3 Phase 4 Wire Multi Function Meter: User Manual
3 Phase 4 Wire Multi Function Meter: User Manual
NOVA
3 Phase 4 Wire Multi Function Meter
USER MANUAL
Standards Applicable
Accuracy : IEC62053-21 (Class 1.0)
Radio Interference : CISPR22
Fast Transient Burst : IEC61000-4-4
Surge Withstand : IEC61000-4-5
ESD : IEC61000-4-2
Impulse Voltage : IEC62052-11
Power On Display
Display check will be the first display when meter is powered ON.
Followed by Meter serial number and then firmware version will be displayed.
Display Modes
3) Freeze Mode
To see the selected parameter continuously, press up & down
scroll buttons together for 2 seconds.There is no time out period
for freeze mode. Press up or down scroll button to come out of
Freeze mode.The meter will go back to its previous scroll mode
(auto/manual).
Display Parameters
2. Average Voltage
3. Average Current
5. Frequency
7. R Phase Voltage
8. Y Phase Voltage
9. B Phase Voltage
16.Phase Sequence
17. Slave id *
19. Parity *
Press and hold the SELECT and scroll UP key together to move
to the Programming Mode. Press scroll DOWN key (used as
Escape key in programming mode) to come out from the
programming mode. “ESCAPE” will be displayed.
-Setting slave Id
-Setting Password
Meter will not record energy when it is in programming mode.Time out period of 2 min is
provided for programming mode.
Password Setting
·CT PT ratio should not exceed 999999, if exceeded the meter will display “dAtA Err”
·When CTPT Ratio is programmed ≥1000, energy in MWh (Mega watt hour) will be displayed as “kkWh”
.Decimal points on the display format will be changed according to the CTPT ratio programmed.
In the Programming Menu, press and hold scroll UP to get “Set SL Id”
and then press SELECT key.
Press UP key to increment the SL Id value. Press together UP and
SELECT key to shift to next digit. Press select key to set the id.
Slave id can be set from 1 to 247.
The RS485 interface uses MODBUS Protocol in RTU mode. Communicating with the
meter involves sending commands to the meter for reading and writing the
Protocol
particular register. The meter can be addressed with specific user defined
meter address (Slave ID) from1 to 247
Memory Map *
Password:
(Function Code 16)
Note: For changing any parameter, first password has to be entered, and then the parameters will
be enabled for writing. Once password is enabled idle time is 2 minutes and then comes out of
programming mode.
Meter Address 1 1
42,385
42,051 PT Primary 1 1
PT Secondary 1 1
42,052
Warranty
Larsen & Toubro warrants that 3 Phase 4 Wire Multi function Meter type NOVA is free from defects in
workmanship and material . Larsen & Toubro obligation under this warranty shall be for a period of 1
year from the date of sale subject to the following terms and conditions provided the notice of
defects and satisfactory proof thereof is given to Larsen & Toubro by its customer within the warranty
period.
1. Larsen & Toubro shall provide only repairs for the sold item.
2. Defective parts shall be serviced or replaced by Larsen & Toubro.
This warranty does not cover any defect in the product caused by accident, misuse, mishandling
includes improper electrical, mechanical installation), tamper, neglect, alteration/modification/
substitution of any of the components or parts or any attempt of internal adjustment by unauthorized
service personnel. For applicability of warranty, Larsen & Toubro shall be the sole judge. Under no
circumstance shall Larsen & Toubro Limited be liable for any consequential or resulting injury or for loss,
damage or expense directly or indirectly from the use of this product.The foregoing warranty is in lieu
of all other warranties expressed or implied and is the sole and exclusive remedy for any claim arising
from any defect in the product.
Disclaimer
Sufficient care is taken to provide all information regarding the product but Larsen & Toubro Limited
does not claim any responsibility for the damage caused by using the product directly or indirectly.
Precautions
1.The device must be installed, wired and serviced only by qualified personnel
2.Prior to any work on the device, de-energize the connected circuits before meter
installation and disconnection.
3.Always use an appropriate voltage detection device to confirm the absence of voltage
4.Always supply the device with the correct rated voltage.
5.Failure to take these precautions could cause serious injuries