XLPE INSULATED CABLE SYSTEM UNIT DATA
Required Offered
3.2 Maximum continuous direct-buried current rating, assuming,
- Maximum Soil thermal resistivity of 2.7K.m/W
- Flat formation configuration
- Special bonding of metal sheaths
For,
Guaranteed Current Rating (Single Circuit in Trench) A
Guaranteed Current Rating (Double Circuit in one Trench, A
distance between middle phases, s = 1500 mm)
Calculation Method IEC 60287
o
3.4 Maximum permissible core temperature for continuous C 90
operation
Page 2 of 15
220kV XLPE INSULATED CABLE SYSTEM UNIT DATA
Required Offered
- Semiconducting binder tape yes
4.3 Insulation
- Material XLPE
- Nominal thickness mm
- Minimum thickness mm
- Nominal overall diameter mm
o
- Maximum continuous operating temperature C 90
- Compound Identification Reference yes
Maximum stress at nominal voltage
- At conductor screen kV/mm
- At insulation screen kV/mm
Maximum stress at impulse voltage
- At conductor screen kV/mm
- At insulation screen kV/mm
Page 3 of 15
220kV XLPE INSULATED CABLE SYSTEM UNIT DATA
Required Offered
- Minimum thickness mm
- Nominal overall diameter over bedding mm
5.0 Losses
5.1 Maximum dielectric loss per metre / phase when operating at W/m
nominal voltage and frequency and at maximum conductor
temperature
5.2 Maximum sheath loss per metre / phase when operating at W/m
nominal voltage and frequency and at current rating stipulated
in Item 3 with sheath bonded and earthed as recommended
(sectionalizing cross bonding)
5.3 Maximum conductor loss per metre / phase when operating at W/m
nominal voltage and frequency and at current rating stipulated
in Item 3.
5.4 Total loss of cable per metre / phase of three phase circuit W/m
Page 4 of 15
220kV XLPE INSULATED CABLE SYSTEM UNIT DATA
Required Offered
6.2 Maximum a.c. resistance of conductor at operating 1-Q/m
temperature
8.0 Testing
8.1 Routine Tests
- As per IEC 62067 Yes
- Additional tests specified in KETRACO spec. yes
8.2 Sample Tests
- 5Uo for 1 hour (as per KETRACO spec.) yes
8.3 Type Tests
- Test Regime IEC 62067
- Location of Test
- Date of Test
- Name of independent witness
8.4 Prequalification Test
- Test Regime
- Date completed
- Location of Test
- Name of independent witness
8.5 Commissioning Tests
- AC voltage withstand test 1.7Uo for 1 hour
Page 5 of 15
220kV XLPE INSULATED CABLE SYSTEM UNIT DATA
Required Offered
- Partial discharge monitoring <10pC
- Oversheath DC voltage test kV 12kV for 15
minutes
9.3 Maximal side wall bearing pressure to the cable at bending kN/m
points
Page 6 of 15
220kV CABLE SHEATH BONDING AND EARTHING EQUIPMENT UNIT DATA
Required Offered
1.1. Manufacturer
1.10. Maximum specified a.c. voltage which can be withstood for 2 sec.
MA
0
1.11. Conductivity characteristics of SVL at 20 V VV
- d.c. test current
- voltage limit minimal MQ
- voltage limit maximal 0 – 10 mA
0
C
1.12. Insulation resistance at 1000V d.c. voltage :: 10
2. LINK BOXES
2.1. Manufacturer
2.3. Type
- along the route
- at the terminal location Yes/no Lockable/
Buried
Page 7 of 15
220kV CABLE SHEATH BONDING AND EARTHING EQUIPMENT UNIT DATA
Required Offered
2.7. Material
- thickness of sheet
- material of gaskets Compound/
dry
- way of gasket fitting
3.1. Manufacturer
Page 8 of 15
220kV CABLE SHEATH BONDING AND EARTHING EQUIPMENT UNIT DATA
Required Offered
- Between conductor and screen kV kA 45
Page 9 of 15
220kV CABLE ACCESSORIES UNIT DATA
Required Offered
1. TERMINATIONS
1.1. Manufacturer
1.5.. Identifying reference number (for cross reference with type test)
1.6. Termination type (ODSE, OISE, GISE, wet type, dry type) ODSE
2. JOINTS
2.1. Manufacturer
2.6. Identifying reference number (for cross reference with type test)
Page 10 of 15
220kV CABLE ACCESSORIES UNIT DATA
Required Offered
2.8. Partial discharge sensor Internal
Page 11 of 15
FIBRE OPTIC PILOT CABLE SYSTEM UNIT DATA
Required Offered
1. FIBRE OPTIC PILOT CABLE
Page 12 of 15
FIBRE OPTIC PILOT CABLE SYSTEM UNIT DATA
Required Offered
1.32. Manufacturer quality system in accordance with ISO 9000 Yes/No Yes
- Applicable Standard
- Certified by (Company Name)
- Certification valid till (year)
Page 13 of 15
FIBRE OPTIC PILOT CABLE SYSTEM UNIT DATA
Required Offered
corrosion resistant
2.8. Dimensions mm kg
Page 14 of 15
3. OPTICAL TERMINAL BOX
3.1. Name of manufacturer
3.9. Dimensions mm kg
Page 15 of 15