Koholer Gasolina

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 88

Service

Marine Generator Sets

Models:
5ECD/4EFCD
7.3ECD/6EFCD
5ECD/4EFCD--Low CO
7.3ECD/6EFCD--Low CO
Controller:
Advanced Digital Control

TP-6391 9/08a
2 TP-6391 9/08
Table of Contents

Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Section 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.2 Generator Set Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.3 Controller Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.4 Alternator Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.5 Alternator Specifications, Continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.6 Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.7 Engine Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.8 Service View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Section 2 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2 Service Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Section 3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2 Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Section 4 Controller ....................................................................... 23
4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2 Controller Display and Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.3 Master Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.4 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.4.1 Starting the Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.4.2 Running Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.4.3 Stopping the Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.5 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.5.1 Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.5.2 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.5.3 SECM Fault Codes and Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.6 Relay Interface Board (RIB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.7 CO Sensor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.8 K5 Main Power Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.9 Silicon Controlled Rectifier (SCR) Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.10 Controller Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.11 Controller Configuration and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.11.1 Voltage Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.11.2 Controller Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Section 5 Component Testing and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.1 Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.2 Separate Excitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.3 Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.4 Main Field (Rotor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.4.1 Rotor Continuity and Resistance Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5.5 Slip Rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.6 Brushes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.7 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.7.1 Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.7.2 Voltage Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

TP-6391 9/08 Table of Contents 3


Table of Contents, continued

5.8 Voltage Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52


5.9 Governor System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.10 Fault Shutdown Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.10.1 Controller Fault Shutdown Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.10.2 Fault Shutdown Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.11 Electronic Throttle Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.12 Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.13 Continuity Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Section 6 Generator Disassembly/Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.2 Collector Ring and Bearing Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.3 Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Section 7 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Appendix A Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Appendix B Common Hardware Application Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Appendix C General Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Appendix D Common Hardware Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Appendix E Common Hardware List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

4 Table of Contents TP-6391 9/08


Safety Precautions and Instructions

IMPORTANT SAFETY INSTRUCTIONS. Accidental Starting Servicing the air cleaner. A sudden
Electromechanical equipment, backfire can cause severe injury or
including generator sets, transfer death. Do not operate the generator
switches, switchgear, and accessories, WARNING set with the air cleaner removed.
can cause bodily harm and pose
life-threatening danger when Combustible materials. A sudden
improperly installed, operated, or flash fire can cause severe injury or
maintained. To prevent accidents be death. Do not smoke or permit flames
aware of potential dangers and act or sparks near the generator set. Keep
safely. Read and follow all safety the compartment and the generator set
precautions and instructions. SAVE Accidental starting. clean and free of debris to minimize the
THESE INSTRUCTIONS. Can cause severe injury or death. risk of fire. Catch fuels in an approved
container. Wipe up spilled fuels and
Disconnect the battery cables before engine oil.
This manual has several types of safety working on the generator set.
precautions and instructions: Danger, Remove the negative (--) lead first Combustible materials. A fire can
Warning, Caution, and Notice. when disconnecting the battery. cause severe injury or death.
Reconnect the negative (--) lead last Generator set engine fuels and fuel
when reconnecting the battery. vapors are flammable and explosive.
Handle these materials carefully to
DANGER
minimize the risk of fire or explosion.
Disabling the generator set. Equip the compartment or nearby area
Accidental starting can cause with a fully charged fire extinguisher.
Danger indicates the presence of a severe injury or death. Before
hazard that will cause severe Select a fire extinguisher rated ABC or
working on the generator set or BC for electrical fires or as
personal injury, death, or substantial connected equipment, disable the
property damage. recommended by the local fire code or
generator set as follows: (1) Move the an authorized agency. Train all
generator set master switch to the OFF personnel on fire extinguisher
position. (2) Disconnect the power to operation and fire prevention
WARNING the battery charger. (3) Remove the procedures.
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
Warning indicates the presence of a when reconnecting the battery. Follow
hazard that can cause severe these precautions to prevent starting of
Exhaust System
personal injury, death, or substantial the generator set by an automatic
property damage. transfer switch, remote start/stop WARNING
switch, or engine start command from a
remote computer.
CAUTION
Engine Backfire/Flash
Carbon monoxide.
Caution indicates the presence of a Fire Can cause severe nausea,
hazard that will or can cause minor
personal injury or property damage. fainting, or death.
WARNING
The exhaust system must be
NOTICE
leakproof and routinely inspected.
Notice communicates installation,
operation, or maintenance information
that is safety related but not hazard
related. Fire.
Can cause severe injury or death.
Safety decals affixed to the equipment
in prominent places alert the operator Do not smoke or permit flames or
or service technician to potential sparks near fuels or the fuel system.
hazards and explain how to act safely.
The decals are shown throughout this Servicing the backfire flame
publication to improve operator arrester. A sudden backfire can
recognition. Replace missing or cause severe injury or death. Do not
damaged decals. operate the generator set with the
backfire flame arrester removed.

TP-6391 9/08 Safety Precautions and Instructions 5


Carbon monoxide symptoms. Fuel System Draining the fuel system. Explosive
Carbon monoxide can cause severe fuel vapors can cause severe injury
nausea, fainting, or death. Carbon or death. Spilled fuel can cause an
monoxide is a poisonous gas present in WARNING explosion. Use a container to catch fuel
exhaust gases. Carbon monoxide is an when draining the fuel system. Wipe up
odorless, colorless, tasteless, spilled fuel after draining the system.
nonirritating gas that can cause death if
inhaled for even a short time. Carbon Ignition-protected equipment.
monoxide poisoning symptoms include Explosive fuel vapors can cause
but are not limited to the following: severe injury or death. Gasoline
D Light-headedness, dizziness Explosive fuel vapors. vapors can cause an explosion.
D Physical fatigue, weakness in Can cause severe injury or death. USCG Regulation 33CFR183 requires
joints and muscles that all electrical devices (ship-to-shore
D Sleepiness, mental fatigue, Use extreme care when handling, transfer switch, remote start panel,
inability to concentrate storing, and using fuels. etc.) must be ignition protected when
or speak clearly, blurred vision used in a gasoline and gaseous-fueled
D Stomachache, vomiting, nausea environment.
If experiencing any of these symptoms WARNING
and carbon monoxide poisoning is
possible, seek fresh air immediately Hazardous Noise
and remain active. Do not sit, lie down,
or fall asleep. Alert others to the
possibility of carbon monoxide
CAUTION
poisoning. Seek medical attention if Explosion.
the condition of affected persons does Gasoline vapors can cause
not improve within minutes of breathing explosion and severe injury or
fresh air. death.
Inspecting the exhaust system. Before starting the generator set, Hazardous noise.
Carbon monoxide can cause severe operate the blower 4 minutes and Can cause hearing loss.
nausea, fainting, or death. For the check the engine compartment for
safety of the craft’s occupants, install a gasoline vapors. Never operate the generator set
carbon monoxide detector. Never without a muffler or with a faulty
operate the generator set without a exhaust system.
functioning carbon monoxide detector. The fuel system. Explosive fuel
Inspect the detector before each vapors can cause severe injury or
generator set use. death. Vaporized fuels are highly
explosive. Use extreme care when Hazardous Voltage/
Operating the generator set. Carbon handling and storing fuels. Store fuels
monoxide can cause severe nausea, in a well-ventilated area away from Moving Parts
fainting, or death. Be especially spark-producing equipment and out of
careful if operating the generator set the reach of children. Never add fuel to WARNING
when moored or anchored under calm the tank while the engine is running
conditions because gases may because spilled fuel may ignite on
accumulate. If operating the generator contact with hot parts or from sparks.
set dockside, moor the craft so that the Do not smoke or permit flames or
exhaust discharges on the lee side (the sparks to occur near sources of spilled
side sheltered from the wind). Always fuel or fuel vapors. Keep the fuel lines Hazardous voltage. Moving parts.
be aware of others, making sure your and connections tight and in good Can cause severe injury or death.
exhaust is directed away from other condition. Do not replace flexible fuel
boats and buildings. lines with rigid lines. Use flexible Operate the generator set only when
sections to avoid fuel line breakage all guards and electrical enclosures
caused by vibration. Do not operate the are in place.
generator set in the presence of fuel
leaks, fuel accumulation, or sparks. Servicing the generator set when it
Repair fuel systems before resuming is operating. Exposed moving parts
generator set operation. can cause severe injury or death.
Keep hands, feet, hair, clothing, and
Explosive fuel vapors can cause
test leads away from the belts and
severe injury or death. Take
pulleys when the generator set is
additional precautions when using the
running. Replace guards, screens, and
following fuels:
covers before operating the generator
Gasoline—Store gasoline only in set.
approved red containers clearly
marked GASOLINE.

6 Safety Precautions and Instructions TP-6391 9/08


Grounding electrical equipment. Testing live electrical circuits. Notice
Hazardous voltage can cause Hazardous voltage or current can
severe injury or death. Electrocution cause severe injury or death. Have NOTICE
is possible whenever electricity is trained and qualified personnel take
Fuse replacement. Replace fuses
present. Ensure you comply with all diagnostic measurements of live
with fuses of the same ampere rating
applicable codes and standards. circuits. Use adequately rated test
and type (for example: 3AB or 314,
Electrically ground the generator set, equipment with electrically insulated
ceramic). Do not substitute clear
transfer switch, and related equipment probes and follow the instructions of the
glass-type fuses for ceramic fuses.
and electrical circuits. Turn off the main test equipment manufacturer when
Refer to the wiring diagram when the
circuit breakers of all power sources performing voltage tests. Observe the
ampere rating is unknown or
before servicing the equipment. Never following precautions when performing
questionable.
contact electrical leads or appliances voltage tests: (1) Remove all jewelry.
when standing in water or on wet (2) Stand on a dry, approved electrically
NOTICE
ground because these conditions insulated mat. (3) Do not touch the
increase the risk of electrocution. enclosure or components inside the Saltwater damage. Saltwater quickly
enclosure. (4) Be prepared for the deteriorates metals. Wipe up saltwater
Disconnecting the electrical load. system to operate automatically. on and around the generator set and
Hazardous voltage can cause (600 volts and under) remove salt deposits from metal
severe injury or death. Disconnect surfaces.
the generator set from the load by
turning off the line circuit breaker or by
disconnecting the generator set output
Hot Parts
leads from the transfer switch and
heavily taping the ends of the leads. WARNING
High voltage transferred to the load
during testing may cause personal
injury and equipment damage. Do not
use the safeguard circuit breaker in
place of the line circuit breaker. The
safeguard circuit breaker does not Hot coolant and steam.
disconnect the generator set from the Can cause severe injury or death.
load.
Before removing the pressure cap,
Short circuits. Hazardous stop the generator set and allow it to
voltage/current can cause severe cool. Then loosen the pressure cap
injury or death. Short circuits can to relieve pressure.
cause bodily injury and/or equipment
damage. Do not contact electrical
connections with tools or jewelry while
making adjustments or repairs.
Remove all jewelry before servicing the
equipment.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death.
Connect the generator set to the
building/marina electrical system only
through an approved device and after
the building/marina main switch is
turned off. Backfeed connections can
cause severe injury or death to utility
personnel working on power lines
and/or personnel near the work area.
Some states and localities prohibit
unauthorized connection to the utility
electrical system. Install a
ship-to-shore transfer switch to prevent
interconnection of the generator set
power and shore power.

TP-6391 9/08 Safety Precautions and Instructions 7


Notes

8 Safety Precautions and Instructions TP-6391 9/08


Introduction

This manual provides troubleshooting and repair Routine Service Parts


instructions for the generator set models listed on the
front cover. The following table contains part numbers for
recommended spare parts. Contact your Kohler
For engine service procedures not covered in this generator distributor/dealer for a complete list of service
manual, refer to the Engine Service Manual listed below. parts for your generator set or for models or spec
numbers not listed.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to Part Description Part Number
change this publication and the products represented Backfire flame arrestor GM24212
without notice and without any obligation or liability
Fuse, (F1) 10 amp,
whatsoever. 358337
Auxiliary Winding
Read this manual and carefully follow all procedures Fuse, (F2) 10 amp,
223316
and safety precautions to ensure proper equipment Controller
operation and to avoid bodily injury. Read and follow the Fuse, (F3) 10 amp,
223316
Safety Precautions and Instructions section at the Customer Connection
beginning of this manual. Keep this manual with the Fuse, (F4) 15 amp,
283645
equipment for future reference. Coils/Injectors
Fuse, (F5) 15 amp,
The equipment service requirements are very important 283645
ECM, O2 Sensor, and Fuel Pumps
to safe and efficient operation. Inspect the parts often
Fuse, (F6) 15 amp,
and perform required service at the prescribed intervals.
Voltage Regulator and Battery Charging 283645
Maintenance work must be performed by appropriately Alternator
skilled and suitably trained maintenance personnel
Fuse, (F7) 20 amp,
familiar with generator set operation and service. GM39266
Starter Motor and Crank Solenoid
Oil Filter 359771
List of Related Materials Seawater Pump Impeller Kit 359978

Separate manuals contain operation, installation, and Spark Plug GM46180


parts information not provided in this manual. Separate Spray Paint (White) 221335
engine Operation and Service manuals are also Zinc Anode 260085
available. The following table lists the available manual
Figure 2 Maintenance and Service Parts
part numbers.

Literature Type Part Number


Installation Manual TP-5982
Operation Manual (Generator) TP-6390
Operation Manual (Engine) TP-6001
Parts Catalog* TP-5987
Service Manual (Generator) TP-6391
Service Manual (Engine) TP-6002
Service Manual Supplement (Engine) TP-6008
* One manual combines Generator and Engine information.

Figure 1 Generator Set Literature

TP-6391 9/08 Introduction 9


Service Assistance

For professional advice on generator set power China


requirements and conscientious service, please contact North China Regional Office, Beijing
your nearest Kohler distributor or dealer. Phone: (86) 10 6518 7950
(86) 10 6518 7951
D Consult the Yellow Pages under the heading (86) 10 6518 7952
Generators—Electric Fax: (86) 10 6518 7955

D Visit the Kohler Power Systems website at East China Regional Office, Shanghai
KohlerPower.com Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
D Look at the labels and stickers on your Kohler product India, Bangladesh, Sri Lanka
or review the appropriate literature or documents India Regional Office
included with the product Bangalore, India
Phone: (91) 80 3366208
D Call toll free in the US and Canada 1-800-544-2444 (91) 80 3366231
Fax: (91) 80 3315972
D Outside the US and Canada, call the nearest regional
office Japan, Korea
North Asia Regional Office
Headquarters Europe, Middle East, Africa Tokyo, Japan
(EMEA) Phone: (813) 3440-4515
Kohler Power Systems Fax: (813) 3440-2727
3 rue de Brennus
Latin America
93200 Saint Denis
Latin America Regional Office
France
Lakeland, Florida, USA
Phone: (33) 1 49 178300
Phone: (863) 619-7568
Fax: (33) 1 49 178301
Fax: (863) 701-7131
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax: (65) 6264-6455

10 Service Assistance TP-6391 9/08


Section 1 Specifications

1.1 Introduction 1.3 Controller Specifications


The spec sheets for each generator set provide specific The generator set is equipped with the Advanced Digital
generator and engine information. Refer to the Control. For a specific description of the controller, see
generator set spec sheet for data not supplied in this Section 2, Operation, in the operation manual.
manual. Consult the generator set installation manual,
engine operation manual, and engine service manual Environmental Specification ADC 2100
for additional specifications. --20_ to 70_C
Operating temperature
(--4_ to 158_F)
Humidity 0--95% condensing
1.2 Generator Set Ratings
Power requirements:
See the generator set ratings in Figure 1-1. Consult Voltage 12 VDC
generator set nameplate for specific generator set Current 250 mA @ 12 VDC
ratings.

25_C (77_F) 25_C (77_F)


Model Series Alternator Voltage Ph Hz Amps kW/kVA
120 41.67 5/5
5ECD 2F2 1 60
120/240 20.83 5/5
110 36.36 4/4
4EFCD 2F2 110/220 1 60 18.18 4/4
220 18.18 4/4
120 60.83 7.3/7.3
7 3ECD
7.3ECD 2F2 1 60
120/240 30.42 7.3/7.3
110 54.55 6/6
6EFCD 2F2 110/220 1 50 27.27 6/6
220 27.27 6/6
RATINGS: Marine continuous ratings per ISO 3046, ISO 8528-1, and Kohler ISO rating guideline 2.14. Obtain technical information bulletin
(TIB-101) on ratings guidelines for complete ratings definitions.

Figure 1-1 Generator Set Ratings

1.4 Alternator Specifications


Alternator Specification 5ECD/4EFCD 7.3ECD/6EFCD
Alternator model 2F2 2F2
Stator leads, qty. 4 4
Phase 1 1
Rotor resistance, ohms, cold 3.4 3.4
Stator resistance, ohms,* cold
Main winding: 1-2, 3-4 0.16 0.16
Aux. winding: 55-66 1.70 1.70
Stator output voltage with separately excited rotor using 12-volt battery, minimum
Main winding: 1-2, 3-4, volts 145 145
Aux. winding: 55-66, volts 190 190
Rotor field voltage/current readings at rated output voltage, hot
No load, volts/amps 13/3.82 13/3.82
Full load, volts/amps 47/13.82 47/13.82
* Most ohmmeters do not give accurate readings when measuring less than 1 ohm. The stator can be considered good if a low resistance
reading (continuity) is obtained and there is no evidence of shorted windings (discoloration). Do not confuse a low resistance reading with
a reading indicating a shorted winding.

TP-6391 9/08 Section 1 Specifications 11


1.5 Alternator Specifications, 1.6 Torque Specifications
Continued Follow the general torque specification found in Appendix C
of this manual unless noted below or provided in the Engine
5/7.3ECD Service Manual.
Alternator Specification 4/6EFCD
Frequency Hz 60/50 Hz 5/7.3ECD
Torque Specifications 4/6EFCD
Excitation method Brush type
Rotor bolt 23 Nm (204 in. lbs.)
Voltage regulator type Digital
Generator overbolts 13 Nm (120 in. lbs.)
Coupling type Flexible disc
Lifting eye bolt 19 Nm (14 ft. lbs.)
Winding material Class H
Generator adapter to engine bolts 15 Nm (132 in. lbs.)
Bearing, quantity and type 1 sealed
Engine oil drain boss (inside
Circuit protection 47 Nm (35 ft. lbs.)
generator adapter)
Auxiliary winding (F1) 10 amp fuse
Generator adapter to exhaust
Controller (F2) 10 amp fuse 13.6 Nm (120 in. lbs.)
manifold
Customer connection (F3) 10 amp fuse 12--17 Nm
Spark plugs
Coils/injectors (F4) 15 amp fuse (9--12 ft. lbs.)
ECM, O2 sensor, and Tighten the mounting
15 amp fuse bolts to 4 Nm
fuel pumps (F5)
(35 in. lbs.). Then
Voltage regulator and battery
15 amp fuse tighten the bolts in
charging alternator (F6)
Intake manifold to engine sequence 3 Nm (26
Starter motor and crank in. lbs.) at a time until
20 amp fuse
solenoid (F7) the torque on each
Brush length, new 1.9 cm (0.75 in.) bolt is 7.8 Nm (69 in.
lbs.)
Timing wheel to flywheel 9.5 Nm (7 ft. lbs.)
Catalyst assembly 9.5 Nm (7 ft. lbs.)
Seawater pump mounting plate 7 Nm (60 in. lbs.)
Seawater pump 15 Nm (132 in. lbs.)
Vibromounts 24 Nm (16.8 ft. lbs.)
Air intake adapter 0.8 Nm (7.0 in. lbs.)
End drive fitting to pump 11 Nm (96 in. lbs.)
Heat exchanger to exhaust
13.5 Nm (120 in. lbs.)
manifold
Exhaust manifold to cylinder head 7 Nm (5 ft. lbs.)

12 Section 1 Specifications TP-6391 9/08


1.7 Engine Specifications
Engine Specification 5/7.3ECD 4/6EFCD
Manufacturer Kawasaki
Model FD501D
Cycle 4
Number of cylinders 2
Compression ratio 9.3:1
Displacement, L (cu. in.) 0.4 (21.9)
Max. power at rated rpm, HP 16 13.8
Rpm 3600 3000
67 x 62
Bore x stroke, mm (in.)
(2.64 x 2.44)
Cylinder head material Aluminum
Cylinder block material Aluminum
Piston rings 2 compression/1 oil
Piston material Aluminum
Crankshaft material Aluminum
Crankshaft bearings, type Inserts
Governor, type Electronic
Lubrication system Full pressure
Oil capacity (w/filter), L (qt.) 1.36 (1.44)
Oil pressure, kPa (psi) 276 (40)
SC, SD, SE, SF, SG,
Oil recommendation (API)
SH, or SJ
Throttle body
Fuel system, type
fuel injected
Battery charging 15 amps
Battery voltage 12 VDC
Battery ground Negative
Battery recommendation,
260 CCA
minimum
0.6--0.7
Spark plug gap, mm (in.)
(0.024--0.028)
Ignition system Inductive
Bendix automotive
Starter motor
type
Cooling system Water-cooled
Steel alloy
Valve material
(JIS SUH3)

TP-6391 9/08 Section 1 Specifications 13


1.8 Service View

1 2 3 4 5 6 7 8 9 10 11 12 13
14

15
16 17
31
18 19

20

21

30 22

23
SERVICE VIEW
29 28 27 26 25 24

ADV7025A-A

1. Spark plug (also one located on the nonservice side) 17. CO sensor module (available on units with serial number
2. Oil fill 2085259 and later)
3. Overflow tube 18. Generator set master switch
4. Pressure cap (coolant fill location after draining coolant) 19. Catalyst assembly, water outlet/exhaust outlet (nonservice
5. Seawater pressure switch (appears as auxiliary fault on ADC) side)
6. Lifting eye 20. Seawater drain (remove plate for service)
21. Seawater pump (water inlet)
7. Heat exchanger
22. Cooling air inlet
8. Anticorrosion zinc anode
23. Fuel filter/fuel inlet
9. AC circuit breaker 24. Fuel pump
10. AC load lead connector (nonservice side) 25. Fuel pump/cooler
11. Nameplate (top) 26. Oil check
12. Remote start connector (nonservice side) 27. Coolant drain (remove hose clamp to drain coolant)
13. Fuses (F1, F2, F3, F4, F5, F6, and F7) 28. Oil drain valve
14. Runtime hour display 29. Lube oil filter
15. ADC 2100 30. Coolant overflow bottle (daily coolant check/fill location)
16. High exhaust temperature switch (located on the catalyst on 31. Air intake silencer/backfire flame arrestor
the nonservice side). Available on units with serial numbers Note: Consult installation drawings in Spec Sheet or Installation
2199434 and later. (Appears as LOC fault on ADC.) Manual for fuel- and battery-connection points.

Figure 1-2 Service Views

14 Section 1 Specifications TP-6391 9/08


Section 2 Scheduled Maintenance

Engine Service. Perform generator set engine service


WARNING at the intervals specified by the engine service literature.
Contact an authorized Kohlerr service distributor/
dealer to obtain engine service literature.

Generator Set Service. See the Safety Precautions


Accidental starting.
and Instructions at the beginning of this manual before
Can cause severe injury or death. attempting to service, repair, or operate the generator
set. Have an authorized Kohlerr service distributor/
Disconnect the battery cables before dealer perform all generator service.
working on the generator set.
Remove the negative (--) lead first
Routine Maintenance. Refer to the following generator
when disconnecting the battery.
Reconnect the negative (--) lead last set service schedule, the engine service schedule, and
when reconnecting the battery. the runtime hours displayed on the ADC 2100 to
determine when to schedule routine maintenance.
Disabling the generator set. Accidental starting can
Service the generator set more frequently if it is subject
cause severe injury or death. Before working on the to extreme weather, long operating hours, or dusty or
generator set or connected equipment, disable the generator dirty conditions.
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger. Service Schedule. Perform maintenance on each item
(3) Remove the battery cables, negative (--) lead first. in the service schedule at the designated interval for the
Reconnect the negative (--) lead last when reconnecting the life of the generator set.
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
Tools. Tools and instruments used to perform some
start/stop switch, or engine start command from a remote
computer. maintenance items are not generally available to the
generator set owner. Therefore, have service
performed by an authorized distributor/dealer.
WARNING

2.1 General
Perform the items listed in the service schedule at the
Hazardous voltage. Moving parts. designated intervals for the life of the generator set. For
Can cause severe injury or death.
example, an item serviced every 100 hours or 3 months
Operate the generator set only when must also be serviced after 200 hours or 6 months,
all guards and electrical enclosures 300 hours or 9 months, etc.
are in place.
Note: See the generator set operation manual and the
Alternator Service. Under normal operating conditions engine service manual for service procedures not
the generator set alternator does not require scheduled included in this manual.
service. Refer to the service schedule for items that
require maintenance.

TP-6391 9/08 Section 2 Scheduled Maintenance 15


2.2 Service Schedule
After Every Every Every
Before 50 Hrs or 100 Hrs or 300 Hrs or 500 Hrs or
Perform Service at Intervals Indicated (X) Starting 1 Month 3 Months 6 Months Yearly
FUEL SYSTEM
Check the fuel level and fill as necessary X
Check fuel lines and replace as necessary *[ X
Replace the fuel filter *[ X
LUBRICATION SYSTEM
Check crankcase oil level and add as necessary X
X (20 hrs
Replace the oil in crankcase * X
break-in)
X (20 hrs
Replace the lube oil filter element * X (200 hrs)
break-in)
COOLING SYSTEM
Check coolant level and fill as necessary * X
X (during
Check seawater outlet and clean as necessary [
operation)
Check function of siphon break, if equipped X
Replace seawater pump impeller *[ X (check) X
Check heat exchanger anticorrosion zinc condition * X
Replace heat exchanger anticorrosion zinc * X
Flush cooling system *[ X (400 hrs)
IGNITION SYSTEM
Clean and regap spark plugs * X
Replace spark plugs * X
INTAKE/EXHAUST SYSTEM
Inspect exhaust system components *[ X
X (during
Check the exhaust gas condition
operation)
Service backfire flame arrestor * X
Check and/or replace the catalyst assembly *[ X
Clean the water passage slots/holes in the exhaust X
manifold/catalyst *[ (200 hrs)
Replace the CO sensor module, if equipped *[ X (2 years)
Check the crankcase breather pipe for obstructions *[ X
Inspect the complete exhaust system [ X
ELECTRICAL SYSTEM
Keep battery charged and in good condition ⊕ X
Check and tighten electrical connections * X
Clean battery cables [ X (200 hrs)
ENGINE AND MOUNTING
Check for water, fuel, coolant, and oil leakage *[] X
Retighten all nuts and bolts * X
Check tightness of mounting bolts/vibromounts * X (200 hrs)
Check and adjust valve clearance *[ X
Clean combustion chamber *[ X
REMOTE CONTROL SYSTEM
Check remote control operation X (break-in) X
GENERATOR
Test run generator set X (weekly)
Blow dust out of generator *[ X
Clean slip rings and inspect brushes *[ X (1000 hrs)
* Requires removal of sound shield, if installed. ] Read WARNING found at the beginning of manual regarding
[ Consult your local distributor/dealer for service. moving parts.
⊕ Consult battery manufacturer’s instructions.

16 Section 2 Scheduled Maintenance TP-6391 9/08


Section 3 Troubleshooting

3.1 Introduction D Blown fuses. See Figure 3-1 for fuse identification.
Always check and replace the fuses before replacing
Corrective action and testing in many cases requires other components. See Figure 2 for fuse part
knowledge of electrical systems and electronic circuits. numbers.
Have an authorized distributor/dealer or trained service
technician perform testing and service. Label Amp Fuse
F1 10 Auxiliary winding
Refer to the Engine Service Manual, TP-6002 and
F2 10 Controller
TP-6008, for engine service information.
F3 10 Customer connection
The first step in troubleshooting the generator set F4 15 Coils/injectors
controls is to verify that the controller is correctly F5 15 ECM, O2 sensor, fuel pumps, and temp.
configured for the generator set. The Generator Set sender
Installation Manual explains how to check and change F6 15 Voltage regulator and battery charging
the controller configuration. alternator
F7 20 Starter motor and crank solenoid
If the troubleshooting procedures in this section identify
a bad part, refer to the parts catalog for replacement part Figure 3-1 Fuse Identification
numbers. See the List of Related Materials in the
D Incorrect controller settings. Always check the
Introduction for the parts catalog number. controller configuration settings before replacing the
controller. Section 4.11 explains how to check and
change the controller settings.
3.2 Initial Checks
When troubleshooting, always check for simple
problems first. Check for the following common
3.3 Troubleshooting Chart
problems before replacing parts: Use the following table(s) as a reference in
troubleshooting individual problems. Generator set
D Loose connections or damaged wiring.
faults are listed in groups and include likely causes and
D Dead battery. remedies. The simplest and most likely causes of the
problem are listed first; follow the recommendations in
D Fault shutdown. Check for a fault code on the the order shown. The reference column provides
ADC 2100 display. Section 4.5 describes the additional sources of information in this and related
warning and shutdown fault codes. manuals regarding the problem and solution.

Note: In the following table(s), O/M refers to the


Operation Manual, I/M refers to the Installation
Manual, and S/M refers to the Service Manual.

TP-6391 9/08 Section 3 Troubleshooting 17


Troubleshooting Chart
Problem Possible Cause Corrective Action Reference
Generator Weak or dead battery Recharge or replace battery. Generator O/M
set does
d Battery connections Check for reversed or poor battery connections. —
not crank
Open circuit in engine/controller Check for loose connections. Section 7
connections Check the wire harness continuity.
Blown fuse F2, controller Replace fuse; if fuse blows again, check circuit and Section 5.12
components. Section 7
Blown fuse F2,, relay
y interface Replace fuse. Section 5.12
b d (RIB)
board If fuse blows again, disconnect the board leads one at a Section 7
time to identify the cause of the blown fuse:
Lead 70A
Leads FP and FN at the rotor
Repair or replace the component causing the blown
fuse.
If fuse continues to blow and the previous step did not Section 7
identify the cause, check the continuity of leads FP and Section 4.6
FN and the leads from the P14 connector. Replace any
bad leads. Use a pin pusher, part #241918 (large) or
241919 (small) to remove leads from the connector, if
necessary. If replacing the leads does not solve the
problem, replace the RIB.
Crank relay on relay interface Check connections to the RIB. Check for 12VDC to the Section 4.6
board (RIB) RIB on lead 71N. Section 7
Check for a good ground connection (lead N). Section 7
Check crank relay K2 operation (LED3). Replace the Section 4.6
RIB if relay does not operate.
Generator set master switch Check connections to the master switch on the Section 4.3
ADC 2100. Section 5.13
Test function of switch. Section 5.13
Poor ground (--) connection Clean and retighten. —
Starter Check starter connections. Section 7
Rebuild or replace starter. Engine S/M
Controller Check controller connections and operation. Check for Section 4
power to the controller. Move generator set master Section 7
switch to OFF/RESET and then to RUN.
Blown F3 fuse Verify line circuit. Section 7
Blown F6 fuse Check voltage regulator wiring. Section 7
Blown F7 fuse Check wiring for open grounds or loose connections. Section 7
Also, check for pushed out pins.

18 Section 3 Troubleshooting TP-6391 9/08


Troubleshooting Chart, continued
Problem Possible Cause Corrective Action Reference
Cranks but No fuel Check the fuel supply. —
d
does not Spark plugs or spark plug Check spark plug wires and connections. Replace or O/M
start connections clean and regap spark plugs.
Loose connection or open circuit Check for loose or open connections at the fuel solenoid Section 7
and at the engine control module. Check
controller/engine wiring continuity.
Backfire flame arrestor clogged Clean or replace. O/M
Incorrect controller configuration Check for correct controller configuration parameters: Section 4.11
unit configuration (UC) and engine configuration (EC).
Ignition system spark control or Test and/or replace components. Engine S/M
ignition coil
No engine rotation sensed (check Check for locked rotor. Section 5.4
for an overcrank fault shutdown)
Blown F2 fuse Replace fuse. Section 5.12
Section 7
Blown F4 fuse Check GNDs on coil. Section 7
Blown F5 fuse Check ECM ground connection pin 14. Section 7
Starts hard Low battery voltage Check battery voltage. O/M
Backfire flame arrestor clogged Clean or replace. O/M
Spark plug(s) Replace or regap spark plug(s). O/M
Spark plug wire(s) Check spark plug wires and connections. Replace Engine S/M
spark plug wires.
Ignition components (spark Test/replace ignition components. Engine S/M
control or ignition module)
Worn piston rings, valves Check compression. Engine S/M
Blown F5 fuse Check ECM ground connection pin 14. Section 7
Blown F6 fuse Check voltage regulator wiring. Section 7
Starts but Fault shutdown Check for a fault shutdown code on the controller’s LED Section 4.5
shuts display. Correct the fault and then move the generator Section 5.10
down set master switch to OFF/RESET to reset the controller.
Stops Fault shutdown Check for a fault shutdown code on the controller’s LED Section 4.5
suddenly display. Correct the fault and then move the generator Section 5.10
set master switch to OFF/RESET to reset the controller.
No fuel Check the fuel supply. —
Fuel line restriction Inspect fuel lines. —
Backfire flame clogged Replace element. O/M
Blown controller fuse (F2) Replace fuse. Section 5.12
Blown auxiliary winding fuse (F1) Replace fuse. If fuse blows again, test generator Section 5.12
components.
Blown relay interface board (RIB) Replace fuse. Section 5.12
fuse (F2)
Spark plug(s) Replace and regap plug(s). Engine S/M
Engine overheated (hot engine Check air intake, fuel, oil level, air inlet/outlet. O/M and I/M
only)
Low oil pressure (LOP) switch Attempt startup. If unit shuts down, remove lead from Engine S/M
LOP switch and reset controller. A successful restart
attempt indicates a faulty LOP shutdown switch.
Note: Check engine oil pressure before performing test
and/or replacing LOP shutdown switch.
Engine overloaded Reduce electrical load. I/M
Loss of generator output voltage Check connections at P15 plug. Section 7
to controller Check continuity of AC sensing leads 11 and 44.
Ignition module Test and/or replace. Engine S/M
K3 (flash) relay Check for Flash LED illumination. Check RIB fuse. Section 4.6
Replace relay board.

TP-6391 9/08 Section 3 Troubleshooting 19


Troubleshooting Chart, continued
Problem Possible Cause Corrective Action Reference
Stops Blown F3 fuse Verify line circuit. Section 7
suddenly
(continued) Blown F5 fuse Check ECM ground connection pin 14. Section 7
Operates
p Backfire flame arrestor clogged Clean or replace. O/M
erratically
i ll Spark plug(s) Replace and regap plugs. O/M
Spark plug wire(s) Replace spark plug wires. Engine S/M
Fuel line restriction Check fuel lines. —
Ignition system Test and/or replace components. Engine S/M
Inadequate cooling (hot engine Inspect air inlet and outlet. —
only)
Carbon buildup in engine Clean cylinder head. Engine S/M
Engine valves not seating Check cylinder pressures with leakdown test. Inspect Engine S/M
correctly valves and valve seats.
Lacks Air intake restriction, inadequate Inspect air intakes and exhaust for obstructions. —
power cooling Check air cleaner.
Generator overloaded Reduce load. —
Spark plug(s) Replace and regap plug(s). O/M
Spark plug wire(s) Replace spark plug wires. Engine S/M
Engine not running at rated rpm Check controller settings for unit configuration (UC) and Section 4.11.2
engine type (EC).
Engine power loss Refer to the Engine Service Manual for troubleshooting Engine S/M
and repair instructions.
Ignition system Test and/or replace. Engine S/M
Blown F5 fuse Check ECM ground connection pin 14. Section 7
Overheats Inadequate cooling Inspect cooling system for air intake obstructions. —
Backfire flame arrestor clogged Clean or replace. O/M
Low output
p Generator overloaded Reduce load. —
or
Incorrect controller configuration Check and adjust the controller configuration Section 4.11.2
excessive
parameters.
drop in
voltage Incorrect controller voltage Check and adjust the controller voltage settings. Section 4.11.2
settings
Alternator or control system Perform separate excitation procedure to isolate Section 5.2
problem to the alternator or the control system.
SCR module Check wiring and connections to the SCR module. Section 5.12
Check auxiliary winding fuse F1 (lead 55). Section 4.9
Replace SCR module and test voltage.
Controller Check controller settings. Check controller fuse, wiring Section 4.11.2
and connections.
Before replacing controller, replace SCR module and Section 4.10
test voltage.
Rotor (open, grounded, or Test and/or replace. Section 5.4
shorted windings)
Stator (open, grounded, or Test and/or replace. Section 5.3
shorted windings)
Brush connection Check for loose brush connections. Section 5.6
Check the resistance through the brushes. Resistance
through the brushes should be low, 0.1--0.2 ohms
without meter lead resistance.
Low engine speed causing Check system voltage/frequency (Uu) and engine type Section 4.11.2
voltage roll-off (Ec) parameters.
Troubleshoot the engine. Engine S/M

20 Section 3 Troubleshooting TP-6391 9/08


Troubleshooting Chart, continued
Problem Possible Cause Corrective Action Reference
Light Voltage stability (gain) setting Check and adjust the voltage stability (gain) setting Section 5.7
flicker using the ADC 2100.
High Incorrect controller configuration Check and adjust the controller configuration Section 4.11.2
p
output parameters.
voltage
lt Incorrect controller voltage Check and adjust the controller voltage settings. Section 5.7
settings
Loose voltage sensing Check connections: stator leads 11 and 44 and P15 Section 7
connections controller connection.
SCR module Check wiring and connections to the SCR module. Section 4.9
Check auxiliary winding fuse F1 (lead 55). Section 5.12
Replace SCR module and recheck voltage. Section 4.9
Controller Check fuses, wiring and connections. Before replacing Section 4.10
controller, replace SCR module and test voltage.
No output AC output circuit breaker open Check for AC voltage on the generator side of circuit —
voltage breaker. If there is AC voltage on the generator side of
the breaker, then a problem in the load circuits is
causing the line circuit breaker to trip. Check for and
correct short circuits or overloading on the load side
before resetting the circuit breaker.
Alternator or control system Perform separate excitation procedure to isolate the Section 5.2
problem to the alternator or the control system. Then
troubleshoot the alternator or control system
components as follows.
Aux. winding F1 fuse blown Replace blown fuse. If fuse blows again, check stator. Section 5.3
SCR module Check auxiliary winding fuse F1 (lead 55). Section 5.12
Replace SCR module and test voltage. Section 4.9
Controller Check controller settings. Check wiring and Section 4.11.2
connections. Before replacing controller, replace SCR Section 4.10
module and check voltage.
Open wiring, terminal, or pin in Check continuity. Section 5.13
buildup circuit or SCR module Section 7
circuit
Brushes Inspect brushes and replace if worn. Section 5.6
Check for brushes sticking in brush holder or broken Section 5.6
brush spring.
Rotor connections Check for open circuit in rotor connection circuit (leads Section 7
FN and FP to SCR and RIB).
Rotor slip rings dirty or corroded Check slip ring condition. Section 5.4
Rotor (open, grounded, or Check voltage and continuity. Section 5.4
shorted windings)
Stator (open, grounded, or Check voltage and continuity. Section 5.3
shorted windings)
Flash relay (K3) on relay Check flash LED on RIB. Section 4.6
interface board (RIB) Check fuse F2 and troubleshoot RIB.
Blown F2 fuse Replace fuse If fuse blows again, check circuit and Section 5.12
components. Section 7
Blown F5 fuse Check ECM ground connection pin 14. Section 7

TP-6391 9/08 Section 3 Troubleshooting 21


Troubleshooting Chart, continued
Problem Possible Cause Corrective Action Reference
Noisy
y Exhaust system leaks Check and replace as necessary. O/M
operation
i Engine not running smoothly See “Generator set operates erratically,” this table. —
Broken or damaged Check and replace as necessary. —
vibromount(s)
Loose or vibrating sheet Retighten screws, replace rivets.

metal/housing
Exhaust piping or air inlets/outlets Inspect for loose parts and secure if necessary. —
not securely installed
Excessive engine/generator Check, rotor, crankshaft, bearing, etc. (disassembly of Engine S/M
vibration engine and/or alternator may be required).

22 Section 3 Troubleshooting TP-6391 9/08


Section 4 Controller

4.1 Introduction A relay interface board (RIB) is used with the ADC
controller. Section 4.6 describes the relay interface
This section describes the operation and replacement of board.
the ADC 2100 controller. Controller configuration and
adjustment are explained in Section 4.11. See Section 3 A silicon controlled rectifier (SCR) module works with
for troubleshooting procedures. the controller to regulate the output voltage. See
Section 4.9.
See Figure 4-1 for the locations of the ADC 2100
controller and related components.

Top View

1
2

3
4

6 7

Service-Side View
8 9

10

GM39685D-J

1. LO stud 7. Fuse location. See Section 5.12


2. Ground stud 8. ADC 2100 controller
3. Relay interface board (RIB) 9. CO sensor module (available on units with serial number
4. SCR module 2085259 and later)
5. K5 main power relay 10. Generator set master switch
6. Line circuit breaker panel (load connection)

Figure 4-1 Advanced Digital Control (ADC 2100)

TP-6391 9/08 Section 4 Controller 23


4.2 Controller Display and Keypad Controller Display
Item Description
The controller has an LED display and a three-button
keypad. See Figure 4-2. The LED display shows Crank indication Displays CC_1, CC_2, or CC_3 to indicate
the first, second or third attempt to start the
runtime hours, fault codes, application program version engine. The last digit flashes during the
number, or controller parameters during configuration crank cycle rest periods.
and adjustment. See Figure 4-3. The keypad is used to Runtime hours Displays total generator set runtime hours
enter the controller’s configuration and adjustment when no other code is displayed.
menus, and to change the controller settings. Fault codes Flashes a 2- or 3-letter fault code to indicate
various fault conditions. See Section 4.5.
A password key sequence is required to enter the System Displays 2-letter codes or 4-digit
parameters alphanumeric codes during system
configuration and adjustment menus. Section 4.11 configuration or adjustment. See
contains the instructions to enter the configuration and Section 4.11.2.
adjustment menus and change the settings using the Application Displays the version number of the
controller keypad. program version controller’s application program before
number entering the configuration or adjustment
mode. See Section 4.11.2.

4.3 Master Switch Figure 4-3 ADC controller LED Display

The generator set master switch is a three-position


(RUN\OFF/RESET\AUTO) rocker switch. The leads
connecting to the master switch are labeled RUN, VBAT,
and AUTO. Check that the three pink connectors are 1
connected to the terminals on the back of the switch as
shown in Figure 4-4. Be careful not to reverse the RUN
and AUTO leads.

3
2

tp6196
AUTO

4 3 2
RUN
VBAT

4
GM28707A-C
1. LED display
2. Select button (use for setup and adjustment only) 1. Engine wiring harness connector plug (P1)
3. Up and down arrow buttons (use for setup and adjustment only) 2. J15 connector
4. Generator set master switch 3. J16 connector
4. Generator set master switch
Figure 4-2 ADC Controller
Figure 4-4 Controller Connections

24 Section 4 Controller TP-6391 9/08


4.4 Sequence of Operation 4.4.3 Stopping the Generator Set
The following sections describe the controller sequence The following procedures describe the actions required
of operation during generator start, run, stop, and fault to stop the generator set.
shutdown modes. Use this as a starting point for
controller and relay board fault identification. Refer to Local Stopping
the wiring diagrams in Section 7 to assist in the
troubleshooting procedure. 1. Run the generator set at no load for at least
2 minutes to ensure adequate engine cooldown.
4.4.1 Starting the Generator Set
2. Move the generator set master switch to the
OFF/RESET position. The run relay deenergizes
Local Starting and the run LED (1) turns off. The generator set
When the master switch is moved to the RUN position, stops.
there is a delay of about 2 seconds before the controller
Auto (Automatic) Stopping.
attempts to start the engine. The run relay energizes
and the run LED (1) turns on. The crank and flash relays 1. Run the generator set at no load for at least
energize and the corresponding LEDs (2 and 3) turn on 2 minutes to ensure adequate engine cooldown.
0.5 seconds later. The controller display indicates the
crank cycle 1 code, CC 1. 2. With the generator set master switch in the AUTO
position, the generator set stops when the remote
The controller attempts to start the generator set three start/stop switch contacts close momentarily.
times (three crank cycles, 7 seconds crank and 15
Note: If the ADC 2100 is configured for a CAN gauge,
seconds off). If the generator set does not start in three consult Figure 4-20 for power-down times.
attempts, the system shuts down on an overcrank fault.
When the engine comes up to speed, the low oil Note: If the ADC 2100 is not configured for a CAN
pressure switch contacts open. gauge, the controller will power down after
48 hours (if the master switch is in the AUTO
Note: The controller circuit board prevents fault position). If the generator has been started, the
shutdowns during startup until the crank controller will power down 48 hours after the
disconnect relay energizes. generator stops.

The cyclic cranking cycle is programmed into the


controller’s application code and is not adjustable in the 4.5 Faults
field.
4.5.1 Shutdowns
The factory sets the cranking cycle for three cycles of
7 seconds on time and 15 seconds off time. If the Under the fault conditions listed in Figure 4-5, the
cranking cycle seems shorter than the factory setting, controller displays a fault code and the generator set
check the engine starting battery. shuts down.

Auto (Automatic) Starting. Always identify and correct the cause of a fault
shutdown before restarting the generator set. Refer to
When the master switch is set to the AUTO position, the Section 3, Troubleshooting, for instructions to identify
generator set starts when the remote start switch and correct the cause of the fault.
contacts close momentarily.
Move the generator set master switch to the
The start sequence proceeds as described in OFF/RESET position to reset the controller after a fault
Section 4.4.1 above. shutdown. Then move the switch to the AUTO or RUN
position.
4.4.2 Running Sequence
When the engine speed reaches 750 rpm, the crank
4.5.2 Warnings
relay deenergizes and the crank LED (3) turns off. The fault conditions listed in Figure 4-6 will cause the
When the output voltage on leads 11 and 44 reaches controller to display a fault code but will not shut down
about 30 VAC, the flash relay deenergizes and the flash the generator set.
LED (2) turns off.

TP-6391 9/08 Section 4 Controller 25


Refer to
Code Fault Description Check Section
AF Auxiliary fault Input from a customer-supplied switch that closes when Check the condition and operation of the —
the fault is active. The generator set shuts down 0.3 customer-supplied equipment
seconds after the fault is detected and will not start when connected to the auxiliary fault input
the fault is active (input is grounded). This protection P21-6.
becomes active 3 seconds after crank disconnect.
CO-1* Carbon Sensor fault shutdown occurs because of the presence Immediate service required. Contact —
monoxide of CO. an authorized distributor/dealer for
shutdown service.
Ensure windows are open for proper
ventilation.
Operate the blower to expel dangerous
fumes.
Move the vessel away from other
vessels (as another vessel may be the
source for the presence of the CO).
Check the generator exhaust system
(see the O/M).
CO-2* Carbon Shutdown occurs because of the presence of CO or Immediate service required. Contact —
monoxide deteriorating emission-control components (such as the an authorized distributor/dealer for
shutdown catalyst). service.
Ensure windows are open for proper
ventilation.
Operate the blower to expel dangerous
fumes.
Move the vessel away from other
vessels (as another vessel may be the
source for the presence of the CO).
Check the generator exhaust system
(see the O/M).
CO-3* Carbon Shutdown occurs if communication is lost between the Check the connections to the CO —
monoxide CO sensor and the ADC. sensor.
sensor
If connections are okay, replace the CO
shutdown
sensor.
Contact an authorized distributor/dealer
for service.
HE High engine Shutdown occurs if the engine coolant temperature Check for blocked air inlets and exhaust 1.8
temperature exceeds the maximum temperature for more than outlets.
5 seconds. This protective becomes active after the
engine reaches the crank disconnect speed.
LCL Low coolant Not used. — —
level
LOC Loss of coolant Shutdown occurs 5 seconds after a loss of coolant Check for a clogged seawater intake or O/M
condition is detected. This protection becomes active sea strainer. I/M
10 seconds after the engine has reached its stated crank
Check for a damaged seawater pump
disconnect speed and remains active as long as the
impeller.
generator run command is active.
Check the high exhaust temperature
Units with serial number 2199434 and later: In the
switch, if equipped.
event of a shutdown because of the high exhaust
temperature switch, the ADC will display fault code LOC.
LOP Low oil Shutdown occurs if a low oil pressure condition exists for Check for leaks in the lubrication O/M
pressure more than 5 seconds. This protective becomes active system.
30 seconds after the engine has reached crank
Check the oil level and add oil if the O/M
disconnect speed (30 second inhibit).
level is low.
Note: The low oil pressure shutdown does not protect
Check low oil pressure switch 5.10
against low oil level. Check the oil level at the engine.
connections and operation.
Check the oil pump and lubrication Engine
system. S/M

26 Section 4 Controller TP-6391 9/08


OC Overcrank Shutdown occurs after 3 unsuccessful starting attempts. Check the fuel supply. I/M
The crank cycle is set for three starting attempts of
Check spark plug and battery. O/M
7 seconds cranking and 15 seconds rest.
See Troubleshooting Chart, generator 3.3
set cranks but does not start.
The generator set shuts down on an overcrank fault if no Check for a locked rotor. 5.4
engine rotation is sensed. Shuts down after 3 seconds of
cranking or 1 second after the fault is detected.
OF Overfrequency Shutdown occurs when the governed frequency exceeds Check system frequency setting 4.11
0% of the system’s
110% y q
frequencyy setpoint
p for more than 5 (parameter UU) on controller.
seconds.
d This
Thi protective
i becomes
b active
i 10 seconds d
Check engine governing system, Engine
after engine start (10 second inhibit).
controlled by the engine ECM. S/M
OS Overspeed Shutdown occurs if the engine speed exceeds 115% of Check engine governing system, Engine
the normal running speed for more than 0.3 seconds. controlled by the engine ECM. S/M
OU Overvoltage Shutdown occurs if the voltage exceeds 120% of the Check AC voltage. 5.7
system nominal voltage for more than 2 seconds.
Check wiring and connections. 7
UF Underfrequency Shutdown occurs when the governed frequency falls Reduce the load and restart the —
blow 90% of the nominal system frequency for more than generator set.
5 seconds or below 59 Hz for more than 60 seconds.
This protective becomes active 10 seconds after engine
start. (10 second inhibit).
UU Undervoltage Shutdown occurs if the voltage falls below 80% of the Reduce the load and restart the —
y
nominal system g for more than 10
voltage 0 seconds. generator set.
Check wiring and connections. 7
Check controller configuration, system 4.11
voltage and frequency (parameter UU).
Check AC voltage and adjust, if 5.7
necessary.
Replace the SCR module and test 4.9
voltage again.
Separately excite unit. 5.2
Check stator continuity. 5.3
SCF0 Software Indicates a software or communication problem within Replace the controller. 4.10
Communication the ADC 2100.
Fault 0
Note: O/M = Generator set Operation Manual; I/M = Generator Set Installation Manual

* Available on units with serial number 2085259 and later.


Figure 4-5 Fault Shutdown Codes

TP-6391 9/08 Section 4 Controller 27


Code Fault Description Check
CO-4* Carbon monoxide Fault code is displayed if the presence of CO is Ensure windows are open for proper ventilation.
warning detected because of the time-weighted average
Operate the blower to expel dangerous fumes.
presence of CO. Activates the CO cabin alarms.
Move the vessel away from other vessels (as another
vessel may be the source for the presence of the CO).
Check the generator exhaust system (see the
Operation Manual).
Contact an authorized distributor/dealer for service if
problem continues.
CO-5* Carbon monoxide Fault code is displayed if the presence of CO is Ensure windows are open for ventilation.
warning detected. Warning occurs if the sensor detects
Operate the blower to expel dangerous fumes.
acceptable but increasing CO levels.
Move the vessel away from other vessels (as another
vessel may be the source for the presence of the CO).
Check the generator exhaust system (see the
Operation Manual).
Generator service for emissions required.
Contact an authorized distributor/dealer for service if
problem continues.
CO-6* Carbon monoxide Fault code is displayed if the CO sensor is inoperative. Replace the CO sensor.
sensor warning
Contact an authorized distributor/dealer for service if
problem continues.
HB High battery Fault code is displayed if the engine starting battery Check the battery rating and condition.
voltage warning voltage rises above 16 VDC for a 12 VDC system or
above 30 VDC for a 24 VDC system for more than
2 seconds when the engine is not running. This fault
condition does not inhibit engine starting.
The fault condition clears when the battery voltage
returns to a voltage within the limits for more than
2 seconds.
LB Low battery Fault code is displayed if the engine starting battery Check the battery rating and condition.
voltage warning voltage falls below 9.5 VDC for a 12 VDC system or
Charge or replace the battery.
below 16 VDC for a 24 VDC system for more than
2 seconds when the engine is not running. This fault
condition does not inhibit engine starting.
The fault condition clears when the battery voltage
returns to a voltage within the limits for more than
2 seconds.

* Available on units with serial number 2085259 and later.


Figure 4-6 Fault Warning Codes

28 Section 4 Controller TP-6391 9/08


4.5.3 SECM Fault Codes and Diagnostics

Fault
Code
Displayed Description Check
No Faults (Fault Code 0)
EC9 Throttle Position Sensor Fault appears if the sensor signal wire is shorted, the sensor has failed, or the SECM has
(TPS1) Input High failed. Check the throttle connector and sensor wiring for a shorted circuit:
ETC Pin 6 to SECM Pin 17 (SIGNAL)
ETC Pin 2 to SECM Pin 1 (GND)
EC10* Throttle Position Sensor Fault appears if the sensor potentiometer has malfunctioned. Check for dirt or oxidation on the
(TPS1) Range High sensor traces. Check the throttle connector and pins for corrosion. To check, disconnect the
throttle connector and measure the resistance of 1.25 kOhms ¦ 30% from:
TPS Pin 2 (GND) to Pin 6 (TPS1 SIGNAL)
TPS Pin 3 (PWR) to Pin 6 (TPS1 SIGNAL)
NOTE: Do not service this sensor. Repair by replacing the throttle body assembly.
EC11* Throttle Position Sensor Fault appears if the sensor potentiometer has malfunctioned. Check for dirt or oxidation on the
(TPS1) Range Low sensor traces. Check the throttle connector and pins for corrosion. To check, disconnect the
throttle connector and measure the resistance of 1.25 kOhms ¦ 30% from:
TPS Pin 2 (GND) to Pin 6 (TPS1 SIGNAL)
TPS Pin 3 (PWR) to Pin 6 (TPS1 SIGNAL)
NOTE: Do not service this sensor. Repair by replacing the throttle body assembly.
EC12 Throttle Position Sensor Fault appears if the sensor signal wire is disconnected or the circuit is opened to the SECM.
(TPS1) Input Low (EC12 and EC11 are expected faults when the ETC connector is unplugged). Check the
throttle connector connection and sensor for an open circuit:
ETC Pin 6 to SECM Pin 17 (SIGNAL)
ETC Pin 2 to SECM Pin 1 (GND)
EC39 Electronic Throttle Control Fault appears if either of the electronic throttle control driver signals are opened or
(ETC) Sticking disconnected. This happens if the throttle plate sticks inside the throttle body. Check for debris
or obstructions inside the throttle body; a loose throttle plate, or the throttle-plate shaft for
bearing wear. Check the ETC driver wiring for an open circuit:
ETC+ Pin 1 to SECM Pin 22
ETC-- Pin 4 to SECM Pin 24
Check the ETC internal motor drive by disconnecting the throttle connector and measuring the
motor drive resistance at the throttle:
TPS Pin 1 (+DRIVER) to Pin 4 (--Driver) approx. 3.0 Ohms ¦ 30%.
NOTE: Do not service the throttle components. Repair or replace the throttle body assembly.
EC40* Electronic Spark Trigger The Electronic Spark Trigger is a current driver signal. This fault appears if the signal from the
(EST) 1 Low SECM is shorted to ground or the coil driver signal is low or undercurrent. Check the coil driver
wiring and connector for shorts:
SECM Pin 7 (EST 1) to COIL Pin A
Verify GND on COIL Pin B
Verify GND on COIL Pin C
Verify GND on COIL Pin D
Verify +12VDC on COIL Pin E
To check the internal circuit, disconnect the coil connector and measure the resistance from pin
to pin. See Figure 5-20.
EC41* Electronic Spark Trigger The Electronic Spark Trigger is a current driver signal. This fault appears if the signal from the
(EST) 1 High SECM is open or lost or the coil driver signal is high or overcurrent.
Check the coil driver wiring for an open circuit or disconnected connector:
SECM Pin 7 (EST 1) to COIL Pin A
Verify GND on COIl Pin B
Verify GND on COIL Pin C
Verify GND on COIL Pin D
Verify +12VDC on COIL Pin E
To check the internal circuit, disconnect the coil connector and measure the resistance from pin
to pin. See Figure 5-20.
EC42* Electronic Spark Trigger The Electronic Spark Trigger is a current driver signal and this fault appears if the signal from
(EST) 2 Low the SECM is shorted to ground or the coil driver signal is low or undercurrent. Check the coil
driver wiring and connector for shorts:
SECM Pin 7 (EST1) to COIL Pin A
Verify GND on COIL Pin B
Verify GND on COIL Pin C
Verify GND on COIL Pin D
Verify +12VDC on COIL Pin E
To check the internal circuit, disconnect the coil connector and measure the resistance from pin
to pin. See Figure 5-20.

* Indicates a stored fault code.

TP-6391 9/08 Section 4 Controller 29


SECM Fault Codes and Diagnostics (Continued)

Fault
Code
Displayed Description Check
EC43* Electronic Spark Trigger The Electronic Spark Trigger is a current driver signal and this fault appears if the signal from
(EST) 2 High the SECM is open or lost or the coil driver signal is high or overcurrent.
Check the coil driver wiring for an open circuit or disconnected connector:
SECM Pin 7 (EST 1) to COIL Pin A
Verify GND on COIl Pin B
Verify GND on COIL Pin C
Verify GND on COIL Pin D
Verify +12VDC on COIL Pin E
To check the internal circuit, disconnect the coil connector and measure the resistance from pin
to pin. See Figure 5-20.
EC46 Injector Input is Low Fault appears when the power to the injector is low.
LOP Low Oil Pressure Fault appears when the oil pressure switch is opened or disconnected, normally indicating a
low oil condition. See Figure 4-5.
EC48 Electronic Throttle Control Upon initial engine startup, the SECM performs a safety test of the throttle return spring. If this
(ETC) Spring Test Failed spring has become weak, the throttle will fail this test and set the fault. Perform a throttle spring
test by cycling the ignition and rechecking for the fault.
NOTE: Do not service the throttle components. Repair or replace the throttle body assembly.
EC49 Manifold Air Pressure The manifold air pressure sensor fault appears if the TMAP pressure signal wire is shorted to
(MAP) Sensor Input High power, shorted to the IAT signal, the TMAP has failed, or the SECM has failed. Check the
TMAP connector and MAP signal wiring for a shorted circuit:
TMAP Pin 4 to SECM Pin 5 (SIGNAL)
TMAP Pin 1 to SECM Pin 1 (GND)
TMAP Pin 3 to SECM Pin 18 (XDCR +5VDC)
Check the MAP sensor by disconnecting the TMAP connector and measuring at the sensor:
TMAP Pin 1 (GND) to Pin 4 (PRESSURE SIGNAL KPA) of 2.4 kOhms -- 8.2 kOhms
TMAP Pin 3 (PWR) to Pin 4 (PRESSURE SIGNAL KPA) of 3.4 kOhms -- 8.2 kOhms
EC50 Manifold Air Pressure The manifold air pressure sensor fault appears if the TMAP pressure signal wire is
(MAP) Sensor Input Low disconnected or the circuit is opened to the SECM. (EC50 and EC56 are expected faults when
the TMAP connector is unplugged). Check the TMAP connector and MAP signal wiring for an
open circuit:
TMAP Pin 4 to SECM Pin 5 (SIGNAL)
TMAP Pin 1 to SECM Pin 1 (GND)
TMAP Pin 3 to SECM Pin 18 (XDCR +5VDC)
Check the MAP sensor by disconnecting the TMAP connector and measuring at the sensor:
TMAP Pin 1 (GND) to Pin 4 (PRESSURE SIGNAL KPA) of 2.4 kOhms -- 8.2 kOhms
TMAP PIn 3 (PWR) to Pin 4 (PRESSURE SIGNAL KPA) of 3.4 kOhms -- 8.2 kOhms
EC51 Electronic Throttle Control Fault appears if an overcurrent condition occurs on either the ETC+ or ETC-- driver signals.
(ETC) Driver Fault Check the ETC driver wiring for a shorted circuit:
ETC+ Pin 1 to SECM Pin 22
ETC-- Pin 4 to SECM Pin 24
Check the ETC internal motor drive by disconnecting the throttle connector and measuring the
motor drive resistance at the throttle:
TPS Pin 1 (+DRIVER) to Pin 4 (--DRIVER) approx. 3.0 Ohms ¦ 30 %.
HB* Battery Voltage Sensor Fault appears if the power to the SECM increases above 15.9 VDC. See Figure 4-6.
Input High Check the battery and charging system voltage:
Check the battery voltage during starting and with the engine running.
Check the voltage regulator, alternator, and charging system.
Check the battery and wiring for overheating and damage.
Measure the battery power at the SECM with a multimeter:
SECM Pin 13 (BATT+) to SECM Pin 14 (BATT--)
LB* Battery Voltage Sensor Fault appears if the power to the SECM drops below 9.5 VDC. See Figure 4-6.
Input Low Check the battery voltage:
Perform a maintenance check on the electrical connections to the battery and ground.
Check the battery voltage during starting and with the engine running to verify charging
system and alternator function.
Measure the battery power at the SECM with a multimeter:
SECM Pin 13 (BATT+) to SECM Pin 14 (BATT--)
EC54 Transducer Voltage (XDRP) Fault appears if the sensor power from the SECM increases above 5.9 VDC.
Sensor Input High Measure the transducer power at the TMAP connector with a multimeter:
TMAP Pin 3 +5VDC to TMAP Pin 1 XDCR GND
Verify transducer power at the SECM with a multimeter:
SECM Pin 18 +5VDC to SECM Pin 1 XDCR GND
Verify transducer power at ETC with a multimeter:
ETC Pin 3 XDCR PWR to ETC Pin 2 XDCR GND

* Indicates a stored fault code.

30 Section 4 Controller TP-6391 9/08


SECM Fault Codes and Diagnostics (Continued)

Fault
Code
Displayed Description Check
EC55 Transducer Voltage (XDRP) Fault appears if the sensor power from the SECM drops below 4.8 VDC. (EC11, EC12, and
Sensor Input Low EC50 are expected faults when the transducer power is lost).
Measure the transducer power at the TMAP connector with a multimeter:
TMAP Pin 3 +5VDC to TMAP Pin 1 XDCR GND
Verify transducer power at the SECM with a multimeter:
SECM Pin 18 +5VDC to SECM Pin 1 XDCR GND
Verify transducer power at the ETC with a multimeter:
ETC Pin 3 XDCR PWR to ETC Pin 2 XDCR GND
EC56* Intake Air Temperature (IAT) Fault appears if the TMAP temperature signal wire is disconnected or the circuit is open to the
Input Sensor High SECM. Check the TMAP connector and IAT signal wiring for an open circuit:
TMAP Pin 2 to SECM Pin 4 (SIGNAL)
TMAP Pin 1 to SECM Pin 1 (GND)
TMAP Pin 3 to SECM Pin 18 (XDCR +5VDC)
To check the IAT sensor of the TMAP, disconnect the TMAP connector and measure the IAT
resistance. See Figure 5-15.
EC57* Intake Air Temperature (IAT) Fault appears if the TMAP temperature signal wire has become shorted to ground, shorted to
Input Sensor Low the MAP signal, the TMAP has failed or the SECM has failed. Check the TMAP connector and
IAT signal wiring for a shorted circuit:
TMAP Pin 2 to SECM Pin 4 (SIGNAL)
TMAP Pin 1 to SECM Pin 1 (GND)
TMAP Pin 3 to SECM Pin 18 (XDCR +5VDC)
To check the IAT sensor of the TMAP, disconnect the TMAP connector and measure the IAT
resistance. See Figure 5-15.
EC58* Engine Coolant Fault appears if the coolant sensor wire is disconnected or the circuit is opened to the SECM.
Temperature (ECT) Sensor Check if the sensor connector is disconnected or for an open circuit:
Input High SECM (SIGNAL) Pin 16 to ECT Pin A
SECM (GND) Pin 1 to ECT Pin B
EC59* Engine Coolant Fault appears if the coolant sensor wire is shorted to ground or the sensor has failed. Check
Temperature (ECT) Sensor the sensor connector and wiring for a short to GND:
Input Low SECM (SIGNAL) Pin 16 to ECT Pin A
SECM (GND) Pin 1 to ECT Pin B
EC60* Oxygen Sensor Input High Fault appears if the O2 sensor SECM driver signal is shorted to power. Check if the O2 sensor
is shorted to +5VDC or battery:
O2 (SIGNAL) Pin B to SECM Pin 3
Verify operation of O2 sensor heater circuit by measuring circuit resistance of 2.1 ohms
¦ 0.4 ohms:
O2 Pin C (HEATER GND) to Pin D (HEATER PWR)
EC61 Oxygen Sensor Input Low Fault appears if the oxygen sensor input is low. Check the O2 sensor connector and wiring for
a short to ground:
ECM (SIGNAL) Pin 3 to O2 Sensor Pin B
ECM (GND) Pin 1 to O2 Sensor Pin A
EC62 Seawater Pump Pressure Fault appears when seawater cooling is lost. Check the seawater strainer for clogged material.
Check the seawater pump impeller. Check if wire 215 is shorted to ground. See Figure 4-5.
OS Engine Overspeed Fault Fault appears when the engine RPM increases beyond the max. RPM setpoint. Typically this
occurs with one or more throttle faults. Check for ETC sticking or other ETC faults. See
Figure 4-5.
HE Engine Coolant Fault appears when the sensor has measured an excessive coolant temperature typically due
Temperature (ECT) Sensor to engine overheating. Check the coolant system for seawater blockages, proper coolant level,
Range High and any leaks in the coolant system. See Figure 4-5. Check for possible ECT short to GND.
Check the ECT signal wiring:
SECM (SIGNAL) Pin 16 to ECT Pin A
SECM (GND) Pin 1 to ECT Pin B
EC69* O2 Sensor Switching Fault Fault appears when the O2 sensor can no longer switch or be driven above and below 500mv
by the SECM. O2 Sensor is not switching across the reference AFR voltage. Check for an
open coil by disconnected the connector and measuring the resistance (approx. 26 ohms¦
2 ohms):
Pin A (SIGNAL) to Pin B (PWR)
EC72* CAN Receive Message See Figure 4-7 and Figure 4-8.
Fault

* Indicates a stored fault code.

TP-6391 9/08 Section 4 Controller 31


Note: Generator sets built after serial number 2175814 have a different engine harness design. For serial numbers
after 2175814, the communication wires are green and yellow. Pin locations remain the same. Resistors are
removable.

Note: For complete wiring diagram details, see Section 7.

Verify Battery Voltage to ECM


Verify battery voltage between P10-13 (positive) referenced to P10-14 (negative).
If no battery voltage, change the negative reference on the meter to the engine block ground. If there’s now a battery voltage
reading, the ground wire to the ECM is open. Trace the negative wire to its ground source and determine the cause of the
open circuit. If there’s still no battery voltage, the problem is the positive supply (F5 wire).
The F5 wire supplies the battery voltage to the ECM and is switched thru the K5 relay contacts. Access the K5 relay on the
non-service side of the generator set (behind the ADC 2100 control).
NOTE: Older harness designs have a small black relay that is mounted to the generator end bell with spade connectors at
the bottom. Newer harness designs (after serial number 2175814) have the relay attached directly to the harness (P30
connector) at the same location.
Verify power at 12P wire at the K5 relay. Reference negative to P10-14.

If there’s power at 12P, verify power on PF4 (the other side of the normally open (NO) relay contact).
If there’s power at PF4, verify power to PF5 off of the F5 fuse.
If there’s power at PF5 at the F5 fuse, the problem’s between the F5 fuse and the ECM connection.
If there’s no power at 12P, verify power at F3 fuse, wires F3 and PF2.
If there’s power at this point, trace the wire between F3 and 12P on the K5 relay.
If there’s no power at F3 fuse, verify that F3 is not open. If F3 is open, replace it.
If there’s no power to F3, verify connections at the Crank Solenoid (CS) PF3 and battery positive connection.

Figure 4-7 Troubleshooting EC72 Fault Code (Verifying Battery Voltage to the ECM)

32 Section 4 Controller TP-6391 9/08


Note: Generator sets built after serial number 2175814 have a different engine harness design. For serial numbers
after 2175814, the communication wires are green and yellow. Pin locations remain the same. Resistors are
removable.

Note: For complete wiring diagram details, see Section 7.

Verify Control Area Network (CAN) Resistance


Disconnect the ADC 2100 control plug (P1), ECM (P10), remote12-pin customer interface (P4), and SmartCraftt
communications plug (P19).
Measure the resistance at the P1 (ADC) connector pins 11 and 10 (YEL and GRN labeled wires). The meter should indicate
60 ohms.
If the meter reads 0 ohms, there’s an open circuit between the pins to the R1 resistor.

If the meter reads 120 ohms, the two resistors in the harness are no longer in parallel. Check the connections between the
resistors.

Verify a resistance of 60 ohms at the P4 (customer interconnect) connector, pins 1 and 2 (YEL and GRN). The meter should
read 60 ohms.

If the meter reads 0 ohms, there are open wires from the P4 connector to the Insul 14 and Insul 12.
If the meter reads 120 ohms, the two resistors in the harness are no longer in parallel. Check the connections between the
resistors.

TP-6391 9/08 Section 4 Controller 33


Verify resistance of 60 ohms at P19 (SmartCraftt) wire 219 and 206, pins C and D.

If the meter reads 0 ohms, there’s an open circuit to the R2 resistor.


If the meter reads 120 ohms, the two resistors in the harness are no longer in parallel. Check the connections between the
resistors.
Verify resistance of 60 ohms at the P10 (ECM) connector, wires BLK and RED, pins 6 and 19.

If the meter reads 0 ohms, there’s an open circuit between these pins, wires and/or the harness resistors.
If the meter reads 120 ohms, the two resistors in the harness are no longer in parallel. Check the connections between the
resistors.

Figure 4-8 Troubleshooting EC72 Fault Code (Verifying Control Area Network (CAN) Resistance)

34 Section 4 Controller TP-6391 9/08


4.6 Relay Interface Board (RIB) 4.7 CO Sensor Module
The relay interface board (RIB) contains the K2 crank, The CO sensor module is located behind the ADC 2100.
K3 flash, and K5 run relays. Three LEDs indicate relay Replace the CO sensor module every two years. See
operation. See Figure 4-9. Figure 4-10.

Refer to the schematic diagram in Section 7 for the relay Note: The CO sensor module is equipped on generator
board connections. sets with serial number 2085259 and later.

The RIB is protected by a 10 amp fuse (F2). If the fuse


blows repeatedly, disconnect the board leads one at a
time to identify the cause of the blown fuse:

D Lead 70A
D Leads FP and FN at the rotor
If the fuse continues to blow and disconnecting
components did not identify the cause, remove the
leads from the P14 connector using a pin pusher, part
#241918 (large) or 241919 (small). If replacing the GM463262-
leads does not solve the problem, replace the RIB.
Figure 4-10 CO Sensor Module
The individual relays are not replaceable. If one or more
relays are faulty, replace the entire RIB.
4.8 K5 Main Power Relay
To replace the RIB:
The K5 relay powers the ECM, injector, coils, governor
1. Disconnect P14 and the brush leads FP and FN. assembly/throttle body, TMAP sensor, and O2 sensor.
See Figure 4-11.
2. Pull the board straight off the mounting stand-offs.

3. Snap the new board onto the stand-offs and


reconnect P14 and the brush leads.

7
1 4
3 1

COMMON AUX
K1 FAULT K4 RUN

2
D1

6 4
P13 5
K2
CRANK P14 K5
D6

D7

RUN
D2

3 1

3
9 7
D3

SCHEMATIC
(sINGLE POLE DOUBLE THROW)
R1

T1
R2

R3

FN LED1
RUN
VBAT LED2 R GM28787-K
FLASH R

LED3
K3 FLASH FP CRANK Rated Voltage 12 VDC
D4

D5

T2 R

GM29671-A Operating Current 133 mA


1. K1 common fault relay (optional) 6 Coil Resistance 90 ± 10 ohms
2. K2 crank relay (standard) Pull-In Voltage <8V
3. K3 flash relay (standard) Release Voltage 1.2 V
4. K4 auxiliary run relay (optional) Max. Operating Voltage 15.6 V
5. K5 run relay (standard)
6. P14, engine harness connection (standard)
7. P13, connection to optional relay harness (optional)
Figure 4-11 K5 Relay Specs
Figure 4-9 Relay Board

TP-6391 9/08 Section 4 Controller 35


4.9 Silicon Controlled Rectifier 3. Connect the ohmmeter from AC1 to (+) on the SCR
module. You should read high resistance in both
(SCR) Module directions.
The silicon controlled rectifier (SCR) module works with
4. Connect the ohmmeter from AC1 to (--) on the SCR
the ADC 2100 to regulate the output voltage. The module. You should read high resistance in one
ADC 2100 monitors generator output voltage and direction and low resistance in the other.
adjusts the excitation current to the rotor through the
SCR module. The SCR module location is shown in 5. Repeat steps 3 and 4 for AC2.
Figure 4-1.
6. Connect the ohmmeter from G1 to (+) on the SCR
The SCR module is powered through stator leads 55 module. You should read low resistance in both
and 66 connected to SCR terminals AC1 and AC2. directions.
Leads G connected to terminals G1 and G2 provide the
controller signal. Leads FP and FN connected to the 7. Repeat step 6 for G2. You should read low
positive (+) and negative (--) SCR terminals provide resistance in both directions.
excitation current to the rotor. See Figure 4-12 and the
8. See Figure 4-13. Connect the negative (--) lead
wiring diagrams in Section 7.
from the DC power source to the positive (+)
terminal on the SCR module.
The SCR module is protected by a 10-amp fuse (F1) in
lead 55 in the wiring harness. Check the fuse and Note: The SCR module may be damaged if the
replace it, if blown. power supply is connected incorrectly. Be
sure to connect the negative lead from the
In the case of output voltage problems, check the
battery to the positive terminal on the SCR
controller configuration and settings. Then test the SCR module.
module using the following procedure.

(--) (+) 2
SCR Module Test Procedure

Required equipment:

D Ohmmeter 1
4
D 12-volt test lamp (or voltmeter)
D 12-volt DC power source
5
D 100--500 ohm resistor
D Jumper 3
G1
1. Set the ohmmeter to the R x 1 scale.

2. Connect the ohmmeter from (+) to (--) on the SCR AC1


module. You should read high resistance in one AC2
direction and low resistance in the other (reverse (+) (--)
the leads).
G2
tp6198

1. 12VDC power source


2. 12 VDC test lamp
AC1 G1 -- 3. SCR module
4. Jumper
5. 100--500 ohm resister

AC2 G2 + Figure 4-13 SCR Test

9. Connect the positive (+) lead from the DC power


GM28483
source, with the lamp in series, to terminal AC1 on
the SCR module. The lamp should not glow.
Figure 4-12 Silicon Controlled Rectifier (SCR)
Module

36 Section 4 Controller TP-6391 9/08


10. Connect the jumper, with the resistor in series, from 7. Attach plugs P1, P15, and P16 to the new
the positive lead of the DC power source to terminal controller.
G1 on the SCR module. The lamp should glow.
8. Place the new controller into position and install the
11. Repeat steps 9 and 10, with the positive (+) lead four mounting screws.
and lamp connected to terminal AC2 on the SCR
module, and connecting the jumper with resister to 9. Verify that the generator set master switch is in the
terminal G2. OFF position.

12. If any of the above checks indicates a bad SCR 10. Reconnect the engine starting battery, negative (--)
module, replace the module. lead last.

11. Reconnect power to the battery charger, if


4.10 Controller Replacement equipped.

If the troubleshooting procedures in Section 3 identify a 12. Follow the instructions in Section 4.11 to change
bad controller, use the procedure in this section for the new controller’s configuration settings to match
controller replacement. Always check the controller the generator set system voltage and frequency,
configuration, fuse, wiring, and connections before unit configuration, engine type, engine data input
replacing the controller. For output voltage problems, types, battery voltage, and communications
replace the SCR module and check the operation again settings.
before replacing the controller.
13. Use a voltmeter to check the output voltage. Follow
After replacing the controller, verify that the new the instructions in Section 5.7.2, Voltage
controller’s configuration settings match the generator Adjustment, to adjust the output voltage and
stability.
set system voltage and frequency, unit configuration,
engine type, engine data input types, battery voltage, 14. Place the generator set master switch in the AUTO
and communications settings. Refer to Section 4.11 for position if an ATS or remote start/stop switch is
instructions to check the controller configuration and to used.
change the settings, if necessary.

After the controller configuration has been checked and


set to match the generator set, use a voltmeter to check
the generator set output voltage. If the output voltage 1
needs adjustment, use the Voltage Adjustment
Procedure in Section 5.7.2 and the controller voltage
adjustment instructions in Section 4.11.

ADC 2100 Controller Replacement Procedure


1. Place the generator set master switch in the OFF
position.

2. Disconnect power to the battery charger, if


equipped.

3. Disconnect the generator set engine starting


battery, negative (--) lead first.

4. Remove four mounting screws from the front of the


controller.

5. Carefully pull the controller forward, angling it so


that the P1 connector on the right side clears the
opening in the mounting plate.
tp6196
3 2
6. Disconnect plugs P1, P15, and P16 from the ADC 1. Engine wiring harness connector plug (P1)
2. J15 connector
controller. See Figure 4-14. 3. J16 connector

Figure 4-14 Controller Connections

TP-6391 9/08 Section 4 Controller 37


4.11 Controller Configuration and controller to adjust the output voltage while the
generator set is running. The flowcharts in Figure 4-16
Adjustment and Figure 4-17 outline the adjustment procedures.
This section contains instructions for using the
controller’s password-protected menus to check and Note: Be sure to save your settings before exiting the
adjust the generator output and controller configuration. configuration mode.
The controller configuration and generator set output
Voltage changes are lost if they are not saved before the
are factory-set and should not require field adjustment
generator set shuts down. The generator set continues
under normal circumstances. Check and adjust the
to run with the new settings until it shuts down but then
configuration and/or output in the following cases:
reverts to the previous settings at the next startup if the
D Check and adjust the controller configuration and
changes have not been saved.
generator output after generator set reconnection to a
Pressing the Select button when SAVE is displayed
different voltage.
returns to the first parameter, voltage adjust (1P).
D Check the controller configuration when
troubleshooting generator set problems. Note: Refer to the flowcharts in Figure 4-16 and
Figure 4-17 during the voltage adjustment
D Check and adjust the generator set output after procedure.
installation if the voltage requires adjustment for a
particular application. Voltage Adjustment Procedure

1. With the generator set off, connect a digital


4.11.1 Voltage Adjustments multimeter to the output leads or an electrical outlet
on the load side of the generator set. Set the meter
WARNING to measure AC voltage.

2. Start the generator set by moving the generator set


master switch to the RUN position.

3. Use the ADC controller to adjust the voltage


Hazardous voltage. Moving parts. (parameter 1P) until the output voltage reaches the
Can cause severe injury or death.
desired value. See Figure 4-15 for the
Operate the generator set only when approximate change in voltage per step in
all guards and electrical enclosures parameter 1P.
are in place.
Measured Voltage Change per Step, VAC
Short circuits. Hazardous voltage/current can cause Voltage,
V l VAC
severe injury or death. Short circuits can cause bodily injury Coarse Adjust Fine Adjust
and/or equipment damage. Do not contact electrical 85--132 5 0.5
connections with tools or jewelry while making adjustments or
180--251 7 0.7
repairs. Remove all jewelry before servicing the equipment.
Figure 4-15 Voltage Adjustment (approximate)
The controller’s adjustment mode allows adjustment of
the output voltage, if necessary. Have adjustments 4. Adjust the voltage stability (gain, parameter 2P) to
performed by an authorized distributor/dealer or service minimize light flicker.
technician.
5. Readjust the voltage, if necessary.
Note: A digital voltmeter is required for these
adjustments. 6. Save the settings.

Use a voltmeter to check the output voltage. If the output 7. Stop the generator set.
voltage is not within specifications, use the ADC

38 Section 4 Controller TP-6391 9/08


Output Voltage Adjustment Mode: Display :*
Move the generator set master switch to the RUN position. The generator set x x x x
engine starts and the controller display shows the engine runtime hours.
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
x. x x
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller “password.”)
1 P x x

The controller is now in the voltage coarse adjustment mode.

Press:

or
To raise or lower the voltage in large increments 1 P x x
(approximately 5--7 volts per step).

To enter fine voltage adjustment mode.


1 P x x
To raise or lower the voltage in smaller increments
or
(approximately 0.5--0.7 volts per step).

To enter coarse voltage stability (gain) adjustment mode.


2 P x x
To raise or lower the voltage stability (gain) in large
or increments.

To enter fine voltage stability (gain) adjustment mode.


2 P x x
or To raise or lower the voltage stability (gain) in smaller
increments.

To enter volts/Hz adjustment mode.


3 P 0 x
or To raise or lower the volts/Hz: 00=low; 09= high

Continued on Figure 4-17.


* Shaded boxes show which character in the controller display changes for each adjustment. “x” in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model. TP6196

Figure 4-16 Output Voltage Adjustments

TP-6391 9/08 Section 4 Controller 39


Continued from Figure 4-16: Display : *

To enter SAVE mode. S AV E

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.

There are 3 options when the display says SAVE: S AV E


Press:
To return to the first parameter, coarse voltage adjustment, to check 1 P x x
or change settings before saving. See Figure 4-16.
or

To save changes. Y E S
or
To discard changes without saving. n o

“Yes”or “no” flashes when the up or down arrow is pressed and then the
controller exits the configuration mode. The display returns to the x x x x
runtime hours.

Now move the master switch to OFF/RESET.

* “x” in the examples above denotes any number from 0 to 9. The actual values may vary from
model-to-model.

Figure 4-17 Output Voltage Adjustments, Continued

40 Section 4 Controller TP-6391 9/08


4.11.2 Controller Configuration Engine configuration (Ec). The engine configuration
must match the generator set engine type. The engine
The controller configuration for each generator model is configuration setting for the 5/7.3ECD and 4/6EFCD is
set at the factory and should not normally require Ec04.
changes. The controller’s configuration mode allows
adjustment of the system parameters listed in this Advanced configuration mode (Adnc). The data
section. Use the instructions in this section to check the input types, battery voltage, and communications
configuration after installation and change them to setting can be changed in the advanced configuration
match the settings shown in Figure 4-18, if necessary. mode. Press the up arrow button when Adnc is
displayed to enter the advanced configuration mode.
The controller will automatically exit the configuration
mode without saving any changes after about 1 minute Engine data input types (Ed). This setting defines the
if no buttons are pressed. Start the configuration type of senders used on the generator set engine. Use
procedure over again from the beginning if the controller Ed00 for the 5/7.3ECD and 4/6EFCD.
exits the configuration mode before the settings have
been saved. The remote digital gauge requires the optional analog oil
pressure sender. Install the optional sender and change
Follow the instructions in Figure 4-21 to enter the the Ed parameter to Ed02.
configuration mode while the engine is not running and
then step through the following parameters. Use the up Battery voltage (Bt). This setting toggles between 12
(∧) and down (∨) arrow buttons to select the appropriate and 24 VDC for the engine starting battery voltage. The
setting for the application. 5/7.3ECD and 4/6EFCD uses a 12-volt battery, Bt12.

Voltage/frequency setting (Uu). Select the system Communications setting (Cn). This setting allows the
voltage and frequency from the table in Figure 4-18. For user to set the controller for communication with
system voltages not listed in the table, select the setting optional meters. The 5/7.3ECD and 4/6EFCD is
closest to the system voltage and then adjust the output factory-set for CAN communications, Cn02.
voltage to the desired level using the instructions in
Section 4.11.1. Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
Note: This parameter sets the nominal system voltage last saved settings when the master switch is
and frequency. To adjust the output (measured) moved to the OFF/RESET position.
voltage, see Section 4.11.

Unit configuration (Uc). This parameter sets the


generator set type: marine, standby, or mobile. The
setting for the 5/7.3ECD and 4/6EFCD is Uc00, marine.

TP-6391 9/08 Section 4 Controller 41


Volts, Engine Data Battery CANbus
Hz Market Type Inputs CO Voltage Comm.
Marine Gasoline Freq.
Freq
Model Hz Voltage, Phases Uu* Uc Ec Ed[ CO Bt Cn]
230 V, 1 Ph, 2 W 2
4EFCD 50 115/230 V, 1 Ph, 3 W 6
115 V, 1 Ph, 2 W 5
120/240 V, 1 Ph, 3 W 1
5ECD 60 120 V, 1 Ph, 3 W 0
ECD 120 V, 1 Ph, 2 W 0
0 4 0 1 12 2 or 8]
EFCD 230 V, 1 Ph, 2 W 2
6EFCD 50 115/230 V, 1 Ph, 3 W 6
115 V, 1 Ph, 2 W 5
120/240 V, 1 Ph, 3 W 1
7.3ECD 60 120 V, 1 Ph, 3 W 0
120 V, 1 Ph, 2 W 0
* Use voltage/frequency parameters Uu07--Uu23 only with ADC application program version 1.20 or higher.
[ See Figure 4-19 for Ed settings with optional sender kits.
] See Figure 4-20 for Cn settings with optional digital gauges (gauges are available on selected models only).
Note: Replacement controllers from Kohler Aftermarket Parts are shipped with factory settings for the 8.5/12RES.
Note: Setting the Ec parameter automatically selects the Ed parameter for the standard data inputs for that engine.
If you change Ec, check the Ed setting.

Figure 4-18 Configuration Parameters

Model Sender Kit Ed


5/7.3ECD None 0
4/6EFCD GM45891-KA1 * No Change
* OP and WT sender kits

Figure 4-19 Ed Settings with Optional Sender Kits

Power Down
Time (when
Cn master switch in
Gauge Kit Gauge Description Setting AUTO position) Description
None — Cn00 48 hours No CAN communication (not for use with these models)
GM32337-KP1 Remote Digital Gauge for Cn01 Never/None 3-inch J1939 gauge with no sleep mode
Marine CAN communication (not for use with these models)
GM46035-KP1 Three-Inch Digital
g Gauge
g Cn02 48 hours Smartcraftt 3-inch gauge for generator set #1 with ECM [
Cn03 48 hours Smartcraftt 3-inch gauge for generator set #2 with ECM [
Cn04 48 hours Smartcraftt 3-inch gauge for generator set #3 with ECM [
Cn05 48 hours Smartcraftt 3-inch gauge for generator set #4 with ECM [
Cn07 48 hours Smartcraftt 3-inch gauge for generator set #1 without ECM [
(not for use with these models)
GM50822-KP1 Two-Inch Digital
g Gauge
g Cn08 1 hour w Smartcraftt 2-inch gauge for generator set #1 with ECM ]
Cn09 1 hour w Smartcraftt 2-inch gauge for generator set #1 without ECM ]
(not for use with these models)
* For ADCs with removable power mode jumpers, refer to TT-1439 for power down information.
[ Smartcraftt settings for ADC code version 2.00 or higher only, for models 5/7.3ECD and 4/6EFCD.
] Smartcraftt settings for ADC code version 2.20 or higher only.
w Before ADC code version 3.20, the power-down time was 48 hours.
SmartCraftt is a trademark of Mercury Marine, a division of Brunswick Corporation.

Figure 4-20 Communication Parameter Cn Settings (optional gauges are available on selected models only)

42 Section 4 Controller TP-6391 9/08


Controller Configuration Mode:

Hold the Select button: Display:


Move the generator set master switch to the RUN . 0
position. (The generator set engine will not start.)

Wait about 5 seconds until the display shows the


program version number. (The number may be 1 0 4
different than the one shown here.)

Press the down arrow key and then the up arrow


key 3 times to enter the configuration mode.
(This is the controller “password.”)
Uu 0 x

Now release the Select button.


Press:

To set the voltage/frequency setting to Uu01. See Uu 0 x


or
Figure 4-18.

To step to the next parameter, unit configuration


Uc.

To set the unit configuration setting to Uc00, if


or
necessary.
Uc 0 0

To step to the next parameter, engine type Ec.

or To set the engine type to Ec04, if necessary.


E c 0 4
To step to the next parameter, advanced Ad n c
configuration mode or save mode selection.

Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.

Press:
To enter advanced configuration mode. E d 0 0
Go to Figure 4-22.
or
or To proceed to the save mode without
entering the advanced configuration mode. S AV E
Go to Figure 4-23.

Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. x

Figure 4-21 Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)

TP-6391 9/08 Section 4 Controller 43


Pressing the up arrow key at the Adnc display (See Figure 4-21) puts you
into the Advanced Configuration Mode.
Press:

or To set the engine data input type to Ed00. E d 0 0


See Figure 4-18.

To enter battery voltage selection mode.

or To toggle between 12 and 24 VDC. Set this B t 1 2


parameter to 12 VDC.

To enter communications selection mode.

To set the communications parameter to C n 0 0


or Cn00 or Cn01. See Figure 4-18.

To enter SAVE mode. Go to Figure 4-23.


S AV E

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts
to the last saved settings when the master switch is moved to the OFF/RESET position.

Figure 4-22 Advanced Configuration Mode (engine data input types, battery voltage, and engine
communications)

There are 3 options when the display says SAVE: S AV E


Press:
To return to the first parameter, system voltage/frequency
Uu, to check or change settings before saving. See Uu 0 1
Figure 4-21.
or

To save changes. Y E S
or
To discard changes without saving. n o

“Yes”or “no” flashes when the up or down arrow is pressed and then
the controller exits the configuration mode. The display returns to
the runtime hours.
x x x x

Now move the master switch to OFF/RESET.

* “x” in the runtime hours display above denotes any number from 0 to 9.

Figure 4-23 Save Mode (after configuring generator set parameters)

44 Section 4 Controller TP-6391 9/08


Section 5 Component Testing and Adjustment

5.1 Theory of Operation 1


Model 5/7.3ECD and 4/6EFCD generator sets utilize a 55
rotating-field alternator to produce AC voltage. Upon 66
ADC 2100
activation of the generator master switch, DC current 55 AC1 SCR 2
66 AC2
from the battery magnetizes the rotor (field). When the G1
G G2
magnetized rotor rotates within the stator windings, an F+ (+)
electrical voltage develops within the stator. As engine FP (--)
3
speed and generator output increase, the SCR module
FN
feeds rectified stator output current to the rotor through
the brushes/slip rings to increase the strength of the
FP
rotor field. As the rotor field increases in strength, 11
FN
generator output also increases. The ADC 2100 44 4 3 2 1 11
55 66
controller monitors the generator output voltage through 44
leads 11 and 44 and adjusts the DC current from the
SCR module to the rotor to meet load requirements. 8
7
See Figure 5-1. 4

6 5
5.2 Separate Excitation TP6198

To determine the cause of no or low AC output, refer to 1. Fuse 5. Slip rings


2. Power lead (55) 6. Main field (rotor)
the troubleshooting flow chart in Figure 5-2. Before 3. Excitation to rotor 7. Stator windings
beginning the test procedures, read all safety 4. Brushes 8. Sensing leads (11--44)
precautions at the beginning of this manual. Many of the
test procedures include additional safety precautions. Figure 5-1 Generator Schematic

Check the condition of the alternator fuse before


performing the separate excitation procedure. See No Generator Output
Figure 5-1. The fuse is located on the fuse panel. See
Figure 4-1 for the fuse panel location. If the fuse is not
blown, use the following procedure to separately excite Output within
Separate Excitation Specifications
the generator using an external voltage source (a
12-volt automotive battery).

Separately exciting the generator can identify faulty Check Wiring, Fuses,
voltage regulation by the ADC controller or reveal a Erratic or No Output SCR Module and
Controller
running fault in the rotor and/or stator. An external
power source duplicates the role of the voltage regulator
and excites the generator field (rotor). A generator Check Rotor Check Stator
component that appears to be in good condition while
stationary may exhibit a running open or short circuit TP563273

while moving. Centrifugal forces acting on the windings Figure 5-2 Generator Troubleshooting
during rotation cause a broken circuit to open, or
increasing temperatures cause the insulation to break
down, resulting in a running fault.

TP-6391 9/08 Section 5 Component Testing and Adjustment 45


Grounding electrical equipment. Hazardous voltage can Main Field (Rotor), to test the rotor. If the ammeter
cause severe injury or death. Electrocution is possible reading is stable, proceed to step 4.
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the 4. Check for AC output across the stator leads; see
generator set, transfer switch, and related equipment and Section 5.3, Stator. Compare the readings to the
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
AC output values shown in Section 1,
electrical leads or appliances when standing in water or on wet Specifications. If the readings vary considerably, a
ground because these conditions increase the risk of faulty stator is likely. Refer to Section 5.3, Stator,
electrocution. for further information.
Short circuits. Hazardous voltage/current can cause 5. If this test shows that the rotor and stator are in
severe injury or death. Short circuits can cause bodily injury
good condition, check the wiring and fuses. Check
and/or equipment damage. Do not contact electrical
connections with tools or jewelry while making adjustments or the SCR module. See Section 4.9, Silicon
repairs. Remove all jewelry before servicing the equipment. Controlled Rectifier (SCR) Module. Check the
controller settings and connections. See
Separate Excitation Procedure Section 4, Controller.

Perform the following procedure to use an external


voltage source to excite the main field (rotor).

1. Disconnect the black FN and FP leads from the


alternator at the SCR module (+) and (--) terminals. 1 2 3 4
5
2. Connect a DC ammeter, 10-amp fuse, and a
12-volt automotive battery to the positive (FP) and
FN
negative (FN) brush leads as shown in Figure 5-3. FP

Note and record the ammeter reading. - + 7 6


+ -

Note: The approximate ammeter reading should


be the battery voltage divided by the
specified rotor resistance. See Section 1, 9 8
TP563274
Specifications, for specified rotor resistance
values.
1. SCR module
Example: 2. FN lead disconnected from SCR
3. FP lead disconnected from SCR
12 volts (battery voltage) 3.5 amps 4. 10-amp fuse
=
3.4 ohms (rotor resistance) (rotor current) 5. DC ammeter
6. 12V battery
3. Start the engine and check that the ammeter 7. Brushes
8. Slip rings
reading remains stable. An increasing meter 9. Main field (rotor)
reading indicates a shorted rotor. A meter reading
decreasing to zero or an unstable reading Figure 5-3 Separate Excitation Connections
suggests a running open. Refer to Section 5.4,

46 Section 5 Component Testing and Adjustment TP-6391 9/08


5.3 Stator Note: For single-phase models, leads 1--4 are the
generator output leads. Leads 11, 44, 55,
The stator contains a series of coils of wire laid in a and 66 are the controller and SCR module
laminated steel frame. The stator leads supply AC sensing and supply leads. Refer to the
voltage to the load and voltage regulator. Before testing schematic in Figure 5-5 when performing
the stator, inspect it for heat discoloration and visible the following steps.
damage to housing lead wires, exposed coil windings,
and exposed areas of frame laminations. Be sure the Note: When taking an ohmmeter reading using
stator is securely fastened to the stator housing. lead 55, make the connection before the
in-line fuse.
Note: Disconnect all stator leads before performing all
6. Contact the ohmmeter leads and readjust the
stator tests.
ohmmeter to read zero ohms.

WARNING 7. Check the cold resistance of the stator windings by


connecting the meter leads to the stator leads. See
Section 1.4, Alternator Specifications, for stator
winding resistances.

Hazardous voltage. Moving parts.


Note: Most ohmmeters do not provide accurate
Can cause severe injury or death. readings below 1 ohm. Low resistance
readings (continuity) and no evidence of
Operate the generator set only when shorted windings (heat discoloration)
all guards and electrical enclosures indicate a stator in good condition. See
are in place.
Figure 5-6.

High voltage test. Hazardous voltage can cause severe 8. If the resistance test proves inconclusive, use a
injury or death. Follow the instructions of the test equipment megohmmeter to test the stator as described in the
manufacturer when performing high-voltage tests on the rotor
next step.
or stator. An improper test procedure can damage equipment
or lead to generator set failure.
Note: Because ohmmeter accuracy varies,
Short circuits. Hazardous voltage/current can cause resistance readings are approximate
severe injury or death. Short circuits can cause bodily injury readings. Take readings of the rotor and
and/or equipment damage. Do not contact electrical stator at room temperature.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment. Note: Make sure that all stator leads are
disconnected before running the
Stator Continuity and Resistance Tests megohmmeter test.
1. Place the generator set master switch in the OFF
position.

2. Disconnect power to the battery charger, if


equipped.

3. Disconnect the generator set engine starting


battery, negative (--) lead first.

4. Disconnect all stator leads before performing all


stator tests.

5. To check for stator continuity, set the ohmmeter on R14807-14


R x 1 scale. First set the ohmmeter zero by holding
the red and black meter leads together and setting Figure 5-4 Testing Stator Windings
the ohmmeter reading to zero. Then check the
stator continuity by connecting the meter leads to
the stator leads as shown in Figure 5-4.

TP-6391 9/08 Section 5 Component Testing and Adjustment 47


9. Use a megohmmeter to determine whether the 5.4 Main Field (Rotor)
stator is shorted to ground.
The two-pole rotor creates the magnetic field needed to
a. Apply 500 volts DC to any stator lead and the produce alternating current in the stator windings.
stator frame. Perform the megohmmeter test Before testing, inspect the rotor for visible damage to
following the instructions of the megohmmeter pole shoes, insulation, exposed coil windings, and slip
manufacturer. ring surfaces. Rotate the bearing to check for wear, heat
discoloration, or noise.
b. Repeat the test on the other stator leads until
each coil is tested.
5.4.1 Rotor Continuity and Resistance
Note: A reading of approximately 500 kOhms
Tests
(1/2 megohm) and higher indicates a
good stator.
WARNING
c. Repair or replace the stator if any reading is
less than approximately 500 kOhms. A reading
of less than 500 kOhms indicates deterioration
of the winding insulation and possible current
flow to ground. Hazardous voltage. Moving parts.
Can cause severe injury or death.

4 44 Operate the generator set only when


all guards and electrical enclosures
3 are in place.

66 High voltage test. Hazardous voltage can cause severe


injury or death. Follow the instructions of the test equipment
55 manufacturer when performing high-voltage tests on the rotor
or stator. An improper test procedure can damage equipment
2
or lead to generator set failure.
Grounding electrical equipment. Hazardous voltage can
1 11 cause severe injury or death. Electrocution is possible
6198 whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
Figure 5-5 Single-Phase Alternator Stator Leads generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
Leads Continuity power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
1 and 2
ground because these conditions increase the risk of
1 and 11 electrocution.
2 and 11
3 and 4 Yes Rotor Test Procedure
3 and 44
1. Place the generator set master switch in the OFF
4 and 44
position.
55 and 66
1 and 3, 4, 44, 55, or 66 2. Disconnect power to the battery charger, if
2 and 3, 4, 44, 55, or 66 equipped.
3 and 1, 2, 11, 55, or 66
No 3. Disconnect the generator set engine starting
4 and 1, 2, 11, 55, or 66
battery, negative (--) lead first.
Any stator lead and ground on stator
housing or frame laminations
4. Remove the brush cover from the alternator end
Figure 5-6 Continuity Test Results on a Good Stator bracket.
(Single-Phase)

48 Section 5 Component Testing and Adjustment TP-6391 9/08


5. Check the rotor for continuity and resistance. 6. Perform a megohmmeter test to determine
Raise the brushes from the slip rings while whether the rotor is shorted to ground.
performing ohmmeter tests. Measure the rotor
resistance (ohms) between the two slip rings; see a. Raise and secure the brushes away from the
Figure 5-7. See Section 1.4, Alternator slip rings by inserting a retaining wire in the
Specifications, for rotor resistance readings. If the brush holder hole.
resistance readings are low, perform a
megohmmeter test on rotor as described in the b. Using a megohmmeter, apply 500 volts DC to
next step. one rotor slip ring and the rotor poles or shaft.
Follow the instructions of the megohmmeter
Note: Because ohmmeter accuracy varies, manufacturer when performing this test.
resistance readings are approximate. Take
readings at room temperature. Note: A reading of approximately 500 kOhms
(1/2 megohm) or higher indicates a
good rotor.

c. Repair or replace the rotor if the reading is less


than approximately 500 kOhms. A reading of
less than 500 kOhms indicates deterioration of
the winding insulation and possible current flow
to ground.

d. Following the test, remove the retainer wire


from the brush holder and check the brush
positions on the slip rings. See Section 5.6,
2-221 Brushes.
R13929-7

Figure 5-7 Rotor Resistance Check e. Reinstall the brush cover on the end bracket.

TP-6391 9/08 Section 5 Component Testing and Adjustment 49


5.5 Slip Rings
Slip rings acquire a glossy brown finish in normal
operation. Do not attempt to maintain a bright,
newly-machined appearance on the slip rings. Cleaning
with a dry, lint-free cloth is usually sufficient. Use very
fine sandpaper (#00) and apply light pressure to remove
roughness. Do not use emery or carborundum paper or
cloth. Clean all carbon dust from the generator after
sanding the slip rings. If the rings are black or pitted,
remove the rotor and use a lathe to remove some of the Alternator End View
1
slip ring surface material.

5.6 Brushes
2
The brushes transfer current from the SCR module to
the slip rings. The brushes should last the life of the
generator. Abrasive dust on the slip rings, however,
shortens the life of the brushes. Excessive arcing at the
brushes could damage the SCR module and the
controller. Weak springs, damaged slip rings, sticking
brushes, a loose brush holder, or poor brush contact Front View
causes arcing. GM39685A-J

4
The brushes must be free to move within the holder and
be held in contact with the slip rings by the springs.
When correctly positioned, spring pressure on the brush
surface causes the brush to wear evenly. The entire
brush must ride on the ring or arcing occurs and causes
burned rings or voltage regulator failure. Figure 5-8 7 5
Side View
shows the correct positioning of the brushes. Add or 6
remove shims as necessary to center the brushes on 8 9
the slip rings. Replace the brushes if they show uneven 3
wear or are worn to one half their original length. New 1.9 cm (0.75 in.)

Check the resistance through the brushes. Resistance 2 2


through the brushes should be low, 0.1--0.2 ohms
without meter lead resistance. 3
TP5867
1. Brush holder 7. Brush holder
2. Slip ring 8. Correctly positioned
3. Brush brush
4. Retainer wire 9. Incorrectly positioned
5. Shim brush
6. Spring

Figure 5-8 Brush Assembly

50 Section 5 Component Testing and Adjustment TP-6391 9/08


5.7 Voltage WARNING

5.7.1 Voltage Regulation


Voltage regulation is performed by the Advanced Digital
Control (ADC) and the SCR module. The ADC monitors Hazardous voltage. Moving parts.
generator output voltage and adjusts the excitation Can cause severe injury or death.
current to the rotor through the SCR module.
Operate the generator set only when
all guards and electrical enclosures
5.7.2 Voltage Adjustment are in place.

The factory sets the voltage for correct generator Short circuits. Hazardous voltage/current can cause
operation under a variety of load conditions. Usually, the severe injury or death. Short circuits can cause bodily injury
voltage needs no further adjustment. Adjust the voltage and/or equipment damage. Do not contact electrical
when necessary according to the following procedure. connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
The adjustment procedure requires a meter that can Grounding electrical equipment. Hazardous voltage can
measure voltage and frequency. cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
Use the ADC controller to adjust the voltage, gain, and applicable codes and standards. Electrically ground the
volts/Hz. Refer to Section 4.11.2 for instructions to generator set, transfer switch, and related equipment and
adjust each parameter and save the changes using the electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
controller keypad. electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
Note: The ADC controller will time out and exit the electrocution.
adjustment mode after approximately 1 minute if
no buttons are pressed. Any unsaved changes
Voltage Adjustment Procedure
are discarded if the controller times out before the
settings are saved. Refer to Section 4.11.2 for 1. Connect a digital voltmeter from one side of the
instructions to save your settings. circuit breaker to the LO terminal on the end
bracket casting. See Figure 5-9. Set the meter to
Voltage Adjustment. Adjusts generator output measure voltage.
between 100 and 130 volts.
Note: For 120- or 240-volt systems the voltage
Gain (Stability) Adjustment. Fine tunes regulator measured from one side of the breaker to
circuitry to reduce light flicker. LO should be approximately 120 VAC. For
240-volt systems, the voltage measured
Volts/Hz Adjustment. Determines frequency (Hz) at from one side of the circuit breaker to the
which generator output voltage begins to drop. other should be approximately 240 VAC.
The controller maintains generator output at the 2. Start the generator set.
specified voltage under load until the generator engine
speed drops to a preset level (factory setting 57.5 Hz on 3. Follow the controller instructions in Section 4.11.2
60 Hz models and 47.5 Hz on 50 Hz models). Then the to enter the adjustment mode and increase voltage
controller allows the generator voltage and current to or decrease voltage (parameter 1P) until the output
drop. The voltage/current drop enables the engine to reaches the desired voltage.
pick up the load. When the generator speed returns to
normal (60 Hz or 50 Hz) as load is accepted, the
generator output also returns to normal.

TP-6391 9/08 Section 5 Component Testing and Adjustment 51


4. Follow the controller instructions to step to the 5.10 Fault Shutdown Tests
voltage gain adjustment menu. Adjust the voltage
gain (parameter 2P) until the light flicker minimizes. Verify the operation of the generator set overspeed,
Save the settings. overcrank, and low oil pressure shutdowns by
performing the following tests. If these tests are
5. Check and readjust the voltage if necessary. inconclusive, test individual shutdown circuit
components (wiring harness, switch, etc.) as described
6. Save the settings.
elsewhere in this section.
Note: The controller will revert to the previous
settings at the next startup if the changes WARNING
are not saved.

7. Stop the generator set.

Top View Hazardous voltage. Moving parts.


Can cause severe injury or death.

1 Operate the generator set only when


all guards and electrical enclosures
2
are in place.

Servicing the generator set when it is operating. Exposed


moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
3 and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
4 GM39685D-J Short circuits. Hazardous voltage/current can cause
1. Load connection terminal LO severe injury or death. Short circuits can cause bodily injury
2. Ground connection terminal GRD and/or equipment damage. Do not contact electrical
3. Controller location
connections with tools or jewelry while making adjustments or
4. Line circuit breaker
repairs. Remove all jewelry before servicing the equipment.
Figure 5-9 Circuit Breaker, LO, and GRD Terminal
Locations 5.10.1 Controller Fault Shutdown
Functions
5.8 Voltage Reconnection Check the operation of the fault functions programmed
Voltage Reconnection is covered in the generator set in the ADC 2100 by performing the following tests. If the
Installation Manual. See the List of Related Materials for ADC 2100 does not operate as described, check the
the document number. controller configuration settings; see Section 4.11. Also
check the controller wiring and connections.

5.9 Governor System


The frequency of the alternator output is determined by
the speed of the engine. A two-pole alternator must be
driven at 3600 RPM to provide 60 Hertz and 3000 RPM
to provide 50 Hertz. The engine speed is maintained by
the Engine Control Module (ECM). See the engine
documentation for ECM information.

52 Section 5 Component Testing and Adjustment TP-6391 9/08


Overcrank Shutdown Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
Disconnect the starter motor lead at the starter solenoid. and/or equipment damage. Do not contact electrical
Move the controller master switch to the RUN position. connections with tools or jewelry while making adjustments or
Observe that the generator set simulates cranking for repairs. Remove all jewelry before servicing the equipment.
7 seconds and then rests for 15 seconds. Check that the
generator set shuts down after the third crank/rest cycle. Temperature Sensor (CTS)
The coolant temperature sensor (CTS) is used to
High Engine Temperature Shutdown monitor engine temperature for the high engine
temperature fault shutdown (HE). See Figure 5-11 for
Remove the connector from the coolant temperature
the coolant temperature sensor location. Set the
sensor (CTS). Attempt to start the generator set by
generator set master switch to the OFF position and
moving the master switch to the RUN position. The unit
allow the generator set to cool. Disconnect the CTS and
should not start and the ADC control should display fault
use an ohmmeter to measure the resistance across the
code EC58. Move the master switch to the OFF position.
sensor. The sensor resistance varies with temperature
Connect a jumper wire across terminals A and B of the and should be within the values shown in Figure 5-10. If
connector, shorting the wires. Attempt to start the the resistance is very low (indicating a short circuit) or
generator set by moving the master switch to the RUN very high (indicating an open circuit) replace the CTS.
position. The unit should start and run but the ADC
Temperature, _C Sensor Resistance, Signal
control should display warning code EC59. Move the
(_F) Ohms Voltage
master switch to the OFF position.
100 (212) 177 0.75
90 (194) 241 0.97
If available, insert a resistor (100--120 Ohm) into the
80 (176) 332 1.25
CTS connector. Attempt to start the generator set by
70 (158) 467 1.59
moving the master switch to the RUN position. Shortly
60 (140) 667 2.00
after ignition, the unit should shut down and the ADC
50 (122) 973 2.47
control should display fault code HE. Move the master
40 (104) 1459 2.97
switch to the OFF position.
30 (86) 2238 3.46
Replace the CTS connector onto the coolant 20 (68) 3520 3.89
temperature sensor. 10 (50) 5670 4.25
--40 (--40) 100700 4.95

5.10.2 Fault Shutdown Switches Figure 5-10 Coolant Temperature Sensor Resistance
Readings
Check the low oil pressure and high engine temperature
shutdown switches on the engine by performing the 1
following tests. If the sensor does not function as
described, replace it.

WARNING

Hazardous voltage. Moving parts.


Can cause severe injury or death.
GM39685D-J
Operate the generator set only when 1. Coolant temperature sensor (CTS)
all guards and electrical enclosures
are in place. Figure 5-11 Coolant Temperature Sensor (CTS)

Servicing the generator set when it is operating. Exposed


moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.

TP-6391 9/08 Section 5 Component Testing and Adjustment 53


Seawater Pressure Switch
See Figure 5-12. Remove the seawater pressure 2
switch and install a pressure gauge to verify that the
1
seawater pressure is within the range specified before
testing or replacing the seawater pressure switch. To
test the seawater pressure switch, reinstall the switch
and start the generator set. If the unit shuts down, 3
disconnect lead 87 from the seawater pressure switch
and reset the controller. Restart the generator set and
verify that it does not shut down. A successful restart
indicates a bad seawater pressure switch. Replace the
switch.

The calibration pressure of the seawater pressure


switch is 0.5 psi ¦ 0.3. 1. TMAP Sensor GM39685D-J

2. Manifold elbow
3. Intake manifold assembly
1
Figure 5-13 TMAP Sensor Location

Thermal Characteristics
Nominal
Sensor Sensor
Temperature, Resistance, Temperature, Resistance,
_C (_F) Ohms _C (_F) Ohms
130 (266) ¦ 1 85.45 45 (113) ¦ 1 1008.6
125 (257) ¦ 1 96.68 40 (104) ¦ 1 1199.6
120 (248) ¦ 1 109.65 35 (95) ¦ 1 1431.8
115 (239) ¦ 1 124.66 30 (86) ¦ 1 1715.4
110 (230) ¦ 1 142.08 25 (77) ¦ 1 2062.9
105 (221) ¦ 1 162.35 20 (68) ¦ 1 2510.6
100 (212) ¦ 1 186.00 15 (59) ¦ 1 3074.9
GM39685C-J
95 (203) ¦ 1 213.68 10 (50) ¦ 1 3791.1
1. Seawater pressure switch
90 (194) ¦ 1 246.15 5 (41) ¦ 1 4706.9
85 (185) ¦ 1 284.06 0 (32) ¦ 1 5886.7
Figure 5-12 Seawater Pressure Switch Location
80 (176) ¦ 1 329.48 --5 (23) ¦ 1 7419.0
75 (167) ¦ 1 382.89 --10 (14) ¦ 1 9426.0
TMAP Sensor 70 (158) ¦ 1 466.33 --15 (5) ¦ 1 12078
The TMAP sensor monitors intake manifold 65 (149) ¦ 1 521.91 --20 (--4) ¦ 1 15614
temperature and pressure. This allows the ECM full 60 (140) ¦ 1 612.27 --25 (--13) ¦ 1 20376
control to monitor actual airflow compared to desired 55 (131) ¦ 1 720.65 --30 (--22) ¦ 1 26855
airflow. The TMAP sensor incorporates both intake 50 (122) ¦ 1 851.10 --35 (--31) ¦ 1 35763
manifold temperature and pressure measurements in Figure 5-14 TMAP Sensor Resistance Readings
one, single unit. See Figure 5-13 for the TMAP sensor
location. TMAP Sensor Pin Resistance Check
TMAP Pin 1 (GND) to Pin 4 2.4 -- 8.2 kOhms
To test the TMAP sensor, set the generator set master (PRESSURE SIGNAL KPA)
switch to the OFF position and allow the generator set to TMAP Pin 3 (PWR) to Pin 4 3.4 -- 8.2 kOhms
cool. Disconnect the TMAP sensor and use an (PRESSURE SIGNAL KPA)
ohmmeter to measure the resistance across the sensor. TMAP Pin 1 (GND) to Pin 2 See Figure 5-14
The sensor resistance varies with temperature and (TEMPERATURE SIGNAL)
should be within the values shown in Figure 5-15. If the
Figure 5-15 TMAP Sensor Resistance
resistance is very low (indicating a short circuit) or very
high (indicating an open circuit) replace the TMAP
Max. Ratings of TMAP Sensor
sensor.
Supply voltage 16 volts
Pressure 500 kPa

54 Section 5 Component Testing and Adjustment TP-6391 9/08


Crankshaft Position Sensor 1

The crankshaft position sensor monitors speed control,


timing (firing of spark plugs), and fuel injection. See
Figure 5-16 for the crankshaft position sensor location.
The crankshaft position sensor is an electromagnetic
device which contains a permanent magnet surrounded
by a winding. The sensor is used with the timing wheel.
The timing wheel has 30 gear teeth with 5 teeth removed
at precise locations allowing the ECM a very accurate
speed reference signal. The timing wheel rotation near
the sensor’s tip changes the magnetic flux, creating an
analog voltage signal in the sensor coil.
GM39685B-J
1. Crankshaft position sensor
The spark is sent to the appropriate cylinder via the rotor
arm and spark plug wires. The ECM uses the signal Figure 5-16 Crankshaft Position Sensor Location
from the crankshaft position sensor to determine the
Model Crankshaft Position Sensor Gap
engine position and RPM. This information, together
All 0.030--0.060 in.
with the TPS and TMAP sensor information is used to
calculate the correct ignition timing settings. Figure 5-17 Crankshaft Position Sensor Gap

To test the crankshaft position sensor, set the generator Crankshaft Position Sensor Pin Resistance (approx.)
set master switch to the OFF position and allow the Pin 1 (+) to Pin 2 (--) 320 Ohms
generator set to cool. Disconnect the crankshaft
position sensor and use an ohmmeter to measure the Figure 5-18 Crankshaft Position Sensor Resistance
resistance across the sensor pins. See Figure 5-18. Check

Ignition Coil
This system uses a single coil incorporating the ignition
driver circuitry inside the coil. See Figure 5-19. The
ECM signals the coil to begin its cycle. Then the coil
waits for the trigger signal from the ECM.

To test the ignition coil, set the generator set master


switch to the OFF position and allow the generator set to
cool. Disconnect the ignition coil and use an ohmmeter
to measure the resistance across the coil pins. See
Figure 5-20 for the coil resistance.

Figure 5-19 Ignition Coil

Ignition Coil Pin Resistance Check (approx.)


Pin A (SIGNAL) to Pin B 10 kOhms
Pin A (SIGNAL) to Pin D 34 kOhms
Pin A (SIGNAL) to Pin E (PWR) 15 kOhms
Pin B to Pin D 44 kOhms
Pin B to Pin E (PWR) 26 kOhms
Pin D to Pin E (PWR) 17 kOhms

Figure 5-20 Ignition Coil Resistance Check

TP-6391 9/08 Section 5 Component Testing and Adjustment 55


Heated Oxygen (O2) Sensor Detail A
2
The heated oxygen sensor is used to monitor O2 in the
exhaust. See Figure 5-22 for the heated oxygen sensor
location.

Note: The heated oxygen sensor is calibrated to work


with this system. Do not use alternate sensors.
See Detail A 1
The oxygen sensor operates like an electrolyte with its
Top View
platinum layers serving as electrodes. After the internal
element reaches approx. 600_ F, it becomes electrically
conductive and attracts negatively charged ions of
oxygen. These ions collect on the inner and outer
platinum surfaces.

A heated element is added to the sensor housing in


order for the sensor to conduct and create an electrical
signal below 600_ F. Two wires provide 12VDC and a
ground signal for the heater element. A fourth wire
provides an independent ground for the sensor. The 1. Heated oxygen sensor GM39685B-J
targeted air/fuel ratio signal is approx. 500mV and 2. Exhaust manifold
changes slightly based on speed and load conditions.
When the sensor sends a voltage signal less than Figure 5-22 Heated Oxygen Sensor Location
500mV, the ECM interprets the air/fuel mixture as lean
so the ECM decreases the duty cycle. If the ECM High Exhaust Temperature (HET) Switch
receives a voltage signal above 500mV, the air/fuel
Note: The high exhaust temperature switch is installed
mixture would be interpreted as too rich and the ECM
on units with serial numbers 2199434 and later.
would increase the duty cycle.
In the event of a shutdown because of the high exhaust
Set the generator set master switch to the OFF position
temperature switch, the ADC 2100 controller will display
and allow the generator set to cool. Disconnect the
fault code LOC. See Figure 5-23 for the high exhaust
heated oxygen sensor and use an ohmmeter to
temperature switch location.
measure the resistance across the sensor pins. See
Figure 5-21. High exhaust temperature of 215_±5_F (102_±2.8_C)
will cause the unit to shut down.
O2 Sensor Pin Resistance Check
Pin C (HEATER GND) to Top View
2.1 ¦ 0.4 Ohms
Pin D (HEATER PWR) 1
Figure 5-21 O2 Sensor Resistance

1. High exhaust temperature switch

Figure 5-23 High Exhaust Temperature (HET) Switch


Location

56 Section 5 Component Testing and Adjustment TP-6391 9/08


5.11 Electronic Throttle Assembly 5.12 Fuses
The electronic throttle body assembly (ETC) contains
See Figure 5-26 for fuse ratings and part numbers.
the throttle valve, throttle valve actuator, and throttle
position sensor (TPS1). The ECM calculates the correct Always identify and correct the cause of a blown fuse
throttle valve opening, makes any adjustments, and before restarting the generator set. Refer to Section 3,
then generates an electrical signal to the throttle-valve Troubleshooting, for conditions that may indicate a
actuator. The ECM calculates the correct throttle blown fuse. Replace blown fuses with identical
position based on RPM and MAP and compares this to replacement parts.
the actual throttle position based on TPS1. The ECM
continuously checks and monitors all sensors and Part
calculated data. If no redundant signal is available or the Label Fuse Amps Number
calculated data cannot solve the malfunction, the ECM F1 Auxiliary Winding 10 358337
shuts the engine down, storing the fault information in F2 Controller 10 223316
the ECM. F3 Customer Connection 10 223316
F4 Coils/Injectors 15 283645
F5 ECM, O2 Sensor, and Fuel 15 283645
Pumps
F6 Voltage Regulator and Battery 15 283645
Charging Alternator
F7 Starter Motor and Crank 20 GM39266
Solenoid

Figure 5-26 Fuses

F1 F2 F3

F6

F4
F7

F5
Figure 5-24 Electronic Throttle Body Assembly

Set the generator set master switch to the OFF position


and allow the generator set to cool. Disconnect the TPS
sensor and use an ohmmeter to measure the resistance
across the sensor pins. See Figure 5-25.
ADV7025A-A

TPS (Electronic Throttle) Sensor Figure 5-27 Fuse Location


Pin Resistance Check (approx.)
1.25 kOhms
Pin 2 (GND) to Pin 6 (TPS1 SIGNAL)
¦ 30%
1.25 kOhms
Pin 3 (PWR) to Pin 6 (TPS1 SIGNAL)
¦ 30%
3.0 Ohms
Pin 1 (+DRIVER) to Pin 4 (--DRIVER)
¦ 30%
Figure 5-25 TPS (Electronic Throttle) Sensor
Resistance

TP-6391 9/08 Section 5 Component Testing and Adjustment 57


5.13 Continuity Checks Figure 5-28 illustrates the generator set master switch
continuity with the switch in the RUN and AUTO
WARNING positions.

Zero ohms (continuity) across


RUN and COM terminals

Hazardous voltage. Moving parts. 3 2 1


Can cause severe injury or death. Master Switch
Operate the generator set only when in RUN Position
all guards and electrical enclosures

RUN

AUTO
are in place.

Short circuits. Hazardous voltage/current can cause


severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical Zero ohms (continuity) across
connections with tools or jewelry while making adjustments or COM and AUTO terminals
repairs. Remove all jewelry before servicing the equipment.
3 2 1
Note: Disconnect the generator set battery before Master Switch in
performing continuity checks to prevent damage AUTO Position
to the ohmmeter.

RUN

AUTO
To further check generator set components, disconnect
the battery and remove wiring harness plugs from the tp6196

controller circuit board. Refer to the wiring diagrams in Figure 5-28 Generator Set Master Switch Continuity
Section 7, and use an ohmmeter to check for continuity Checks (back view of switch)
and good ground connections. A zero reading on the
ohmmeter indicates continuity. No ohmmeter reading
indicates very high resistance or an open circuit.

58 Section 5 Component Testing and Adjustment TP-6391 9/08


Section 6 Generator Disassembly/Reassembly

6.1 Disassembly
Disconnect all of the external connections—battery
cables at the battery (negative (--) lead first), AC-output
leads, remote interface connector. Close the seacock.
Remove the water line at the seawater pump, fuel line at
the fuel pump filter inlet, and exhaust line at the catalyst 1
assembly. Remove the sound shield enclosure, if
equipped. Observe all of the safety precautions listed at
the beginning of this manual during the
disassembly/reassembly procedures.

Note: Because this manual covers several models, the


procedure for disassembly may vary because of
tp6196
product updates and the assembly variations. 1. Controller mounting screws (4 ea.)

Note: Mark leads that are disconnected. Refer to the


Figure 6-1 ADC 2100 Mounting Screws
wiring diagrams in Section 7 during reassembly.
6. Disconnect the generator output leads from the
1. Place the generator set master switch in the OFF
circuit breaker and disconnect QCON1 from the F1
position.
fuse.
2. Disconnect power to the battery charger, if
7. Disconnect the LO and GRD lead connections.
equipped.
See Figure 6-2.
3. Disconnect the generator set engine starting
8. Disconnect the FP and FN leads.
battery, negative (--) lead first.
9. Remove the SCR module and relay board as
WARNING necessary. See Figure 6-2.

Top View

1
Accidental starting.
Can cause severe injury or death. 2
3
Disconnect the battery cables before 4
working on the generator set. 5
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
1. LO stud GM39685D-J
2. Ground stud
4. Disconnect wiring harness plugs P1, P15, and P16 3. Relay interface board (RIB)
from the ADC 2100. 4. SCR module
5. K5 main power relay
5. Loosen and remove the four controller mounting
Figure 6-2 Advanced Digital Control (ADC 2100)
screws at the front of the controller. See
Figure 6-1. Remove the controller.

TP-6391 9/08 Section 6 Generator Disassembly/Reassembly 59


10. Remove the junction box from the support bracket.

11. Disconnect the ground strap.

12. Remove the fuel inlet hose

13. Close the seacock and remove the water inlet hose
from the seawater pump.

14. Remove the fuel pump and line from the generator.

15. Remove the alternator cover plate. See


Figure 6-3. 1
598691
16. Push the brushes into the holder. Secure the
1. Block of wood
brushes into position by sliding a retainer into the
brush keeping holder. See Section 5.6. Figure 6-4 Raising the Generator

17. Remove the brush holder and carefully pull the 21. Remove the overbolts. See Figure 6-6. Use a
leads out of the stator housing. See Figure 6-6. rubber mallet to separate the end bracket from the
stator housing.
18. Remove the generator end vibromount hardware.
See Figure 6-3. 22. Carefully remove the stator assembly from the
generator adapter plate.
1
23. Remove the rotor bolt and end drive fitting.

24. Reinstall the rotor bolt (without end fitting), finger


tighten, and back off two turns.

25. Strike the bolt with a hammer until the rotor is freed
from the engine’s tapered drive shaft. Do not
damage the through bolt threads or bolt head. See
Figure 6-5.

3 2
1. Alternator cover plate
2. Vibromount hardware
3. Seawater pump
2

Figure 6-3 Alternator End Cover

19. Attach a hoist hook to the generator lifting eye.


598692
1. Rotor bolt
Note: The hoist capacity rating should be one-half 2. Hammer
ton or greater.
Figure 6-5 Removing the Rotor
20. Tilt the generator set up and brace it with a block of
wood. See Figure 6-4.

60 Section 6 Generator Disassembly/Reassembly TP-6391 9/08


6 10 11
2 3, 4, 5
9
8 9
1 8

7
12

14 13

21 20 19 18 17 16 9 8 15 8 9
GM39685A-K

1. Generator adapter plate bolt, quantity 4 12. Bracket, brush holder


2. Generator adapter 13. Fan guard bolts, quantity 2
3. Spring 14. Fan guard
4. Brush holder 15. End bracket
5. Brush, quantity 2 16. Pipe plug
6. Brush holder shim 17. End drive fitting
7. Rotor bolt 18. End bracket bearing
8. Hardened washer 19. O-ring
9. Generator overbolt, quantity 4 20. Stator assembly
10. Retainer wire 21. Rotor assembly
11. Brush assembly mounting screws, quantity 2

Figure 6-6 Alternator Assembly Components

TP-6391 9/08 Section 6 Generator Disassembly/Reassembly 61


6.2 Collector Ring and Bearing .38 maximum
(as soldered)
Replacement
1. Unsolder the collector ring leads from the collector
A
ring terminals.

2. Remove the collector rings with a three-jaw puller.

3. Remove the bearing with a three-jaw puller. A

4. Press the new bearing onto the rotor shaft. 1

5. Align the collector ring keyway with the keyway on 90°


the rotor shaft. See Figure 6-8.

6. Press the new collector rings onto the rotor shaft.


2
Note: The new collector rings must be turned down to a
finish of 32 micro inches using a lathe and
commutator stones. Turn down the collector
598695
rings on the rotor shaft. View A-A
1. Collector ring leads
7. Solder the leads onto the collector ring terminals. 2. Keyways
The connection is not to exceed 9.65 mm (0.38 in.)
Figure 6-8 Rotor Assembly
beyond the collector rings. See Figure 6-8.

8. Test to ensure continuity at the collector rings.

Min. diameter mm (in.) 57.15 (2.250)


Max. finish 32 micro inches
Max. eccentricity mm (in.) 0.08 (0.003)
Max. out-of-round mm (in.) 0.01 (0.0002)

Figure 6-7 Collector Ring Dimensions

62 Section 6 Generator Disassembly/Reassembly TP-6391 9/08


6.3 Reassembly 11. Reinstall the support bracket to mount the junction
box. See Figure 4-1.
Note: See Section 1.6 and Appendix C for torque
specifications. 12. Install tie wraps to secure the wires as necessary.

1. Apply antiseize compound to the tapered shaft of 13. Reconnect the leads to the circuit breaker, QCON1
the engine. to the F1 fuse, FP and FN leads, neutral stud (LO),
and ground stud (GRD) as marked during
2. Align the rotor onto the engine shaft and secure disassembly. Refer to the wiring diagrams in
with the end drive fitting and rotor bolt. Torque the Section 7.
rotor to 23.1 Nm (204 in. lbs.).
Note: Check the generator set nameplate to verify
3. Carefully slide the stator assembly over the rotor. the original voltage configuration.

4. Replace the end bracket o-ring. See Figure 6-6. 14. Reinstall the ADC 2100.

5. Install the end bracket and torque the overbolts to 15. Reconnect the P1, P15, and P16 connectors.
13.6 Nm (120 in. lbs). Connect the ground strap using bolt, washer, and
lock washer (install the lock washer against the
6. Feed the brush leads inside the stator housing up ground strap).
through the opening. Secure the brush holder
using the original screws. 16. Reconnect all of the external connections—the
exhaust line to the catalyst assembly, the fuel line
7. Remove the brush retainer and check the brush to the fuel pump filter inlet, the water line to the
alignment. See Section 5.6. seawater pump, the remote interface connector,
the AC output leads, and the battery cables to the
8. Install the coverplate and torque the coverplate battery (negative (--) lead last).
bolts to 6.8 Nm (60 in. lbs.).
17. Verify that the generator set master switch is in the
9. Use the hoist to raise the alternator end. Remove OFF position.
the wood block from under the locator plate. Lower
the generator set and install a bolt, a large washer, 18. Reconnect the engine starting battery, negative (--)
two small washers, and a locknut on each lead last.
vibromount. Tighten the mounting bolts.
19. Reconnect power to the battery charger, if
10. Install the SCR module and relay board. equipped.

TP-6391 9/08 Section 6 Generator Disassembly/Reassembly 63


Notes

64 Section 6 Generator Disassembly/Reassembly TP-6391 9/08


Section 7 Wiring Diagrams

WARNING WARNING

Hazardous voltage. Moving parts.


Accidental starting. Can cause severe injury or death.
Can cause severe injury or death.
Operate the generator set only when
Disconnect the battery cables before all guards and electrical enclosures
working on the generator set. are in place.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last Grounding electrical equipment. Hazardous voltage can
when reconnecting the battery. cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
Disabling the generator set. Accidental starting can generator set, transfer switch, and related equipment and
cause severe injury or death. Before working on the electrical circuits. Turn off the main circuit breakers of all
generator set or connected equipment, disable the generator power sources before servicing the equipment. Never contact
set as follows: (1) Move the generator set master switch to the electrical leads or appliances when standing in water or on wet
OFF position. (2) Disconnect the power to the battery charger. ground because these conditions increase the risk of
(3) Remove the battery cables, negative (--) lead first. electrocution.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

Model Specification Number Point-to-Point Wiring Diagram Schematic Wiring Diagram


Before Serial Number 2085259:
5ECD GM39685-GA1
4EFCD GM39685-GA3 GM39836 revision F ADV-7029 revision F
7.3ECD GM39685-GA2 (Figure 7-1 and Figure 7-2) (Figure 7-3 and Figure 7-4)
6EFCD GM39685-GA4

Model Specification Number Point-to-Point Wiring Diagram Schematic Wiring Diagram


With Serial Number 2085259 to 2199434:
5ECD GM39685-GA1
4EFCD GM39685-GA3 GM39836 revision H ADV-7029 revision G
7.3ECD GM39685-GA2 (Figure 7-5 and Figure 7-6) (Figure 7-7 and Figure 7-8)
6EFCD GM39685-GA4

Model Specification Number Point-to-Point Wiring Diagram Schematic Wiring Diagram


5ECD GM39685-GA5
4EFCD GM39685-GA7 GM50546 ADV-7285
7.3ECD GM39685-GA6 (Figure 7-9 and Figure 7-10) (Figure 7-11 and Figure 7-12)
6EFCD GM39685-GA8

TP-6391 9/08 Section 7 Wiring Diagrams 65


GM39836A--F

Figure 7-1 Point-to-Point Wiring Diagram (Sheet 1 of 2). For Units With Serial Numbers before 2085259.

66 Section 7 Wiring Diagrams TP-6391 9/08


GM39836B--F

Figure 7-2 Point-to-Point Wiring Diagram (Sheet 2 of 2). For Units With Serial Numbers before 2085259.

TP-6391 9/08 Section 7 Wiring Diagrams 67


ADV7029A--F

Figure 7-3 Schematic Wiring Diagram (Sheet 1 of 2). For Units With Serial Numbers before 2085259.

68 Section 7 Wiring Diagrams TP-6391 9/08


ADV7029B--F

Figure 7-4 Schematic Wiring Diagram (Sheet 2 of 2). For Units With Serial Numbers before 2085259.

TP-6391 9/08 Section 7 Wiring Diagrams 69


GM39836A--H

Figure 7-5 Point-to-Point Wiring Diagram (Sheet 1 of 2). For Units With Serial Number 2085259 to 2199434.

70 Section 7 Wiring Diagrams TP-6391 9/08


GM39836B--H

Figure 7-6 Point-to-Point Wiring Diagram (Sheet 2 of 2). For Units With Serial Number 2085259 to 2199434.

TP-6391 9/08 Section 7 Wiring Diagrams 71


ADV7029A--G

Figure 7-7 Schematic Wiring Diagram (Sheet 1 of 2). For Units With Serial Number 2085259 to 2199434.

72 Section 7 Wiring Diagrams TP-6391 9/08


ADV7029B--G

Figure 7-8 Schematic Wiring Diagram (Sheet 2 of 2). For Units With Serial Number 2085259 to 2199434.

TP-6391 9/08 Section 7 Wiring Diagrams 73


GM50546A--B

Figure 7-9 Point-to-Point Wiring Diagram (Sheet 1 of 2).

74 Section 7 Wiring Diagrams TP-6391 9/08


GM50546B--B

Figure 7-10 Point-to-Point Wiring Diagram (Sheet 2 of 2).

TP-6391 9/08 Section 7 Wiring Diagrams 75


ADV7285A--B

Figure 7-11 Schematic Wiring Diagram (Sheet 1 of 2).

76 Section 7 Wiring Diagrams TP-6391 9/08


ADV7285B--B

Figure 7-12 Schematic Wiring Diagram (Sheet 2 of 2).

TP-6391 9/08 Section 7 Wiring Diagrams 77


Notes

78 Section 7 Wiring Diagrams TP-6391 9/08


Appendix A Abbreviations

The following list contains abbreviations that may appear in this publication.
A, amp ampere cfm cubic feet per minute exh. exhaust
ABDC after bottom dead center CG center of gravity ext. external
AC alternating current CID cubic inch displacement F Fahrenheit, female
A/D analog to digital CL centerline fglass. fiberglass
ADC analog to digital converter cm centimeter FHM flat head machine (screw)
adj. adjust, adjustment CMOS complementary metal oxide fl. oz. fluid ounce
ADV advertising dimensional substrate (semiconductor) flex. flexible
drawing cogen. cogeneration freq. frequency
AHWT anticipatory high water com communications (port) FS full scale
temperature coml commercial ft. foot, feet
AISI American Iron and Steel Coml/Rec Commercial/Recreational ft. lbs. foot pounds (torque)
Institute conn. connection
ALOP anticipatory low oil pressure ft./min. feet per minute
cont. continued g gram
alt. alternator CPVC chlorinated polyvinyl chloride
Al aluminum ga. gauge (meters, wire size)
crit. critical gal. gallon
ANSI American National Standards CRT cathode ray tube
Institute gen. generator
(formerly American Standards CSA Canadian Standards genset generator set
Association, ASA) Association GFI ground fault interrupter
AO anticipatory only CT current transformer
Cu copper GND, ground
API American Petroleum Institute
cu. in. cubic inch gov. governor
approx. approximate, approximately
cw. clockwise gph gallons per hour
AR as required, as requested
CWC city water-cooled gpm gallons per minute
AS as supplied, as stated, as
suggested cyl. cylinder gr. grade, gross
ASE American Society of Engineers D/A digital to analog GRD equipment ground
ASME American Society of DAC digital to analog converter gr. wt. gross weight
Mechanical Engineers dB decibel HxWxD height by width by depth
assy. assembly dBA decibel (A weighted) HC hex cap
ASTM American Society for Testing DC direct current HCHT high cylinder head temperature
Materials DCR direct current resistance HD heavy duty
ATDC after top dead center deg., ° degree HET high exhaust temperature,
ATS automatic transfer switch high engine temperature
dept. department
auto. automatic hex hexagon
dia. diameter
aux. auxiliary Hg mercury (element)
DI/EO dual inlet/end outlet
A/V audiovisual HH hex head
DIN Deutsches Institut fur Normung
avg. average e. V. HHC hex head cap
AVR automatic voltage regulator (also Deutsche Industrie HP horsepower
AWG American Wire Gauge Normenausschuss) hr. hour
AWM appliance wiring material DIP dual inline package HS heat shrink
bat. battery DPDT double-pole, double-throw hsg. housing
BBDC before bottom dead center DPST double-pole, single-throw HVAC heating, ventilation, and air
BC battery charger, battery DS disconnect switch conditioning
charging DVR digital voltage regulator HWT high water temperature
BCA battery charging alternator E, emer. emergency (power source) Hz hertz (cycles per second)
BCI Battery Council International EDI electronic data interchange IC integrated circuit
BDC before dead center EFR emergency frequency relay ID inside diameter, identification
BHP brake horsepower e.g. for example (exempli gratia) IEC International Electrotechnical
blk. black (paint color), block EG electronic governor Commission
(engine) EGSA Electrical Generating Systems IEEE Institute of Electrical and
blk. htr. block heater Association Electronics Engineers
BMEP brake mean effective pressure EIA Electronic Industries IMS improved motor starting
bps bits per second Association in. inch
br. brass EI/EO end inlet/end outlet in. H2O inches of water
BTDC before top dead center EMI electromagnetic interference in. Hg inches of mercury
Btu British thermal unit emiss. emission in. lbs. inch pounds
Btu/min. British thermal units per minute eng. engine Inc. incorporated
C Celsius, centigrade EPA Environmental Protection ind. industrial
Agency int. internal
cal. calorie
EPS emergency power system int./ext. internal/external
CARB California Air Resources Board
CB circuit breaker ER emergency relay I/O input/output
cc cubic centimeter ES engineering special, IP iron pipe
engineered special ISO International Organization for
CCA cold cranking amps ESD electrostatic discharge Standardization
ccw. counterclockwise est. estimated J joule
CEC Canadian Electrical Code E-Stop emergency stop JIS Japanese Industry Standard
cert. certificate, certification, certified etc. et cetera (and so forth)
cfh cubic feet per hour

TP-6391 9/08 Appendix 79


k kilo (1000) MTBF mean time between failure RHM round head machine (screw)
K kelvin MTBO mean time between overhauls rly. relay
kA kiloampere mtg. mounting rms root mean square
KB kilobyte (210 bytes) MW megawatt rnd. round
kg kilogram mW milliwatt ROM read only memory
kg/cm2 kilograms per square μF microfarad rot. rotate, rotating
centimeter N, norm. normal (power source) rpm revolutions per minute
kgm kilogram-meter NA not available, not applicable RS right side
kg/m3 kilograms per cubic meter nat. gas natural gas RTV room temperature vulcanization
kHz kilohertz NBS National Bureau of Standards SAE Society of Automotive
kJ kilojoule NC normally closed Engineers
km kilometer NEC National Electrical Code scfm standard cubic feet per minute
kOhm, kΩ kilo-ohm NEMA National Electrical SCR silicon controlled rectifier
kPa kilopascal Manufacturers Association s, sec. second
kph kilometers per hour NFPA National Fire Protection SI Systeme international d’unites,
kV kilovolt Association International System of Units
kVA kilovolt ampere Nm newton meter SI/EO side in/end out
kVAR kilovolt ampere reactive NO normally open sil. silencer
kW kilowatt no., nos. number, numbers SN serial number
kWh kilowatt-hour NPS National Pipe, Straight SPDT single--pole, double--throw
kWm kilowatt mechanical NPSC National Pipe, Straight-coupling SPST single--pole, single--throw
L liter NPT National Standard taper pipe spec, specs
LAN local area network thread per general use specification(s)
L x W x H length by width by height NPTF National Pipe, Taper-Fine sq. square
lb. pound, pounds NR not required, normal relay sq. cm square centimeter
lbm/ft3 pounds mass per cubic feet ns nanosecond sq. in. square inch
LCB line circuit breaker OC overcrank SS stainless steel
LCD liquid crystal display OD outside diameter std. standard
ld. shd. load shed OEM original equipment stl. steel
manufacturer tach. tachometer
LED light emitting diode OF overfrequency
Lph liters per hour TD time delay
opt. option, optional TDC top dead center
Lpm liters per minute OS oversize, overspeed
LOP low oil pressure TDEC time delay engine cooldown
OSHA Occupational Safety and Health TDEN time delay emergency to
LP liquefied petroleum Administration normal
LPG liquefied petroleum gas OV overvoltage TDES time delay engine start
LS left side oz. ounce TDNE time delay normal to
Lwa sound power level, A weighted p., pp. page, pages emergency
LWL low water level PC personal computer TDOE time delay off to emergency
LWT low water temperature PCB printed circuit board TDON time delay off to normal
m meter, milli (1/1000) pF picofarad temp. temperature
M mega (106 when used with SI PF power factor term. terminal
units), male ph., ∅ phase TIF telephone influence factor
m3 cubic meter
PHC Phillips head crimptite (screw) TIR total indicator reading
m3/min. cubic meters per minute
PHH Phillips hex head (screw) tol. tolerance
mA milliampere
PHM pan head machine (screw) turbo. turbocharger
man. manual
PLC programmable logic control typ. typical (same in multiple
max. maximum locations)
PMG permanent-magnet generator
MB megabyte (220 bytes) pot potentiometer, potential UF underfrequency
MCM one thousand circular mils ppm parts per million UHF ultrahigh frequency
MCCB molded-case circuit breaker PROM programmable read-only UL Underwriter’s Laboratories, Inc.
meggar megohmmeter memory UNC unified coarse thread (was NC)
MHz megahertz psi pounds per square inch UNF unified fine thread (was NF)
mi. mile pt. pint univ. universal
mil one one-thousandth of an inch PTC positive temperature coefficient US undersize, underspeed
min. minimum, minute PTO power takeoff UV ultraviolet, undervoltage
misc. miscellaneous PVC polyvinyl chloride V volt
MJ megajoule qt. quart, quarts VAC volts alternating current
mJ millijoule qty. quantity VAR voltampere reactive
mm millimeter R replacement (emergency) VDC volts direct current
mOhm, mΩ power source VFD vacuum fluorescent display
milliohm rad. radiator, radius VGA video graphics adapter
MOhm, MΩ RAM random access memory
megohm VHF very high frequency
RDO relay driver output W watt
MOV metal oxide varistor ref. reference
MPa megapascal WCR withstand and closing rating
rem. remote w/ with
mpg miles per gallon Res/Coml Residential/Commercial
mph miles per hour w/o without
RFI radio frequency interference wt. weight
MS military standard
RH round head xfmr transformer
m/sec. meters per second

80 Appendix TP-6391 9/08


Appendix B Common Hardware Application Guidelines

Use the information below and on the following pages to Steps for common hardware application:
identify proper fastening techniques when no specific
reference for reassembly is made. 1. Determine entry hole type: round or slotted.

Bolt/Screw Length: When bolt/screw length is not given, 2. Determine exit hole type: fixed female thread
use Figure 1 as a guide. As a general rule, a minimum (weld nut), round, or slotted.
length of one thread beyond the nut and a maximum
length of 1/2 the bolt/screw diameter beyond the nut is For round and slotted exit holes, determine if
hardware is greater than 1/2 inch in diameter, or
the preferred method.
1/2 inch in diameter or less. Hardware that is
Washers and Nuts: Use split lock washers as a bolt greater than 1/2 inch in diameter takes a standard
locking device where specified. Use SAE flat washers nut and SAE washer. Hardware 1/2 inch or less in
with whiz nuts, spiralock nuts, or standard nuts and diameter can take a properly torqued whiz nut or
spiralock nut. See Figure 2.
preloading (torque) of the bolt in all other applications.
3. Follow these SAE washer rules after determining
See Appendix C, General Torque Specifications, and
exit hole type:
other torque specifications in the service literature.
a. Always use a washer between hardware and a
slot.
Preferred Nut/Bolt Clearance
1 2 b. Always use a washer under a nut (see 2 above
for exception).

c. Use a washer under a bolt when the female


thread is fixed (weld nut).

4. Refer to Figure 2, which depicts the preceding


hardware configuration possibilities.

Unacceptable Nut/Bolt Clearance

2
3 1

G-585

1. 1/2 of bolt diameter


2. Min. 1 full thread beyond top of nut
3. Below top of nut

Figure 1 Acceptable Bolt Lengths


5
4
6

G-585

1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types

Figure 2 Acceptable Hardware Combinations

TP-6391 9/08 Appendix 81


Appendix C General Torque Specifications

American Standard Fasteners Torque Specifications


Assembled into Cast Iron or Steel Assembled into
Torque Aluminum
Size Measurement Grade 2 Grade 5 Grade 8 Grade 2 or 5
8-32 Nm (in. lb.) 1.8 (16) 2.3 (20) —
10-24 Nm (in. lb.) 2.9 (26) 3.6 (32) —
10-32 Nm (in. lb.) 2.9 (26) 3.6 (32) —
1/4-20 Nm (in. lb.) 6.8 (60) 10.8 (96) 14.9 (132)
1/4-28 Nm (in. lb.) 8.1 (72) 12.2 (108) 16.3 (144)
5/16-18 Nm (in. lb.) 13.6 (120) 21.7 (192) 29.8 (264)
5/16-24 Nm (in. lb.) 14.9 (132) 23.1 (204) 32.5 (288)
3/8-16 Nm (ft. lb.) 24.0 (18) 38.0 (28) 53.0 (39)
3/8-24 Nm (ft. lb.) 27.0 (20) 42.0 (31) 60.0 (44)
7/16-14 Nm (ft. lb.) 39.0 (29) 60.0 (44) 85.0 (63)
7/16-20 Nm (ft. lb.) 43.0 (32) 68.0 (50) 95.0 (70) See Note 3
1/2-13 Nm (ft. lb.) 60.0 (44) 92.0 (68) 130.0 (96)
1/2-20 Nm (ft. lb.) 66.0 (49) 103.0 (76) 146.0 (108)
9/16-12 Nm (ft. lb.) 81.0 (60) 133.0 (98) 187.0 (138)
9/16-18 Nm (ft. lb.) 91.0 (67) 148.0 (109) 209.0 (154)
5/8-11 Nm (ft. lb.) 113.0 (83) 183.0 (135) 259.0 (191)
5/8-18 Nm (ft. lb.) 128.0 (94) 208.0 (153) 293.0 (216)
3/4-10 Nm (ft. lb.) 199.0 (147) 325.0 (240) 458.0 (338)
3/4-16 Nm (ft. lb.) 222.0 (164) 363.0 (268) 513.0 (378)
1-8 Nm (ft. lb.) 259.0 (191) 721.0 (532) 1109.0 (818)
1-12 Nm (ft. lb.) 283.0 (209) 789.0 (582) 1214.0 (895)

Metric Fasteners Torque Specifications, Measured in Nm (ft. lb.)


Assembled into Cast Iron or Steel Assembled into
Aluminum
Size (mm) Grade 5.8 Grade 8.8 Grade 10.9 Grade 5.8 or 8.8
M6 x 1.00 6.2 (4.6) 9.5 (7) 13.6 (10)
M8 x 1.25 15.0 (11) 23.0 (17) 33.0 (24)
M8 x 1.00 16.0 (11) 24.0 (18) 34.0 (25)
M10 x 1.50 30.0 (22) 45.0 (34) 65.0 (48)
M10 x 1.25 31.0 (23) 47.0 (35) 68.0 (50)
M12 x 1.75 53.0 (39) 80.0 (59) 115.0 (85)
M12 x 1.50 56.0 (41) 85.0 (63) 122.0 (90) See Note 3
M14 x 2.00 83.0 (61) 126.0 (93) 180.0 (133)
M14 x 1.50 87.0 (64) 133.0 (98) 190.0 (140)
M16 x 2.00 127.0 (94) 194.0 (143) 278.0 (205)
M16 x 1.50 132.0 (97) 201.0 (148) 287.0 (212)
M18 x 2.50 179.0 (132) 273.0 (201) 390.0 (288)
M18 x 1.50 189.0 (140) 289.0 (213) 413.0 (305)

Notes:
1. Do not use these values when the torque values are specified on the assembly drawing.
2. These values are based on new plates threads. Increase values by 15% if non-plated threads are used.
3. Hardware threaded into aluminum must have two diameters of thread engagement or may require 30% or more reduction in the torque.
4. Torques are calculated as equivalent stress loading to American hardware and approximately a preload of 90% of yield strength and
friction coefficient of 0.125.

82 Appendix TP-6391 9/08


Appendix D Common Hardware Identification

Screw/Bolts/Studs Nuts Hardness Grades


Head Styles Nut Styles American Standard

Hex Head or Machine Head Hex Head Grade 2

Hex Head or Machine Head


Lock or Elastic Grade 5
with Washer

Flat Head (FHM) Square Grade 8

Grade 8/9 (Hex Socket


Round Head (RHM) Cap or Acorn
Head)
Metric
Pan Head Wing
Number stamped on 5.8
Hex Socket Head Cap or Washers hardware; 5.8 shown
Allent Head Cap
Washer Styles
Hex Socket Head or Allent
Head Shoulder Bolt Plain

Sheet Metal Screw Split Lock or Spring

Stud Spring or Wave

Drive Styles
External Tooth Lock
Hex
Internal Tooth Lock
Hex and Slotted
Internal-External Tooth Lock
Phillipsr

Slotted

Hex Socket

Allent head screw is a trademark of Holo-Krome Co.


Phillipsr screw is a registered trademark of Phillips Screw Company.

Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts) Plain Washers
1/4-20 x 1 9/32 x 5/8 x 1/16
Length In Inches (Screws and Bolts) Thickness
Threads Per Inch External Dimension
Major Thread Diameter In Fractional Inches Or Screw Number Size Internal Dimension
Metric (Screws, Bolts, Studs, and Nuts)
M8-1.25 x 20 Lock Washers
Length In Millimeters (Screws and Bolts) 5/8
Distance Between Threads In Millimeters Internal Dimension
Major Thread Diameter In Millimeters

TP-6391 9/08 Appendix 83


Appendix E Common Hardware List

The Common Hardware List lists part numbers and dimensions for common hardware items.

American Standard
Part No. Dimensions Part No. Dimensions Part No. Dimensions Type
Hex Head Bolts (Grade 5) Hex Head Bolts, cont. Hex Nuts
X-465-17 1/4-20 x .38 X-6238-14 3/8-24 x .75 X-6009-1 1-8 Standard
X-465-6 1/4-20 x .50 X-6238-16 3/8-24 x 1.25
X-465-2 1/4-20 x .62 X-6238-21 3/8-24 x 4.00 X-6210-3 6-32 Whiz
X-465-16 1/4-20 x .75 X-6238-22 3/8-24 x 4.50 X-6210-4 8-32 Whiz
X-465-18 1/4-20 x .88 X-6210-5 10-24 Whiz
X-465-7 1/4-20 x 1.00 X-6024-5 7/16-14 x .75
X-6024-2 7/16-14 x 1.00 X-6210-1 10-32 Whiz
X-465-8 1/4-20 x 1.25
X-465-9 1/4-20 x 1.50 X-6024-8 7/16-14 x 1.25 X-6210-2 1/4-20 Spiralock
X-465-10 1/4-20 x 1.75 X-6024-3 7/16-14 x 1.50 X-6210-6 1/4-28 Spiralock
X-465-11 1/4-20 x 2.00 X-6024-4 7/16-14 x 2.00 X-6210-7 5/16-18 Spiralock
X-465-12 1/4-20 x 2.25 X-6024-11 7/16-14 x 2.75 X-6210-8 5/16-24 Spiralock
X-465-14 1/4-20 x 2.75 X-6024-12 7/16-14 x 6.50
X-6210-9 3/8-16 Spiralock
X-465-21 1/4-20 x 5.00 X-129-15 1/2-13 x .75 X-6210-10 3/8-24 Spiralock
X-465-25 1/4-28 x .38 X-129-17 1/2-13 x 1.00 X-6210-11 7/16-14 Spiralock
X-465-20 1/4-28 x 1.00 X-129-18 1/2-13 x 1.25 X-6210-12 1/2-13 Spiralock
X-125-33 5/16-18 x .50 X-129-19 1/2-13 x 1.50 X-6210-15 7/16-20 Spiralock
X-125-23 5/16-18 x .62 X-129-20 1/2-13 x 1.75 X-6210-14 1/2-20 Spiralock
X-125-3 5/16-18 x .75 X-129-21 1/2-13 x 2.00
X-129-22 1/2-13 x 2.25 X-85-3 5/8-11 Standard
X-125-31 5/16-18 x .88 X-88-12 3/4-10 Standard
X-125-5 5/16-18 x 1.00 X-129-23 1/2-13 x 2.50
X-129-24 1/2-13 x 2.75 X-89-2 1/2-20 Standard
X-125-24 5/16-18 x 1.25
X-125-34 5/16-18 x 1.50 X-129-25 1/2-13 x 3.00
X-125-25 5/16-18 x 1.75 X-129-27 1/2-13 x 3.50
X-125-26 5/16-18 x 2.00 X-129-29 1/2-13 x 4.00 Washers
230578 5/16-18 x 2.25 X-129-30 1/2-13 x 4.50 Bolt/
X-125-29 5/16-18 x 2.50 X-463-9 1/2-13 x 5.50
X-129-44 1/2-13 x 6.00 Part No. ID OD Thick. Screw
X-125-27 5/16-18 x 2.75
X-125-28 5/16-18 x 3.00 X-129-51 1/2-20 x .75 X-25-46 .125 .250 .022 #4
X-125-22 5/16-18 x 4.50 X-129-45 1/2-20 x 1.25 X-25-9 .156 .375 .049 #6
X-125-32 5/16-18 x 5.00 X-129-52 1/2-20 x 1.50 X-25-48 .188 .438 .049 #8
X-125-35 5/16-18 x 5.50 X-25-36 .219 .500 .049 #10
X-125-36 5/16-18 x 6.00 X-6021-3 5/8-11 x 1.00 X-25-40 .281 .625 .065 1/4
X-125-40 5/16-18 x 6.50 X-6021-4 5/8-11 x 1.25 X-25-85 .344 .687 .065 5/16
X-6021-2 5/8-11 x 1.50 X-25-37 .406 .812 .065 3/8
X-125-43 5/16-24 x 1.75 X-6021-1 5/8-11 x 1.75 X-25-34 .469 .922 .065 7/16
X-125-44 5/16-24 x 2.50 273049 5/8-11 x 2.00
X-125-30 5/16-24 x .75 X-25-26 .531 1.062 .095 1/2
X-6021-5 5/8-11 x 2.25 X-25-15 .656 1.312 .095 5/8
X-125-39 5/16-24 x 2.00 X-6021-6 5/8-11 x 2.50
X-125-38 5/16-24 x 2.75 X-25-29 .812 1.469 .134 3/4
X-6021-7 5/8-11 x 2.75
X-25-127 1.062 2.000 .134 1
X-6238-2 3/8-16 x .62 X-6021-12 5/8-11 x 3.75
X-6238-10 3/8-16 x .75 X-6021-11 5/8-11 x 4.50
X-6238-3 3/8-16 x .88 X-6021-10 5/8-11 x 6.00
X-6238-11 3/8-16 x 1.00 X-6021-9 5/8-18 x 2.50
X-6238-4 3/8-16 x 1.25
X-6238-5 3/8-16 x 1.50 X-6239-1 3/4-10 x 1.00
X-6238-1 3/8-16 x 1.75 X-6239-8 3/4-10 x 1.25
X-6238-6 3/8-16 x 2.00 X-6239-2 3/4-10 x 1.50
X-6238-17 3/8-16 x 2.25 X-6239-3 3/4-10 x 2.00
X-6238-7 3/8-16 x 2.50 X-6239-4 3/4-10 x 2.50
X-6238-8 3/8-16 x 2.75 X-6239-5 3/4-10 x 3.00
X-6238-9 3/8-16 x 3.00 X-6239-6 3/4-10 x 3.50
X-6238-19 3/8-16 x 3.25 X-792-1 1-8 x 2.25
X-6238-12 3/8-16 x 3.50 X-792-5 1-8 x 3.00
X-6238-20 3/8-16 x 3.75 X-792-8 1-8 x 5.00
X-6238-13 3/8-16 x 4.50
X-6238-18 3/8-16 x 5.50
X-6238-25 3/8-16 x 6.50

84 Appendix TP-6391 9/08


Metric
Hex head bolts are hardness grade 8.8 unless noted.

Part No. Dimensions Part No. Dimensions Part No. Dimensions


Hex Head Bolts (Partial Thread) Hex Head Bolts (Partial Thread), Hex Head Bolts (Full Thread),
M931-05055-60 M5-0.80 x 55 continued continued
M931-06040-60 M6-1.00 x 40 M960-16090-60 M16-1.50 x 90 M933-12016-60 M12-1.75 x 16
M931-06055-60 M6-1.00 x 55 M931-16090-60 M16-2.00 x 90 M933-12020-60 M12-1.75 x 20
M931-06060-60 M6-1.00 x 60 M931-16100-60 M16-2.00 x 100 M961-12020-60F M12-1.50 x 20
M931-06060-SS M6-1.00 x 60 M931-16100-82 M16-2.00 x 100* M933-12025-60 M12-1.75 x 25
M931-06070-60 M6-1.00 x 70 M931-16120-60 M16-2.00 x 120 M933-12025-82 M12-1.75 x 25*
M931-06070-SS M6-1.00 x 70 M931-16150-60 M16-2.00 x 150 M961-12030-60 M12-1.25 x 30
M931-06075-60 M6-1.00 x 75 M933-12030-82 M12-1.75 x 30*
M931-06090-60 M6-1.00 x 90 M931-20065-60 M20-2.50 x 65 M961-12030-82F M12-1.50 x 30*
M931-06145-60 M6-1.00 x 145 M931-20090-60 M20-2.50 x 90 M933-12030-60 M12-1.75 x 30
M931-06150-60 M6-1.00 x 150 M931-20100-60 M20-2.50 x 100 M933-12035-60 M12-1.75 x 35
M931-20120-60 M20-2.50 x 120 M961-12040-82 M12-1.25 x 40*
M931-08035-60 M8-1.25 x 35 M931-20140-60 M20-2.50 x 140 M933-12040-60 M12-1.75 x 40
M931-08040-60 M8-1.25 x 40 M931-20160-60 M20-2.50 x 160 M933-12040-82 M12-1.75 x 40*
M931-08045-60 M8-1.25 x 45
M931-08050-60 M8-1.25 x 50 M931-22090-60 M22-2.50 x 90 M961-14025-60 M14-1.50 x 25
M931-08055-60 M8-1.25 x 55 M931-22120-60 M22-2.50 x 120 M933-14025-60 M14-2.00 x 25
M931-08055-82 M8-1.25 x 55* M931-22160-60 M22-2.50 x 160 M961-14050-82 M14-1.50 x 50*
M931-08060-60 M8-1.25 x 60 M931-24090-60 M24-3.00 x 90
M931-08070-60 M8-1.25 x 70 M961-16025-60 M16-1.50 x 25
M931-24120-60 M24-3.00 x 120 M933-16025-60 M16-2.00 x 25
M931-08070-82 M8-1.25 x 70* M931-24160-60 M24-3.00 x 160
M931-08075-60 M8-1.25 x 75 M961-16030-82 M16-1.50 x 30*
M931-24200-60 M24-3.00 x 200 M933-16030-82 M16-2.00 x 30*
M931-08080-60 M8-1.25 x 80
M931-08090-60 M8-1.25 x 90 M933-16035-60 M16-2.00 x 35
M931-08095-60 M8-1.25 x 95 Hex Head Bolts (Full Thread) M961-16040-60 M16-1.50 x 40
M931-08100-60 M8-1.25 x 100 M933-16040-60 M16-2.00 x 40
M933-04006-60 M4-0.70 x 6 M961-16045-82 M16-1.50 x 45*
M931-08110-60 M8-1.25 x 110
M931-08120-60 M8-1.25 x 120 M933-05030-60 M5-0.80 x 30 M933-16045-82 M16-2.00 x 45*
M931-08130-60 M8-1.25 x 130 M933-05035-60 M5-0.80 x 35 M933-16050-60 M16-2.00 x 50
M931-08140-60 M8-1.25 x 140 M933-05050-60 M5-0.80 x 50 M933-16050-82 M16-2.00 x 50*
M931-08150-60 M8-1.25 x 150 M933-16060-60 M16-2.00 x 60
M933-06010-60 M6-1.00 x 10 M933-16070-60 M16-2.00 x 70
M931-08200-60 M8-1.25 x 200 M933-06012-60 M6-1.00 x 12
M931-10040-82 M10-1.25 x 40* M933-06014-60 M6-1.00 x 14 M933-18035-60 M18-2.50 x 35
M931-10040-60 M10-1.50 x 40 M933-06016-60 M6-1.00 x 16 M933-18050-60 M18-2.50 x 50
M931-10045-60 M10-1.50 x 45 M933-06020-60 M6-1.00 x 20 M933-18060-60 M18-2.50 x 60
M931-10050-60 M10-1.50 x 50 M933-06025-60 M6-1.00 x 25 M933-20050-60 M20-2.50 x 50
M931-10050-82 M10-1.25 x 50* M933-06030-60 M6-1.00 x 30 M933-20055-60 M20-2.50 x 55
M931-10055-60 M10-1.50 x 55 M933-06040-60 M6-1.00 x 40
M931-10060-60 M10-1.50 x 60 M933-06050-60 M6-1.00 x 50 M933-24060-60 M24-3.00 x 60
M931-10065-60 M10-1.50 x 65 M933-24065-60 M24-3.00 x 65
M933-07025-60 M7-1.00 x 25 M933-24070-60 M24-3.00 x 70
M931-10070-60 M10-1.50 x 70
M931-10080-60 M10-1.50 x 80 M933-08010-60 M8-1.25 x 10
M931-10080-82 M10-1.25 x 80* M933-08012-60 M8-1.25 x 12 Pan Head Machine Screws
M931-10090-60 M10-1.50 x 90 M933-08016-60 M8-1.25 x 16
M931-10090-82 M10-1.50 x 90* M933-08020-60 M8-1.25 x 20 M7985A-03010-20 M3-0.50 x 10
M931-10100-60 M10-1.50 x 100 M933-08025-60 M8-1.25 x 25 M7985A-03012-20 M3-0.50 x 12
M931-10110-60 M10-1.50 x 110 M933-08030-60 M8-1.25 x 30 M7985A-04010-20 M4-0.70 x 10
M931-10120-60 M10-1.50 x 120 M933-08030-82 M8-1.25 x 30* M7985A-04016-20 M4-0.70 x 16
M931-10130-60 M10-1.50 x 130 M7985A-04020-20 M4-0.70 x 20
M931-10140-60 M10-1.50 x 140 M933-10012-60 M10-1.50 x 12
M961-10020-60 M10-1.25 x 20 M7985A-04050-20 M4-0.70 x 50
M931-10180-60 M10-1.50 x 180 M7985A-04100-20 M4-0.70 x 100
M931-10235-60 M10-1.50 x 235 M933-10020-60 M10-1.50 x 20
M931-10260-60 M10-1.50 x 260 M933-10025-60 M10-1.50 x 25 M7985A-05010-20 M5-0.80 x 10
M960-10330-60 M10-1.25 x 330 M961-10025-60 M10-1.25 x 25 M7985A-05012-20 M5-0.80 x 12
M933-10025-82 M10-1.50 x 25* M7985A-05016-20 M5-0.80 x 16
M931-12045-60 M12-1.75 x 45 M961-10030-60 M10-1.25 x 30 M7985A-05020-20 M5-0.80 x 20
M960-12050-60 M12-1.25 x 50 M933-10030-60 M10-1.50 x 30 M7985A-05025-20 M5-0.80 x 25
M960-12050-82 M12-1.25 x 50* M933-10030-82 M10-1.50 x 30* M7985A-05030-20 M5-0.80 x 30
M931-12050-60 M12-1.75 x 50 M961-10035-60 M10-1.25 x 35 M7985A-05080-20 M5-0.80 x 80
M931-12050-82 M12-1.75 x 50* M933-10035-60 M10-1.50 x 35 M7985A-05100-20 M5-0.80 x 100
M931-12055-60 M12-1.75 x 55 M933-10035-82 M10-1.50 x 35*
M931-12060-60 M12-1.75 x 60 M961-10040-60 M10-1.25 x 40 M7985A-06100-20 M6-1.00 x 100
M931-12060-82 M12-1.75 x 60*
M931-12065-60 M12-1.75 x 65 Flat Head Machine Screws
M931-12075-60 M12-1.75 x 75
M931-12080-60 M12-1.75 x 80 M965A-04012-SS M4-0.70 x 12
M931-12090-60 M12-1.75 x 90 M965A-05012-SS M5-0.80 x 12
M931-12100-60 M12-1.75 x 100 M965A-05016-20 M5-0.80 x 16
M931-12110-60 M12-1.75 x 110 M965A-06012-20 M6-1.00 x 12

* This metric hex bolt’s hardness is grade 10.9.

TP-6391 9/08 Appendix 85


Metric, continued
Part No. Dimensions Type
Hex Nuts
M934-03-50 M3-0.50 Standard
M934-04-50 M4-0.70 Standard
M934-04-B M4-0.70 Brass
M934-05-50 M5-0.80 Standard
M934-06-60 M6-1.00 Standard
M934-06-64 M6-1.00 Std. (green)
M6923-06-80 M6-1.00 Spiralock
M982-06-80 M6-1.00 Elastic Stop
M934-08-60 M8-1.25 Standard
M6923-08-80 M8-1.25 Spiralock
M982-08-80 M8-1.25 Elastic Stop
M934-10-60 M10-1.50 Standard
M934-10-60F M10-1.25 Standard
M6923-10-80 M10-1.50 Spiralock
M6923-10-62 M10-1.50 Spiralock[
M982-10-80 M10-1.50 Elastic Stop
M934-12-60 M12-1.75 Standard
M934-12-60F M12-1.25 Standard
M6923-12-80 M12-1.75 Spiralock
M982-12-80 M12-1.75 Elastic Stop
M982-14-60 M14-2.00 Elastic Stop
M6923-16-80 M16-2.00 Spiralock
M982-16-80 M16-2.00 Elastic Stop
M934-18-80 M18-2.5 Standard
M982-18-60 M18-2.50 Elastic Stop
M934-20-80 M20-2.50 Standard
M982-20-80 M20-2.50 Elastic Stop
M934-22-60 M22-2.50 Standard
M934-24-80 M24-3.00 Standard
M982-24-60 M24-3.00 Elastic Stop
M934-30-80 M30-3.50 Standard

Washers
Bolt/
Part No. ID OD Thick. Screw
M125A-03-80 3.2 7.0 0.5 M3
M125A-04-80 4.3 9.0 0.8 M4
M125A-05-80 5.3 10.0 1.0 M5
M125A-06-80 6.4 12.0 1.6 M6
M125A-08-80 8.4 16.0 1.6 M8
M125A-10-80 10.5 20.0 2.0 M10
M125A-12-80 13.0 24.0 2.5 M12
M125A-14-80 15.0 28.0 2.5 M14
M125A-16-80 17.0 30.0 3.0 M16
M125A-18-80 19.0 34.0 3.0 M18
M125A-20-80 21.0 37.0 3.0 M20
M125A-24-80 25.0 44.0 4.0 M24

[ This metric hex nut’s hardness is grade 8.

86 Appendix TP-6391 9/08


TP-6391 9/08 87
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Kohler Power Systems
Asia Pacific Headquarters
TP-6391 9/08a 7 Jurong Pier Road
Singapore 619159
E 2006 and 2008 by Kohler Co. All rights reserved. Phone (65) 6264-6422, Fax (65) 6264-6455

You might also like