Professional Documents
Culture Documents
Mozina2003 PDF
Mozina2003 PDF
Mozina2003 PDF
MOODY
E
LECTRICAL GENERATION AT PAPER in Maryland, USA, where 1960-vintage electromechanical
mills is becoming an increasingly critical as- relays were replaced with modern digital protection. This
set and should be well protected from faults, article points out the advantages of this technology versus
system upsets and abnormal operating con- conventional electromechanical protection and also dis-
ditions. The loss of a major generating unit for an extended cusses the unique application considerations in applying
period would result in very costly replacement power and re- digital protection.
pair costs for any paper mill. This article presents the reasons Background
why mill generator owners should consider upgrading the Contrary to popular belief, generators do experience short
electrical protection of their generators to meet today’s stan- circuits and abnormal electrical conditions. In many cases,
dards. It specifically outlines the risks assumed in protection equipment damage due to these events can be reduced or
areas where 20-year-old (and older) generator protection is prevented by proper generator protection. As generators
inadequate. The article relates the experience of completed become older, the likelihood for failure increases as insula-
protection upgrade projects at MeadWestvaco’s Luke Mill tion begins to deteriorate. Generators, unlike some other 37
1077-2618/03/$17.00©2003 IEEE
power system components, need to be Significant improvements in protec-
protected not only from short circuits, tion using multifunction digital relays
but also from abnormal operating condi- ELECTRICAL are described in the first sections of this
tions. Examples of such abnormal condi-
tions are overexcitation, loss-of-field,
GENERATION AT article. The protection system improve-
ments applied by Luke Mill are discussed
and unbalanced currents. When sub- PAPER MILLS IS in detail with several benefits to mill
jected to these conditions, damage or generation operations noted. The process
complete failure can occur within sec- BECOMING AN of upgrading generator protection af-
onds, thus requiring automatic detec- forded an excellent learning experience
tion and tripping. INCREASINGLY for mill personnel in understanding the
In the late 1980s, the IEEE Power Sys- protection scheme, both from an engi-
tem Relay Committee first issued CRITICAL ASSET. neering and operations standpoint. The
ANSI/IEEE C37.102, the guide for the new Luke Mill generator relays are lo-
protection of synchronous generators [1]. cated a considerable distance from the
Most of the recommended practices applicable to indus- plant control room. The communications capabilities of
trial-sized generators have been incorporated in the latest re- the newly installed relays were used to remotely display re-
vision of The IEEE Buff Book [2]. These industry guides lay data to the control room for rapid operator analysis.
outline current recommended practices for the protection of
generators and document the substantial changes that have Areas of Protection Upgrade
occurred in generator protection over the last 20 years. These on Older Mill Generators
changes fall into three broad categories: improved sensitiv- The areas of upgrade on generator protection that is 20
ity, new protection areas, and special protection applica- years old or more fall into three broad categories:
tions. These are the key functional areas that need to be n Improved sensitivity and reduction of damage in
addressed when developing an upgrade program to bring protection areas where older relaying does not pro-
generator protection up to current industry standards. vide the level of detection required. Examples of pro-
The protection at the Luke Mill is a typical example of tection in this area are the following:
generator protection installed in the 1960s, employing n stator ground and ground differential protection
electromechanical relays that remained basically un- n field ground fault protection
changed since they were commissioned decades ago. The
I EEE I NDUSTRY A PPLI CA TI ONS MA GA ZI NE • MA R|A PR 2003 • WWW.I EEE.ORG/I A S
Power
Improved Sensitivity and Reduced Damage
G
System
Stator Grounding and
Ground Differential Protection
Isystem
When a generator stator ground fault is detected by protec-
tive relays, the generator is shut down by tripping the gener-
ator breaker, field breaker, and turbine. The system
contribution to the fault will immediately be removed when
Current the generator breaker trips, as illustrated in Figure 1. The
Igen current ground decay generator stator ground current, however, will continue to
flow after the tripping. The generator short-circuit current
cannot be “turned off” instantaneously because of the stored
energy in the rotating machine. The flow of damaging gen-
erator fault current will continue for several seconds after the
Time (s)
0 generator has been tripped. This long decay time results in
the vast majority of the damage occurring after tripping [3].
Generator Reducing the decay time is very difficult; however, reducing
Breaker Trips
1 the fault current during the generator “coast-down” can be
done. As machines get older, the possibility of stator ground
38 Generator ground-fault relay. faults increase. Reducing the damage, therefore, becomes a
major objective. Recent high Utility System
costs and long outages of mill gen-
erators have caused engineers to R
ponder the problem of reducing
Typically
ground fault damage during gen- 200-400 A A
erator coast-down. The most To Other
promising solution is called hy- Bus Sections
brid generator grounding. Industrial System Bus
B
In mill applications, generators
are directly connected to a bus that
services the local load. Figure 2 il-
lustrates this type of configuration.
Hybrid grounding can be typically Mill Load
applied to these types of generators.
The generator is both high- and
low-resistance grounded. Under 87G
normal operating conditions, both
generator ground sources are oper-
ated in parallel. For ground faults G
on the mill system, the ground fault
contribution from the generator
will typically be almost entirely
from the low-resistance (200-400 51G
A) source. This provides the re-
Ground
quired level of system ground cur- Interrupting
59N
rent for proper mill ground relay Device R Typically
operation, allowing the generator to 200-400 A
supply the mill load when the util-
ity system is unavailable (breakers
where
n −31 O is the residual current from the bus side CTs
n I N especially, electronic is the generator neutral cur- 87 - Generator
Differential
rent 51 87G - Generator
n Θ is the phase angle between the currents. G Ground Differential
The scheme is illustrated in Figure 3. The use of digital 51G - Neutral Overcurrent
R
technology allows the scheme to be applied using the nor-
mal complement of generator CTs without the need for aux- 3
iliary CTs. The 87G was an upgrade area on the Luke Mill
generators that previously had only 87-phase differential Sensitive stator ground fault protection. 39
protection. This change substantially im- chine. These unbalanced fluxes produce
proved stator ground fault sensitivity. unbalanced magnetic forces that result in
A MORE SECURE machine vibration. A field ground fault
Field Ground Fault Detection
The field circuit of a generator is an un-
FIELD GROUND also produces rotor iron heating from the
short-circuit currents. The tripping prac-
grounded (typically 600 V) dc system, as RELAY IS tices within the industry for field ground
shown in Figure 4. A single field ground relaying are not well established. Some
fault will generally not affect the opera- DESIRABLE IF users trip while others prefer to alarm,
tion of a generator, nor will it produce thereby risking a second ground fault
any immediate damaging effects. How- AUTOMATIC and major damage before the first ground
ever, the probability of a second ground is cleared.
fault occurring is greater after the first TRIPPING IS The existing practice within the in-
ground fault has established a ground
reference. When a second ground fault BEING dustry has been to use dc voltage relaying
to detect field ground faults. These volt-
occurs, a portion of the field winding
will be short-circuited, thereby produc-
CONSIDERED. age schemes have been prone to false op-
eration—especially during start-up.
ing unbalanced air-gap fluxes in the ma- Unit operators routinely reset the alarm
and continue with start-up procedures. If
a persistent alarm occurred, operators attempted to locate
Brush the problem.
Field
A more secure field ground relay is desirable if auto-
matic tripping is being considered. Such a relay is shown in
Figure 5 and uses an injection principle. This principle has
been widely used in Europe with great success, but, until
recently, it was not available in a multifunction relay. As il-
lustrated in Figure 5, a 15-V square wave signal is injected
Exciter Field into the field through a coupling network. The return sig-
Breaker nal waveform is modified due to field winding capacitance.
The injection frequency setting is adjusted (0.1 to 1.0 Hz)
I EEE I NDUSTRY A PPLI CA TI ONS MA GA ZI NE • MA R|A PR 2003 • WWW.I EEE.ORG/I A S
Negative Sequence
(Unbalanced Current) Protection
There are a number of system conditions that can cause un-
balanced three-phase currents in a generator. These system
conditions produce negative sequence components of cur-
rent that induce a double-frequency (120 Hz) current on 7
the surface of the rotor. The skin effect of the double-fre-
Unbalance currents in the rotor surface.
quency rotor current causes it to be forced into the rotor
surface, causing excessive rotor temperatures in a very short
time. The general flow of this current in a cylindrical ma-
chine rotor is shown in Figure 7. The current flows across TABLE 1. CONTINUOUS UNBALANCED CURRENT
the metal-to-metal contact of the retaining rings to the ro- CAPABILITY OF A GENERATOR.
tor forging wedges. Because of the skin effect, only a very
small portion of this current flows in the field windings. Type of Generator: Permissible I2
Excessive negative sequence heating beyond rotor thermal Cylindrical rotor (percent of stator rating)
limits results in failure. These limits are based on the fol- Indirectly cooled 10
lowing equation, for a given generator:
Directly cooled
8
K = I t,
2 to 960 MVA
2 41
sequence relay is usually the only protection. The low mag- sensitivity. Thus, these relays will provide no protection for
nitude of negative sequence currents created by this type of open-phase or open-generator breaker pole conditions that
event (typically 10-33% of stator rating) prevents other are frequent negative-sequence events within the industry.
fault relays from providing protections. For electrome- The sensitivity of negative-sequence static or digital relays
chanical negative sequence relays, the minimum pickup is required. Almost all generators that are over 20 years old
can be set to only about 60% of the stator-rated current are protected with electromechanical negative-sequence
relays, which make this an important upgrade area. This
was an upgrade area on the Luke Mill generators.
Sequential Tripping
This method of shutting down a generator is used on
Where
steam generators to prevent overspeed when delayed trip- X1S System Positive Sequence Reactance
ping has no detrimental effect on the generating unit.
X2G Generator Negative Sequence Reactance
This generator tripping method was recommended by
generator manufacturers of steam turbines some years ago ES System Voltage
as a result of overspeed generator failures. The first de- EG Generator Terminal Voltage
vices tripped are the turbine valves. A reverse power relay
in series with the valves’ close position switches provides I Current
security against possible overspeed of the turbine by en- 9
suring that steam flows have been reduced below the
Inadvertent energizing equivalent circuit.
amount necessary to produce an
overspeeding condition before
the generator breaker is tripped.
For boiler or turbine mechanical Mechanical Devices
Trip Generator
“Turbine Tripped” Lockout
problems, this is the preferred Steam Valves Closed
Breakers
or
tripping mode since it prevents AND Auxilary
the overspeed of the machine. Fig- Relay Trip Field
ure 10 shows the block diagram Breaker
for sequential tripping. Generator Reverse Timer
On steam machines, reverse Power Relay (32)
power sensitivities of ½% or lower Time
of generator winding megawatt Delay
rating can occur, requiring a very 10
sensitive reverse of power relay.
This trip mode should not override Sequential tripping logic. 43
proper. Oscillographic information can overexcitation condition. Some method
positively identify the cause of a tripping of detection is required so that the af-
incident. This valuable information CONTRARY TO fected relay tripping can be blocked and
gives the mill engineer the necessary
data to keep machines offline for testing
POPULAR BELIEF, the voltage regulator transferred to
manual operation. Typically, protective
and inspection, when necessary, after an GENERATORS functions, such as 32, 40, and 51 V, are
electrical tripping incident or to return impacted and normally blocked when a
the unit to service with minimum delay. DO EXPERIENCE loss of potential is detected.
Oscillographic data provided key infor- On larger generators, it is common
mation in analyzing tripping events (de- SHORT CIRCUITS practice to use two sets of VTs in the gen-
scribed later in this article) on the Luke erator zone of protection. As shown in
Mill generators. AND Figure 11(a), the VTs are usually con-
Special Protection
ABNORMAL nected grounded wye-grounded wye and
normally have primary and secondary
Application Considerations ELECTRICAL fuses. These VTs are used to provide po-
tential for protective relays and the volt-
Voltage Transformer CONDITIONS. age regulator. If a fuse blows in the VT
Fuse Loss Protection circuits, the secondary voltages applied
Loss of the VT signal can occur due to a to the relays and voltage regulators will
number of causes, the most common be- be reduced in magnitude and shifted in
ing a VT fuse blowing. Other causes may be a wiring fail- phase angle. A voltage balance relay is used to detect this
ure, an opening in the draw-out assemblies, a contact loss of VT input.
opening due to corrosion, or a blown fuse due to screw- On many mill-sized generators, only one set of VTs is
driver shorts during online maintenance. This loss of a frequently provided. It is not possible to use a voltage bal-
VT signal can cause protective relay misoperations or ance relay unless a second set of VTs is added. Thus, many
generator voltage regulator runaway, leading to an mill generators do not have VT fuse-loss protection. A
modern digital method can be used in VT failure detection
where only one set of VTs are available. Figure 11(b) illus-
trates this method, which makes use of the relationships of
I EEE I NDUSTRY A PPLI CA TI ONS MA GA ZI NE • MA R|A PR 2003 • WWW.I EEE.ORG/I A S
3-CT
52
3-CT Metering
Generator Protection (B)
VT VT
24 59 27 81
Generator Protection (A)
3-CT Exciter
81 27 59 24 50
+ BF
50 87
BF − G
87 64F Field
50 46 32 51V 60
40
FL
60 46 50
FL 40 51V 32 27
27 3-CT
87 3-CT
G 51G
1-CT 51G 87
Upgrade G
Function
R
12
Mill generator protection. 45
service with all sources energized to termining the cause of the disrup-
limit the system available fault cur- tion and in assessing any equipment
rents to within the interrupting ca- ABNORMAL damage involved can add hours to
pacity of the 1,000-MVA
switchgear. The reactor is bypassed
OPERATIONS re-energizing and returning to nor-
mal operations. Should either mill
when either utility tie or generator SEQUENCES CAN generator be involved, it is critical
is out of service to prevent excessive to assess the integrity of the unit and
reactor voltage drop to mill loads PRESENT SERIOUS perform any testing necessary before
should the loss of the second source reconnecting to the system. It is
occur on the same side of the reactor. INCIDENTS THAT critical to have good sequence of
With two reliable utility ties events and oscillographic data to re-
and two in-house generators, the REQUIRE ACCURATE view protective relay performance,
mill’s 13.8-kV system is normally
very stable, and major upset condi- EVENT DATA TO assess fault levels, and clear the ma-
chine of any damage. To proceed
tions are quite rare. Should they oc-
cur, however, such events can be
ASSESS AND otherwise risks restarting the unit
with possible increased damage and
very disruptive and costly to mill RESOLVE. extensive downtime.
production processes. Delays in de- Abnormal operations sequences
can also present serious incidents
that require accurate event data to
assess and resolve. In these cases,
#1 #2 oscillographic data from the relays
Transformer Utility Substation Transformer can provide objective, unbiased in-
50 MVA 50 MVA
put for revising operating proce-
APS 1 APS 2 dures and training. Even where
generation is not directly involved,
data from the digital generator re-
lays is valuable in determining
fault levels at other points in the
I EEE I NDUSTRY A PPLI CA TI ONS MA GA ZI NE • MA R|A PR 2003 • WWW.I EEE.ORG/I A S