Sl. No. Items Unit Tender Specification Tenderer Compliance
Sl. No. Items Unit Tender Specification Tenderer Compliance
Sl. No. Items Unit Tender Specification Tenderer Compliance
1 GENERAL
5 Breaker, VCB Panel 5 Breaker, VCB Panel
1.1 No. of panels 1 No.
1 incomer & 4 outgoings 1 incomer & 4 outgoings
1.2 System voltage KV 33 33
1.3 Mounting ---- Indoor Indoor
1.4 Physical Dimension (mm) LxBxH Supplier to indicate During detail engineering
To be provided including earthing
1.5 Individual Breaker Trolley trolley & truck included in offer
truck
2 CIRCUIT BREAKER
2.1 No. of breakers ---- 5 5
2.2 Type ---- Vacuum Circuit Breaker Vacuum Circuit Breaker
2.3 Voltage rating KV 33 33
2.4 Highest system voltage KV 36 36
2.5 Current rating A 630 630
2.6 Impulse with stand voltage KV 170 125
2.7 1 min. power frequency with stand voltage KV 70 70
2.8 SHORT CIRCUIT RATING
2.8.1 Symmetrical breaking current for 3 sec KA 26 26
Symmetrical short circuit breaking
2.8.2 MVA 1500 1500
capacity
2.8.3 Symmetrical making current KA 62.5 62.5
2.8.4 Max. opening time Millisec 45 to 60 45 to 60
2.8.5 Max. closing time Millisec 60 60
2.8.6 Max. Arching time Millisec 15 15
2.7 OPERATION
2.7.1 Type Motorised spring closing Motorised spring closing
2.7.3 Closing 110V 110VDC
2.8 AUXILIARY CONTACTS
2.8.1 Normally open No. 6 6
2.8.2 Normally closed No. 6 6
5 VOLTAGE TRANSFORMER
1 no. (Withdrawable) for incomer
5.1 Number 03 Nos. single phase PT consider.
indoor, epoxy resin cast
Burden 100VA, 3 ph. Class 0.5
5.2 Winding rating 33000V/ 110V, 3 lines as per IS : Core 1 :- 100VA, Cl 0.5
3156
CURRENT TRANSFORMER
6
(MEASURING &PROTECTION)
6.1 Numbers One set on each breaker
150A/ 5A for indoor epoxy resin
6.2 Rating – Incomer 150/5-5A
cast type, CTs shall be dual ratio
50A/5A for, indoor epoxy resin
6.3 Rating - Outgoing 50/5-5A
cast type, CTS shall be dual ratio
Two, 1 for metering & 1 for
6.4 No. of secondary 5-5A
protection
6.5 Burden/class 15VA, Class 0.5 accuracy 15VA, CL0.5
6.6 Standard IS : 2705 as per latest IS/IEC standard
7 MEASURING INSTRUMENTS
Digital Load Manager to read
voltage, current, kWh, demand MFM with CL 0.5 with RS 485
7.1 Multifunction Meter on each breaker
meter, THD & PF, Class 0.5 Comm.
accuracy