PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)

SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2

B
No. FROM TO A C D
= Ax1.2

1 SP-CEP-13(N) 15.00 15.00 27.28 32.74 100 4C-


2 PEBP-01(N) 252.50 247.45 405.02 486.02 630 4C-
3 CWP-CEP-13(N) 168.30 168.30 306.07 367.29 630 4C-
4 PE-JP01(N) 3.70 3.50 6.37 7.96 63 4C-
5 CT-CEP-13(N) 75 75.00 136.40 163.68 400 4C-
6 SMB-E(N) 57.46 49.42 80.89 97.07 250 4C-
7 MV-7 PE-DFP01(N) 3 3.00 5.46 6.55 63 4C-
(MDB-01)
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2

B
No. FROM TO A C D
= Ax1.2
MV-7
8 (MDB-01) PCHWP-CEP-13(N) 55.00 55.00 100.02 120.03 320 4C-
9 PE-EFP01(N) 187.5 187.50 340.99 409.19 630 4C-
10 DB-HV 16.13 15.27 24.99 29.99 63 4C-
11 E-PEBP01(N) 131 98.20 160.73 192.88 250 4C-
12 CEP-UPS1 25.50 25.50 41.74 50.08 250 4C-
13 HV-ACDB 20.30 20.30 33.23 39.87 100 4C-
14 CEP-UPS2 20.00 20.00 32.74 39.28 250 4C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2

B
No. FROM TO A C D
= Ax1.2

1 DB-EB1(N) 3.94 3.34 5.47 6.57 63 4C-


2 DB-EG1(N) 23.50 19.95 32.66 39.19 63 4C-
3 DB-EG2(N) 0 0.00 - - 63 -
4 DB-EG3(N) 2.885 2.45 4.01 4.81 63 4C-
5 SMB-E(N) DB-EM1(N) 3.26 2.77 4.53 5.44 63 4C-
6 (SMDB-01) DB-EM2(N) 2.18 1.85 3.03 3.64 63 4C-
7 PB-GH3(N) 8.20 6.96 11.39 13.67 80 4C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2


SMB-E(N)
(SMDB-01) B
No. FROM TO A C D
= Ax1.2

8 MCP-AHU-CEP-28-29-30 4.20 4.20 7.64 9.17 100 4C-


9 PB-MG1(N) 4.57 3.88 6.34 7.61 80 4C-
10 PB-GH2 4.80 4.08 6.67 8.00 80 4C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2

B
No. FROM TO A C D
= Ax1.2

1 BOILER-1 36.00 36.00 58.92 70.71 100 4C-


2 BOILER-2 36.00 36.00 58.92 70.71 100 4C-
3 BOILER-3 36.00 36.00 58.92 70.71 100 4C-
4 CONDENSATE PUMP 26.00 26.00 47.28 56.74 63 4C-
5 DEAREATED PUMP 18.00 18.00 32.74 39.28 63 4C-
PEBP-01(N)
6 SOFTNER 13 8.4487 13.83 16.59 32 4C-
(SMDB-02)
7 AIR COMPRESSOR 12 12.00 21.82 26.19 32 4C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2


PEBP-01(N) B
No. FROM
(SMDB-02) TO A C D
= Ax1.2

8 CHEMICAL #1 13 13.00 21.28 25.53 32 4C-


9 CHEMICAL #2 13 13.00 21.28 25.53 32 4C-
10 CHEMICAL #3 13.00 13.00 21.28 25.53 32 4C-
11 AUX.EQUIPMENT 36.00 36.00 58.92 70.71 80 4C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2

B
No. FROM TO A C D
= Ax1.2

1 BOILER-4 36.00 36.00 58.92 70.71 100 4C-


2 CHEMICAL #4 13.00 13.00 21.28 25.53 32 2C-
3 MASTER PROCESSOR 4 2.40 3.93 4.71 32 2C-
4 SP. EQUIPMENT 4 2.40 3.93 4.71 32 4C-
5 STEAM UNIT 6.00 3.60 5.89 7.07 32 2C-
E-PEBP01(N)
6 CONDENSATE UNIT 26.00 15.60 25.53 30.64 63 2C-
(SMDB-03)
7 SP. EQUIPMENT 12.00 7.20 11.78 14.14 32 2C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2


E-PEBP01(N) B
No. FROM
(SMDB-03) TO A C D
= Ax1.2

8 Tank Compressor Control Panel 7.50 4.50 7.37 8.84 20 2C-


9 Tank Compressor Control Panel 7.5 4.50 7.37 8.84 20 2C-
10 Tank Compressor Control Panel 7.5 4.50 7.37 8.84 20 2C-
11 Tank Compressor Control Panel 7.50 4.50 7.37 8.84 20 2C-
PROJECT:ADDITIONAL POWER DISTRIBUTION AT CENTRAL ENERGY PLANT (CEP)
SUBJECT: FEEDER CABLE, CIRCUIT BREAKER AND VOLTAGE DROP SIZING CALCULATION - MDB-01
FEEDER NO.

CONNECTED LOAD

DEMAND LOAD

DEMAND CURRENT

(20%)
MD CURRENT + SPARE

(In)
SELECTED CB RATING

PHASE CONDUCTOR
SELECTED CABLE SIZE
DESCRIPTION

(kW) (kW) (A) (A) (A) mm2

B
No. FROM TO A C D
= Ax1.2

1 CEP-UPS1 DB-UG1 25.00 25.00 40.92 49.10 63 4C-


1 DB-UM1 8.00 8.00 13.09 15.71 63 4C-
CEP-UPS2
2 DB-UM2 12 12.00 19.64 23.57 63 4C-
PHASE CONDUCTOR
SELECTED CABLE SIZE

EARTHING CONDUCTOR
SELECTED CABLE SIZE

(Iz)
CABLE RATED CURRENT

(Ca)
AMBIENT AIR FACTOR

(Cg)
GROUPING FACTOR

CURRENT (It)
CABLE DERATED

VOLTAGE

PHASE

LENGTH

METER
PER AMPERE PER
CABLE VOLTAGE DROP

NO. OF CABLES

DROP
CALCULATED VOLTAGE

DROP
PERCENT VOLTAGE

VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 124.88 415 3 30 0.76 1 0.75 0.18 4
240 1C- 120 952 0.91 0.88 786.71 415 3 20 0.211 1 2.05 0.49 1.5
150 1C- 150 812 0.91 0.88 786.71 415 3 20 0.303 2 1.11 0.27 4
50 1C- 25 197 0.91 0.88 78.67 415 3 50 0.76 1 0.30 0.07 4
240 1C- 240 952 0.91 0.88 499.50 415 3 35 0.211 2 0.60 0.15 4
240 1C- 120 353 0.91 0.88 312.19 415 3 15 0.211 1 0.31 0.07 1.5
50 1C- 25 197 0.91 0.88 78.67 415 3 45 0.76 1 0.22 0.05 4
PHASE CONDUCTOR
SELECTED CABLE SIZE

EARTHING CONDUCTOR
SELECTED CABLE SIZE

(Iz)
CABLE RATED CURRENT

(Ca)
AMBIENT AIR FACTOR

(Cg)
GROUPING FACTOR

CURRENT (It)
CABLE DERATED

VOLTAGE

PHASE

LENGTH

METER
PER AMPERE PER
CABLE VOLTAGE DROP

NO. OF CABLES

DROP
CALCULATED VOLTAGE

DROP
PERCENT VOLTAGE

VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
240 1C- 240 952 0.91 0.88 399.60 415 3 25 0.211 2 0.32 0.08 4
150 1C- 150 812 0.91 0.88 786.71 415 3 40 0.303 2 2.48 0.60 4
50 1C- 25 197 0.91 0.88 78.67 415 3 20 0.76 1 0.46 0.11 2.5
240 1C- 120 353 0.91 0.88 312.19 415 3 17 0.211 1 0.69 0.17 1.5
240 1C- 120 353 0.91 0.88 312.19 415 3 40 0.211 1 0.42 0.10 1.5
50 1C- 25 197 0.91 0.88 124.88 415 3 23 0.76 1 0.70 0.17 2.5
240 1C- 120 353 0.91 0.88 312.19 415 3 40 0.211 1 0.33 0.08 1.5
PHASE CONDUCTOR
SELECTED CABLE SIZE

EARTHING CONDUCTOR
SELECTED CABLE SIZE

(Iz)
CABLE RATED CURRENT

(Ca)
AMBIENT AIR FACTOR

(Cg)
GROUPING FACTOR

CURRENT (It)
CABLE DERATED

VOLTAGE

PHASE

LENGTH

METER
PER AMPERE PER
CABLE VOLTAGE DROP

NO. OF CABLES

DROP
CALCULATED VOLTAGE

DROP
PERCENT VOLTAGE

VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 78.67 415 3 27 0.76 1 0.13 0.03 1.0
50 1C- 25 197 0.91 0.88 78.67 415 3 15 0.76 1 0.45 0.11 1.0
50 - 25 197 - - - - - 15 0.76 1 - - -
50 1C- 25 197 0.91 0.88 78.67 415 3 20 0.76 1 0.07 0.02 1.0
50 1C- 25 197 0.91 0.88 78.67 415 3 25 0.76 1 0.10 0.02 1.0
50 1C- 25 197 0.91 0.88 78.67 415 3 27 0.76 1 0.07 0.02 1.0
50 1C- 25 197 0.91 0.88 99.90 415 3 47 0.76 1 0.49 0.12 1.0
ALLOWABLE PERCENT
(%)

1.0
1.0
1.0
Q

VD LIMIT
(O/J) x
100%

PERCENT VOLTAGE
0.03
0.05
0.05
(%)
P=

DROP
(1000xN)
(BxMxL)/

CALCULATED VOLTAGE
0.14
0.20
0.23
O=
(V)

DROP
NO. OF CABLES
N

1
1
1

CABLE VOLTAGE DROP


(mV)

0.76
0.76
0.76

PER AMPERE PER


M

METER
(m)

20
35
37

LENGTH
L

PHASE
Ø

3
3
3
415
415
415
(V)

VOLTAGE
J

124.88
I = C/
(GxH)

99.90
99.90
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR

0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR

0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT

197
197
197
(A)

F
(Iz)

1C- 25
1C- 25
1C- 25
SELECTED CABLE SIZE

mm2

E
EARTHING CONDUCTOR

50
50
50
SELECTED CABLE SIZE

mm2

D
PHASE CONDUCTOR
PHASE CONDUCTOR
SELECTED CABLE SIZE

EARTHING CONDUCTOR
SELECTED CABLE SIZE

(Iz)
CABLE RATED CURRENT

(Ca)
AMBIENT AIR FACTOR

(Cg)
GROUPING FACTOR

CURRENT (It)
CABLE DERATED

VOLTAGE

PHASE

LENGTH

METER
PER AMPERE PER
CABLE VOLTAGE DROP

NO. OF CABLES

DROP
CALCULATED VOLTAGE

DROP
PERCENT VOLTAGE

VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 124.88 415 3 5 2.50 1 0.88 0.21 2.5
50 1C- 25 197 0.91 0.88 124.88 415 3 10 2.50 1 1.77 0.43 2.5
50 1C- 25 197 0.91 0.88 124.88 415 3 15 2.50 1 2.65 0.64 2.5
10 1C- 10 99 0.91 0.88 78.67 415 3 13 3.60 1 2.66 0.64 2.5
10 1C- 10 99 0.91 0.88 78.67 415 3 10 6.00 1 2.36 0.57 2.5
6 1C- 6 45 0.91 0.88 39.96 415 3 20 3.60 1 1.19 0.29 2.5
6 1C- 6 45 0.91 0.88 39.96 415 3 10 6.00 1 1.57 0.38 2.5
ALLOWABLE PERCENT
(%)

2.5
2.5
2.5
2.5
Q

VD LIMIT
(O/J) x
100%

PERCENT VOLTAGE
0.22
0.22
0.22
0.64
(%)
P=

DROP
(1000xN)
(BxMxL)/

CALCULATED VOLTAGE
0.92
0.92
0.92
2.65
O=
(V)

DROP
NO. OF CABLES
N

1
1
1
1

CABLE VOLTAGE DROP


(mV)

3.60
3.60
3.60
2.50

PER AMPERE PER


M

METER
(m)

10
10
10
15
LENGTH
L

PHASE
Ø

3
3
3
3
415
415
415
415
(V)

VOLTAGE
J
I = C/
(GxH)

39.96
39.96
39.96
99.90
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR

0.88
0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR

0.91
0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT

197
(A)

45
45
45
F
(Iz)

1C- 25
SELECTED CABLE SIZE

mm2

1C- 6
1C- 6
1C- 6
E
EARTHING CONDUCTOR

50
SELECTED CABLE SIZE

mm2

6
6
6
D
PHASE CONDUCTOR
PHASE CONDUCTOR
SELECTED CABLE SIZE

EARTHING CONDUCTOR
SELECTED CABLE SIZE

(Iz)
CABLE RATED CURRENT

(Ca)
AMBIENT AIR FACTOR

(Cg)
GROUPING FACTOR

CURRENT (It)
CABLE DERATED

VOLTAGE

PHASE

LENGTH

METER
PER AMPERE PER
CABLE VOLTAGE DROP

NO. OF CABLES

DROP
CALCULATED VOLTAGE

DROP
PERCENT VOLTAGE

VD LIMIT
ALLOWABLE PERCENT
mm2 mm2 (A) (A) (V) Ø (m) (mV) (V) (%) (%)
O= P=
I = C/
D E F G H J K L M N (BxMxL)/ (O/J) x Q
(GxH)
(1000xN) 100%
50 1C- 25 197 0.91 0.88 124.88 415 3 20 2.50 1 3.54 0.85 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 20 3.60 1 1.84 0.44 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.25 0.06 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.25 0.06 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.38 0.09 2.5
16 1C- 16 131 0.91 0.88 78.67 415 3 15 3.60 1 1.65 0.40 2.5
10 1C- 10 99 0.91 0.88 39.96 415 3 15 3.60 1 0.76 0.18 2.5
ALLOWABLE PERCENT
(%)

2.5
2.5
2.5
2.5
Q

VD LIMIT
(O/J) x
100%

PERCENT VOLTAGE
0.13
0.13
0.13
0.13
(%)
P=

DROP
(1000xN)
(BxMxL)/

CALCULATED VOLTAGE
0.54
0.54
0.54
0.54
O=
(V)

DROP
NO. OF CABLES
N

1
1
1
1

CABLE VOLTAGE DROP


(mV)

3.60
3.60
3.60
3.60

PER AMPERE PER


M

METER
(m)

17
17
17
17
LENGTH
L

PHASE
Ø

3
3
3
3
415
415
415
415
(V)

VOLTAGE
J
I = C/
(GxH)

24.98
24.98
24.98
24.98
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR

0.88
0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR

0.91
0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT

(A)

99
99
99
99
F
(Iz)

1C- 10
1C- 10
1C- 10
1C- 10
SELECTED CABLE SIZE

mm2

E
EARTHING CONDUCTOR

10
10
10
10
SELECTED CABLE SIZE

mm2

D
PHASE CONDUCTOR
ALLOWABLE PERCENT
(%)

1.0
1.0
1.0
Q

VD LIMIT
(O/J) x
100%

PERCENT VOLTAGE
0.64
0.27
0.41
(%)
P=

DROP
(1000xN)
(BxMxL)/

CALCULATED VOLTAGE
2.65
1.13
1.70
O=
(V)

DROP
NO. OF CABLES
N

1
1
1

CABLE VOLTAGE DROP


(mV)

3.60
3.60
3.60

PER AMPERE PER


M

METER
(m)

15
20
20

LENGTH
L

PHASE
Ø

3
3
3
415
415
415
(V)

VOLTAGE
J
I = C/
(GxH)

78.67
78.67
78.67
CABLE DERATED
(A)
CURRENT (It)
GROUPING FACTOR

0.88
0.88
0.88
H
(Cg)
AMBIENT AIR FACTOR

0.91
0.91
0.91
G
(Ca)
CABLE RATED CURRENT

131
131
131
(A)

F
(Iz)

1C- 16
1C- 16
1C- 16
SELECTED CABLE SIZE

mm2

E
EARTHING CONDUCTOR

16
16
16
SELECTED CABLE SIZE

mm2

D
PHASE CONDUCTOR