Short Circuit Converter

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 10

"FAULT MVA TO THEVENIN IMPEDANCE" CONVERTER read comment

Enter the Voltage Level, Fault MVA, and X/R ratio:


Voltage Level in kVLL 69.000000
MVA 79.635300
3PH Fault
X/R ratio 2.519600
MVA 61.125000
SLG Fault
X/R ratio 2.969200

ANALYSIS RESULT:
Actual Impedance in Ohms
R1 22.054470
Z1
X1 55.568444
R2 22.054470
Z2 = Z1
X2 55.568444
R0 30.472368
Z0
X0 110.309935

Per-Unit Impedance in p.u. (Enter Base MVA)


kVbase 69.0000
Enter MVAbase 10.0000
Zbase 476.100000
R1pu 0.046323
Z1pu
X1pu 0.116716
R2pu 0.046323
Z2pu = Z1pu
X2pu 0.116716
R0pu 0.064004
Z0pu
X0pu 0.231695

Computation for Z1, Z2 Computation for Z0


Voltage Level in kVLL 69.000000 Voltage Level in kVLL 69.000000
Z1 59.785045 Re(2Z1 + Z0) 74.581309
θ 1.192975 Im(2Z1 + Z0) 221.446822
R1 22.054470 R1 22.054470
X1 55.568444 X1 55.568444
θ 1.245937
R0 30.472368
X0 110.309935
"THEVENIN IMPEDANCE TO FAULT MVA" CONVERTER

Enter the Thevenin Impedance:


R1 22.054470
Z1
X1 55.568444
R2 22.054470
Z2 = Z1
X2 55.568444
R0 30.472368
Z0
X0 110.309935
Fault Impedance RF 0.000000
Voltage Level in kVLL 69.000000

ANALYSIS RESULT:
Fault Current, Amps 666.340027
3PH Fault MVA 79.632964
X/R ratio 2.519600
Fault Current, Amps 511.457032
SLG Fault MVA 61.123207
X/R ratio 2.969200

3-Phase Fault Calculator using Actual Impedance in Ohms: 3-Phase Fault Calculator using Impedance in pu:
VLN in kV 39.8371685741 Enter Base MVA
Z1 22.0544704727245+55.5684438030767i Base kV
Z1 + RF 22.0544704727245+55.5684438030767i Base I
3PHF/1000 0.245810243034644-0.619343488350089i Base Z
I3PHF 245.810243034644-619.343488350089i Z1pu
I3PHF (magnitude) 666.3400274202 RFpu
3PH FAULT MVA 79.6329639969 Z1pu + RFpu
X1 55.568444 I3PHFpu
R1 22.054470 I3PHFpu (mag)
X1/R1 2.5196 I3PHF actual

Single Line to Ground Fault Calculation using Actual Impedance in Ohms: Single Line to Ground Fault Calculation using Imp
VLN in kV 39.8371685741 2Z1pu
Z1 = Z2 22.0544704727245+55.5684438030767i Z0pu
Z0 30.4723679717211+110.309934830708i 3RFpu
2Z1 44.108940945449+111.136887606153i ISLGFpu
2Z1 + Z0 74.5813089171701+221.446822436861i ISLGFpu (mag)
(2Z1 + Z0)/3 24.8604363057234+73.8156074789537i I3PHF actual
(2Z1 + Z0)/3 + RF 24.8604363057234+73.8156074789537i
ISLGF/1000 0.163244512399439-0.484705606216413i
ISLGF 163.244512399439-484.705606216413i
ISLGF (magnitude) 511.4570319452
ISLGF FAULT MVA 61.1232069737
2X1 + X0 221.4468224369
2R1 + R0 74.5813089172
(2X1+X0)/(2R1+R0) 2.969200
0
30

Fault Calculator using Impedance in pu:


10.0000
69.0000
83.673952
476.100000
0.0463231893987072+0.116715908008983i
0
0.0463231893987072+0.116715908008983i
2.9377152267023-7.40186728519914i
7.963530
666.34002742

ine to Ground Fault Calculation using Impedance in pu:


0.0926463787974144+0.233431816017965i
0.0640041335259842+0.23169488517267i
0
1.95095974777519-5.79278968309407i
6.112500
511.45703195
IN PER UNIT QUANTITY:

Where: Vf = nominal line-to-line voltage in pu; Vf = 1.0


a = 1<120 deg

IN ACTUAL QUANTITY (OHMS) from DISTRIBUTION SYSTEM HANDBOOK by TA Short:

From Basler Transformer Pro


From Basler Transformer Protection Guide: