Professional Documents
Culture Documents
Lafarge Thermography Program
Lafarge Thermography Program
TABLE OF CONTENTS
ii
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
1 What is Thermography
a) Introduction
Of the many myths being propagated today, the four main ones that,
unfortunately, can still be heard regarding infrared electrical inspections are:
Infrared inspections are not necessary because each year all the connections
are tightened.
Infrared inspection of electrical components can accurately be made
through cabinet doors and other covers.
It is not necessary to obtain the current flow reading of the electrical
system.
1
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
Temperature measurement is accurate as long as you can see the hot spot.
To have a good connection, two elements must be taken into account. Clean
contact surfaces, along with the proper exertion of force and pressure. Contact
resistance decreases as forces are increased, but only to a certain point. You
can go too far.
2
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
However, after stating this, it is good practice to take a quick look at the
cabinet doors prior to the electrician opening them. The reason is, should an
exceptionally warm door be found, the electrician can be cautioned. There
may be an exceptional problem behind the door and it is in fact creating
enough thermal energy to warm up the cabinet and the door. Be careful.
Some electrical cabinets cannot be opened up while under load, if you attempt
to do so, it will shut down. What method can you use to inspect these with
thermography? One method is to document a number of parameters to
establish a baseline to compare future readings.
If on future inspections the overall cabinet temperature has risen and the load
and ambient temperatures are the same, one can suspect a problem. If the
thermal pattern has changed and the load and ambient have remained the same,
suspect an anomaly again. Please note this is not exact. When the cabinet is
opened, the actual anomaly will still have to be identified from many
possibilities. If possible, open up the cabinet quickly after shutdown and
attempt to identify the anomaly by looking at the residual heat.
3
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
Another method is to drill small holes, approximately 1/2", into the cabinet
door in strategic places. When performing the inspection, place the lens of the
instrument against the hole and observe the thermal pattern of the components
in the cabinet. Before drilling any holes, make sure this is legal for the specific
equipment and industry.
The best method is to put an infrared window into the cabinet door. The
windows are approximately 3" in diameter and are both transparent to SW and
LW infrared as well as the visible spectrum. This makes it simple to identify
anomalies and measure the temperatures. There are transmission losses that
will have to be taken into consideration for accurate temperature measurement.
The concern is that some thermographers consider there is enough load on the
circuit as long as they can see some thermal emitting from the components.
Without knowing the actual load, temperature measurement is misleading.
Without accurate temperatures, it is difficult, if not impossible, to evaluate and
classify the severity of the problem.
4
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
Along with load, there are a number of important parameters to consider when
evaluating the severity of an anomaly on an electrical system. They are: size
and mass of the component, angle of view, obstructions between the infrared
instrument and the component, heat transfer rates of conduction, radiation and
convection, size of the target and distance, importance of component to the
system or process, calibration of the infrared instrument, ambient fluctuations,
equipment cycling, component temperature rating and so on.
There are several different types of infrared imaging radiometers with varying
optics. The effect of object size, thermal contrast, and distance-to-the-object
are very different from a classroom and in the field. The other lesson that is
drilled home is just because you can "see" the anomaly that does not mean you
can measure it accurately. The criticality of the target size and distance ratio
for electrical inspection ranks right up there with emissivity, reflectivity, and
load. In many cases, this ratio is the greatest source of error both for
qualitative and quantitative evaluation. With this in mind, what can be done to
reduce the problem to a manageable level? The answer is simple, education!
Just by being aware of the problem gives us a good beginning to increased
accuracy.
5
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
f) Conclusion
These four myths are the most prevalent to infrared electrical inspections.
Furthermore, not considering operator competence or specific equipment
capabilities, there are three important factors to consider and correlate when
making a temperature measurement: object size and distance, electrical load
and wind speed. Also when performing IR analysis, additional studies and
investigation must be undertaken for resistance temperature, the effects of
convection on electric components, fault classification - combining delta-T
method, direct temperature, component temperature rating, and temperature
trending.
a) Purpose
Temperature is one of the first observable parameters that can indicate the
condition of operating equipment. Infrared condition monitoring is a technique
capable of revealing the presence of an anomaly by virtue of the thermal
distribution profile which the defect produces on the surface of the component.
The defect will normally alter the thermal signature of the surface due to the
change in the amount of heat generated and the heat transfer properties of the
component. To determine an adverse operating temperature of a component, it
is necessary to first determine a baseline. This is the thermal signature and
temperature distribution indicating a normal loading condition. Once the
baseline is established, new data collected on a regular schedule will be
compared to it.
6
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
c) Alarm Levels
There are two methods for several classification of faults, the temperature rise
(Delta T) method and the direct temperature method. The first method has
been the standard in the industry for 20 years but has some weaknesses. This
classifies the temperature rise to be minor, intermediate or major. For example,
a temperature rise between 10C and 30C would be classified as an
intermediate fault with a recommendation to be repaired at the next shutdown.
The main problem with this method is it does not take ambient and running
conditions or the maximum rated temperature of the component into
consideration. This means that a 30C rise may not be an intermediate fault
classification but a major fault because the actual temperature of the
component exceeds the rated component temperature and should be dealt with
immediately.
The trend today is to create fault classifications based on the actual component
temperature. This means that the thermographer will have to do his/her
homework to obtain the rated temperature from manufacturers and electrical
standards institutes. As well, temperature corrections must be made for
varying load conditions and wind.
d) Electrical Equipment
7
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
8
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
e) Mechanical Equipment
Oil and vibration analysis techniques are normally used to evaluate the
condition of rotating equipment. Oil and vibration analysis techniques are
used to detect and diagnose equipment problems. Excessive heat is normally
generated at a later stage in the equipment deterioration when there is an
inadequate lubrication, misuse, overload, and/or abnormal wear.
Infrared thermography can be used for the same reasons, however, this
technique is very useful to confirm problems and to find the root cause of
problems.
9
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
10
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
f) Steam Systems
11
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
g) Refractory Inspections
12
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
h) Buildings
13
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
i) Built-up Roofs
Even though a roof is part of the building envelope, we will deal with it as a
separate item. A roof inspection goes well beyond the detection of heat loss,
for the roof functions not only as a thermal barrier for conserving energy but
also as a waterproof membrane for the building.
Lafarge Personnel
Using this technique on a regular basis is very helpful for the plant to properly
diagnose temperature related equipment problems and develop trending data to
predict equipment failure. However, one or two employees should be trained
and dedicated to the infrared thermography program to get maximum benefit
from the equipment investment. A regularly scheduled training program must
be established to continue the learning process and expand the program to
encompass new applications.
14
PPM GUIDELINES
LAFARGE INFRARED THERMOGRAPHY PROGRAM 9/13/1999 04:05:00 PM
Outside Services
According to cautions mentioned on the previous page, the plant should be
very careful when selecting outside services. It is recommended to use a good
company, well established, and with experienced people. The plant should
insist on always having the same thermographer performing the work.
15