Items Unit Tender specification Tenderer Compliance

1 GENERAL
5 Breaker, VCB Panel 5 Breaker, VCB Panel
1.1 No. of panels 1 No.
1 incomer & 4 outgoings 1 incomer & 4 outgoings
1.2 System voltage KV 33 33
1.3 Mounting ---- Indoor Indoor
1.4 Physical Dimension (mm) LxBxH Supplier to indicate During detail engineering
To be provided including earthing
1.5 Individual Breaker Trolley trolley & truck included in offer
truck

2 CIRCUIT BREAKER
2.1 No. of breakers ---- 5 5
2.2 Type ---- Vacuum Circuit Breaker Vacuum Circuit Breaker
2.3 Voltage rating KV 33 33
2.4 Highest system voltage KV 36 36
2.5 Current rating A 630 630
2.6 Impulse with stand voltage KV 170 125
2.7 1 min. power frequency with stand voltage KV 70 70
2.8 SHORT CIRCUIT RATING
2.8.1 Symmetrical breaking current for 3 sec KA 26 26
Symmetrical short circuit breaking
2.8.2 MVA 1500 1500
capacity
2.8.3 Symmetrical making current KA 62.5 62.5
2.8.4 Max. opening time Millisec 45 to 60 45 to 60
2.8.5 Max. closing time Millisec 60 60
2.8.6 Max. Arching time Millisec 15 15
2.7 OPERATION
2.7.1 Type Motorised spring closing Motorised spring closing
2.7.3 Closing 110V 110VDC
2.8 AUXILIARY CONTACTS
2.8.1 Normally open No. 6 6
2.8.2 Normally closed No. 6 6

3 STATIC RELAY PANEL


Overcurrent cum short circuit and earth 1 no. 50-200% OC & 1 no. 20-80% O/C + E/F Relay (Aux. supply
3.1
fault (self powered relay) EF relay on all breakers 110VDC)
To trip on WTI & OTI / Integrated
Aux. relay for Trafo faults, Type :-
3.2 Auxiliary relays (self powered relay) relay on transformer outgoing
CRM (Aux. supply 110VDC)
feeders
Type :- PQ8nch2js(Aux. supply
3.3 Master trip relays (self powered relay) For incomer
110VDC)
Type :- UVT92M (Aux. supply
3.4 PT fuse relay For incomer
110VDC)
3.5 Anti-pumping relay On all breakers Consider

4 SUNDRY (for each breaker)


a) On/off indicator Red/Green R/G indicating lamps consider.
b) Phase RYB RYB indicating lamps consider.
c) Terminations 300 sq.mm XLPE arrangement consider
d) Padlock with key One consider
e) Raising lowering handle One consider
f) Trip circuit healthy Amber lamp indicating A indicating lamps consider.
g) Auxiliary contacts 6 nos. NO/NC consider
h) Space heater with switch One consider
i) Cubicle lamps with switch One consider
j) Breaker charge One -
4 window for each part with test /
Acknowledge/re-set push button
for incomer & 6 windows for
4 Window for incomer & 12 window
k) Fault Annunciator Panel transformer controlling breakers
required for Trafo. Feeder.
with rest / acknowledge / re-set
push buttons & with common
hooter.

5 VOLTAGE TRANSFORMER
1 no. (Withdrawable) for incomer
5.1 Number 03 Nos. single phase PT consider.
indoor, epoxy resin cast
Burden 100VA, 3 ph. Class 0.5
5.2 Winding rating 33000V/ 110V, 3 lines as per IS : Core 1 :- 100VA, Cl 0.5
3156

CURRENT TRANSFORMER
6
(MEASURING &PROTECTION)
6.1 Numbers One set on each breaker
150A/ 5A for indoor epoxy resin
6.2 Rating – Incomer 150/5-5A
cast type, CTs shall be dual ratio
50A/5A for, indoor epoxy resin
6.3 Rating - Outgoing 50/5-5A
cast type, CTS shall be dual ratio
Two, 1 for metering & 1 for
6.4 No. of secondary 5-5A
protection
6.5 Burden/class 15VA, Class 0.5 accuracy 15VA, CL0.5
6.6 Standard IS : 2705 as per latest IS/IEC standard

7 MEASURING INSTRUMENTS
Digital Load Manager to read
voltage, current, kWh, demand MFM with CL 0.5 with RS 485
7.1 Multifunction Meter on each breaker
meter, THD & PF, Class 0.5 Comm.
accuracy

8 Interlocking Not applicable NA

3 nos. 33 kV, 100 kA (4/10 micro


second) High current impulse, DA 30KV, 10KA Indoor Surge arrestor
9 Distribution Surge Arrestor
series as per IEC. Make : Tyco consider in incomer panel.
Electronics

CRCA with pro treatment and oven


CRCA 2mm, RAL7032, 7tank
10 Enclosure baked epoxy paint finish, RAL –
process
7032.