Help For Installing Fujitsu Air Conditioners PDF
Help For Installing Fujitsu Air Conditioners PDF
Contents
1. SAFETY PRECAUTIONS........................................................................................... 1
2. ABOUT THE PRODUCT............................................................................................ 3
3. SELECTING THE MOUNTING POSITION................................................................ 4
4. INSTALLATION DIAGRAM......................................................................................... 5
5. INSTALLATION ......................................................................................................... 5
6. PUMP DOWN............................................................................................................. 7
WARNING
1. SAFETY PRECAUTIONS
Do not modify this unit, such as opening a hole in the cabinet.
•• Read carefully all of safety information written in this manual before you install or use
During the pump-down operation, make sure that the compressor is turned off before
the air conditioner.
you remove the refrigerant piping.
•• The warnings and precautions indicated in this manual contain important information
Do not remove the connection pipe while the compressor is in operation with 2 way or 3
pertaining to your safety. Be sure to observe them.
way valve open. This may cause abnormal pressure in the refrigeration cycle that leads
•• Hand this manual, together with the operating manual, to the customer. Request the
to rupture and even injury.
customer to keep them on hand for future use, such as for relocating or repairing the
unit.
WARNING
Indicates a potentially or imminently hazardous situation which, if CAUTION
not avoided, could result in death or serious injury.
This unit must be installed by qualified personnel with a capacity certification of handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
Indicates a potentially hazardous situation that may result in minor or
CAUTION moderate injury or damage to property. Install the unit by following local codes and regulations in force at the place of
installation, and the instructions provided by the manufacturer.
This unit is part of a set constituting an air conditioner. The unit must not be installed
WARNING alone or be installed with non-authorized device by the manufacturer.
To avoid getting an electric shock, never touch the electrical components soon after the When installing pipes shorter than 3 m, sound of the outdoor unit will be transferred to
power supply has been turned off. After turning off the power, always wait 10 minutes or the indoor unit, which will cause large operating sound or some abnormal sound.
more before you touch the electrical components..
To protect the persons, earth( ground) the unit correctly, and use the power cable
Installation of this product must be done by experienced service technicians or combined with an Earth Leakage Circuit Breaker (ELCB).
professional installers only in accordance with this manual. Installation by non-
professional or improper installation of the product might cause serious accidents such The units are not explosion proof, and therefore should not be installed in explosive atmosphere.
as injury, water leakage, electric shock, or fire. If the product is installed in disregard of This unit contains no user-serviceable parts. Always consult experienced service
the instructions in this manual, it will void the manufacturer’s warranty. technicians for repairing.
Do not turn on the power until all work has been completed. Turning on the power before When moving or relocating the air conditioner, consult experienced service technicians
the work is completed can cause serious accidents such as an electric shock or a fire. for disconnection and reinstallation of the unit.
If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant is Children should be monitored to ensure they do not play with the device.
exposed to a direct flame, it may produce a toxic gas. This appliance is not intended for use by persons (including children) with reduced
Installation must be performed in accordance with regulations, codes, or standards for physical, sensory or mental capabilities, or lack of experience and knowledge, unless
electrical wiring and equipment in each country, region, or the installation place. they have been given supervision or instruction concerning use of the appliance by a
Do not use this equipment with air or any other unspecified refrigerant in the refrigerant person responsible for their safety. Children should be supervised to ensure that they do
lines. Excess pressure can cause a rupture. not play with the appliance.
During installation, make sure that the refrigerant pipe is attached firmly before you Do not touch the aluminum fins of heat exchanger built-in the indoor or outdoor unit to
run the compressor. Do not operate the compressor under the condition of refrigerant avoid personal injury when you install or maintain the unit.
piping not attached properly with 2-way or 3-way valve open. This may cause abnormal Do not place any other electrical products or household belongings under indoor unit or
pressure in the refrigeration cycle that leads to rupture and even injury. outdoor unit. Condensation dripping from the unit might get them wet, and may cause
When installing or relocating the air conditioner, do not mix gases other than the damage or malfunction of your property.
specified refrigerant (R32) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to Precautions for using R32 refrigerant
an abnormally high value and cause rupture, injury, etc.
The basic installation work procedures are the same as conventional refrigerant (R410A,
For appropriate working of the air conditioner, install it as written in this manual. R22) models.
However, pay careful attention to the following points:
To connect indoor unit and outdoor unit, or indoor unit and branch box, use air
conditioner piping and cables available through your local distributor. This manual
describes proper connections using such installation set.
WARNING
Since the working pressure is 1.6 times higher than that of refrigerant R22 models,
Do not modify power cable, use extension cable or branch wiring. Improper use may
some of the piping and installation and service tools are special. (See “2.1. Special
cause electric shock or fire by poor connection, insufficient insulation or over current.
tools for R32 (R410A)”.)
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model,
always replace the conventional piping and flare nuts with the R32 and R410A piping
There is no extra refrigerant in the outdoor unit for air purging.
and flare nuts on the outdoor unit side.
Do not use means to accelerate the defrosting process or to clean, other than those For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be used.
recommended by the manufacturer.
Models that use refrigerant R32 and R410A have a different charging port thread diam-
The appliance shall be stored in a room without continuously operating ignition eter to prevent erroneous charging with refrigerant R22 and for safety. Therefore, check
sources (for example: open flames, an operating gas appliance or an operating beforehand. [The charging port thread diameter for R32 and R410A is 1/2 inch.]
electric heater. Be more careful than R22 so that foreign matter (oil, water, etc.) does not enter the piping.
Do not pierce or burn. Also, when storing the piping ,securely seal the opening by pinching, taping, etc. (Han-
dling of R32 is similar to R410A.)
Be aware that refrigerants may not contain an odour.
Using the same vacuum pump for different refrigerants may damage the vacuum pump
or the unit.
Use a clean gauge manifold, vacuum pump and charging hose for R32 or R410A
exclusively.
En-1
En-2
En-3
WARNING The outdoor unit with the refrigerant removed from the packaging is sealed.
(Indoor unit, the refrigerant is not sealed.)
Always use a special branch circuit and install a special receptacle to supply power to
the room air conditioner. 2.5. Additional charge
Use a circuit breaker and receptacle matched to the capacity of the air conditioner. For the additional amount, see the table below.
Install a leakage circuit breaker in accordance with the related laws and regulations Pipe length 20 m 25 m 30 m Rate
and electric company standards. model 07,09,12,18KU None - - -
Additional refrigerant
model 18*1,22,24 None +100 g +200 g 20 g/m
The circuit breaker is installed in the permanent wiring. Always use a circuit that can
trip all the poles of the wiring and has an isolation distance of at least 3 mm between
Maximum amount of refrigerant charge
the contacts of each pole.
model 07,09,12 850 g
model 18KU 1270 g
CAUTION model 18*1,22,24 1470 g (1270 g + 200 g)
The power source capacity must be the sum of the air conditioner current and the cur- *1
Except 18KU
rent of other electrical appliances. When the current contracted capacity is insufficient,
change the contracted capacity. 2.6. Operating range
When the voltage is low and the air conditioner is difficult to start, contact the power
company the voltage raised.
Cooling mode
Heating mode
Dry mode
2.3. Electric requirement Outdoor temperature
model 07,09,12,18KU 10 to 46 ˚C
-15 to 24 ˚C
model 18*1,22,24 -10 to 46 ˚C
CAUTION *1
Except 18KU
Voltage rating 1 ø 240 V (50 Hz) Drain pipe*1 Drain cap*1*2 Cable tie Installation
manual
Operating range 198-264 V
1 3
1 1
Cable Conductor size [mm2]*1 Type Remarks
model *1 : Included only reverse cycle model
1.5
07,09,12 *2 : Included only model 18,22,24
2cable + Earth
Power supply model One set of following parts are necessary installation of this product.
2.5 Type 60245 IEC57 (Ground),
cable 18
1ø240V
Name
model Connection pipe assembly
4.0
22,24 Connection cable
Wall pipe
model Decorative tape
1.5
07,09,12 3cable + Earth Vinyl tape
Connection
Type 60245 IEC57 (Ground), Wall cap
cable
model 1ø240V
1.5-2.5 Saddle
18,22,24
Drain hose
Demand Tapping screws
Double insulated Sealant
control signal
0.5-1.5 AS/NZS 5000.2. (Max. length :
transmission
30m)
cable 3. SELECTING THE MOUNTING POSITION
*1
elected sample: Select the correct cable type and size according to the country or
S
• Decide the mounting position with the customer as follows.
region’s regulations.
Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the • Do not set to a place where there is oily smoke, oil is used in the factory, the unit can
wire diameter when the wire length is long. contact sea breeze, sulfide gases will be generated in the hot spring area, corrosive
gases will be generated, animal may urine on the unit and ammonia will be generated
Breaker Specification*2 and a dusty place.
En-4
Terminal board
54 cm
Terminal block
Screw with special washer
32 cm
Crimp-type terminal
Wire
• Do not directly install it on the ground, otherwise it will cause failure. CAUTION
• To obtain better operation efficiency, when the outdoor unit is installed,
be sure to open the front and left side. Match the terminal block numbers and connection cable colors with those of the outdoor
unit or branch box. Incorrect wiring may cause a fire..
Outdoor unit bottom Connect the connection cables firmly to the terminal block. Imperfect installation may
cause a fire.
When fixing the connection cable with the cable clamp, always fasten the cable at the
plastic jacket portion, but not at the insulator portion. If the insulator is chafed, electric
leakage may occur.
Do not use an earth screw for an external connector. Only use for interconnection
between two units.
Drain pipe Drain pipe
Drain caps Be careful not to generate a spark as follows for using a flammable refrigerant.
Without caps With caps • Do not remove the fuse while power is on.
• Do not disconnect plug from the wall outlet and the wiring while the power is on.
CAUTION • It is recommended to position the outlet connection in a high position. Place the
cords so that they do not get tangled.
When the outdoor temperature is 0 ˚C or less, do not use the accessory drain pipe
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may Confirm the indoor unit model name before connecting.If the indoor unit is not R32
freeze in extreme cold weather. (Reverse cycle model only) compatible, error signal will be displayed, and the unit will be inoperable.
In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with
snow, it might become difficult to get warm and it is likely to cause of the breakdown. 5.4. Outdoor unit wiring
Please construct a canopy and a pedestal or place the unit on a high stand (local
configured). (1) Remove the outdoor unit Switch cover A, B.
(2) Remove the outdoor unit cable clamp.
(3) Bend the end of the cable as shown in the figure.
5. INSTALLATION (4) Connect the end of the connection cable fully into the terminal block.
(5) Fasten the sheath with a cable clamp.
(6) Fasten the sheath with a cable tie. (Demand control )
5.1. Outdoor unit installation (7) Install the Switch cover A, B.
• Set the unit on a strong stand such as thing made of concrete blocks to minimize shock and vibration.
• Do not set the unit directly on the ground because it will cause trouble.
Demand control signal
WARNING terminal block
1 : DRM 1 Screw
Install the unit where it will not be tilted by more than 5°.
2 : DRM 2 1 2 3 C 1 2 3 L N
When installing the outdoor unit where it may exposed to strong wind, fasten it securely. 3 : DRM 3
To smart meter Cable clamp
C : COMMON
5.2. Switch cover remove
Thread the cable tie Cable tie
Switch cover A, B removal through the hole and (Accessories)
tighten securely
Hook (1) Remove the tapping screws.
(2) Push downward the Switch cover B. Cut off the excess
Switch cover A (3) Push upward the Switch cover A.
Switch cover B
Hooks
En-5
30 mm
or more 30 mm CAUTION
or more
Earth
Fasten a flare nut with a torque wrench as instructed in this manual. If fastened too
(Ground) tight, the flare nut may be broken after a long period of time and cause a leakage of
cable Connection cable Demand control
signal transmission refrigerant.
40 mm Power supply cable
cable
or more
Run the connection cable to the rear of the outdoor unit CAUTION
within the "A "range of the arrows shown in the figure.
(The switch cover becomes difficult to install.) Refrigerant must not be discharged into atmosphere.
HOLE Connection and Power After connecting the piping , check the joints for gas leakage with gas leak detector.
supply cable
Demand control signal (1) Check if the piping connections are secure.
transmission cable (2) Check that the stems of 2-way valve and 3-way valve are closed fully.
"A"
(3) Connect the gauge manifold charge hose to the charging port of the 3-way valve (side
• Enquiries when testing the operation of the demand control : with the projection for pushing in the valve core).
Consult Fujitsu General Customer Service and your energy (4) Open the low pressure side valve of the gauge manifold fully.
HOLE provider if you have any operational issues or errors are caused. (5) Operate the vacuum pump and start pump down.
(6) Slowly loosen the flare nut of the 3-way valve and check if air enters, then retighten
CAUTION the flare nut.
(When the flare nut is loosened the operating sound of the vacuum pump changes
Route the demand control signal transmission cable away from the power supply and the reading of the compound pressure gauge goes from minus to zero.)
cable. Adjacent wiring of those cables may lead the product malfunctions caused by (7) Pump down the system for at least 15 minutes, then check if the compound pressure
generated noise. gauge reads -0.1 MPa (-76 cmHg, -1 bar).
(8) At the end of pump down, close the low pressure side gauge of the gauge manifold
fully and stop the vacuum pump.
(9) Slowly loosen the valve stem of the 3-way valve. When the compound pressure
5.5. Connecting the piping gauge reading reaches 0.1-0.2 MPa, retighten the valve stem and disconnect the
charge hose from the 3-way valve charging port.
CONNECTION (If the stem of the 3-way valve is opened fully before the charge hose is disconnect-
ed, it may be difficult to disconnect the charge hose.)
(1) Install the outdoor unit wall cap (supplied with the optional installation set or pro-
(10) Fully open the valve stems of the 2-way valve and 3-way valve using a hexagon
cured at the site) to the wall pipe.
wrench. (After the valve stem begins to turn, turn it with a torque of less than
(2) Connect the outdoor unit and indoor unit piping. 2.9 N • m until it stops turning.)
(3) After matching the center of the flare surface and tightening the nut hand tight, (11) Firmly tighten the 2-way valve and 3-way valve blank cap and the charging port cap.
tighten the nut to the specified tightening torque with a torque wrench. (Table 1)
Gauge manifold
FLARING Compound pressure gauge
Check if [L] is flared uniformly and Pressure gauge
(1) Cut the connection pipe to the necessary -0.1 MPa
length with a pipe cutter. is not cracked or scratched. 2-way valve
3-way valve (-76 cmHg
(2) Hold the pipe downward so that cuttings
Flare nut -1 bar)
will not enter the pipe and remove the
High
burrs.
Low pressure pressure
(3) Insert the flare nut onto the pipe and flare
side valve side valve
the pipe with a flaring tool.
Insert the flare nut (always use the flare nut (closed)
attached to the indoor and outdoor units
respectively) onto the pipe and perform the flare Valve stem
Charge
processing with a flare tool.
Die Blank cap hose
Use the special R410A flare tool, or the R22 Charge hose
flare tool.
When using the conventional flare tool, always A Charging port
use an allowance adjustment gauge and secure Charging port cap Vacuum pump
the A dimension shown in table 2. Pipe
Holding spanner
Body side
90°
Torque wrench
To prevent gas leakage, coat the flare
surface with refrigerator oil.
En-6
6. PUMP DOWN
CAUTION
Please check the refrigerant circuit for any leaks before starting the pump down
operation.
Do not proceed with the pump down operation if there is no refrigerant left in the
circuit due to bent or broken piping
During the pump down operation, be sure to turn off the compressor before
removing the refrigerant piping.
En-7