■ CODING LIST ESSENTIALS

GROUP ITEM DATA FUNCTION


30 10 72 Input selector block
11 0423 X1 connection terminal (field terminal AI)
12 3021 X2 connection terminal (output X0)
31 10 77 Deviation alarm block
11 0423 X1 connection terminal (present volume: field terminal AI)
12 3021 X2 connection terminal (stored volume: input selector output X0)
13 set High deviation setpoint (feed volume)
81 10 95 Sequential control block
11 130001 ST STEP 01
12 103001 OF G30 - 01 Input selector measured output
13 100501 OF DO Valve closed
14 010511 IN DI Feed command ON
15 130002 ST STEP 02
16 093001 ON G30 - 01 Input selector output held
17 130003 ST STEP 03
18 090501 ON DO Valve open
19 013111 IN G31 - 11 (Y1) When the deviation is larger than the set value
20 120001 BR BR 01 Branch to STEP 01

STEP 01 Standing by

• Input Selector providing measured value


STEP 01 • Blowdown valve closed

PBS ON

STEP 02 Input Selector holding present value


STEP 02
• Input Selector holding output

STEP 03 Feeding

• Blowdown valve open

STEP 03 Feeding Complete Deviation Alarm tripping when feeding


exceeds the setpoint.

Branch to STEP 01

SC100/200 Series Function Block Application Manual EM-6460-C 83