TM

NOVA
3 Phase 4 Wire Multi Function Meter
USER MANUAL

L&T Electrical & Automation


Doc. No. 4D060163 Rev D.
Technical Specifications

Enclosure Engineering Plastic complying to IP-51


Dimension 96 X 96X105 mm (HXWXD)Panel Cutout: 92 X 92 mm
Connection 3P 4W
Display LCD with Backlit
Type Multi Function Meter
Measurements kWh / kW / Frequency / Voltage / Current/PF
Starting Current 0.2% of rated current (5A)
Class of Accuracy Class 1.0
Current 5A (rated), 10A (max)
Voltage (P-N) 3 X 240V (-30 % to +20 % of Vref)
Frequency 50Hz ± 5%
Auxiliary Supply 88V TO 300V AC/DC
Weight (Approximate) 470gm
Weight with Packaging 630gm
(Approximate)
Communication Interface RS 485 (Optional)

Standards Applicable
Accuracy : IEC62053-21 (Class 1.0)
Radio Interference : CISPR22
Fast Transient Burst : IEC61000-4-4
Surge Withstand : IEC61000-4-5
ESD : IEC61000-4-2
Impulse Voltage : IEC62052-11

Power On Display

Display check will be the first display when meter is powered ON.

Followed by Meter serial number and then firmware version will be displayed.

Display Modes

1) Auto Scroll Mode


By default meter will be in auto-scroll mode. All the display
parameters will be scrolling automatically in this mode. Scrolling
period for energy parameters is 8 sec and 2 sec for all other
parameters.
2) Manual Scroll Mode
Press UP/DOWN Key to Scroll Manually.In this mode all the
parameters can be scrolled through manually. If no key is
pressed for1minute,it will go back to auto scroll mode.

3) Freeze Mode
To see the selected parameter continuously, press up & down
scroll buttons together for 2 seconds.There is no time out period
for freeze mode. Press up or down scroll button to come out of
Freeze mode.The meter will go back to its previous scroll mode
(auto/manual).

Display Parameters

1. Cumulative Energy KWh

2. Average Voltage

3. Average Current

4. Total Active Power

5. Frequency

6. Total Power factor

7. R Phase Voltage

8. Y Phase Voltage

9. B Phase Voltage

10.R Phase Current

11.Y Phase Current

12.B Phase Current

13.R Phase Active Power

14.Y Phase Active Power

15.B Phase Active Power

16.Phase Sequence
17. Slave id *

18. Baud rate *

19. Parity *

. Display Parameters 17,18,19 are available only in RS485 models.


· Press select key and down key together to see these RS 485 parameters

Entering into Programming Mode

Press and hold the SELECT and scroll UP key together to move
to the Programming Mode. Press scroll DOWN key (used as
Escape key in programming mode) to come out from the
programming mode. “ESCAPE” will be displayed.

Enter the Password by pressing & holding the scroll UP key.


The default password is “0000”. Press and hold scroll UP
to increment the value of the blinking digit. Press and hold
SELECT and scroll UP together to shift to next digit.

Press SELECT key to enter the password. Password Accepted


('PASS ACPTD') or Password Error ('PASS Err') will be displayed.
Only if password is accepted, meter will enter into programming
mode.
The following programming options are available

-Programming CT/PT ratio

-Setting slave Id

-Setting communication port

-Setting Password

Meter will not record energy when it is in programming mode.Time out period of 2 min is
provided for programming mode.

Password Setting

In the Programming Menu, press and hold scroll UP key


to get “Set Pass” and then press SELECT key
Press UP key to change the blinking digit. Press UP and SELECT key
together to shift to next digit. Press SELECT key to save the password
Programming CT/PT ratio

In the Programming Menu, press and hold scroll UP key to get


“Ct Pt Ratio” and then press SELECT key.

-Press SELECT key When “Ct Pr 0001” is displayed to


program CT Primary current.
-Press and hold SELECT and scroll UP keys together to shift digit.
-Press scroll UP key to change value.
-Press SELECT key to save change. “L UPdAtE” will’
come in display. Again press select key to store the value.

-Scroll UP and press SELECT key When “Ct Se 0001” is displayed


to program CT Secondary current.
-In Same process program the CT Secondary value.

-Scroll UP and press SELECT key When “Pt Pr 0001”


is displayed to program PT Primary voltage.

-Press and hold SELECT key and scroll UP key together


to shift digit.
-Press scroll UP key to change value.
-Press SELECT key to save changes. “L UPdAtE” will come in
display. Again press select key to store the value.

-Scroll UP and press SELECT key When “Pt SE0001”


is displayed to program PT Secondary voltage.

-In Same process program the PT Secondary value.

·CT PT ratio should not exceed 999999, if exceeded the meter will display “dAtA Err”

·Pulse Rate = 2500 imp / kWh (for CT PT ratio = 1).

·Pulse rate will vary if CT/PT ratio is changed

·When CTPT Ratio is programmed ≥1000, energy in MWh (Mega watt hour) will be displayed as “kkWh”

.Decimal points on the display format will be changed according to the CTPT ratio programmed.

Communication Port Setting *

In the Programming Menu, press and hold scroll UP key


to get “Set Port” and then press SELECT key.

Baud rate selection (1200 to 19200): Use UP key to


select the desired baud rate then press SELECT
key to set. Similarly parity (Even/odd/none)
can be set here.
Slave ID Setting *

In the Programming Menu, press and hold scroll UP to get “Set SL Id”
and then press SELECT key.
Press UP key to increment the SL Id value. Press together UP and
SELECT key to shift to next digit. Press select key to set the id.
Slave id can be set from 1 to 247.

Communication Interface Details *


Meter is available with and with out RS485 communication.
RS485 interface is available at the terminals. Refer “CONNECTION DETAILS” diagram.
The configuration details to communicate with the meter are given below
Standard RS485 (half duplex)
Baud Rate Selectable (19200, 9600,4800, 2400, 1200).Default is 9600

Parity Selectable (None, Odd, Even ).Default is Even

The RS485 interface uses MODBUS Protocol in RTU mode. Communicating with the
meter involves sending commands to the meter for reading and writing the
Protocol
particular register. The meter can be addressed with specific user defined
meter address (Slave ID) from1 to 247

Memory Map *
Password:
(Function Code 16)
Note: For changing any parameter, first password has to be entered, and then the parameters will
be enabled for writing. Once password is enabled idle time is 2 minutes and then comes out of
programming mode.

Address Parameters Words

40513 Password for programming (PRIDES) 3

Read Only Parameters:


(Function Code 04)
Address Parameters Words MF
Instantaneous Parameters
30,001 Phase 1 Voltage 2 0.01
30,003 Phase 2 Voltage 2 0.01
30,005 Phase 3 Voltage 2 0.01
30,007 Phase 1 Current 2 0.001
30,009 Phase 2 Current 2 0.001
30,011 Phase 3 Current 2 0.001
30,013 Phase 1 Active Power 2 0.0001
30,015 Phase 2 Active Power 2 0.0001
30,017 Phase 3 Active Power 2 0.0001
30,019 Average Voltage 2 0.01
30,021 Average Current 2 0.001
30,023 Total Active Power 2 0.0001
30,025 Line Frequency 2 0.01
30,027 Cumulative kWh Energy 2 0.01
30,029 Power in Mega/Kilo
00: Power in Kilo 2
01: Power in Mega
30,033 Total Power factor 2 0.01
st
For address 07 to 17,23,33 if MSB (1 word) is 1 then 2's complement of the value is to be
taken.
Read write Parameters:
(Supported by function code 6 and 16 for writing and by function code 3 for reading)

Address Parameters Words MF


Communication Parameters

Meter Address 1 1
42,385

42,386 Baud Rate


2->1200; 3->2400; 4-> 1 1
4800; 5->9600; 6->19200
Parity 1 1
42,387
0->None; 1->Odd; 2->Even

CT PT ratio settings (1 to 999999)


42,049 CT Primary 1 1
42,050 CT Secondary 1 1

42,051 PT Primary 1 1

PT Secondary 1 1
42,052

Warranty
Larsen & Toubro warrants that 3 Phase 4 Wire Multi function Meter type NOVA is free from defects in
workmanship and material . Larsen & Toubro obligation under this warranty shall be for a period of 1
year from the date of sale subject to the following terms and conditions provided the notice of
defects and satisfactory proof thereof is given to Larsen & Toubro by its customer within the warranty
period.
1. Larsen & Toubro shall provide only repairs for the sold item.
2. Defective parts shall be serviced or replaced by Larsen & Toubro.
This warranty does not cover any defect in the product caused by accident, misuse, mishandling
includes improper electrical, mechanical installation), tamper, neglect, alteration/modification/
substitution of any of the components or parts or any attempt of internal adjustment by unauthorized
service personnel. For applicability of warranty, Larsen & Toubro shall be the sole judge. Under no
circumstance shall Larsen & Toubro Limited be liable for any consequential or resulting injury or for loss,
damage or expense directly or indirectly from the use of this product.The foregoing warranty is in lieu
of all other warranties expressed or implied and is the sole and exclusive remedy for any claim arising
from any defect in the product.
Disclaimer
Sufficient care is taken to provide all information regarding the product but Larsen & Toubro Limited
does not claim any responsibility for the damage caused by using the product directly or indirectly.

OVERALL DIMENSIONS (mm) CONNECTION DETAILS

1.Meter connection should be done exactly as shown in above diagram


2.Make the CT connections on terminals 1-2 (R-Ph), 3-4 (Y-Ph) and 5-6 (B-Ph)
3.Make the PT connections on the terminals 9 (R), 10 (Y), 11 (B) and 12 (N)
4.Connect the Auxiliary Supply (88V TO 300 V AC/DC) to the terminals 13 (-ve)
and 14 (+ve) to power ON the meter. It can be done by shorting one phase
with auxiliary as shown in the above picture.
Note: Pin numbers 7,8 are used for RS 485 communication which is optional.

* Features available only in RS 485 models.

Precautions
1.The device must be installed, wired and serviced only by qualified personnel
2.Prior to any work on the device, de-energize the connected circuits before meter
installation and disconnection.
3.Always use an appropriate voltage detection device to confirm the absence of voltage
4.Always supply the device with the correct rated voltage.
5.Failure to take these precautions could cause serious injuries

L&T Electrical & Automation

Manufactured by:
L&T Electrical & Automation
KIADB Industrial Area
Hebbal, Hootagalli
Mysore 570018
Karnataka, INDIA

© 2013 LARSEN & TOUBRO LIMITED