Earthing current of about 153 mA (153 thousandths of an

amp). This is not nice, but it is unlikely to kill


you. If there are no shoes and hands are wet, the
Plastic impedance falls to 500 Ω and the current at
230 volts is 460 mA. This is getting decidedly

Pipes By Paul Cook of the


Institution of
Electrical Engineers
unpleasant. Immersion of the body in a bath, in
effect halves the impedance of the body and
current at 230 volts would then be as high as
1,000 mA. This is dangerous, and can kill.

You do not have to earth plastic pipes. Situation Body Current at


Impedance 230 V
Plastic pipes make for a safer electrical installation
and reduce the need for earthing. Festooning an Dry with shoes 3000+ Ω 76 mA
installation that has been plumbed in plastic pipe Dry 1500 Ω 153 mA
with green and yellow earth wire is not necessary Wet 500 Ω 460 mA
and is likely to reduce the level of electrical safety Body ½ immersed 250 Ω 920 mA
of the property, not increase it.
Everyone knows that water and electricity do not Horny dry hands and feet are quite good
mix, that the risk of electric shock is greater when insulators. However, if the hands are wet, salts
there is water around. They know that the risk and and contaminants improve the contact and reduce
severity of an electric shock is increased as a result the resistance of the skin. Dry skin has a high
of the presence of water. This may be the reason resistance, wet skin has a relatively low resistance.
for the concern that water in plastic pipes may The other reason why bathrooms and such places
conduct electricity and that bonding is required. are relatively risky electrically, is the presence of
Because of this, the IEE commissioned the earthed metal. Should you be unfortunate enough
Electrical Research Association to carry out to touch the live parts of broken equipment and
measurements of the electrical conductivity of nothing else except say a well insulated floor,
water in plastic pipes. there would be little result. Electrical jointers and
The ERA tests confirm that tap water in a plastic fitters regularly work live under such controlled
pipe is a poor conductor of electricity. One metre conditions. However, if you touch a live part and
of 15 mm diameter plastic pipe filled with tap an earthed metal pipe, then you get a very
water from Leatherhead where the ERA are based, dangerous electric shock.
has a resistance of 100,000 Ω. This one metre of An earthy environment where there are lots of
pipe will restrict currents to less than fatal values metal pipes is potentially less safe than an earth
and of course in practice, there would be many free environment. We can now start to see why
metres of pipe between metal items of plumbing plastic pipe installations are going to lead to safer
equipment and earth. installations. For a start, there is not all that
earthed metal around.
The resistance of water varies around the country,
it is reduced by impurities, not all of which are The bonding requirements for plastic piped and
harmful. The additives put into the water of metal piped installations is described below.
central heating systems to reduce corrosion make
the most difference, as can be seen from the table At the Service Position - Main Bonding
below.
In each electrical installation, main equipotential
Resistance of the water in 1 metre of bonding conductors (earthing wires) are required
plastic pipe to connect to the main earthing terminal for the
installation the following :
Resistance Ω
15 mm diameter, tap water 115,000 • metal water service pipes
20 mm diameter, tap water 65,000 • metal gas installation pipes
15 mm diameter, water with 20,200
double dose of inhibitor at 60°C • other metal service pipes and ducting
• metal central heating and air conditioning
So why do wet hands and immersion in a bath systems
increase the risk of electric shock?
• exposed metal structural parts of the building
The Human body plus clothes, particularly shoes
has an impedance of about 3,000 Ω - see table in • lightning protection systems
the next column. At 230 volts this will result in a

CD Revised Nov 2002 The IEE is not responsible for the opinions expressed in the above page. 1
It is important to note that the reference on the bonding and metal fitments attached to these
previous page, is always to metal pipes. If the plastic pipes also would not require supplementary
incoming service pipes are made of plastic, they bonding.
do not need to be main bonded.
It seems to be the practice of some builders to
If the incoming pipes are made of plastic, but the effect all the plumbing in plastic except for those
pipes within the electrical installation are made of bits of the pipework that are visible. These short
metal, the main bonding must be carried out. The lengths of metal pipework supplied by plastic
bonding being applied on the customer side of any pipes or metal taps connected to plastic pipes,
meter, main stopcock or insulating insert and of metal baths supplied by plastic pipes and with a
course to the metal pipes of the installation. plastic waste do not require supplementary
bonding.
The connections of the bonding wired to the pipes
has to be made with a proper clamp to BS 951 However, electrical equipment still does require to
complete with the label “SAFETY ELECTRICAL be supplementary bonded and if an electric
CONNECTION - DO NOT REMOVE.” shower, or radiant heater is fitted, they will require
to be supplementary bonded as usual.
If the incoming services are made of plastic and
the pipework within the building is of plastic then Supplementary bonds are required to be connected
no main bonding is required. If some of the to the protective conductor of all circuits
services are of metal and some are of plastic, then supplying electrical equipment in the bathroom
those that are of metal must be main bonded. e.g. at a flex outlet or switch.

Typical earthing arrangements and protective conductor csa - TN-C-S


supplier’s meter
meter tails 25 mm2

16 mm2 consumer unit


or distribution board

LABEL earthing bar


intake LABEL LABEL

10 mm2 LABEL
16 mm2
10 mm2 other
main main equipotential extraneous-
earthing bonding conductors conductive-
supply earth terminal metal metal parts
PME connection water gas pipe
pipe

TN-C-S: PME earth


Note: i) Main equipotential bonding conductors may be separate (as shown) or looped with unbroken conductors.
ii) Local electricity supply network conditions may require larger conductors.
iii) LABEL - Safety Electrical Connection - Do Not Remove.

In the bathroom - Supplementary Bonding


Figure 1 shows the supplementary bonding in a
Supplementary or additional equipotential bonding bathroom where the house is plumbed with metal
(earthing) is required in locations of increased pipes and Figure 2 shows the supplementary
shock risk. In domestic premises the locations bonding required in a bathroom where the
identified as having this increased shock risk are pipework is plastic.
rooms containing a bath or shower (bathrooms)
Metal radiators supplied by plastic pipes should
and if you are lucky enough to have one, in the
not be supplementary bonded. It is not safer to
areas surrounding swimming pools.
supplementary bond them, it is safer not to.
Please note, there is no specific requirement to Locations generally are safer if the location is
carry out supplementary bonding in domestic earth free as discussed earlier.
kitchens, wash rooms and lavatories that do not
There are many possible combinations of metal
have a bath or shower. That is not to say that
and plastic pipe arrangements in a bathroom. To
supplementary bonding in a kitchen or wash room
try and answer questions regarding the
is wrong (it would be wrong for plastic pipes) but
supplementary bonding required in a number of
it is not necessary.
permutations of copper and plastic pipe, Table A
below has been prepared.
For plastic pipe installations within a bathroom the
plastic pipes do not require supplementary

CD Revised Nov 2002 The IEE is not responsible for the opinions expressed in the above page. 2
Figure 1: Supplementary bonding in a bathroom - metal pipe installation

Ceiling
metal Pull cord switch luminaire
pipe
Outside Zones
Zone 2 Zone 3

shower Switch Radiant fire


for fire

Cord

Shaver
3.0 m Zone 1 Zone 2 unit Zone 3 2.25 m Outside Zones

Notes:
1. The protective conductors of
all power and lighting points
within the zones must be
supplementary bonded to all
Zone 0 extraneous-conductive-parts
metal pipes in the zones, including metal
waste, water and central
* heating pipes, and metal
baths and metal shower basins.
metal waste
2. Circuit protective conductors
0.6 m 2.4 m may be used as supplementary
bonding conductors.
* Zone 1 if the space is accessible without the use of a tool. 3. Metal baths not connected
Spaces under the bath, accessible only with the use of a tool, are outside the zones. to a metal building structure
do not require
supplementary bonding if all
metal pipes connected to
them has been bonded.
4. Connections to pipes to be
made with BS 951 clamps
(complete with “Safety
Electrical Connection” label).

Figure 2: Supplementary bonding in a bathroom - plastic pipe installation

Ceiling
plastic Pull cord switch
pipe
Outside Zones
Zone 2 Zone 3

shower Switch Radiant fire


for fire

Cord luminaire

Shaver
3.0 m Zone 1 Zone 2 unit Zone 3 2.25 m Outside Zones

Notes:
1. The protective conductors of
all power and lighting points
within the zones must be
supplementary bonded. The
Zone 0 bonding connection may be
plastic waste plastic pipes to the earth terminal of a
switch or accessory supplying
* equipment.
2. Circuit protective conductors
plastic waste
may be used as
. 0.6 m 2.4 m supplementary bonding
conductors.
* Zone 1 if the space is accessible without the use of a tool. 3. Supplementary bonding of
Spaces under the bath, accessible only with the use of a tool, are outside the zones. short lengths of copper pipe
installed where the pipes are
visible, is not necessary.
CD Revised Nov 2002 The IEE is not responsible for the opinions expressed in the above page. 3
Table A: Supplementary bonding in a number of permutations of copper and plastic pipe
Pipework material
Waste Cold Hot Central Supplementary bond Comments
Pipes Water Water Heating required between
1 Metal Metal Metal Metal All metal pipes, earth terminals Metal pipes can be used as
of protective conductors of bonding conductors if
class I and class II equipment, joints are metal to metal
and accessible exposed- and electrically continuous.
conductive-parts of the building
structure.
2 Plastic Plastic Plastic Plastic Earth terminals of protective Bonding of metal taps,
conductors of class I and metal radiators or metal
class II equipment and baths is not required unless
accessible exposed-conductive- the bath is connected to the
parts of the building structure. metallic building structure.
3 Plastic Plastic Metal Metal Hot water pipes, central heating A bond is not required to
pipes, earth terminals of the taps either hot nor cold,
protective conductors of or to metal baths unless
class I and class II equipment connected to the metallic
and accessible exposed- building structure.
conductive-parts of the building
structure.
4 Plastic Plastic Plastic Metal Central heating pipes, the earth Bonding of metal water
terminals of protective taps is not required, nor
conductors of class I and metal baths unless
class II equipment and access connected to the metallic
to exposed-conductive-parts of building structure.
the building structure.
5 Plastic Metal Metal Metal All metal pipes, earth terminals Metal pipes themselves can
of protective conductors of be used as bonding
class I and class II equipment, conductors if joints are
and accessible exposed- metal to metal and
conductive-parts of the building electrically continuous.
structure.
6 Plastic Metal Metal Plastic All metal pipes, earth terminals Metal central heating
of protective conductors of radiator does not require
class I and class II equipment, bonding.
and accessible exposed-
conductive-parts of the building
structure.

Notes:

1. Supplementary bonding is carried out to the 3 Metal baths supplied by metal pipes do not
earth terminal of protective conductors of require supplementary bonding if all the pipes
class I and class II equipment within the are bonded and there is no other connection of
bathroom. A supplementary bond is not run the bath to earth
back to the main earth,
4 All bonding connections must be accessible
2. Metal window frames are not required to be and labelled “Safety Electrical Connection -
supplementary bonded unless they are Do Not Remove”.
electrically connected to the metallic structure
of the building.

CD Revised Nov 2002 The IEE is not responsible for the opinions expressed in the above page. 4