Professional Documents
Culture Documents
Automated Control Strategies of Inside Slat-Type Blind Considering Visual Comfort and Building Energy Performance
Automated Control Strategies of Inside Slat-Type Blind Considering Visual Comfort and Building Energy Performance
Automated Control Strategies of Inside Slat-Type Blind Considering Visual Comfort and Building Energy Performance
a r t i c l e i n f o a b s t r a c t
Article history: Windows are the only part in buildings that can directly penetrate the solar radiation into the space and
Received 20 August 2012 thus the shading devices are needed to control the solar penetration. Among different blind types in office
Accepted 20 September 2012 buildings, roll blinds are not operated efficiently and they are usually closed without any operations by
occupants. Therefore, optimized control strategies of slat-type blinds are suggested in this study through
Keywords: two stages. In the first stage, double-sided blind was suggested by applying different reflectance between
Window
front and back sides of the slat and by fully rotating the slat when the system mode was switched between
Slat-type blind
heating and cooling mode. When the double-sided was used along with the lighting dimming control,
Building energy
EnergyPlus
24.6% of the energy saving could be achieved compared to the baseline case and the glare could be avoided
Glare at the same time. In the second stage, the control strategies of slat angle and up/down control logic were
developed to fully remove the glare and improve the energy efficiency. As a result, 29.2% of energy saving
could be achieved and at the same time the chance of glare was only 0.1%.
© 2012 Elsevier B.V. All rights reserved.
0378-7788/$ – see front matter © 2012 Elsevier B.V. All rights reserved.
http://dx.doi.org/10.1016/j.enbuild.2012.09.019
M.H. Oh et al. / Energy and Buildings 55 (2012) 728–737 729
of blinds has also been actively studies thus far to overcome the 2.1. Simulation software
manual blind control. Reinhart suggested the artificial lighting con-
trol integrated with the blind control [9]. Occupancy profile and A robust building energy simulation program, EnergyPlus
workstation illuminance level have been plugged in as the input version 6.0, was used for the simulations. EnergyPlus is a
condition in the control algorithm and improved energy efficiency whole-building energy simulation program developed by DOE
could be achieved compared to the manual blind control. However, [14]. EnergyPlus was selected because it is a heat balance
the study mainly focused on the lighting energy reduction and thus based simulation program and the heat balance method is the
the total building energy and the occupant visual comfort have not current industry standard method for calculating space loads
been taken into account. Lee et al. suggested the lighting control [12,15,16,18,20,21,22,25]. Furthermore, it has the capability to per-
integrated with blind control to consider both cooling energy and form the detailed energy balance analysis of solar radiation, heat
occupant comfort in full-scale office space [10]. Under different slat transfer and air movement between window and blind [17].
angle conditions such as 90◦ , 45◦ , 15◦ and 0◦ optimum blind setting Blind properties for direct radiation are sensitive to the profile
was developed by considering workstation illuminance level, cool- angle, which is the angle of incidence in a plane that is perpen-
ing energy profile and extent to see the outside view. However, dicular to the window plane and to the direction of the slats. The
the glare and heating energy were not taken into account in this blind optical model in EnergyPlus is based on Simmler’s model
study. [11,26]. In addition, the effect of inter-reflection of the interior
In this study, the optimized automatic control strategies of slat- illuminance/luminance between interior reflecting surfaces is cal-
type blinds were developed to efficiently adjust the solar radiation culated using a radiosity method derived from Superlite [11,24].
through the window, which can improve both energy efficiency and This method subdivides each reflecting surface in the zone into
visual comfort by taking into account cooling, heating and lighting nodal patches and uses view factors between all nodal patch pairs
energies as well as the glare phenomena. in an iterative calculation of the total contribution of reflected light
within the zone [11]. For more information on the assumptions,
detailed algorithm and validation of EnergyPlus models related to
windows, blinds and day-lighting calculations, refer to [11].
2. Methods
In order to overcome the functional and control limitations of 2.2. Description of the simulated building
roll blinds commonly used in office buildings, optimized control
strategies of slat-type blinds are suggested in this study. A three-story office building located in Daejeon City, South
Through two stages, the optimized control strategy was devel- Korea having a rectangular shape with the window-to-wall ratio
oped based on the total annual building energy consumption and (WWR) of 65% was selected for this study. TMY weather data of
the Day-light Glare Index (DGI) adjacent to windows to be main- Daejeon City developed by the Korean Solar Energy Society was
tained below 22. In the first stage, double-sided blind was suggested used for the simulation. South Zone 2 in the middle floor illus-
by applying different reflectance between front and back sides of trated in Fig. 1 was selected as the simulation model to develop
the slat and by fully rotating the slat when the system mode was the automatic control strategy of slat-type blind [28].
switched between heating and cooling mode. In the second stage, Table 1 summarizes constructions and the thermal properties
the control strategies of hourly slat angle and hourly up/down of windows and walls, which comply with the Korean Standard
control logic were developed depending on the solar radiation con- for Energy Saving Design in Buildings [23]. Double pane win-
dition [28]. dows (6 mm clear glass + 12 mm air + 6 mm clear glass) with the
The performance of the developed automatic control strategies SHGC, visible transmittance and U-value of 0.765, 0.812 and
of slat-type blinds integrated with the artificial lighting control was 2.72 W/m2 K, respectively were used. Window frames having the
quantitatively evaluated by taking into account cooling, heating width, inside and outside projection and U-value of 0.04 m, 0.01 m
and lighting energy consumptions and DGI. and 3.97 W/m2 K, respectively, compose the aluminum curtain wall
730 M.H. Oh et al. / Energy and Buildings 55 (2012) 728–737
Table 1
Constructions and thermal properties of windows and walls.
2.3. Indoor set-points, ventilation rate, and HVAC system 3.1. Baseline case
From 6:00 till 19:00 during the weekdays the system controls The heating, cooling and lighting loads of the baseline case with-
the internal air temperature to heating and cooling temperature out blind installation are summarized and illustrated in Table 4 and
set-points of 22 ◦ C and 26 ◦ C, respectively. During the night-time Fig. 4, respectively. As summarized in Table 4, the annual cooling
the system was switched off without set-back control. The zone load accounts for 60.1%, followed by the lighting load of 25.7% and
air temperature was controlled and the thermal and lighting load the heating load of 14.2%, indicating that the simulated building
profiles were calculated using the EnergyPlus function “Zone- showed the cooling-dominant pattern.
HVAC:IdealLoadsAirSystem” [14] without modelling the heating The slat-type blind should be controlled differently between
and cooling systems. This object provides the required supply air heating the and cooling period, and for this purpose the specific
capacity to each zone at user specified temperature and humidity heating and cooling periods are determined based on the relative
ratio to calculate the heating and cooling loads. portion of heating and cooling load. In this study, the cooling con-
Infiltration was assumed equal to 0.5 ACH and the ventilation trol mode was operated from April through November when the
was set to be 1.0 ACH. The schedules of infiltration and ventilation cooling load was dominant, while the heating control mode was
are illustrated in Fig. 2. operated from December through March when the heating load
was dominant as shown in Fig. 4 [28].
2.4. Internal heat gains
3.2. Zone heat gain variation with regard to the slat reflectance
The peak internal load levels of the baseline case are summa-
rized in Table 3 and the hourly variations of the internal loads for Zone heat gain through the window can be broken down into
the simulated office building follow the schedules shown in Fig. 3. conductive, convective, infrared and transmitted solar heat gains
HVAC systems operate from 6:00 through 19:00 during the week- in Fig. 5. In case of the window without blind, solar transmittance
days and from 6:00 through 17:00 on Saturdays. turned out to account for the large portion of the zone heat gain,
while the solar transmittance was significantly reduced into the
similar values of infrared and convective heat gains in case where
Table 2
Slat blind properties [28].
the blind with the slat reflectance of 0.5 was installed as shown in
Fig. 5. Since the combined effects of solar transmittance, infrared
Field Unit Value and convective heat gains were interconnected to each other when
Blind position Inside blind
Slat width m 0.048
Slat to slat distance m 0.048 Table 4
Slat thickness m 0.002 Annual heating, cooling and lighting load of the baseline case [28].
Blind to glass distance m 0.050
Field Load (kWh) Portion
Slat solar and visible reflectance – 0.500
Slat infrared hemispherical emissivity – 0.900 Heating 1068.3 14.2%
Slat conductivity W/m K 0.900 Cooling 4528.9 60.1%
◦
Slat angle 45 Lighting 1938.9 25.7%
M.H. Oh et al. / Energy and Buildings 55 (2012) 728–737 731
the blind was installed, the detailed heat gain patterns as a function 31st) days. The main reason for the total heat gain increase was
of the slat reflectance were analyzed in both typical summer day the increase in infrared and convective heat gains despite the solar
(Aug. 30th) and winter day (Jan. 31st). The variations of the zone transmittance reduction at the lower slat reflectance. The reason
heat gain break-down as a function of the slat reflectance with the for the increase in infrared and convective heat gains is consid-
slat angle fixed at 45◦ are illustrated Figs. 6 and 7 for the typical ered to be due to the fact that the solar radiation was absorbed
summer and winter days, respectively. into the blind, increasing the slat surface temperature and the sur-
As shown in the figure, the total heat gains increased at the rounding air temperature at the reduced slat reflectance. Therefore,
lower slat reflectance in both summer (Aug. 30th) and winter (Jan. it can be considered that the slat with high reflectance should
Fig. 4. Monthly heating, cooling and lighting load of the baseline case [28].
Fig. 5. Zone heat gain variation with and without blind [28].
Fig. 7. Heat gain breakdown as a function of slat reflectance (January 31st) [28].
Fig. 6. Heat gain breakdown as a function of slat reflectance (August 30th) [28]. Fig. 8. Schematic of the double-sided blind [28].
M.H. Oh et al. / Energy and Buildings 55 (2012) 728–737 733
Table 5
Heating, cooling and lighting loads without lighting dimming control.
Table 7
Recommended maximum Glare Index in each building type [13].
Art galleries 16
Hospital wards 18
Museums and school classrooms 20
Laboratories and offices 22
Fig. 12. Heating, cooling and lighting loads with lighting dimming control [28].
Table 6
Heating, cooling and lighting loads with lighting dimming control.
Table 8
1st stage control strategy of the slat-type blind [28].
Field Description
Table 9
Summary of the simulated cases.
Fig. 15. Slat angle control algorithm in heating and cooling modes [28]. Figs. 17 and 18 show the verification of whether or not the
slat angle is properly controlled based on the developed control
The 2nd control strategy of the blind slat angle is finally developed algorithm under each solar radiation in the typical summer and
by drawing the trend line after connecting optimum slat angle in winter days. As illustrated in the figures, the slat angle was prop-
each solar radiation region as shown in Fig. 15. erly adjusted with regard to the solar radiation variations based on
The developed optimum slat angles minimizing the total energy the developed 2nd stage control strategy [28].
consumption and removing the glare in each solar radiation region
follow the regression Eqs. (1) and (2) in cooling and heating modes, 3.4.2. Energy performance evaluation of the 2nd stage slat-type
respectively. blind control strategy
After implementing the developed 2nd control strategy of the
f(X,cooling) = 5E − 07x3 − 0.000383 + 0.443x − 16.771 (1)
slat blind into the building, the energy performance was quanti-
f(X,heating) = 4E − 07x3 − 0.000363 + 0.352x − 29.037 (2) tatively evaluated under different conditions of lighting dimming
control, blind type, and blind control strategies, given the complete
In addition, it is necessary to adjust the slat-type blind into removal of the glare. The summary of the different simulated cases
upward position under low solar radiation condition for the light- is provided in Table 9.
ing energy reduction by maximizing the daylight introduction into Heating, cooling and lighting loads of the 6 simulated cases are
the space. However, the DGI should be quantitatively evaluated summarized and illustrated in Table 10 and Fig. 19, respectively.
even under the low solar radiation condition due to the possible The case with the 2nd stage control strategy of the slat blind showed
glare occurrence. Therefore, the additional analysis was performed the total load reduction of 29.2% compared to the baseline case
in this study to decide the solar radiation regions which do not without blind installation and dimming control, which was even
cause the glare in the upward blind position. 4.6% lower than the 1st control strategy described in Section 3.3
As a result of the analysis, the solar radiation region less than [28].
50 W/m2 did not show the DGE exceeding 22 as shown in Fig. 16.
It could be derived from the analysis that there would be no glare 3.4.3. Visual comfort evaluation of the 2nd stage slat-type blind
even in the upward position of the slat blind under the solar radia- control strategy
tion conditions less than 50 W/m2 . Therefore, the suggested control The main limitation of the 1st control strategy of slat-type blind
strategy of the slat-type blind in this study is to adjust the slat angle characterized by the full rotation of the double-sided blind between
in the downward position under the solar radiation greater than the heating and cooling mode was that the glare occurrence was
50 W/m2 , while placing the slat angle in the upward position under still 3.2%, indicating that it could not completely remove visual
the solar radiation less than 50 W/m2 . discomfort caused by the glare. In this sub-section, the visual com-
fort performance of the suggested 2nd control strategy aimed at
the complete removal of the glare was evaluated for the develop-
ment of the optimum slat angle control logic. The same method
was used as the 1st control strategy as described in the Section
3.3.3 and the results are presented in Fig. 20. As shown in Fig. 20,
the glare occurrence of the suggested 2nd stage control strategy
was only 0.1%, indicating that it could completely remove the
glare.
Table 10
Heating, cooling and lighting loads of the simulated cases.
Fig. 17. Slat angle variation in the typical summer days (August 29th–30th) [28].
Fig. 18. Slat angle variation in the typical winter days (January 30th–31st) [28].
The 2nd stage control strategy of the slat-type blind is defined in Table 11. As shown in the simulated results thus far, the
as “slat angle and up/down control of the double-sided blind developed control logic of the slat-type blind in this study
depending on the solar radiation condition integrated with the showed greatly improved performance in terms of the total load
linear lighting dimming control” in this study as summarized and visual comfort, indicating that it can significantly enhance
Fig. 20. Percentage of the annual occupied hours exceeding recommended DGI of
Fig. 19. Load profiles of the simulated cases [28]. 22 [28].
M.H. Oh et al. / Energy and Buildings 55 (2012) 728–737 737
Table 11 Acknowledgement
2nd stage control strategy of the slat-type blind.
Field Description This research was supported by the National Research Foun-
Slat angle control Optimum slat angle control completely dation of Korea (NRF) grant funded by the Korea Government
removing the glare and minimizing the (MEST)(2011-0027338).
total building load
Up/down control Greater than 50 W/m2 : downward References
position
Less than 50 W/m2 : upward position
[1] D. Gouri, Effect of fixed horizontal louver shading devices on thermal per-
(The maximum solar radiation
formance of building by TRANSYS simulation, Renewable Energy 23 (2001)
penetration causing no glare is 497–507.
50 W/m2 ) [2] J. Breitenbach, S. Lart, I. Längle, J.L.J. Rosenfeld, Optical and thermal perfor-
mance of glazing with integral Venetian blinds, Energy and Buildings 33 (2001)
433–442.
[3] J.Y. Paik, J.H. Kim, M.S. Yeo, K.W. Kim, A study on the occupants use of the
blinds in office building, Journal of the Architectural Institute of Korea 22 (2006)
311–318.
the energy efficiency of buildings and the visual comfort of [4] N.A. Kotey, J.L. Wright, M.R. Collins, Determining off-normal solar optical prop-
occupants [28]. erties of roller blinds, ASHRAE Transactions 115 (2009), pp. 1–145.
[5] M. Andersen, M. Rubin, R. Powles, J.L. Scartezzini, Bi-directional transmission
properties of Venetian blinds: experimental assessment compared to ray-
4. Conclusions tracing calculations, Solar Energy 78 (2005) 187–198.
[6] H. Shahid, D. Naylor, Energy Performance Assessment of a Window with a
Horizontal Venetian Blind, Energy and Buildings 37 (2005) 836–843.
Although high performance window systems with the enhanced [7] S. Chaiyapinunt, S. Worasinchai, Development of a model for calculating the
insulation are widely used recently, the traditional shading con- long-wave optical properties and surface temperature of a curved Venetian
trol passively operated by occupants using the roll blind is still blind, Solar Energy 83 (2009) 817–831.
[8] M.K. Urbikain, J.M. Sala, Heat transfer through a double-glazed unit with an
prevalent. This traditional shading control should be improved and internal louvered blind: determination of the thermal transmittance using a
the development of the advanced control strategy of the shading biquadratic equation, International Journal of Heat and Mass Transfer 55 (2012)
devices is needed for the zero-energy building target in this circum- 1226–1235.
[9] C.F. Reinhart, Lightswith-2002: a model for manual and automated control of
stance. In this study, the automated control strategy of the slat-type electric lighting and blinds, Solar Energy 77 (2004) 15–28.
blind aimed at the building energy saving and the improved visual [10] E.S. Lee, D.L. Di Bartolomeo, S.E. Selkowitz, Thermal and day-lighting perfor-
comfort is developed. mance of an automated Venetian blind and lighting system in a full-scale
private office, Energy and Buildings 29 (1998) 47–63.
In the 1st stage, the control algorithm of fully rotating the
[11] EnergyPlus, EnergyPlus engineering reference. The reference to EnergyPlus cal-
double-sided slat blind between the heating and cooling modes culations. <http://www.energyplus.gov>, 2010.
integrated with the lighting dimming control is suggested. It [12] F. Winkelmann, Modeling windows in EnergyPlus, building simulation 2001,
in: 7th International IBPSA Conference, 2001 September, 2001.
turned out that the double-sided blind without dimming con-
[13] R.G. Hopkinson, Glare from daylighting in buildings, Applied Ergonomics 3
trol can reduce the total building load by 6.4% compared to the (1972) 206–215.
baseline case without blind installation and dimming control and [14] EnergyPlus. EnergyPlus input output reference. The encyclopedic reference to
that the double-sided blind integrated with the dimming con- EnergyPlus input and output. <http://www.energyplus.gov>, 2010.
[15] D.K. Arasteh, M.S. Reilly, M.D. Rubin, A versatile procedure for calculating heat
trol can reduce the total building load by 24.6% compared to the transfer through windows, American Society of Heating, Refrigeration and Air-
baseline case. In addition, the glare occurrence ratio was signif- Conditioning Engineers. ASHRAE Transactions 95 (1989), pp. 755–765.
icantly reduced into 3.2%, which was 33.3% smaller than that of [16] E.U. Finlayson, D.K. Arasteh, C. Huizenga, M.D. Rubin, M.S. Reilly, WINDOW 4.0:
documentation of calculation procedures, Lawrence Berkeley National Labora-
the baseline case without blind showing the glare occurrence ratio tory Report no. LBL-33943, 1993.
of 35.5%. [17] ISO 15099, Thermal Performance of Windows, Doors, and Shading
In the 2nd stage, the optimum slat angle control strategy was Devices—Detailed Calculations, International Organization for Standardization,
2003.
suggested which can achieve both the energy saving and the com- [18] D.K. Arasteh, J.C. Kohler, B.T. Griffith, Draft, modeling windows in EnergyPlus
plete removal of the glare. It turned out that the 2nd control with only U, SHGC, and optionally VT, Lawrence Berkeley National Laboratory
logic can reduce the total building load by 29.2% compared to the Report, 2009.
[19] J. Hu, S. Olbina, Illuminance-based slat angle selection model for automated
baseline case and that the glare occurrence ratio was only 0.1%,
control of split blinds, Building and Environment 46 (2011) 786–796.
indicating that it can completely remove the glare when properly [20] F. Winkelmann, S. Shelkowitz, Day-lighting simulation in DOE-2: theory, vali-
designed and operated. dation and applications, Lawrence Berkeley National Laboratory Report, 1985.
[21] B.A. Lomanowski, Modeling fenestration with shading devices in building
In conclusion, the advanced control strategy suggested in this
energy simulation: a practical approach, building simulation 2009, in: 11th
study showed greatly improved performance in terms of the total International IBPSA Conference, July 2009, 2009.
load and visual comfort, indicating that it can significantly enhance [22] C. Chantrasrisalai, D.E. Fisher, Comparative analysis of one-dimensional slat-
the energy efficiency of buildings and the visual comfort of occu- type blind models, in: SimBuild 2004 Conference, Boulder, USA, 2004.
[23] The Korean Ministry of Land, Transport and Maritime Affairs, Standard for
pants in practice. Energy Saving Design in Buildings, 2010.
[24] M. Modest, A general model for the calculation of day-lighting in interior spaces,
Limitations Energy and Buildings 5 (1982) 66–79.
[25] ASHRAE Fundamentals Handbook, American Society of Heating, Refrigerating
and Air-Conditioning Engineers, Inc, 2009.
The main limitation of this study is related to the selection of the [26] H. Simmler, U. Fischer, F. Winkelmann, Solar–thermal window blind model
cases to be simulated. The energy and visual comfort performance for DOE-2. Lawrence Berkeley National Laboratory, Simulation Research Group
Internal Report, 1996.
of the newly suggested blind control strategies was investigated for [27] The Korean Ministry of Commerce, Industry and Energy, 2nd year-end report,
only one particular climate (Daejeon City) and one particular build- The Human Body Dimension Establishment of Korea, 2004.
ing type (office building). Additional climates and building types [28] M.H. Oh, J.H. Yoon, W.C. Shin, Optimum Automated Control Strategies of Inside
Slat-type Blind Considering Visual Comfort and Building Energy Performance,
should be addressed as well for the findings from this study to be in: Proceedings of Autumn Conference of The Korean Solar Energy Society, vol.
generalized. 31, 2011, pp. 187–195.