Shark 270 Revenue Energy Meter Brochure E159710
Shark 270 Revenue Energy Meter Brochure E159710
Socket Form
Switchboard Form
Electro Industries/GaugeTech™
The Leader in Power Monitoring and Smart Grid Solutions™
Description • Transformer/line loss and CT/PT compensation (test certificate
available)
The Shark® 270 is a socket and switchboard form revenue meter • Test mode and energy presets
designed for both critical meter applications and switchboard
commercial/industrial metering applications. It is a significant departure • Multifunction measurement including voltage, current, power,
from existing technology, incorporating high-end revenue metering func- frequency, energy, etc.
tions in an economical design.
• Configurable pulse accumulators and aggregators
The Shark® 270 meter is a full four quadrant, bidirectional revenue meter • Ten logs, including six historical logs for trending data
that can also be used for inter-tie metering. Its 0.1% energy class meets
• Up to 128 MB memory for logging and data storage and analysis
and/or exceeds all the accuracy requirements of ANSI C12.20 Class 0.1%
and IEC 62053-22 CL 0.2S. The meter has advanced revenue metering • Power quality measurement of THD and alarm limits,
features that allow it to be used not only for measuring basic energy, symmetrical components, voltage and current unbalance
but also for providing a full complement of necessary tools, such as
transformer/line loss compensation, CT/PT compensation, advanced test • Sampling rate of up to 512 samples per cycle for waveform
mode, perpetual TOU, and extensive logging for interval energy storage. recording
The Shark® 270 meter also has one of the industry’s most Accuracy
comprehensive communication capabilities, including extensive Ethernet
functionality and 4G LTE™ underglass cellular. It can send out data via a Parameters Accuracry
host of protocols, including Modbus, Level 2 DNP3, and IEC 61850, to Voltage L-N [V] 0.1% of reading
Note: See the Shark® 270 Meter User Manual for full accuracy specifications.
• 0.1% revenue certified energy and demand metering • Primary revenue metering
• Advanced metering infrastructure
• Meets ANSI C12.20 Class 0.1% and IEC 62053-22 CL 0.2S
• Customer power quality
• Time of Use functionality • Grid monitoring and substation metering
• Distribution energy
• Industrial and commercial metering and sub-metering
2
Primary Revenue Metering Time of Use
Energy Metrology - 0.1% Class Certified The Shark® 270 meter uses a perpetual Time of Use (TOU) calendar that
only needs to be set up once. The TOU implementation allows the user to
set up multiple rates to meet any contractual obligation. It also allows the
Utilities today face many challenges when metering customers. Installed
user to customize any energy parameter for TOU. The 16 available TOU
meters need to be highly accurate and verifiable. Due to reductions in
registers can be configured not only for TOU built-in energy readings, but
labor force, modern meters need to be both reliable and designed for a
also for any stored data from pulses.
long operation life. The Shark® 270 meter meets these requirements
with advanced metering technology and superior engineering to improve
reliability. • Perpetual TOU calendar – set up only once and use indefinitely
In addition to test mode pulses, the meter has one standard KYZ pulse
output, and up to 8 optional pulse outputs, that allow the meter to deliver
energy pulses to a separate recorder, RTU or other type of energy data
collector.
Loss Compensation
The meter can also function as a recorder itself, by accepting up to 8
The meter can compensate energy readings for transformer and line optional pulse inputs. These energy values can be logged by the meter’s
losses. This allows a utility to properly bill a customer for usage, even if internal profiling memory, allowing for energy flow analysis over time,
the meter is placed on the secondary side of the transformer. which is useful for billing, planning and/or circuit efficiency analysis. The
input values can also be totalized in the meter's aggregators.
Two test pulses located on the meter's face can be used to simultaneously
test watt hour and VAR hour readings for accuracy verification. When
placed into test mode, the unit freezes and stores all the energy
parameters, allowing users to test and verify energy accuracy without
changing meter readings. The meter can also receive preset energy
values, so that it can replace an existing field installation, without
CT/PT Compensation disturbing faceplate monthly energy reads.
Two
For stringent accuracy requirements, the meter can compensate for the Programmable
Test Pulses
inaccuracies of the instrument transformers. The Shark® 270 meter has
built-in features that allow a utility provider to adjust the energy meter to Display Shows
Test Status Image Face
compensate for these inaccuracies, using both amplitude and phase angle
adjustments. Test Mode
Button
3
Unique Screen Designer Normal Mode
The Shark® 270 meter provides one of the industry’s most advanced LCD • Wh delivered and received • Com port settings
display configuration technologies - the Screen Designer, which lets you
• VAh delivered and received • Peak Rolling Window
create fully customized display screens for any specific application. Use
demand
the Screen Designer to build user display screens that provide information • VARh delivered and
on anything the meter measures. In addition to the custom displays, the received • Peak Block Window
meter comes pre-programmed with multiple display screens. demand
The meter’s memory has 250 slots for custom and/or pre-programmed
screens. These slots can be allocated to any view mode, with any number
of slots used in each of the modes.
• Provide ambient and transformer temperature, or any other Select from a large offering of diagnostic screens, such as:
desired critical operational data
• Use the meter as an aggregator and display total usage • Voltage phase angles • Segment checks
• Phasor diagram
4
Data Trending & Analysis • Voltage unbalance • Based on % of full scale
settings
• Current unbalance
The Shark® 270 meter has up to 128 MB of memory for data logging,
Test Mode and Energy Presets
used for historical trends, limit alarms, I/O changes and sequence of
events. The meter's advanced storage means the unit can be programmed
to store historical and waveform data for many years. The unit's real-time To protect critical billing information, the meter records and logs the fol-
clock allows for time stamping of all the data in the instrument when log lowing with a time stamp:
events are created. The clock is accurate to 3 ppm and is very stable over
temperature. • Demand resets • Critical data repairs
Programmable settings
Historical Logs • System startup changes
• Energy resets • Password requests/sealing
• 6 assignable historical logs
• Log resets switch changes
• Independently programmed
trending profiles Power Quality Measurement &
• Up to 64 parameters per log Analysis
Historical Trending The Shark® 270 meter records up to 512 samples per cycle for a voltage
System Events Log sag or swell, or a current fault event. The unit provides the pre and
post-event recording capability shown in the table below. Waveform
records are programmable to the desired sampling rate. V5 provides up to
To protect critical billing information, the meter records and logs the fol-
128 MB of storage.
lowing with a time stamp:
Limit/Alarm Log
Waveform Scope
5
Standard & Optional 3. INP300S: IEC 61850 Protocol Ethernet Card*
Communication Capabilities
• Simultaneous Modbus TCP/IP and IEC 61850
• 5 simultaneous MMS clients
The meter has a standard RS485 serial port that can be used for either • Multiple Logical Nodes, including LLN0, LPHD,
Modbus RTU /ASCII or Level 2 DNP3. The optional INP100S Ethernet card MMXU, MHAI, MMTR, and others.
allows the meter to speak multiple sessions of Modbus TCP and DNP3. • Polled operation mode (queried reports)
The optional INP300S Ethernet card allows the meter to speak via Modbus • Buffered and unbuffered reports
TCP and IEC 61850. The meter supports different communication options, • Configurable .CID file
including serial, Ethernet, and optical. Using these, the meter connects to • Offers Enhanced security to protect from unau-
multiple third party systems and to EIG’s meter reading software, Energy thorized programming of meter settings
Manager EXT.
The Shark® 270 meter offers unequaled I/O 5. 20mAOS: Four Channel 4-20 mA Outputs
expandability. Using the two universal option slots, configure the
meter to accept I/O cards. The unit auto-detects installed I/O option cards.
• Assignable to any parameter
Up to 2 cards can be used per meter. The Shark® 270 meter is able
• 0.1% of full scale
to send data to many different systems, using multiple open protocols.
• 850 Ω at 24 V DC
These protocols include Modbus RTU/ASCII/TCP, DNP3 and IEC 61850.
• Loop powered using up to 24 V DC
The meter’s communication architecture is flexible, and designed to
• Ideal for any process control application
integrate directly into most existing systems.
1. RS1S: Serial Communication Card 6. PO1S: Four Pulse Outputs / Four Status Inputs
• Embedded web server, smartphone compatible 7. RO1S: Two Relay Outputs / Two Status Inputs
• Network Time Protocol (NTP) support (Network
Clock Sync) • 30 V AC / 30 V DC - 0.25 A relays, form C
• 12 simultaneous Modbus TCP/IP connections • Trigger on user set alarms
• Simultaneous Level 2 DNP3 over • Set delays and reset delays
TCP/IP connections • Status inputs – dry contact status detection, only
• Supports Alarm emails and periodic email • Allows for control, alarm and status (must be at
notification of meter status/reading data V4 or higher for limit alarms and control)
• Offers enhanced security to protect from
unauthorized programming
*Only one Ethernet or 4G LTE™ card is allowed per socket meter.
• Supports Data push to cloud servers
Two Ethernet cards are supported in the switchboard case meter.
6
Shark® 270 Underglass 4G LTE™
Wireless Cellular Communication
(4GLTE)*
• Verizon certified
* 4GLTE is not available with the switchboard case meter. Only one 4GLTE card is supported per socket meter.
7
V-Switch™ Key Technology
The Shark® 270 meter is equipped with EIG's V-Switch™ key technology.
This technology uses an algorithm to generate a code that activates more
advanced features for the meter. This code can be applied in the field,
without needing to remove the meter from installation. Below is a list of
the features available for each V-Switch™ key:
*See the Shark® 270 Meter Modbus Protocol Application Guide for instructions on • Wiring follows industry conventions, eliminating the need for
using Modbus with the meter. new wiring
Meter Seal
8
Utility Metering
Highly Accurate Measurements for Grid Metering Power Quality and Fault Analysis
and Power Generation
The Shark® 270 meter’s power quality features allow a user to not only
The Shark® 270 meter is designed with the latest DSP technology, analyze real time data, but to have access to fault data and power quality
providing highly accurate measurements that allow users to obtain reliable information, via a host of analytical tools. These tools provide easy con-
data for inter-tie billing, power generators and alternative energy solutions. version to COMTRADE and PQDIF formats, making the meter very helpful
The meter provides a versatile, reliable solution for measuring energy and in standardizing fault data power system-wide. The meter measures and
providing accurate cost analysis and allocation. records critical power quality data such as harmonics, PF and phase
imbalance, to provide advanced analysis options for improving power
system reliability.
With the Shark® 270 meter, the user obtains advanced communication
usually found only in higher-end, more costly, solutions. Whether it’s
communicating DNP3 or IEC 61850 in smart substation applications, the
meter has the ability to send data to multiple software systems, provid-
ing real time information as well as stored interval data. The Shark® 270
meter is capable of communicating with an RTU to bring SCADA informa-
tion back via one protocol, while itself being evaluated by other software
systems for interval or power quality analysis.
IEC 61850
Ethernet
Serial
Level 2 DNP3
Alarm Indication
Voltage Sag Waveform Zoomed
Control Relay Outputs
9
Industrial & Commercial Energy Diagnose Power Quality Events at Incoming Circuts
Metering
With the Shark® 270 meter, a facility manager or engineer can view
power quality events that occurred at the incoming service point, allowing
The Perfect Upgrade Solution to Existing Mechanical
Meters him or her to analyze the cause of these events and implement remedia-
tion. With the Shark® 270 meter’s power quality information, users will
be able to see how many events occurred and what types of events were
The Shark® 270 meter is an ideal upgrade to existing, non-communicat-
experienced, and also be able to determine if these events could affect
ing mechanical, or older solid state, meters. By just replacing the existing
their installed sensitive equipment.
meter with the new Shark® 270 unit, the basic metering capability is
transformed into a communicating solution. With the standard Shark®
270 unit, the meter is provided with an RS485 Modbus port. With the Power quality events include records of faults, voltage surges and sags,
optional Ethernet module, the meter is capable of communicating over harmonics, imbalances, power factor and many other indices. This data is
Ethernet to send Modbus data to most standard energy management and automatically collected and stored in remote databases for system-wide
building automation systems. analysis.
The Ethernet capability of the Shark® 270 meter offers many advanced
features that are useful for industrial and commercial applications. In ad-
dition to communicating via Modbus TCP, the meter can be configured to
send emails on alarm conditions. These emails allow facility managers to
be made aware of high demand conditions, alarms and other issues that
affect both energy reliability and cost.
The email feature also allows users to send periodic notifications of val-
ues, such as demand and energy consumption. This is useful for energy
dashboards and other cloud software applications, which can receive data
on usage and alarms in this way. And it is essential for IOT applications,
in which a user wants to integrate many, or all, electrical appliances and
pieces of apparatus.
Multi-Cycle Waveform Fault Power Quality Events
The Shark® 270 meter also supports data push to cloud servers that use
the JSON structure, such as Lucid's BuildingOS. The meter can send up to
15 meter readings to the cloud service, to support cloud-based building
management applications.
10
Shark® 270 Socket Meter Dimensional Drawings
7.03 in
17.87 cm
7.51 in
19.08 cm
6.96 in 8.75 in
17.68 cm 22.23 cm
7.51 in
6.96 in 0.87 in 19.08 cm
17.68 cm 2.21 cm
10.4 in
26.42 cm
2.02 in
5.13 cm
6.84 in
17.37 cm 9.46 in
24.03 cm
11
Shark® 270 Socket Meter Wiring Diagrams
3
FORM: 9S (TRANSFORMER RATED) 3
3
FORM: 36S (TRANSFORMER RATED) SERVICE: WYE / DELTA, 4 WIRE
SERVICE: WYE, 4 WIRE NO PTs, 3 CTs
NO PTs, 3 CTs 1
1 LINE
LINE
*REFFER TO SHORTING BLOCK
V3 V2 V1 N 2 1
INSTRUCTIONS TO APPLY
*REFFER TO SHORTING BLOCK SHORTS
V3 V2 V1 N
INSTRUCTIONS TO APPLY 2
SHORTS
2
*
*
*
*
*
*
Earth Ground
Earth Ground
N
V1
V1 V2
N V3
V3 FUSES
FUSES
LOAD
LOAD
Earth Ground
Earth Ground
3
FORM: 45S (TRANSFORMER RATED)
SERVICE: DELTA, 3 WIRE
NO PTs, 2 CTs
LINE
Earth Ground
V1
V2
V3
FUSES
LOAD
Earth Ground
12
Shark® 270 Switchboard Case Dimensional Drawings
21.51 cm
[8.47 in]
[10.74 in]
27.28 cm
[1.150 in]
2.92 cm
[7.85 in] [5.99 in]
19.94 cm 15.21 cm
Front Back
Dimensions Dimensions
[6.34 in]
16.10 cm
20.21 cm
[7.96 in]
[8.97 in]
22.77 cm
Side
Dimensions
13
Shark® 270 Switchboard Form Meter Wiring Diagrams
3
3 FORM: 9S (TRANSFORMER RATED)
FORM: 9S (TRANSFORMER RATED) 3
SERVICE: DELTA, 3 WIRE
SERVICE: WYE / DELTA, 4WIRE
2 PTs, 2 CTs
3 PTs, 3 CTs
N
1 LINE CT Shorting Block
CT Shorting Block EI# SB-6TC 1
LINE EI# SB-6TC N V3 V2 V1
*REFER TO SHORTING BLOCK
*REFER TO SHORTING BLOCK INSTRUCTIONS TO APPLY
INSTRUCTIONS TO APPLY 2 1 SHORTS
V3 V2 V1 N SHORTS
2
I3-HI
I3-HI *
* I3-LO
I3-LO
*
I2-HI
I2-LO
I1-HI
I1-HI NETWORK 1 CONN.3 NETWORK 2 *
* RS-485/KYZ
I1-LO
I1-LO REFER TO METER
-
Earth Ground
NEUTRAL
Earth Ground
L N
(+) (-)
GND V1 Vn Vc Ia-Lo Ia-Hi Ib-Lo Ib-Hi Ic-Lo Ic-Hi Vb Va
Vn Vc Ia-Lo Ia-Hi Ib-Lo Ib-Hi Ic-Lo Ic-Hi Vb Va
V2
V1 Earth Ground
V3
Earth Ground
V2
V3
N
FUSES
*
FUSES
* LOAD
Earth Ground
Earth Ground
N
V3
I1-LO
I1-HI
I2-LO
I2-HI
I3-LO
I3-HI
V2
V1
LOAD
N
V3
I1-LO
I1-HI
I2-LO
I2-HI
I3-LO
I3-HI
V2
V1
The CONN20163 terminal breakout box lets you connect the Shark® 270
meter to your equipment in a simple, one-step process. The CONN20163
gives you access to the meter's high accuracy without having to change
your current wiring scheme. Simply use the kit's cable to connect
from one of the meter's RJ45 I/O connectors to the RJ45 port on the
CONN20163 unit. The CONN20163 converts the RJ45 cable connection
to an 8 pole screw terminal receptacle that you can use to connect I/O
wiring to your equipment, saving you time and providing a convenient
point of termination.
Conn20163
14
Specifications
Sense Inputs 36S, 2 x L-N: 50/45 V AC • RS485 Transceiver; meets or Internal Battery (for Time
Electrical Ratings • 4W Delta service, Form 9S, 3 x exceeds EIA/TIA-485 Standard Only):
Current: L-N: 70(40)/52(30) V AC - high • Type: Two-wire, half duplex • 3V Lithium Battery maintains time
• Transformer rated (low) phase • Min. input impedance: 96 kΩ during outages - part #BATT21214
• Two or three current inputs depending • 3W Delta service, Form • Battery life 10 years from date of
• Max. output current: ±60 mA
on Form (Ia, Ib, Ic) 45S, 3 x L-L: 65/55 V AC manufacture when
• Wh Pulse: properly installed in meter
• Class 2 - 1 A nominal, burden 0.0112 • Absolute minimum startup/dropout
VA at 2 A Input/phase voltage for externally powered , fully • KYZ output contacts, and infrared Compliance:
loaded unit ("-SE" option), at 75/70 LED light pulses through face
• Class 20 - 5 A nominal, burden • ANSI C12.18 (Type 2 Optical Port)
V AC or DC plate - "P" light port, Kh value is
0.0112 VA at 20 A Input/phase user definable • ANSI C12.20 Certified 0.1% Accuracy
• Pickup Current: Shall begin reading at • Frequency range: (45 to 65)Hz or DC Class
• Pulse Width: 100 ms, fixed
0.001 A (1 mA) for Class 2 and 0.005 • Ride through characteristics at 120 • CE (IEC 61000-6-2 & IEC 61000-
A (5 mA) for Class 20 V maximum power consumption: • Full Scale Frequency: ~5 Hz
6-4)
• Continuous maximum ratings: Class ~33 ms • Contact type:
• FCC Class B (Radiated and
2 - 5 A AC Class 20 - 30 A AC • Power consumption (burden), SPDT (NO – C – NC)
Conducted Emissions)
maximum: 8 VA/4.5 W per Phase – • Relay type: Solid state
• Overcurrent ratings as the • IEC 61000-4-2 (Electrostatic
with 3 phase supply; Typical burden
factor of Current Class: 5x - for 10 • Peak switching voltage: Discharge)
with 1 Ethernet Card installed: 3.3
seconds, 15x - for 3 seconds, 25x - AC/DC 30 V • IEC 61000-4-3 (Radiated EM
VA/1.7 W per phase – at 3 phase
for 1 second • Continuous load current: Immunity)
120 V AC
• The current inputs are only to be 120 mA • IEC 61000-4-4 (EFT)
Display:
connected to external CTs
• Graphical back-illuminated TFT LCD • Peak load current: 350 mA for • IEC 61000-4-5 (Surge Immunity)
Voltage: 10 ms
programmable display • IEC 61000-4-6 (Conducted
• Absolute Maximum rating, between • On resistance, max.: 35 Ω Immunity)
• Pre-configured screens and Screen
any voltage inputs: Unit with external
Designer for fully customized screens • Leakage current: 1 μA maximum • IEC 61000-4-7 (Harmonics)
power connection: 720 V AC; Unit
powered from voltage blades ("-S" • Size: 2.7" • Isolation: 3750 V AC • IEC 61000-4-8 (Magnetic Immunity)
option): 576 V AC • Resolution: 400 X 240 • Reset state: (NC - C) Closed: (NO • IEC 61000-4-11 (Voltage Variations
• Supported common Power Mains Isolation: - C) Open immunity)
with direct voltage connections: • Between human accessible I/O Clock Timing: • IEC 61557-12 (Performance
Forms 9S, 36S, 45S with blade ("-S") connections and power, voltage, measuring and
• Internal Clock Crystal - accuracy
or external ("-SE") power option; current inputs: 2500 V AC better than 15 seconds per month monitoring devices (PMD))
57.7/100 V, 69/120 V, 120/208 V, • IEC 62052-11 (General
• Between power and voltage and • Line Frequency Clock
230/400 V, 277/480 V; Form 45S requirements, testing, and test
current inputs: 2500 V AC Synchronization - accuracy
with external ("-SE") power option conditions)
only: 347/600 V; for lower or higher • Between human accessible I/O better than 1 second per month
connections: 500 V AC • Internet synchronization with optional • IEC 62053-22 CL 0.2S (0.2%
voltage Power Mains use voltage
• Isolation is Hi-Pot test verified in Network card (SNTP Protocol) Accuracy)
transformers
factory 4G LTE™ Option: • IEC 62053-23 (Static meters for
• Input Impedance: 4 Mohm per phase
Memory: reactive energy)
• Surge withstand. See compliance • Carrier: Verizon certified
• Up to 128 MB of Flash memory • IEC/CISPR 11 (Radiated Emissions)
section for details • LTE™/4G Category: Cat-1
Standard • IEEE C37.90.1 (Surge Withstand)
• Burden: with external power connec- • LTE™/4G Band: 1700/2100/700 MHz
tion: 0.09 VA/input at 600 V AC (4 Communication: • IEEE C62.41 (Surge Immunity)
• Dual antennas for greater sensitivity
MΩ/input); Unit powered from volt- • LCD display and reception • EU Directive 2011/65/EU (RoHS 2
age blades: see power supply ratings Directive)
• ANSI Type 2 Optical port • Modbus TCP compliant
Power Supply: • REACH Compliant
• RS485 serial port • MV90 Capable
• Input Voltage range: Shipping
• Modbus® RTU, Modbus ASCII and Environmental
• Absolute maximum continuous: 576 Level 2 DNP3 protocols Dimensions Socket:
(Temperature Specifications to
V AC (between any voltage inputs in • Data Speeds of up to 57600 bps Indirect Light): • Size: 10" W x 10" D x 12" H
blade powered units, "-S" option); • Weight: 4.4 lbs./1.83 kg (with Option
Optional • Operating Temperature: (-40 to
277 V AC or 400 V DC (externally cards 5.6 lbs./2.54 kg)
Communication: +70) °C
powered units, "-SE" option)
• INP100S: 10/100BaseT Ethernet with • Display Operating Switchboard:
• Absolute minimum startup/
Total Web Solutions Temperature: (-30 to +60) °C • Size: 13" W x 10" D x 11" H
dropout voltage for blade powered,
fully loaded unit ("-S" option), at 60 • INP300S: IEC 61850 Protocol server • Humidity: 95% RH • Weight: 16 lbs./7.25 kg (with Option
Hz. All applicable blades are • Modbus TCP/IP, Level 2 DNP3, IEC noncondensing cards 19 lbs./8.62 kg)
symmetrically energized: 61850 • Storage Temperature: (-40 to +85) A-Base:
• 4W Wye service, Form Standard KYZ/RS485 Card °C • Size: 14.5" W x 16" D x 11" H
9S, 3 x L-N: 45/35 V AC Specifications: • Raintight Lexan Cover, UV protected • Weight 9 lbs./4.08 kg (with
• 4W Wye service, Form • RS485 Port: • Protection Class: front IP65, rear IP51 Option cards 9.5 lbs./4.31 kg)
15
Ordering Chart
Ordering Information - All fields must be filled in to create a valid part number.
Model Form Frequency Current V-Switch™ Power I/O Slot 1 I/O Slot 2 Custom
Class Pack Supply
Option
Numbers: - - - - - - - -
Shark270 9S 60 2 V1 S X X X
(Revenue Meter) 3 Element 60 Hz 2A Multifunction Meter Blade Powered No Option No Option No Option
System Secondary (Not available for
SWB3)
36S 50 20 V2 SE PO1S PO1S MC
2.5 Element 50 Hz 20 A Standard Data Logging Externally Powered 4 Pulses/4 Inputs 4 Pulses/4 Inputs Measurement
System Memory Canada Seal
Accessories
Software Communication Converters Standalone I/O Module Kits for the Shark® 270 Socket
Form Meter*
COMEXT4P1Y Communicator EXT™ 4.0 E159343 RS485 to USB Converter Cable PO1S-KT 4 Pulses/4 Inputs plus cable
Software for Windows Single-
Computer License (One Year)
Unicom 2500 RS485 to RS232 Converter RO1S-KT 2 Relays/2 Inputs plus cable
Conn20163-KT Terminal Breakout Box Kit for I/O (converts 20mAOS-KT 4 Channel, 4-20 mA, Analog Outputs plus cable
RJ45 cable connection to an 8 pole screw
terminal receptacle)
1mAOS-KT 4 Channel, 0-1 mA, Analog Outputs
RS1S-KT RS232/RS485
* I/O cards can be ordered separately using the part numbers shown above.
** Only one of these cards can be ordered per meter for the socket form. Two cards can be ordered for the switchboard form.