SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
B
No. FROM TO A C D
= Ax1.2
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
B
No. FROM TO A C D
= Ax1.2
MV-7
8 (MDB-01) PCHWP-CEP-13(N) 55.00 55.00 100.02 120.03 320 4C-
9 PE-EFP01(N) 187.5 187.50 340.99 409.19 630 4C-
10 DB-HV 16.13 15.27 24.99 29.99 63 4C-
11 E-PEBP01(N) 131 98.20 160.73 192.88 250 4C-
12 CEP-UPS1 25.50 25.50 41.74 50.08 250 4C-
13 HV-ACDB 20.30 20.30 33.23 39.87 100 4C-
14 CEP-UPS2 20.00 20.00 32.74 39.28 250 4C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
B
No. FROM TO A C D
= Ax1.2
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
B
No. FROM TO A C D
= Ax1.2
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
B
No. FROM TO A C D
= Ax1.2
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
CONNECTED LOAD
DEMAND LOAD
DEMAND CURRENT
(20%)
MD CURRENT + SPARE
(In)
SELECTED CB RATING
PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION
B
No. FROM TO A C D
= Ax1.2
EARTHING CONDUCTOR
SELECTED CABLE SIZE
(Iz)
CABLE RATED CURRENT
(Ca)
AMBIENT AIR FACTOR
(Cg)
GROUPING FACTOR
CURRENT (It)
CABLE DERATED
VOLTAGE
PHASE
LENGTH
METER
PER AMPERE PER
CABLE VOLTAGE DROP
NO. OF CABLES
DROP
CALCULATED VOLTAGE
DROP
PERCENT VOLTAGE
VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 124.88 415 3 30 0.76 1 0.75 0.18 4
240 1C- 120 952 0.91 0.88 786.71 415 3 20 0.211 1 2.05 0.49 1.5
150 1C- 150 812 0.91 0.88 786.71 415 3 20 0.303 2 1.11 0.27 4
50 1C- 25 197 0.91 0.88 78.67 415 3 50 0.76 1 0.30 0.07 4
240 1C- 240 952 0.91 0.88 499.50 415 3 35 0.211 2 0.60 0.15 4
240 1C- 120 353 0.91 0.88 312.19 415 3 15 0.211 1 0.31 0.07 1.5
50 1C- 25 197 0.91 0.88 78.67 415 3 45 0.76 1 0.22 0.05 4
PHASE CONDUCTOR
SELECTED CABLE SIZE
EARTHING CONDUCTOR
SELECTED CABLE SIZE
(Iz)
CABLE RATED CURRENT
(Ca)
AMBIENT AIR FACTOR
(Cg)
GROUPING FACTOR
CURRENT (It)
CABLE DERATED
VOLTAGE
PHASE
LENGTH
METER
PER AMPERE PER
CABLE VOLTAGE DROP
NO. OF CABLES
DROP
CALCULATED VOLTAGE
DROP
PERCENT VOLTAGE
VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
240 1C- 240 952 0.91 0.88 399.60 415 3 25 0.211 2 0.32 0.08 4
150 1C- 150 812 0.91 0.88 786.71 415 3 40 0.303 2 2.48 0.60 4
50 1C- 25 197 0.91 0.88 78.67 415 3 20 0.76 1 0.46 0.11 2.5
240 1C- 120 353 0.91 0.88 312.19 415 3 17 0.211 1 0.69 0.17 1.5
240 1C- 120 353 0.91 0.88 312.19 415 3 40 0.211 1 0.42 0.10 1.5
50 1C- 25 197 0.91 0.88 124.88 415 3 23 0.76 1 0.70 0.17 2.5
240 1C- 120 353 0.91 0.88 312.19 415 3 40 0.211 1 0.33 0.08 1.5
PHASE CONDUCTOR
SELECTED CABLE SIZE
EARTHING CONDUCTOR
SELECTED CABLE SIZE
(Iz)
CABLE RATED CURRENT
(Ca)
AMBIENT AIR FACTOR
(Cg)
GROUPING FACTOR
CURRENT (It)
CABLE DERATED
VOLTAGE
PHASE
LENGTH
METER
PER AMPERE PER
CABLE VOLTAGE DROP
NO. OF CABLES
DROP
CALCULATED VOLTAGE
DROP
PERCENT VOLTAGE
VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 78.67 415 3 27 0.76 1 0.13 0.03 1.0
50 1C- 25 197 0.91 0.88 78.67 415 3 15 0.76 1 0.45 0.11 1.0
50 - 25 197 - - - - - 15 0.76 1 - - -
50 1C- 25 197 0.91 0.88 78.67 415 3 20 0.76 1 0.07 0.02 1.0
50 1C- 25 197 0.91 0.88 78.67 415 3 25 0.76 1 0.10 0.02 1.0
50 1C- 25 197 0.91 0.88 78.67 415 3 27 0.76 1 0.07 0.02 1.0
50 1C- 25 197 0.91 0.88 99.90 415 3 47 0.76 1 0.49 0.12 1.0
ALLOWABLE PERCENT
(%)
1.0
1.0
1.0
Q
VD LIMIT
(O/J) x
100%
PERCENT VOLTAGE
0.03
0.05
0.05
(%)
P=
DROP
(1000xN)
(BxMxL)/
CALCULATED VOLTAGE
0.14
0.20
0.23
O=
(V)
DROP
NO. OF CABLES
N
1
1
1
0.76
0.76
0.76
METER
(m)
20
35
37
LENGTH
L
PHASE
Ø
3
3
3
415
415
415
(V)
VOLTAGE
J
124.88
I = C/
(GxH)
99.90
99.90
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR
0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR
0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT
197
197
197
(A)
F
(Iz)
1C- 25
1C- 25
1C- 25
SELECTED CABLE SIZE
mm2
E
EARTHING CONDUCTOR
50
50
50
SELECTED CABLE SIZE
mm2
D
PHASE CONDUCTOR
PHASE CONDUCTOR
SELECTED CABLE SIZE
EARTHING CONDUCTOR
SELECTED CABLE SIZE
(Iz)
CABLE RATED CURRENT
(Ca)
AMBIENT AIR FACTOR
(Cg)
GROUPING FACTOR
CURRENT (It)
CABLE DERATED
VOLTAGE
PHASE
LENGTH
METER
PER AMPERE PER
CABLE VOLTAGE DROP
NO. OF CABLES
DROP
CALCULATED VOLTAGE
DROP
PERCENT VOLTAGE
VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 124.88 415 3 5 2.50 1 0.88 0.21 2.5
50 1C- 25 197 0.91 0.88 124.88 415 3 10 2.50 1 1.77 0.43 2.5
50 1C- 25 197 0.91 0.88 124.88 415 3 15 2.50 1 2.65 0.64 2.5
10 1C- 10 99 0.91 0.88 78.67 415 3 13 3.60 1 2.66 0.64 2.5
10 1C- 10 99 0.91 0.88 78.67 415 3 10 6.00 1 2.36 0.57 2.5
6 1C- 6 45 0.91 0.88 39.96 415 3 20 3.60 1 1.19 0.29 2.5
6 1C- 6 45 0.91 0.88 39.96 415 3 10 6.00 1 1.57 0.38 2.5
ALLOWABLE PERCENT
(%)
2.5
2.5
2.5
2.5
Q
VD LIMIT
(O/J) x
100%
PERCENT VOLTAGE
0.22
0.22
0.22
0.64
(%)
P=
DROP
(1000xN)
(BxMxL)/
CALCULATED VOLTAGE
0.92
0.92
0.92
2.65
O=
(V)
DROP
NO. OF CABLES
N
1
1
1
1
3.60
3.60
3.60
2.50
METER
(m)
10
10
10
15
LENGTH
L
PHASE
Ø
3
3
3
3
415
415
415
415
(V)
VOLTAGE
J
I = C/
(GxH)
39.96
39.96
39.96
99.90
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR
0.88
0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR
0.91
0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT
197
(A)
45
45
45
F
(Iz)
1C- 25
SELECTED CABLE SIZE
mm2
1C- 6
1C- 6
1C- 6
E
EARTHING CONDUCTOR
50
SELECTED CABLE SIZE
mm2
6
6
6
D
PHASE CONDUCTOR
PHASE CONDUCTOR
SELECTED CABLE SIZE
EARTHING CONDUCTOR
SELECTED CABLE SIZE
(Iz)
CABLE RATED CURRENT
(Ca)
AMBIENT AIR FACTOR
(Cg)
GROUPING FACTOR
CURRENT (It)
CABLE DERATED
VOLTAGE
PHASE
LENGTH
METER
PER AMPERE PER
CABLE VOLTAGE DROP
NO. OF CABLES
DROP
CALCULATED VOLTAGE
DROP
PERCENT VOLTAGE
VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 124.88 415 3 20 2.50 1 3.54 0.85 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 20 3.60 1 1.84 0.44 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.25 0.06 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.25 0.06 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.38 0.09 2.5
16 1C- 16 131 0.91 0.88 78.67 415 3 15 3.60 1 1.65 0.40 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.76 0.18 2.5
ALLOWABLE PERCENT
(%)
2.5
2.5
2.5
2.5
Q
VD LIMIT
(O/J) x
100%
PERCENT VOLTAGE
0.13
0.13
0.13
0.13
(%)
P=
DROP
(1000xN)
(BxMxL)/
CALCULATED VOLTAGE
0.54
0.54
0.54
0.54
O=
(V)
DROP
NO. OF CABLES
N
1
1
1
1
3.60
3.60
3.60
3.60
METER
(m)
17
17
17
17
LENGTH
L
PHASE
Ø
3
3
3
3
415
415
415
415
(V)
VOLTAGE
J
I = C/
(GxH)
24.98
24.98
24.98
24.98
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR
0.88
0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR
0.91
0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT
(A)
99
99
99
99
F
(Iz)
1C- 10
1C- 10
1C- 10
1C- 10
SELECTED CABLE SIZE
mm2
E
EARTHING CONDUCTOR
10
10
10
10
SELECTED CABLE SIZE
mm2
D
PHASE CONDUCTOR
ALLOWABLE PERCENT
(%)
1.0
1.0
1.0
Q
VD LIMIT
(O/J) x
100%
PERCENT VOLTAGE
0.64
0.27
0.41
(%)
P=
DROP
(1000xN)
(BxMxL)/
CALCULATED VOLTAGE
2.65
1.13
1.70
O=
(V)
DROP
NO. OF CABLES
N
1
1
1
3.60
3.60
3.60
METER
(m)
15
20
20
LENGTH
L
PHASE
Ø
3
3
3
415
415
415
(V)
VOLTAGE
J
I = C/
(GxH)
78.67
78.67
78.67
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR
0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR
0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT
131
131
131
(A)
F
(Iz)
1C- 16
1C- 16
1C- 16
SELECTED CABLE SIZE
mm2
E
EARTHING CONDUCTOR
16
16
16
SELECTED CABLE SIZE
mm2
D
PHASE CONDUCTOR