Cross Girders Drawing-Model

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

2L-Y16-150c/c

Middle Girder welded lap joint Y16 lap to be welded End Girder
Y16-Dowel Rod with Dowel rod
Sec-1
Y16-Dowel Rod
4-Y12 4-Y12 4-Y25

200 2L-Y16-175c/c 128 108 128 108 128 128 108 128 108 128 2L-Y16-175c/c
7-Y12 7-Y12
Y10-175c/c 600 600 Y10-175c/c

Y16-150 c/c
1000
Y12-200 c/c

Y12-200 c/c
128 108 128 108 128 128 108 128 108 128
2L-Y16-150c/c
Cable 3 Cable 3
600 600
Flux
2L-Y16-175c/c 2L-Y16-175c/c Flux
Cable 1&2 128 108 128 108 128 128 108 128 108 128 Cable 1&2 2-Y16 Hangers
2L-Y12-175c/c 2L-Y12-175c/c
370 Y25-Dowel Rod
6-Y25
3-Y12 3-Y12 3-Y12 3-Y12 300
Y25 lap to be welded
4-Y12 with Dowel rod 4-Y12
Sec-1 Section at 1-1
800 1350 800 625

Sectional Details of End Cross Girder


Notes on Lap Welding:
1. Lap joint shall be made for dowels of 25dia, 16dia whose Ld is not Complied with the Codal Requirement.
2. Welding shall be carried out as per the recommendations for welding of BIS 9417-1989.
3.The Size of Electrodes according to the diameter of the bar to be welded shall be as follows.
Dia of the bar Size of the Electrode
Dia > (16mm to 28mm) 4.00 mm
4. The Arc welding shall be struck some where to the middle of the Joint and not at the begining of the Joint,