COMMISSIONING
CM
Commissioning P54x/EN CM/Ia4
CONTENTS
(CM) 10-
1. INTRODUCTION 7
2. COMMISSIONING TESTS - RELAY FACILITIES 8
2.1 Opto I/P status 9
2.2 Relay O/P status 9
2.3 Test port status 9
2.4 Red LED status and green LED status 9
2.5 Monitor bits 1 to 8 9
2.6 Test mode 10
2.7 Test pattern 10
2.8 Contact test 10
2.9 Test LEDs 10
2.10 Test auto-reclose 10
2.11 Static test mode 11
2.12 Loopback mode 12
2.13 IM64 test pattern 12
2.14 IM64 test mode 12
2.15 Using a monitor/download port test box 12
3. SETTING FAMILIARIZATION 13
4. EQUIPMENT REQUIRED FOR COMMISSIONING 14
4.1 Minimum equipment required 14
4.2 Optional equipment 14
5. PRODUCT CHECKS 15 CM
5.1 With the relay de-energized 15
5.1.1 Visual inspection 16
5.1.2 Current transformer shorting contacts (optional check) 16
5.1.3 Insulation 18
5.1.4 External wiring 18
5.1.5 Watchdog contacts 18
5.1.6 Auxiliary supply 19
5.2 With the relay energized 19
5.2.1 Watchdog contacts 19
5.2.2 LCD front panel display 19
5.2.3 Date and time 20
5.2.3.1 With an IRIG-B signal 20
5.2.3.2 Without an IRIG-B signal 20
5.2.4 Light emitting diodes (LEDs) 21
5.2.4.1 Testing the alarm and out of service LEDs 21
P54x/EN CM/Ia4 Commissioning
7. GPS SYNCHRONIZATION 36
7.1.1 Commission the P594 36
7.1.2 P594 optical signal strength at P54x relay 36
7.1.3 Check synchronization signal at P54x relay 36
7.1.4 Check GPS failure condition 36
7.1.5 Restore GPS 36
8. SETTING CHECKS 37
8.1 Apply application-specific settings 37
8.1.1 Protection communications loopback 37
8.1.2 Reset statistics 37
8.2 Demonstrate correct relay operation 38
8.3 Demonstrate correct relay operation – current differential elements 38
8.3.1 Current differential bias characteristic 38
8.3.1.1 Connect the test circuit 38
8.3.1.2 Lower slope 38
8.3.1.3 Upper slope 39
CM
8.3.2 Current differential operation and contact assignment 40
8.3.2.1 Phase A 40
8.3.2.2 Phase B 40
8.3.2.3 Phase C 40
8.4 Demonstrate correct relay operation – non-current differential elements 41
8.4.1 Protection dependencies 41
8.4.2 Distance protection single-end testing 41
8.4.2.1 Connection and preliminaries 41
8.4.2.2 Zone 1 reach check 42
8.4.2.3 Zone 2 reach check 42
8.4.2.4 Zone 3 reach check 43
8.4.2.5 Zone 4 reach check (if enabled) 43
8.4.2.6 Zone P reach check (if enabled) 43
8.4.2.7 Resistive reach (quadrilateral characteristics only) 43
P54x/EN CM/Ia4 Commissioning
FIGURES
Figure 1 Auto-reclose default PSL mapping – P543 & P545 software versions 44 and 54 11
Figure 2 Auto-reclose default PSL mapping – P544 & P546 software versions 45 and 55 11
Figure 3 Rear terminal blocks on size 80TE case 16
Figure 4 Location of securing screws for heavy duty terminal blocks 17
Figure 5 Connection for bias characteristic testing 38
Figure 6 Four state impedances 51
P54x/EN CM/Ia4 Commissioning
CM
Commissioning P54x/EN CM/Ia4
1. INTRODUCTION
The P54x employs a high degree of self-checking and, in the unlikely event of a failure, will
give an alarm. As a result of this, the commissioning tests do not need to be as extensive as
with non-numeric electronic or electro-mechanical relays.
To commission numeric relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay. It is
considered unnecessary to test every function of the relay if the settings have been verified
by one of the following methods:
• Extracting the settings applied to the relay using appropriate setting software (preferred
method)
CM
P54x/EN CM/Ia4 Commissioning
Note: When the ‘Test Mode’ cell is set to ‘Contacts Blocked’ this cell will
continue to indicate which contacts would operate if the relay was in-
service, it does not show the actual status of the output relays.
Monitor Bit 1 2 3 4 5 6 7 8
Monitor/Download Port Pin 11 12 15 13 20 21 23 24
Note: When the ‘Test Mode’ cell is set to ‘Contacts Blocked’ the ‘Relay O/P
Status’ cell does not show the current status of the output relays and
hence can not be used to confirm operation of the output relays.
Therefore it will be necessary to monitor the state of each contact in
turn.
CM When the ‘Apply Test’ command in this cell is issued the eighteen user-programmable LEDs
will illuminate yellow for approximately 2 seconds before they extinguish and the command
text on the LCD reverts to ‘No Operation’.
Note: The default settings for the relay’s programmable scheme logic has
the ‘AR Trip Test’ signals mapped to the ‘Trip Input’ signals as shown
in Figure 1 (P543 & P545 software version 54) and Figure 2 (P544 &
P546 software version 55). If the programmable scheme logic has
been changed, it is essential that these signals retain this mapping for
the ‘Test Auto-reclose’ facility to work.
Figure 1 Auto-reclose default PSL mapping – P543 & P545 software versions
44 and 54
Figure 2 Auto-reclose default PSL mapping – P544 & P546 software versions
45 and 55
CM
2.11 Static test mode
Modern dynamic secondary injection test sets are able to accurately mimic real power
system faults. The test sets mimic an instantaneous fault “shot”, with the real rate of rise of
current, and any decaying DC exponential component, according to the point on (voltage)
wave of fault inception. Injections for all three phases provide a six signal set of analog
inputs: Va, Vb, Vc, Ia, Ib, Ic. Such injection test sets can be used with the P54x, with no
special testing limitations.
• A real fault shot (instead a gradually varying current or voltage may be used)
• A six signal set of analog inputs (instead, these may offer for example: Va, Vb, Ia, Ib
only, to test for an A-B injection)
Such injection sets may be referred to as “Static” simulators.
P54x/EN CM/Ia4 Commissioning
As the P54x relies on voltage memories and delta step changes as would happen on a real
power system, certain functions within the relay must be disabled or bypassed to allow
injection testing. Selecting the Static Mode test option serves to bypass the delta phase
selectors, and power swing detection.
For the tests, the delta directional line is also replaced by a conventional distance directional
line, and the digital filtering slows to use a fixed one cycle window. Memory polarizing is
replaced by cross-polarizing from unfaulted phases.
The Static Test mode allows older injection test sets to be retained, and used to commission
and test the P54x.
Note: Trip times may be up to ½ cycle longer when tested in the static
mode, due to the nature of the test voltage and current, and the
slower filtering. This is normal, and perfectly acceptable.
Note: Selecting the [0F13 Loopback Mode] to Internal, only the internal
software of the relay is checked whereas External will check both the
software and hardware.
When the relay is switched into either ‘Loopback Mode’, the relay will automatically use
generic addresses (address 0-0) and will respond as if it is connected to a remote relay with
the current at the remote end equal to and in phase with the current injected at the local end.
The signals sent and received (IM64) continue to be routed to and from the signals defined
in the programmable logic.
3. SETTING FAMILIARIZATION
When commissioning a relay P54x for the first time, sufficient time should be allowed to
become familiar with the method by which the settings are applied.
The Introduction (P54x/EN GS) contains a detailed description of the menu structure of P54x
relays.
With the secondary front cover in place all keys except the key are accessible. All menu
cells can be read. LEDs and alarms can be reset. However, no protection or configuration
settings can be changed, or fault and event records cleared.
Removing the secondary front cover allows access to all keys so that settings can be
changed, LEDs and alarms reset, and fault and event records cleared. However, menu cells
that have access levels higher than the default level will require the appropriate password to
be entered before changes can be made.
Alternatively, if a portable PC is available together with suitable setting software (such as
MiCOM S1 Studio), the menu can be viewed a page at a time to display a full column of data
and text. This PC software also allows settings to be entered more easily, saved to a file on
disk for future reference or printed to produce a setting record. Refer to the PC software
user manual for details. If the software is being used for the first time, allow sufficient time to
become familiar with its operation.
CM
P54x/EN CM/Ia4 Commissioning
Note: Modern test equipment may contain many of the above features in
one unit.
Fiber optic power meter.
Fiber optic test leads (type and number according to application).
P594 Commissioning Instructions. If the scheme features P594 time synchronizing devices,
these will need commissioning. Separate documentation containing commissioning
instructions is available for the P594.
5. PRODUCT CHECKS
These product checks cover all aspects of the relay which should be checked to ensure that
it has not been physically damaged prior to commissioning, is functioning correctly and all
input quantity measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow their restoration later. This could be
done by:
• Obtaining a setting file on a diskette from the customer (this requires a portable PC with
appropriate setting software for transferring the settings from the PC to the relay)
• Extracting the settings from the relay itself (this again requires a portable PC with
appropriate setting software)
• Manually creating a setting record. This could be done using a copy of the setting
record located at the end of this chapter to record the settings as the relay’s menu is
sequentially stepped through via the front panel user interface
If password protection is enabled and the customer has changed password 2 that prevents
unauthorized changes to some of the settings, either the revised password 2 should be
provided, or the customer should restore the original password prior to commencement of
testing.
Note: In the event that the password has been lost, a recovery password
can be obtained from AREVA T&D by quoting the serial number of the
relay. The recovery password is unique to that relay and is unlikely to
work on any other relay.
A B C DE FG H J K L M N
1
1
1
1
1 2 3 19
2
2
3
3
3
4 5 6 20
4
4
5
5
5
IRIG-B
6
6
6
7 8 9 21
7
7
8
8
9
9
9
10 11 12 22
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
12
12
12
12
12
13 14 15 23
13
13
13
13
13
13
13
13
TX
RX
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
16 17 18 24
16
16
16
16
16
16
16
16
17
17
17
17
17
17
17
17
18
18
18
18
18
18
18
18
P3003ENb
20
4
21
7
9
11
22
12
10
15
13
14
23
CM
16
17
18
24
P1042ENa
5.1.3 Insulation
Insulation resistance tests are only necessary during commissioning if it is required for them
to be done and they have not been performed during installation.
Isolate all wiring from the earth and test the insulation with an electronic or brushless
insulation tester at a dc voltage not exceeding 500 V. Terminals of the same circuits should
be temporarily connected together.
The main groups of relay terminals are:
• Relay contacts
• Case earth
Contact state
Terminals
Relay de-energized Relay energized
J11 - J12 (P543 & P544) Closed Open
J13 - J14 (P543 & P544) Open Closed
M11 - M12 (P545 & P546) Closed Open
M13 - M14 (P545 & P546) Open Closed
Note: It is likely that alarms related to the communications channels will not
reset at this stage.
Terminals
Supply rail
P54x
+ve J7 & 8 - (P543 & P544)
–ve J9 & J10 - (P543 & P544)
+ve M7 & M8 - (P545 & P546)
–ve M9 & M10 - (P545 & P546)
• P543 and P544 have either 14 standard relay outputs or a combination of 7 standard
outputs and 4 high break outputs according to model listing option selected
• P545 has either 32 standard relay outputs or a combination of 16 standard outputs and 8
high break outputs according to model listing option selected
• P546 has either 32 standard relay outputs, or a combination of 16 standard outputs and
8 high break outputs, or a combination of 8 standard outputs and 12 high break outputs
according to model listing option selected
Note: The high break output contacts fitted to I/O options “C” and “D” are
polarity sensitive. External wiring should, wherever possible, be
verified against polarity requirements described in the external
connection diagram (10P4430x) to ensure correct high break
operation when in service.
CM Ensure that the relay is still in test mode by viewing cell [0F0D: COMMISSION TESTS, Test
Mode] to ensure that it is set to ‘Blocked’.
The output relays should be energized one at a time. To select output relay 1 for testing, set
cell [0F0E: COMMISSION TESTS, Test Pattern] as appropriate.
Connect a continuity tester across the terminals corresponding to output relay 1 as given in
external connection diagram (P54x/EN IN).
To operate the output relay set cell [0F0F: COMMISSION TESTS, Contact Test] to ‘Apply
Test’. Operation will be confirmed by the continuity tester operating for a normally open
contact and ceasing to operate for a normally closed contact. Measure the resistance of the
contacts in the closed state.
Reset the output relay by setting cell [0F0F: COMMISSION TESTS, Contact Test] to
‘Remove Test’.
Connection Terminal
K-Bus IEC 60870-5-103 or DNP3.0 P54x
Screen Screen M16 - (P545, P546)
1 +ve M17 - (P545, P546)
2 –ve M18 - (P545, P546)
Screen Screen J16 - (P543, P544)
1 +ve J17 - (P543, P544)
2 –ve J18 - (P543, P544)
Pin* Connection
4 EIA(RS)485 - 1 (+ ve)
7 EIA(RS)485 - 2 (- ve)
1 This port is actually compliant to EIA(RS)574; the 9-pin version of EIA(RS)232, see www.tiaonline.org.
Commissioning P54x/EN CM/Ia4
Pin Connection
1 No Connection
2 RxD
3 TxD
4 DTR#
5 Ground
6 No Connection
7 RTS#
8 CTS#
9 No Connection
[0232: IM Magnitude]
[024C: CB2 CS Volt Mag] (P544 & P546 [0A05 : CB2 CS VT Prim’y]
only) [0A06 : CB2 CS VT Sec’y]
CM
P54x/EN CM/Ia4 Commissioning
• The current differential protection is enabled by setting the [090F Phase Diff] cell in the
configuration column, or if the current differential protection is not being used,
If applicable replace the secondary front cover from the unit. Carefully examine the unit to
see that no physical damage has occurred since installation.
The rating information given under the top access cover on the front of the unit should be
checked to ensure it is correct for the particular installation.
Ensure that the case earthing connection, top left-hand corner at the rear of the case, is
used to connect the unit to a local earth bar using an adequate conductor.
Note: In loopback mode the signals sent and received via the protection
communications / InterMiCOM64 interface continue to be routed to and
from the signals defined in the programmable logic.
Note: A test pattern can be also sent to the remote end in order to test the
whole InterMiCOM communication path by enabling (OF14 IM64 Test
Mode) and connecting two ends. If such a test is performed, special
care has to be taken as the test pattern will be executed via PSL at
the remote end.
CM
P54x/EN CM/Ia4 Commissioning
7. GPS SYNCHRONIZATION
The P54x has a feature whereby the timing information used to align the local and remote
current vectors used in the phase differential algorithm can be very accurately synchronized
via the global positioning satellite (GPS) system. If specified, a P594 GPS synchronizing
unit is employed to decipher GPS signals and provide the P54x relay with a suitable
synchronizing signal.
If the P54x is using GPS synchronization to enhance the phase current differential
protection, then the associated P594 unit will need to be commissioned in accordance with
the relevant commissioning instructions. The P594 commissioning instructions can be found
in the CM chapter of the P594 Technical Manual (P594_EN M/D22).
If P594 synchronizing units are not employed, proceed to section 8.
8. SETTING CHECKS
The setting checks ensure that all of the application-specific relay settings (i.e. both the
relay’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the relay.
If the application-specific settings are not available, ignore sections 8.1 and 8.2.
Note: The trip circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
• Transferring them from a pre-prepared setting file to the relay using a portable PC
running the appropriate software via the relay’s front EIA(RS)232 port, located under the
bottom access cover, or rear communications port (with a KITZ protocol converter
connected). This method is preferred for transferring function settings as it is much
faster and there is less margin for error. If programmable scheme logic other than the
default settings with which the relay is supplied are to be used then this is the only way
of changing the settings.
• If a setting file has been created for the particular application and provided on a diskette,
this will further reduce the commissioning time and should always be the case where
application-specific programmable scheme logic is to be applied to the relay.
• Enter them manually via the relay’s operator interface. This method is not suitable for
changing the programmable scheme logic.
• To determine that the primary protection function of the relay, current differential or
distance can trip according to the correct application settings
• To verify correct setting of any aided scheme DEF (ground overcurrent) protection
To verify correct assignment of the trip contacts, by monitoring the response to a selection of
fault injections.
P540
relay Ia
Ra
A
L Ph a
Rb Ib
A
Ph b
N
CM
Figure 5 Connection for bias characteristic testing
A current is injected into the A phase which is used as the bias current and another current is
injected into the B phase which is used as differential current. Ιa is always greater than Ιb.
Differential
Bias current
current Magnitude of differential current
Phase Magnitude Phase
2 Terminal & Dual
0.25 pu +/-10%
A 1pu B Redundant
3 Terminal 0.216 pu +/-10%
Differential
Bias current Magnitude of differential current
current
Phase Magnitude Phase k2
2 Terminal & Dual 150% 1.15pu +/-10%
Redundant 100% 0.9pu +/-10%
A 3pu B
150% 1.51pu +/-10%
3 Terminal
100% 1.1pu +/-10%
For other differential settings or current injected into A phase (Ia), the formula below can be
used (enter slopes in pu form, i.e. percentage/100):
2 Terminal & Dual Redundant:
Operate current is 0.5 x [(Ia x k2) – {(k2 – k1) x Ιs2 } + Ιs1] pu +/- 20%
3 Terminal:
Operate current is 0.333 x [(1.5 x Ia x k2) – {(k2 – k1) x Ιs2 } + Ιs1] pu +/- 20%
Ensure that Ia > IS2
8.3.2.1 Phase A
Retaining the same test circuit as before, prepare for an instantaneous injection of 3 pu
current in the A phase, with no current in the B phase (B phase switch open). Connect a
timer to start when the fault injection is applied, and to stop when the trip occurs. To verify
correct output contact mapping use the trip contacts that would be expected to trip the circuit
breaker(s), as shown in the table. For two breaker applications, stop the timer once both
CB1 and CB2 trip contacts have closed. This can be achieved by connecting the contacts in
series to stop the timer.
8.3.2.3 Phase C
Repeat 8.3.2.3 for the C phase.
CM The average of the recorded operating times for the three phases should be less than 40 ms
for 50 Hz, and less than 35 ms for 60 Hz when set for instantaneous operation. Switch OFF
the ac supply and reset the alarms.
Note: For applications using magnetizing inrush current restraint, use a test
current higher than the [3313: Inrush High] setting to obtain fast
operating times. At least twice setting is recommended.
Where an IDMT or definite time delay is set in the GROUP 1 PHASE DIFF menu column, the
expected operating time is typically within +/- 5% of that for the curve equation plus the
“instantaneous” delay quoted above.
On completion of the tests any distance, overcurrent, earth fault or breaker fail elements
which were disabled for testing purposes must have their original settings restored in the
CONFIGURATION column.
Commissioning P54x/EN CM/Ia4
1. In order to facilitate testing of the Distance elements using test sets which do not
provide a dynamic model to generate true fault delta conditions, a Static Test Mode
setting is provided. This setting is found in the COMMISSIONING TESTS menu
column. When set, this disables phase selector control and forces the relay to use a
conventional (non-delta) directional line.
2. For lower specification test equipment that cannot apply a full three phase set of
healthy simulated pre-fault voltages, the VT supervision may need to be disabled to
avoid spurious pickup. This is achieved in the CONFIGURATION column, by setting
cell [0921: Supervision] to Disabled).
Connect the test equipment to the relay via the test block(s) taking care not to open-circuit
any CT secondary. If MMLG type test blocks are used, the live side of the test plug must be
provided with shorting links before it is inserted into the test block.
• Connections for an A-N fault. The appropriate loop impedance is given by the vector
sum:
2 x Z2 Ω
Commissioning P54x/EN CM/Ia4
8.4.3.1 Phase A
Prepare a dynamic A phase to neutral fault, at half the Zone 1 reach. Connect a timer to
start when the fault injection is applied, and to stop when the trip occurs. To verify correct
output contact mapping use the trip contacts that would be expected to trip the circuit
breaker(s), as shown in the table. For two breaker applications, stop the timer once CB1
and CB2 trip contacts have both closed, monitored by connecting the contacts in series to
stop the timer if necessary.
Apply the fault and record the phase A trip time. Switch OFF the ac supply and reset the
alarms.
8.4.3.2 Phase B
Reconfigure to test a B phase fault. Repeat the test in 8.4.3.1, this time ensuring that the
breaker trip contacts relative to B phase operation close correctly. Record the phase B trip
time. Switch OFF the ac supply and reset the alarms.
8.4.3.3 Phase C
Repeat 8.4.3.2 for the C phase.
The average of the recorded operating times for the three phases should typically be less
than 20 ms for 50 Hz, and less than 16.7 ms for 60 Hz when set for instantaneous operation.
Switch OFF the ac supply and reset the alarms.
• Where a non-zero tZ1 Gnd time delay is set in the DISTANCE menu column, the
expected operating time is typically within +/- 5% of the tZ1 setting plus the
“instantaneous” delay quoted above.
Note: The P54x allows separate time delay settings for phase (“Ph”) and
ground (“Gnd”) fault elements. BOTH must be checked to ensure that
they have been set correctly.
Commissioning P54x/EN CM/Ia4
• Zone 1 fault: A dynamic forward A-B fault at half the Zone 1 reach will be
simulated.
• End of line fault: A dynamic forward A-B fault at the remote end of the line will be
simulated. The fault impedance simulated should match the
[3003: Line Impedance] setting in the LINE PARAMETERS
menu column.
• Zone 4 fault: A dynamic reverse A-B fault at half the Zone 4 reach will be
simulated.
RELAY RESPONSE
Fault type Forward fault at end
simulated Forward fault in Reverse fault in
of line
zone 1 zone 4
(within Z1X/Z2)
Signal
ON OFF ON OFF ON OFF
receive opto CM
Zone 1
Trip Trip No Trip Trip No Trip No Trip
extension
Trip, Trip, No Trip, Trip, No Trip, No Trip,
Blocking
No Signal No Signal No Signal No Signal Signal Signal
scheme
Send Send Send Send Send Send
Permissive Trip, Trip, Trip, No Trip, No Trip, No Trip,
Scheme Signal Signal No Signal No Signal No Signal No Signal
(PUR/PUTT) Send Send Send Send Send Send
Permissive Trip, Trip, Trip, No Trip, No Trip, No Trip,
Scheme Signal Signal Signal Signal No Signal No Signal
(POR/POTT) Send Send Send Send Send Send
P54x/EN CM/Ia4 Commissioning
• Where a non-zero tZ1 Ph time delay is set in the DISTANCE menu column, the expected
operating time is typically within +/- 5% of the tZ1 setting plus the “instantaneous” delay
quoted above.
• Where a non-zero Distance Dly time delay is set in the DISTANCE menu column, the
expected operating time is typically within +/- 5% of the tZ1 setting plus the
“instantaneous” delay quoted above.
De-energize the channel received opto (remove the temporary energization link, to turn it
OFF).
• For blocking schemes, a non-zero Distance Dly time delay is set, so the expected
operating time is typically within +/- 5% of the delay setting plus the P54x “instantaneous”
operating delay. The trip time should thus be less than 20 ms for 50 Hz, and less than
16.7 ms for 60 Hz, plus 1.05 x Delay setting.
Commissioning P54x/EN CM/Ia4
Signal receive
ON OFF ON OFF
opto
Blocking No Trip, Trip, No Trip, No Trip,
scheme No Signal Send No Signal Send Signal Send Signal Send
Permissive
Trip, No Trip, No Trip, No Trip,
scheme
Signal Send Signal Send No Signal Send No Signal Send
(POR/POTT)
• Step 2: Simulate a forward fault on the A-phase. The A-phase voltage must be
simulated to drop by 3 times the [3313: ΔV Fwd] setting, i.e:
Va = Vn - 3 x ΔV Fwd
The fault current on the A-phase should be set to 3 times the [3315: ΔI Fwd] setting, lagging
Va by a phase angle equal to the line angle, i.e:
8.4.7.1 Phase A
Prepare a dynamic A phase to neutral fault, as detailed above. Ensure that the test set is
simulating Steps 1 and 2 as one continuous transition. Connect a timer to start when the
fault injection (Step 2) is applied, and to stop when the trip occurs. To verify correct output
contact mapping use the trip contacts that would be expected to trip the circuit breaker(s), as
shown in the table. For two breaker applications, stop the timer once CB1 and CB2 trip
contacts have both closed, monitored by connecting the contacts in series to stop the timer if
necessary.
Apply the fault and record the phase A trip time. Switch OFF the ac supply and reset the
alarms.
8.4.7.2 Phase B
Reconfigure to test a B phase fault. Repeat the test in 8.4.7.1, this time ensuring that the
breaker trip contacts relative to B phase operation close correctly. Record the phase B trip
time. Switch OFF the ac supply and reset the alarms.
8.4.7.3 Phase C
Repeat 8.4.7.2 for the C phase.
The average of the recorded operating times for the three phases should typically be less
than 20 ms for 50 Hz, and less than 16.7 ms for 60 Hz when set for instantaneous operation,
as in Permissive schemes. Switch OFF the ac supply and reset the alarms.
• For Blocking schemes, where a non-zero Delta Dly time delay is set, the expected
operating time is typically within +/- 5% of the delay setting plus the “instantaneous”
delay quoted above.
• Step 2: Simulate a reverse fault on the A-phase. The A-phase voltage must be
simulated to drop by 3 times the [3314: ΔV Rev] setting, i.e.:
Va = Vn - 3 x ΔV Rev
P54x/EN CM/Ia4 Commissioning
The fault current on the A-phase should be set to 3 times the [3316: ΔI Rev] setting, and in
antiphase to the forward injections, i.e:
CM
Commissioning P54x/EN CM/Ia4
+jX
Z6
Z5
State 4
State 3
State 2
State 1
R
R6' R5' R5 R6
∆R
Z5'
Z6'
P1982ENa
Angle 0° 0° 0°
Longer than 25 ms but
Duration 500 ms 500 ms
shorter that ‘Delta t’ set time
Note: Angle in the table above is the angle between voltages and their
respective currents.
Now apply the 3 state sequence to the relay under test and observe that the relay has
tripped 3 phase and that an associated ‘Predictive OST’ alarm is displayed on the local LCD.
Clear all alarms.
P54x/EN CM/Ia4 Commissioning
Angle 0° 0° 0° 180°
Longer than
Duration 500 ms 100 ms 500 ms
‘Delta t’ set time
Note: Angle in the table above is the angle between voltages and their
respective currents. Also note that in state 4 the currents are
displaced 180° from their respective voltages.
Now apply the 4 state sequence to the relay under test and observe that the relay has
tripped 3 phase and that an associated ‘OST’ alarm is displayed on the local LCD.
8.4.10 Directional earth fault aided scheme (ground current pilot scheme)
If the Aided DEF protection function is being used, it should be tested. If not, skip to section
8.4.12.
Refer to section 8.4.1, check for any possible dependency conditions and simulate as
appropriate.
To avoid spurious operation of any phase diff, distance, overcurrent, earth fault or breaker
CM fail elements, these should be disabled for the duration of the DEF tests. This is done in the
relay’s CONFIGURATION column. If the earth fault element is enabled without qualification
of communication channel failure, then the current differential element [090F: Phase Diff],
should be disabled. If the earth fault protection is enabled on communication channel failure,
then the differential element should remain enabled and the communication should be
disrupted to cause a suitable failure of the phase differential protection. Make a note of
which elements need to be re-enabled after testing.
Testing of the P54x DEF scheme is detailed in the case of conventional signaling scheme
implementation as it is expected that the signaling will be independent to that of the
communication for the phase differential protection. In the case where an InterMiCOM64
scheme is being employed to provide the signaling, it may be that the scheme logic does not
use opto-inputs for the aided scheme implementation and that internal logic signals (DDBs)
will need to be set/reset in order to test the operation of the protection scheme. The IM64
Test Mode in conjunction with the IM64 Test Pattern should be used to assert/monitor the
relevant signals.
This set of injection tests aims to determine that a single P54x relay, at one end of the
scheme is performing correctly. The relay is tested in isolation, with the communications
channel to the remote line terminal disconnected. Verify that the P54x relay cannot send or
receive channel scheme signals to/from the remote line end.
Commissioning P54x/EN CM/Ia4
• Simulate a forward fault on the A-phase. The A-phase voltage must be simulated to
drop by 4 times the [3905] or [3906] : “DEF Vpol” setting, i.e.:
Va = Vn - (4 x DEF Vpol)
The fault current on the A-phase should be set to 2 times the [3907: DEF Threshold] setting,
and in the forward direction. For a forward fault, the current Ia should lag the voltage Va by
the DEF Char Angle setting, i.e.:
Signal
ON OFF ON OFF
Receive Opto
Blocking No Trip, Trip, No Trip, No Trip,
Scheme No Signal Send No Signal Send Signal Send Signal Send
Permissive
Trip, No Trip, No Trip, No Trip,
Scheme
Signal Send Signal Send No Signal Send No Signal Send
(POR/POTT)
A forward fault will be injected as described, with the intention to cause a scheme trip. As in CM
the table, for a Permissive scheme the Signal Receive opto input will need to be ON
(energized). This should be performed by applying a continuous DC voltage onto the
required opto input, either from the test set, station battery, or relay field voltage
(commissioning engineer to ascertain the best method).
For a blocking scheme, the opto should remain de-energized (“OFF”).
• The aided ground fault (DEF) scheme trip time for POR schemes should be less than 40 ms.
• For blocking schemes, where a non-zero DEF Dly time delay is set, the expected
operating time is typically within +/- 5% of the delay setting plus the “instantaneous”
(40 ms) delay quoted above.
• There is no need to repeat the test for phases B and C, as these trip assignments have
already been proven by the distance/delta trip tests.
P54x/EN CM/Ia4 Commissioning
If the overcurrent protection function is being used, the Ι>1 element should be tested. If not,
skip to section 8.4.13.
Refer to section 8.4.1, check for any possible dependency conditions and simulate as
appropriate.
To avoid spurious operation of any distance, DEF, earth fault or breaker fail elements, these
should be disabled for the duration of the overcurrent tests. This is done in the relay’s
CONFIGURATION column. If the overcurrent element is enabled without qualification of
communication channel failure, then the current differential element [090F: Phase Diff],
CM should be disabled. If the overcurrent protection is enabled on communication channel
failure, then the differential element should remain enabled and the communication should
be disrupted to cause a suitable failure of the phase differential protection. Make a note of
which elements need to be re-enabled after testing.
Determine which output relay has been selected to operate when an Ι>1 trip occurs by
viewing the relay’s programmable scheme logic.
The relay assigned for Trip Output A (DDB 523) faults should be used.
Stage 1 should be mapped directly to an output relay in the programmable scheme logic. If
default PSL is used, Relay 3 can be used as I1> is mapped to Trip inputs 3 Ph (DDB 529)
that in turn is internally mapped to Any Trip (DDB 522) mapped to relay 3 (see trip
conversion logic on chapter P54x/EN OP) .
Connect the output relay so that its operation will trip the test set and stop the timer.
Connect the current output of the test set to the ‘A’ phase current transformer input of the
relay (terminals C3 and C2 where 1A current transformers are being used and terminals C1
and C2 for 5A current transformers).
If [3503: GROUP 1 OVERCURRENT, Ι>1 Directional] is set to ‘Directional Fwd’, the current
should flow out of terminal C2 but into C2 if set to ‘Directional Rev’.
Commissioning P54x/EN CM/Ia4
If cell [3503: GROUP 1 OVERCURRENT, Ι>1 Directional] has been set to ‘Directional Fwd’
or ‘Directional Rev’ then rated voltage should be applied to terminals C20 and C21.
Ensure that the timer will start when the current is applied to the relay.
Note: If the timer does not stop when the current is applied and stage 1 has
been set for directional operation, the connections may be incorrect
for the direction of operation set. Try again with the current
connections reversed.
Apply a current of twice the setting in cell [3504: GROUP 1 OVERCURRENT, Ι>1 Current
Set] to the relay and note the time displayed when the timer stops.
Check that the red trip LED has illuminated.
Note: Except for the definite time characteristic, the operating times given in
Table 14 are for a time multiplier or time dial setting of 1. Therefore,
to obtain the operating time at other time multiplier or time dial
settings, the time given in Table 14 must be multiplied by the setting of
cell [3506: GROUP 1 OVERCURRENT, Ι>1 TMS] for IEC and UK
characteristics or cell [3507: GROUP 1 OVERCURRENT, Time Dial]
for IEEE and US characteristics.
In addition, for definite time and inverse characteristics there is an additional delay of up to
0.02 second and 0.08 second respectively that may need to be added to the relay’s
acceptable range of operating times.
For all characteristics, allowance must be made for the accuracy of the test equipment being
used.
• The “CB Healthy” DDB should not be mapped, or if it is mapped, it must be asserted
high.
• The CB status inputs (52 A, etc.) should not be mapped, or if they are mapped, they
should be activated so as to mimic the circuit breaker operation.
• If configured for single pole tripping, either the VT Connected setting should be set to
No, or appropriate voltage signals need to be applied to prevent the pole dead logic from
converting to 3-pole tripping.
To test the first three-phase auto-reclose cycle, set cell [0F11: COMMISSION TESTS, Test
Auto-reclose] to ‘3 Pole Test’. The relay will perform a trip/reclose cycle. Repeat this
operation to test the subsequent three-phase auto-reclose cycles.
Check all output relays used for circuit breaker tripping and closing, blocking other devices,
etc. operate at the correct times during the trip/close cycle.
The auto-reclose cycles for single phase trip conditions can be checked one at a time by
sequentially setting cell [0F11: COMMISSION TESTS, Test Auto-reclose] to ‘Pole A Test’,
‘Pole B Test’ and ‘Pole C Test’.
CM
Commissioning P54x/EN CM/Ia4
Note: The trip circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
Maximum
transmitter power
-16.8 dBm -6 dBm -6 dBm
(average value)
Minimum
transmitter power
-25.4 dBm -49 dBm -49 dBm
(average value)
Maximum
transmitter power
-16.8 dBm -7 dBm -7 dBm
(average value)
Minimum
transmitter power
-25.4 dBm -37 dBm -37 dBm
(average value)
CM
P54x/EN CM/Ia4 Commissioning
• Confirm the external wiring to the current and voltage inputs is correct
• Ensure the on-load differential current is well below the relay setting
• Check the polarity of the line current transformers at each end is consistent
If cell [0D02: MEASURE’T. SETUP, Local Values] is set to ‘Primary’, the values displayed
should be equal to the applied secondary voltage multiplied the corresponding voltage
transformer ratio set in the ‘CT & VT RATIOS’ menu column (see Table 10). Again the
values should be within 1% of the expected value, plus an additional allowance for the
accuracy of the test equipment being used.
Check that the setting of cell [3302: GROUP 1 PHASE DIFF, Phase Ιs1] is higher than 2.5
times the capacitive charging current. If this is not the case, notify the Engineer who
determined the original settings of the setting required to ensure stability under normal
operating conditions. CM
11.3 Check differential current
With the feeder supplying load current check that the relay measurements in the
MEASUREMENTS 3 menu column are as expected and that the differential current is similar
to the value of capacitive charging current previously measured for all.
• For load current flowing in the Forward direction - i.e. power export to the remote line
end, cell [0301: MEASUREMENTS 2, A Phase Watts] should show positive power
signing
• For load current flowing in the Reverse direction - i.e. power import from the remote line
end, cell [0301: MEASUREMENTS 2, A Phase Watts] should show negative power
signing
Note: The check above applies only for Measurement Modes 0 (default),
and 2. This should be checked in [0D05: MEASURE’T. SETUP,
Measurement Mode = 0 or 2]. If measurement modes 1 or 3 are
used, the expected power flow signing would be opposite to that
shown in the bullets above.
In the event of any uncertainty, check the phase angle of the phase currents with respect to
their phase voltage.
CM
Commissioning P54x/EN CM/Ia4
• Extract the settings from the relay using a portable PC running the appropriate software
via the front EIA(RS)232 port, located under the bottom access cover, or rear
communications port (with a KITZ protocol converter connected). Compare the settings
transferred from the relay with the original written application-specific setting record.
(For cases where the customer has only provided a printed copy of the required settings
but a portable PC is available).
• Step through the settings using the relay’s operator interface and compare them with the
original application-specific setting record. Ensure that all protection elements required
have been ENABLED in the CONFIGURATION column.
If the relay is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. These counters can be reset
using cell [0609: CB CONDITION, Reset All Values]. If the required access level is not
active, the relay will prompt for a password to be entered so that the setting change can be
made.
If the menu language has been changed to allow accurate testing it should be restored to the
customer’s preferred language.
If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the
cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records, alarms and LEDs and
communications statistics have been reset before leaving the relay.
CM
If applicable, replace the secondary front cover on the relay.
P54x/EN CM/Ia4 Commissioning
Model:
Injection test set
Serial No:
Model:
Optical power meter
Serial No:
Model:
Phase angle meter
Serial No:
Model:
Phase rotation meter
Serial No:
CM
Model:
Insulation tester
Serial No:
Type:
Setting software:
Version:
Commissioning P54x/EN CM/Ia4
*Delete as appropriate
Have all relevant safety instructions been
Yes* No*
followed?
5. Product checks
5.1 With the relay de-energized
5.1.1 Visual inspection
Relay damaged? Yes* No*
Rating information correct for installation? Yes* No*
Case earth installed? Yes* No*
Yes* No*
5.1.2 Current transformer shorting contacts close?
Not checked*
Yes* No*
5.1.3 Insulation resistance >100MΩ at 500V dc
Not tested*
5.1.4 External wiring
Wiring checked against diagram? Yes* No*
Yes* No*
Test block connections checked?
N/A*
5.1.5 Watchdog contacts (auxiliary supply off)
Terminals 11 and 12 Contact closed? Yes* No*
Terminals 13 and 14 Contact open? Yes* No*
*Delete as appropriate
*Delete as appropriate
Yes* No*
Opto input 27 working?
N/A*
Yes* No*
Opto input 28 working?
N/A*
Yes* No*
Opto input 29 working?
N/A*
Yes* No*
Opto input 30 working?
N/A*
Yes* No*
Opto input 31 working?
N/A*
Yes* No*
Opto input 32 working?
N/A*
5.2.7 Standard output relays
Relay 1 working? Yes* No*
Relay 2 working? Yes* No*
Relay 3 working? Yes* No*
Relay 4 working? Yes* No*
Relay 5 working? Yes* No*
Relay 6 working? Yes* No*
Relay 7 working? Yes* No*
Yes* No*
Relay 8 working?
N/A*
Yes* No*
Relay 9 working?
N/A*
Yes* No*
Relay 10 working?
N/A* CM
Yes* No*
Relay 11 working?
N/A*
Yes* No*
Relay 12 working?
N/A*
Yes* No*
Relay 13 working?
N/A*
Yes* No*
Relay 14 working?
N/A*
Yes* No*
Relay 15 working?
N/A*
Yes* No*
Relay 16 working?
N/A*
Yes* No*
Relay 17 working?
N/A*
P54x/EN CM/Ia4 Commissioning
*Delete as appropriate
Yes* No*
Relay 18 working?
N/A*
Yes* No*
Relay 19 working?
N/A*
Yes* No*
Relay 20 working?
N/A*
Yes* No*
Relay 21 working?
N/A*
Yes* No*
Relay 22 working?
N/A*
Yes* No*
Relay 23 working?
N/A*
Yes* No*
Relay 24 working?
N/A*
Yes* No*
Relay 25 working?
N/A*
Yes* No*
Relay 26 working?
N/A*
Yes* No*
Relay 27 working?
N/A*
Yes* No*
Relay 28 working?
N/A*
Yes* No*
Relay 29 working?
N/A*
Yes* No*
CM Relay 30 working?
N/A*
Yes* No*
Relay 31 working?
N/A*
Yes* No*
Relay 32 working?
N/A*
*Delete as appropriate
P545 & Yes* No*
High break Relay 17
P546
External wiring polarity check? N/A*
option I
*Delete as appropriate
Courier*
5.2.8 Communication standard IEC 60870-5-103*
DNP3.0*
Communications established? Yes* No*
Yes* No*
Protocol converter tested?
N/A*
K-Bus*
5.2.9 Second rear communication interface EIA485*
EIA232*
Communications established? Yes* No*
*Delete as appropriate
5.2.11 Voltage inputs
Displayed voltage Primary* Secondary*
Main VT ratio N/A*
C/S VT ratio N/A*
Input VT Applied Value Displayed value
VAN V V
VBN V V
VCN V V
C/S voltage V N/A* V
CB2 CS voltage V N/A* V
P593*
Fiber connections made with P59x unit on Ch 1? Yes* N/A*
Direct* C37.94*
P593* N/A* CM
Fiber connections made with P59x unit on Ch 2? Yes* N/A*
*Delete as appropriate
Communications using P59x units
n=4 for P591
n=5 for P592
6.1.n
n=6 for P593
Apply to MiCOMho Ch1 and/or Ch2 as
appropriate
6.1.n.1 Visual inspection (P59x units only) Ch1
Yes* No*
Ch 1 unit damaged?
N/A*
Yes* No*
Ch 1 rating information correct?
N/A*
Yes* No*
Ch 1 earthed?
N/A*
CM
6.1.n.5 Light emitting diodes (P59x units only)
Yes* No*
Ch 1 unit LED’s working?
N/A*
*Delete as appropriate
6.1.n.1 Visual inspection (P59x units only) Ch2
Yes* No*
Ch 2 unit damaged?
N/A*
Yes* No*
Ch 2 rating information correct?
N/A*
Yes* No*
Ch 2 earthed?
N/A*
*Delete as appropriate
7 GPS Synchronization
7.1.1 P594 commissioned? Yes* N/A*
dBm
7.1.2 P594 optical signal strength at P54x relay
N/A*
Check synchronization signal at P54x relay
7.1.3 Yes* N/A*
Bit pattern **11********** ?
Check GPS failure condition
7.1.4 Yes* N/A*
Bit pattern **00********** ?
Restore GPS
7.1.5 Yes* N/A*
Bit pattern **11********** ?
8 Setting checks
8.1 Application-specific function settings applied? Yes* No*
CM CB fail
Na*
8.3.1.2 Current differential lower slope pickup A
8.3.1.3 Current differential upper slope pickup A
8.3.2.1 Current differential phase A contact routing OK? Yes* No*
Current differential phase A trip time s
8.3.2.2 Current differential phase B contact routing OK? Yes* No*
Current differential phase B trip time s
8.3.2.3 Current differential phase C contact routing OK? Yes* No*
Current differential phase C trip time s
Average trip time, phases A, B and C s
Commissioning P54x/EN CM/Ia4
*Delete as appropriate
Protection dependencies noted & preparations
8.4.1 Yes* N/A*
made?
8.4.2 Injection testing - distance zones
Current diff
Earth fault
*Delete as appropriate
8.4.4 Distance protection scheme testing
8.4.4.1 Scheme trip zone 1 extension scheme
No trip for fault with reset Z1X energized Yes* No*
Trip time with reset Z1X de-energized ms
8.4.4.2 Scheme trip permissive schemes (PUR/POR)
Trip time with signal receive energized ms
8.4.4.3 Scheme trip blocking scheme
No trip for fault with signal receive energized Yes* No*
Trip time with signal receive de-energized ms
8.4.4.4 Signal send test for permissive schemes
Signal send operate time ms
8.4.4.5 Signal send blocking schemes
Signal send operate time ms
8.4.5 Scheme timer settings
Visual inspection
Time delays settings are correct? Yes* No*
All disabled elements which were noted/circled
Yes* No*
previously are restored?
8.4.6 Delta directional comparison
Current diff
Distance
Earth fault
Elements to be re-enabled after testing (circle
Overcurrent
any that have been temporarily disabled)
DEF
CB fail
CM Na*
Directional comparison protection Phase A
8.4.7.1 Yes* No*
contact routing OK?
Directional comparison protection Phase A trip
ms
time
Directional comparison protection Phase B
8.4.7.2 Yes* No*
contact routing OK?
Directional comparison protection Phase B trip
ms
time
Directional comparison protection Phase C
8.4.7.3 Yes* No*
contact routing OK?
Directional comparison protection phase C trip
ms
time
Average trip time, phases A, B and C ms
Commissioning P54x/EN CM/Ia4
*Delete as appropriate
8.4.8.1 Signal send test for permissive schemes
Signal send operate time ms
8.4.8.2 Signal send blocking schemes
Signal send operate time ms
All disabled elements which were noted/circled
Yes* No*
previously are restored?
8.4.9 Out of step protection
8.4.9.1 Predictive OST Enabled* N/A*
Operated correctly? Yes* No*
Operating time ms
8.4.9.2 OST Enabled* N/A*
Operated correctly? Yes* No*
Operating time ms
8.4.9.3 Predictive and OST Enabled* N/A*
Operated correctly? Yes* No*
Operating time ms
*Delete as appropriate
Applied current A
Expected operating time s
8.4.12.3 Measured operating time s
All disabled elements which were noted/circled
Yes* No*
previously are restored?
END-TO-END PROTECTION
9
COMMUNICATION TESTS
9.1 Communication Alarm Check
Any Ch 1 communication alarm? Yes* No*
Yes* No*
Any Ch 2 communication alarm?
N/A*
*Delete as appropriate
9.1.1 - 9.1.4 All local connections restored?
Local Ch 1 Yes* No*
Yes* No*
Local Ch 2
N/A*
Application-specific settings applied? (P592
only)
Yes* No*
Local Ch 1
N/A*
Yes* No*
Local Ch 2
N/A*
Cover replaced? (P59x only)
Yes* No*
Local Ch 1
N/A*
Yes* No*
Local Ch 2
N/A*
*Delete as appropriate
10 END-TO-END SCHEME TESTS
10.1 Signaling channel check
10.1.1.1 Aided scheme 1 signaling channel test
10.1.1.2 Yes* No*
Local - remote end signal received
N/A*
10.1.1.3 Yes* No*
Remote - local end signal received
N/A*
10.1.2 Aided scheme 2 signaling channel test
Yes* No*
Local - remote end signal received
N/A*
Yes* No*
Remote - local end signal received
N/A*
12 Final checks
All test equipment, leads, shorts and test blocks
Yes* No*
removed safely?
Yes* No*
Disturbed customer wiring re-checked?
N/A*
All commissioning tests disabled? Yes* No*
Application settings checked? Yes* No*
Yes* No*
Circuit breaker operations counter reset?
N/A*
Commissioning P54x/EN CM/Ia4
*Delete as appropriate
Yes* No*
Current counters reset?
N/A*
Event records reset? Yes* No*
Fault records reset? Yes* No*
Disturbance records reset? Yes* No*
Alarms reset? Yes* No*
COMMENTS #
CM
CM
Date: Date:
Commissioning P54x/EN CM/Ia4
*Delete as appropriate
Group 1 Yes* No*
Group 2 Yes* No*
Group 3 Yes* No*
Group 4 Yes* No*
0900 CONFIGURATION
0902 Setting Group Select via Menu* Select via Optos*
Group 1* Group 2* Group 3*
0903 Active Settings
Group 4*
0907 Setting Group 1 Disabled* Enabled*
0908 Setting Group 2 Disabled* Enabled*
0909 Setting Group 3 Disabled* Enabled*
090A Setting Group 4 Disabled* Enabled*
090B Distance Disabled* Enabled*
090C Directional E/F Disabled* Enabled*
090F Phase Diff Disabled* Enabled*
0910 Overcurrent Disabled* Enabled*
0911 Neg Sequence O/C Disabled* Enabled*
0912 Broken Conductor Disabled* Enabled*
0913 Earth Fault Disabled* Enabled*
0915 Sensitive E/F Disabled* Enabled*
0916 Residual O/V NVD Disabled* Enabled*
0917 Thermal Overload Disabled* Enabled*
0918 PowerSwing Block Disabled* Enabled*
091D Volt Protection Disabled* Enabled*
091E Freq Protection Disabled* Enabled*
091F df/dt Protection Disabled* Enabled*
0920 CB Fail Disabled* Enabled*
0921 Supervision Disabled* Enabled*
0923 System Checks Disabled* Enabled*
0924 Auto-Reclose Disabled* Enabled*
CM
0925 Input Labels Invisible* Visible*
0926 Output Labels Invisible* Visible*
0928 CT & VT Ratios Invisible* Visible*
0929 Record Control Invisible* Visible*
092A Disturb Recorder Invisible* Visible*
092B Measure't Setup Invisible* Visible*
092C Comms Settings Invisible* Visible*
092D Commission Tests Invisible* Visible*
092E Setting Values Primary* Secondary*
092F Control Inputs Invisible* Visible*
0935 Control I/P Config Invisible* Visible*
0936 Ctrl I/P Labels Invisible* Visible*
0939 Direct Access Disabled* CB Control only*
Hotkey only* Enabled*
64
0941 InterMiCOM Fiber Disabled* Enabled*
Commissioning P54x/EN CM/Ia4
0900 CONFIGURATION
0950 Function Key Invisible* Visible*
09FF LCD Contrast
0E00 COMMUNICATIONS
Courier* IEC870-5-103*
0E01 RP1 Protocol
DNP3.0*
0E02 RP1 Address
0E03 RP1 InactivTimer
1200* 2400* 4800*
0E04 RP1 Baud Rate
9600* 19200* 38400*
0E05 RP1 Parity Odd* Even* None*
0E06 RP1 Meas. Period
P54x/EN CM/Ia4 Commissioning
0E00 COMMUNICATIONS
0E07 RP1 Physical Link EIA(RS)485* Fiber Optic*
0E08 RP1 Time Sync. Disabled* Enabled*
Disabled* Monitor Blocking*
0E0A RP1 CS103 Blocking
Command Blocking*
K-bus* EIA 485*
0E0C RP1 Port Config. Not applicable*
Primary* Secondary*
0E0F Meas scaling. Normalized* Not applicable*
2002/3 Address
2010 Comms Mode
2011 Baud Rate Ch1 56kbits 64kbits
2012 Baud Rate Ch2 56kbits 64kbits
2013 Clock Source Ch1 Internal External
2014 Clock Source Ch2 Internal External
2015 Ch1 N*64kbits/s
2016 Ch2 N*64kbits/s
2018 Comm Fail Timer
2019 Comm Fail Mode
201A GPS Sync
201B Char Mod Time
201C Prop Delay Equal
201D Re-Configuration
201E Channel Timeout
201F IM Msg Alarm Lvl
2020 Prop Delay Stats
2021 MaxCh 1 PropDelay
2022 MaxCh 2 PropDelay
2023 TxRx Delay Stats
2024 MaxCh1 Tx-RxTime
2025 MaxCh2 Tx-RxTime
2026 GPS Fail Timer
CM
2027 GPS Trans Fail
2028 GPS Trans Count
2029 GPS Trans Timer
2030 IM1 Cmd Type
2031 IM1 FallBackMode
2032 IM1 DefaultValue
2034 IM2 Cmd Type
2035 IM2 FallBackMode
2036 IM2 DefaultValue
2038 IM3 Cmd Type
2039 IM3 FallBackMode
203A IM3 DefaultValue
203C IM4 Cmd Type
203D IM4 FallBackMode
203E IM4 DefaultValue
Commissioning P54x/EN CM/Ia4
CM Group 1 settings
Group 1
settings
Group 2
settings
Group 3
settings
Group 4
settings
310C Setting Mode
3111 Phase Chars
3112 Quad Resistance
3113 Fault Resistance
3120 Zone 1 Ph Status
3121 Zone 1 Ph Reach
3130 Zone 2 Ph Status
3131 Zone 2 Ph Reach
3140 Zone 3 Ph Status
3141 Zone 3 Ph Reach
3142 Zone 3 Ph Offset
3143 Z3Ph Rev Reach
3150 Zone P Ph Status
3151 Zone P Ph Dir
Commissioning P54x/EN CM/Ia4
CM 3311 Susceptance
3312 Inrush Restraint
3313 Id High Set
3314 Kr (Temporary)
3315 Vectorial Comp
3316 Phase Is1 CTS
PIT I Selection
3500 OVERCURRENT
Group 1 Group 2 Group 3 Group 4
Group 1 settings
settings settings settings settings
350C I>2 Directional
350D I>2 Current Set
350E I>2 Time Delay
350F I>2 TMS
3510 I>2 Time Dial
3511 I>2 Reset Char
3512 I>2 tRESET
3513 I>3 Status
3514 I>3 Directional
3515 I>3 Current Set
3516 I>3 Time Delay
3518 I>4 Status
3519 I>4 Directional
351A I>4 Current Set
351B I>4 Time Delay
351C I> Char Angle
351D I> Blocking
4600 SUPERVISION
Group 1 Group 2 Group 3 Group 4
Group 1 settings
settings settings settings settings
4601 VTS Mode
4602 VTS Status
4603 VTS Reset Mode
4604 VTS Time Delay
4605 VTS I> Inhibit
4606 VTS I2> Inhibit
460E INRUSH DETECTION
460F I>2nd Harmonic
4610 WEAK INFEED BLK
4611 WI Inhibit
4612 I2/I1 Setting
4630 CT SUPERVISION
4631 CTS Mode
4632 CTS Status
4633 CTS Reset Mode
4634 CTS Time Delay
4635 CTS VN< Inhibit
4636 CTS IN> Set
4637 CTS i1
4638 CTS i2/i1>
4639 CTS i2/i1>>
P543/P545
4800 SYSTEM CHECKS
CM model
Group 1 Group 2 Group 3 Group 4
Group 1 settings
settings settings settings settings
4815 Live Voltage
4816 Dead Voltage
4818 CS1 Status
4819 CS1 Phase Angle
481A CS1 Slip Control
481B CS1 Slip Freq.
481C CS1 Slip Timer
481D CS2 Status
481E CS2 Phase Angle
481F CS2 Slip Control
4820 CS2 Slip Freq.
4821 CS2 Slip Timer
4822 CS Undervoltage
Commissioning P54x/EN CM/Ia4
P543/P545
4800 SYSTEM CHECKS
model
Group 1 Group 2 Group 3 Group 4
Group 1 settings
settings settings settings settings
4823 CS Overvoltage
4824 CS Diff. Voltage
4825 CS Voltage Block
4827 SS Status
4828 SS Phase Angle
4829 SS Under V Block
482A SS Undervoltage
482B SS Timer
P543/P545
4900 AUTO-RECLOSE
model
Group 1 Group 2 Group 3 Group 4
Group 1 settings
settings settings settings settings
4905 Single Pole Shot
4906 Three Pole Shot
4907 1 Pole Dead Time
4908 Dead Time 1
4909 Dead Time 2
490A Dead Time 3
490B Dead Time 4
490C CB Healthy Time
Commissioning P54x/EN CM/Ia4
P543/P545
4900 AUTO-RECLOSE
model
Group 1 Group 2 Group 3 Group 4
Group 1 settings
settings settings settings settings
490F Reclaim Time
4910 AR Inhibit Time
4925 Check Sync Time
4927 Z2T AR
(Only in models with
distance option)
4928 Z3T AR
(Only in models with
distance option)
4929 ZPT AR
(Only in models with
distance option)
492A Z4T AR
(Only in models with
distance option)
492B DEF Aided AR
(Only in models with
distance option)
492C Dir. Comp AR
(Only in models with
distance option)
492D TOR AR
(Only in models with
distance option)
492F I>1 AR
4930 I>2 AR CM
4931 I>3 AR
4932 I>4 AR
4933 IN>1 AR
4934 IN>2 AR
4935 IN>3 AR
4936 IN>4 AR
4939 Mult Phase AR
493A Dead Time Start
493B Discrim Time
493C ISEF>1 AR
493D ISEF>2 AR
493E ISEF>3 AR
493F ISEF>4 AR
4940 SYSTEM CHECKS
P54x/EN CM/Ia4 Commissioning
P543/P545
4900 AUTO-RECLOSE
model
Group 1 Group 2 Group 3 Group 4
Group 1 settings
settings settings settings settings
4941 CS1 Close Enable
4942 CS2 Close Enable
4943 LiveLine/DeadBus
4944 DeadLine/LiveBus
4945 DeadLine/DeadBus
4946 CS AR Immediate
4947 SysChk on Shot 1
Date: Date: