SUNLINE™ SPLIT-SYSTEM
EVAPORATOR BLOWER
(AIR COOLED)
INSTALLATION INSTRUCTION Supersedes: 550.39-N5YI (399) 035-18261-000 Rev. A (0501)
MODEL K3EU180A50
(WORLD 50 HZ)
GENERAL INSPECTION
This completely assembled blower unit is manufactured under As soon as a unit is received, it should be inspected for possible
ISO 9002 Quality System Certification and includes a well- damage during transit. If damage is evident, the extent of the
insulated cabinet, a DX cooling coil with copper tubes and alu- damage should be noted on the carrier's delivery receipt. A
minum fins, an expansion valve, a distributor, throwaway fil- separate request for inspection by the carrier's agent should
ters, a centrifugal blower, a blower motor, a blower motor be made in writing. See Local Distributor for additional infor-
contactor, an adjustable belt drive and a small holding charge mation. NOMENCLATURE
of Refrigerant-22. K 3 EU 180 A 50
The unit is shipped in the vertical position with a vertical air dis- Product Category
charge. The blower section can be repositioned as shown in Fig-
K = Split-System Evaporator Blower
ure1 for horizontal applications.
Product Generation
REFERENCE 1,2,3 = Design Level
This instruction covers the installation of the evaporator blower Product Identifier
unit. For information on the installation and operation of the EU = Evaporator Blower Unit
matching condensing unit refer to Form 035-17263-000.
Additional information for the accessories on this equipment is Nominal Cooling Capacity
available in the following instructions: 180 = 180Mbh (52.7kW)
Standard Register
WARNING
INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE
2101 West Tecumseh Road OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY
Norman, OK 73069 OR PROPERTY DAMAGE.
Installer should pay particular attention to the words: NOTE, CAU-
TION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment dam-
age. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not
035-18261-000 Rev. A (0501)I
INSTALLATION
LIMITATIONS Table 1 - PHYSICAL DATA
These units must be installed in accordance with applicable na-
Rows Deep 4
tional, local and municipal safety codes.
Rows High 26
If components are to be added to a unit to meet local codes, Finned Length (in./mm) 54.5/1384
they are to be installed at the dealer's and/or the customer's ex- Evaporator Coil
Fin/Inch 13
pense. Refer to Table 2 for Unit Application Data.
Tube O.D. (in./mm) 3/8/9.6
LOCATION Face Area (Ft.2/m2) 12.4/1.15
This blower unit is not designed for outdoor installation. It must Centrifugal inches 18 x 18
Wheel Dia. x Width
be located within the building structure, either inside or outside Blower1 mm 457 x 457
the conditioned space.
inches 20 x 20 x1
The unit should be located as close to the condensing unit as Filters2 Size 508 x 508
mm
practical and positioned to minimize bends in the refrigerant (6 Req'd) x 25
piping. Face Area (Ft.2/m2) 16.7/1.5
Units being installed vertically or horizontally can be set directly Operating Charge ( Refrigerant 22) (Lbs/Kg) 5.5/2.5
on a floor or platform, or they can be supported by metal or Shipping 480/218
wooden beams. Weight (Lbs/Kg)
Operating 440/200
CLEARANCES 36 kW 74/33.5
These units can be rigged with slings under the bottom skid.
Before rigging any unit, determine its weight from Table 1. Bef-
ore rigging a unit for horizontal installation, make sure that its
weight will be distributed equally.
(559)
(8)
(457
(254) (8)
1. Drill two holes 5 16" (8mm) dia. in the side panel as shown in
Figure 5.
2. Insert at least 8" (200mm) of 14" (6.3mm) O.D. tubing into NOTE; SHUT DOWN THE REFRIGERANT SYSTEM BEF-
each of these holes for sufficient penetration into the air ORE TAKING ANY TEST MEASUREMENTS TO AS-
flow on both sides of the evaporator coil. SURE A DRY EVAPORATOR COIL
4. Knowing the pressure drop across a dry coil, the actual air-
flow through the unit can be determined from the curve in
Figure 6.
If the airflow is above or below the specified valve, the supply FIG 6 - PRESSURE DROP VS SUPPLY AIRFLOW
air motor pulley may have to be readjusted. After one hour of
LEGEND:
RPM range for standard Exceeds the output limitation of the standard
factory-mounted drive components. factory-mounted blower motor.
UNIT
ACCESSORIES
•ELECTRIC HEATER
Add 15" (381mm) to Unit Height when using 10, 16, 26 or 36kW Heater
•SUPPLY AIR PLENUM
Add 27" (686mm) to Unit Height when used
•BASE
Add 24" (610mm) to Unit Height when used
MINIMUM CLEARANCES (in./mm)
Side with RETURN AIR opening - 24 / 610
Side with SUPPLY AIR opening - 24 / 6101
Side with PIPING CONNECTIONS - 61 / 15492
Side opposite PIPING CONNECTIONS - 26 / 6603
Bottom - 4
NOTES:
1
Overall dimension of the unit will vary if an electric heater, a supply air plenum or a base is used.
2
This dimension is required for removal of the DX coil. Only 26" (660mm) is required for normal serv-
icing.
3
If the DX coil has to be removed, this dimension is required to loosen screws that secure the coil to
the unit frame. This dimension will also be required for blower motor access if the piping
connections are made on the opposite side of the unit.
4
Allow enough clearance to trap the condensate drain line.
Blower Adjustable Motor Pulley Fixed Blower Pulley Belt MOTOR SPECIFICATIONS
Motor
Range Pitch Dia Bore Pitch Dia. Bore Pitch Lg. •1450 RPM
(HP/kW) Designation
(RPM) (In./mm) (In./mm) (In./mm) (In./mm) (In./mm) •380/415-3-50
3.4 - 4.4 / 86 7
•Solid base
3 / 2.2 615/800 8 / 22.2 8.0 / 203 1 / 25 A54 55.3 / 1405
- 112
•56 Frame
•Inherently protected
•Permanently lubricated
ball bearings
MAINTENANCE
FILTERS — The filters must be replaced as often as necessary LUBRICATION — The bearings for the blower shaft and the
to assure good air flow and filtering action. blower motors are permanently lubricated and should not re-
quire additional lubricant.
EVAPORATOR COIL — Do not allow dirt to accumulate on the
DRAIN PAN — The drain pan should be inspected regularly
evaporator coil or other parts of the evaporator air circuit. Clean
to assure proper drainage.
as often as necessary to assure good system performance.
Use a brush, vacuum cleaner attachment or other suitable BELTS — Maintain belt tension to extend belt life. Replace
means. when signs of failure begin to appear.