Indian Standard
CODEOFPRACTICEFORFIRESAFETYOF
INDUSTRIALBUILDINGS: COTTONGINNING
ANDPRESSING(INCLUDINGCOTTONSEED
DELINTERING)FAGTORIES
(First Revision )
0. FOREWORD
0.1 This Indian Standard ( First Revision > was arrangements for storage of kapas, cotton seeds,
adopted by the Bureau of Indian Standards on waste cotton, if any, and fully pressed bales.
29 February 1988, after the draft finalized by the This standard has been formulated to cover all
Fire Safety Sectional Committee had been these aspects. This standard was first published
approved by the Civil Engineering Division in 1964. Based on the recommendations of
Council. Tariff Advisory Committee on the basis of
0.2 Fires occur quite frequently in the gin experience gained by them in the past 24 years,
houses, delintering machines and cotton openers this revision has been prepared.
usually installed in press houses due to frictional 0.3 For the purpose of deciding whether a parti-
heat of high speed machines and also sparks from cular requirement of this standard is complied
foreign material coming in along with kupas, with, the final value, observed or calculated,
cotton or cotton seeds. Further, oily and greasy expressing the result of a test or analysis, shall
cotton waste and cotton seeds are subject to be rounded off in accordance with IS : 2-1960*.
spontaneous heating. The other causes of fire The number of significant places retained in the
in this type of factories are bad house-keeping, rounded off value should be the same as that of
congestion and faulty electrical equipment. In the specified value in this standard.
order to reduce fire losses, besides installation of
adequate fire-fighting equipment, it is necessary
to plan carefully and layout of buildings and the *Rules for rounding off numerical values ( revised ).
1
IS : 2716 - 1988
2
IS- : 2726 ; 1988
should be no other external windows or openings l&&l Ail wiring shall be carried out in steel
except ventilators and windows. Ventilator5 conduits ( see IS : 1653:1972* ).
should-be located at a height of not less than 3 m
from the ground level and same should be pro- 19.1.2 ‘All lighting fittings shall be of dust-
tected by 6 mm thick wired glass in steel frames. tight type.
Windows which are meant for exclusive use of 10.1.3 All electrical motors shall be of totally
firemen in an emergency should be of 6 mm enclosed type ( see IS : 1646.1982t ). -
thick wired glass in steel framework and normally
kept locked. They should be placed at a height 10.1.4 Switchgear installed in gin house, press
convenient for fire fighting operations and not house, delintering rooms and godowns should be
more than 15 m apart and 7 m from a blind of dust-tight type.
corner.
11. ILLUMINATION
8.4 Roofs - Roofs should be directly supported
from wall to wall without any intermediate 11.1 For effective fire fighting purposes, the
columns or posts. If the roofs are covered factory shall be fully illuminated as indicated
with corrugated iron sheets, it is necessary to below:
insert corrugated asbestos sheets at intervals of
6 m along the lower edge of the roof to facilitate Minimum Illumination
entry through the roof for fire fighting purposes. Godowns, 50 lux
It is advisable to leave the undersides of roofs of
corrugated iron sheets unpainted but if they are Ginning, delintering and 100 hlx
painted, non-flammable paint should be used. pressing sections
8.5 Ventilation - It is necessary to provide Open compound ’ 20 lux
ventilator openings in corrugated iron sheet roofs.
The ventilator openings should not exceed 12. FIRE FIGHTING ARRANGEMENTS
1’2 x 0.3 m and at least one ventilator should be
provided in, every other bay. All ventilators 12.1 Al.1fire -fighting arrangements should be in
should be protected by either expanded metal or accordance with the following.
wire netting having apertures of 12’5 mm size.
12.1.2 The hydrant pump should be of not
9.. MACHINERY less than 1 800 litres per minute capacity, deliver-
ing water at a minimum pressure of 7 kgf/cm*
9.1 All machinery and line shafts should be fitted and located at least 15 m away from all the
with ball or roller bearings. buildings and 90 m away from any storage area.
9.2 Machinery should be 50 installed, arranged 12.1.2 Pump should draw water from a pucca-
and worked as to prevent, as far as is practicable, lined ground reservoir of not less than 180 000
the access of kupas, cotton or cotton seeds to litres capacity.
moving parts or the machinery not intended to
receive kupas, cotton or cotton seeds. 12.1.3 All underground hydrant mains and
hydrant branches should be not less than 100
9.3 Immediately before any material is intro- mm and 80 mm in diameter, respectively. Large
duced into any machinery for the first time in size mains should be provided in case of factories
any ginning season, all the machinery should be which are larger than average or which have
run for at least four hours and during and at the ginning seasons above normal. The mains should
end of this running, all bearings should be tested be so designed that a minimum pressure of
for over-heating. 7 kgf/cm* is available at the hydraulically most
remote point whilst considering full flow in the
9.4 In case of any replacement of a bearing or
mains.
shaft during the season, the machinery should be
run empty for two hours and the bearings tested 121.4 Hydrants should be distributed in the
for over-heating before any material is passed compound in such a way that every portion of a
through them. storage area is protected by at least two hydrants
at a distance not exceeding 35 m and at least two
9.5 Gins should be equipped with efficient and hydrants exist within 15 m of godowns or sheds
practicable stripping arrangements. used for the storage of cotton or kapas. There
should also be at least three hydrants within 3 m
10. ELECTRICAL INSTALLATION
of pressing, ginning or delintering houses.
10.1 The electrical installation shall be in accord-
ance with IS : 1646-1982*. *Specification for rigid steel conduits for electrical
wiring ( second revision).
*Code of practice for fire safety of building ( general 1: f&de of practice for fire safety of buildings ( general ):
Electrical installations. Electrical installations.
c
IS :2726 - 1988
4
BUREAU OF INDIAN STANDARDS
Headquarters:
Branch Offices:
Pushpanjali, First Floor, 205A West High Court Road, Shankar Nagar ‘25171
Square, NAGPUR 440010
Institution of Engineers ( India ) Building, 1332 Shivaji Nagar, 52435
PUNE 411005
*Sales Office in Calcutta is at 5 Chowringhee Approach, P. 0. Princep Street, Calcutta 700072 275800
@ales Office in Bombay is at Novelty Chambers, Grant Road, Bombay 400097 896528