Professional Documents
Culture Documents
DTank Inspection (DRAFT) Rev.2
DTank Inspection (DRAFT) Rev.2
DTank Inspection (DRAFT) Rev.2
DEFORMING POSI- r (mm), Measurement from the tank's center (plumb line) to the inner shell wall
TANK TION
0⁰ 90⁰ 180⁰ 270⁰
TOP 693 (-7) 697 (-3) 700 700
EP-P-110-1 CENTER N/A 699 (-1) 702 (+2) 702 (+2)
BOTTOM 697 (-3) 696 (-4) 700 700
TOP 697 (-3) 694 (-6) 698 (-2) 700
EP-P-110-2 CENTER N/A 693 (-7) 702 (+2) 701 (+1)
BOTTOM 694 (-6) 696 (-4) 704 (+4) 702 (+2)
TOP 694 (-6) 699 (-1) 704 (+4) 698 (-2)
EP-R-110-1 CENTER N/A 701 (+1) 704 (+4) 698 (-2)
BOTTOM 696 (-4) 703 (+3) 703 (+3) 695 (-5)
TOP 689 (-11) 684 (-16) 702 (+2) 707 (+7)
EP-R-110-2 CENTER N/A 684 (-16) 705 (+5) 711 (+11)
BOTTOM 692 (-8) 686 (-14) 709 (+9) 710 (+100)
TOP 694 (-6) 695 (-5) 700 706 (+6)
EP-S-110-1 CENTER N/A 688 (-12) 702 (+2) 708 (+8)
BOTTOM 693 (-7) 691 (-9) 704 (+4) 709 (+9)
TOP 695 (-5) 696 (-4) 701 (+1) 698 (-2)
EP-S-110-2 CENTER N/A 698 (-2) 701 (+1) 699 (-1)
BOTTOM 701 (+1) 701 (+1) 698 (-2) 696 (-4)
Notes:
1. Center of the tank's diameter is taken from the plumb line originating from the center of the agitator nozzle.
2. Inside Diameter of the tank is ø1,400 mm, rdesign = 700 mm
3. "N/A" is due to the Manhole positioning.