CIAC AFTER SALES

TRAINNING
D.C. Inverter VRF

Category of IMVF Malfunction


Category of IMVF Malfunction
Category of IMVF Malfunction
Category of IMVF Malfunction

Main Board

valve control of complete unit, pressure test, temperature test of


temperature sensor, malfunction display, communication with drive panel
Category of IMVF Malfunction

Transfer Board

communication with main control panel, indoor unit


Category of IMVF Malfunction

3-phase Filter Board

Prevent the electric network from affecting the complete unit.


Category of IMVF Malfunction

Compressor Board

• filter
• rectifier
• Cement
resistance
• AC contactor
• electrolytic
capacitor
• module

control DC inverter compressor


Category of IMVF Malfunction

Overcurrent Protection Board

Detect the current of


the constant
frequency
compressor. When
the current is too
heavy, protection will
happen.
Category of IMVF Malfunction

Fan Motor Board

Drive DC fan
Category of IMVF Malfunction

Trouble shows on:


Category of IMVF Malfunction

1. Refrigeration System Type

2. Control and Communication Type

3. Drive Control Type

4. Part and Device Type


Analysis of Refrigeration System Type Malfunction

1. High Pressure Protection E1

Defining:
High pressure switch: Higher than a specific level (e.g. 4.2MPa)
High pressure sensor:4.4Mpa
The system pressure has a lot to do with the compressor running load.
Thus it has a direct influence on the operating life of the compressor. To
control the high pressure is to protect the compressor.

2 Ways to Achieve
High Pressure High Pressure
Sensor Switch
Analysis of Refrigeration System Type Malfunction

1. High Pressure Protection E1

High pressure protection

Use pressure gauge to No Is the pressure Yes


measure the pressure whether switch working normally? replace main board of the outdoor unit
it's real high ?

Yes
No

No
Are the operational modes
refer to specification of indoor unit
of the indoor unit set correctly?

replace the pressure switch


Yes

No
Are the gas and liquid completely open the valve
valves open?

Yes
Analysis of Refrigeration System Type Malfunction

1. High Pressure Protection E1


Yes

Has the panel of No


outdoor unit been install the panel
sealed properly?

Yes

Is the ventilation No
for the indoor and outdoor remove obstacles
units smooth?

Yes

No
Are the fans of the indoor and measure the fan motor and the signal input
outdoor units working?

Yes

No
Are the swing blades Check the swing motor and the signal input
completely open?

Yes
Analysis of Refrigeration System Type Malfunction

1. High Pressure Protection E1

Yes

Is the capacity output No


of the outdoor unit the same as refer to the capacity of indoor and outdoor unit
that of the indoor unit

Yes

No
Does the electronic expansion make sure the valve body meshs with the valve coil
valve works properly?

Yes

Are the filters or


Yes
heat exchange fins for the
indoor and outdoor units refer to maintenance in specification
contaminated or jammed?

No

the system pipes are jammed check the inlets and outlets of the main pipes that are connected with the indoor unit and the electronic
expansion valve of the outdoor unit. Replace the expansion valve and the dryer filter.
Analysis of Refrigeration System Type Malfunction

2. Prevention Against Low Temperature E2

Defining: When the coil temperature of IDU is lower -2°C,


IDU would stop cooling and switch to fan mode

Avoid the frosting of the IDU coil,


which would do harm to the cooling performance and other relevant safety parameter.
Similar to the Defrost function of ODU
Analysis of Refrigeration System Type Malfunction

3. Low Pressure Protection E3


Low pressure switch: lower than a specific level (e.g. 0.15 MPa)
Low pressure sensor:

Outdoor Temp. Protection Recover


(℃ ) (MPa) (MPa)
T>0 0.661
cooling T≤0 0.332 0.418
heating T≤0 0.168 0.373
Analysis of Refrigeration System Type Malfunction

4. Exhaust Temperature Protection E4

Defining:
When exhaust temperature (or the shell) of the compressor is higher than a specific level (e.g.
118°C), the system would automatically shuts down

Influence
Bad radiating of Bad lubricating
the compressor property of the
winding, cause refrigeration oil,
the damage of the even cause the
compressor charring
Analysis of Refrigeration System Type Malfunction

4. Exhaust Temperature protection E4

Cause by:
Lack of refrigerant
Over current of compressor
High outdoor ambient temp.
Less refrigerant flow (blockage )
Analysis of Control & Communication Type Malfunction

5. Communication Protection E6

Cause:
1) Connection of the ODU and IDU
2) Connection of the ODU and ODU
3) Wrong setting of the main board switch and
address DIP switch

Please refer to the MAIN BOARD SWITCH GUIDE.


Analysis of Control & Communication Type Malfunction

5. Communication Protection E6

1) To check the connection: Add the ODU or IDU one by one;


2) Change the ADD switch and No. switch on main-board when add a ODU.
Analysis of Control & Communication Type Malfunction

6. Sensor malfunction

Temperature sensors:
1) 15K: Ambient temp sensor of IDU/ODU
2) 20K: Inlet/middle/outlet temp sensor of heat
exchanger
3) 50K: Discharge temp or shell temp
Analysis of Control & Communication Type Malfunction

6. Sensor malfunction

Temperature sensors:
1) 15K: Ambient temp sensor of IDU/ODU
Analysis of Control & Communication Type Malfunction

6. Sensor malfunction

Temperature sensors:
2) 20K: Inlet/middle/outlet temp sensor of heat
exchanger
Analysis of Control & Communication Type Malfunction

6. Sensor malfunction

Temperature sensors:
3) 50K: Discharge temp or shell temp
Analysis of Control & Communication Type Malfunction

6. Sensor malfunction

Pressure sensors:
1) High pressure sensor
2) Low pressure sensor
Analysis of Drive Control Type Malfunction

1. E5 Protection
There are several kinds of causes for
Compressor is running, but E5.
the discharge temp. is lower Please write down the LED display
than the high-pressure. on the main board (both master
Check the wiring or board and drive board) to confirm it.
compressor

Fix frequency
Malfunction of fan Malfunction of the drive
compressor over
board board for compressor
current
Check the led Check the led display and
Check the current and
display and confirm confirm
confirm
Analysis of Drive Control Type Malfunction

1. E5 Protection
Analysis of Drive Control Type Malfunction

1. E5 Protection
How to check: Drive board or DC inverter compressor
Analysis of Drive Control Type Malfunction
2. Ultra-low Voltage of DC Input
Defining: When the voltage of VDC is lower than 375V(205V), drive board shows error,
system shuts down
Avoid compressor running under the ultra low voltage, which would cause the high
current, to protect the compressor
Low-voltage protection of DC bus-bar
Adjust the voltage
Check if input voltage of power yes to 380V(220V) and
check if the
cord is lower than 320V(180V) malfunction will be
cleared.
no

Replace the drive board of no


compressor with a better one.

Finish
Analysis of Drive Control Type Malfunction

2. Ultra-low Voltage of DC Input

Voltage Meter

Filter Board

Commutating
Bridge

voltage Meter
Analysis of Drive Control Type Malfunction

3. Ultra-high Voltage of DC Input


Defining: When the voltage of VDC is higher than 680V(395V), drive board shows
error, system shuts down
Avoid compressor running under the ultra high voltage, to protect the devices and part

Over voltage protection of DC bus-bar


Adjust the voltage
Check if input voltage of yes to 380V(220V) and
power cord exceeds check if the
460V(265V) malfunction will be
cleared.
no

Replace the drive board of no


compressor with a better one.

Finish
Analysis of Drive Control Type Malfunction

4. Abnormal IPM Module

Defining: When the current of IPM module on the drive board is too high, or
temperature is too high, it would show this malfunction.
It’ s a kind of hardware protection.

Avoid over current of compressor , protect the compressor and PCB.


Analysis of Drive Control Type Malfunction
4. Abnormal IPM Module
Procedure to check the IPM

Turn off the unit and wait for the capacitor to discharge until the voltage is under
36V.Use the multimeter, turn to diode testing point, release the U V W wire of the
compressor and start testing. Measure the diode voltage between U-P, V-P, W-P , N-U,
N-V, N-W
Analysis of Drive Control Type Malfunction
4. Abnormal IPM Module
Inside structure of IPM and test conclusion
DC+

PWM1H PWM2H PWM3H

M1 M2 M3

PWM1L PWM2L PWM3L

DC-

Conclusion of the testing result:


1. If the voltage tested is 0.3~0.7V, there is no short circuit of the module.
2. If the voltage tested is 0V, there is short circuit. The IPM board needs to be replaced.
Analysis of Drive Control Type Malfunction

5. Less Phase
Defining: The phase sequency wire U,V,W is not connected.
Make sure the U,V,W wire is connected well before the compressor runs.

Less phase protection


After the power
cord of compressor
Check if power cord of no is connected well,
compressor is connected well. check if
malfunction is
yes removed.
Replace the drive board of no
compressor with a better one

Finish
Analysis of Drive Control Type Malfunction

6. Current protection of compressor


Defining: Over current on the compressor tested by the drive board
When over current occurred on the compressor,
protecting the PCB and compressor.
Over current protection of drive board of compressor

Check if resistances among yes Replace


U,V and W are equal or if the compressor
earthed circuit is short circuit.

no
Drive board of compressor no
is damaged and shall be
replaced.

Finish
Analysis of Drive Control Type Malfunction

7. Malfunction of the current sensor


When the drive board is power on, it inspects the output of current is abnormal. The
error code would be shown and the compressor could not work.

Malfunction of Current Sensor

Drive board of compressor is


abnormal and it shall be
replaced.

Finish
Analysis of Drive Control Type Malfunction
8. Communication error from Inverter
driver to master control
Defining: communication fault between the drive board and master board, the data
transfer between them is abnormal

Make sure the communication between drive board and master board is fine.
Analysis of Drive Control Type Malfunction
8. Communication error from Inverter
drive to master control
Analysis of Drive Control Type Malfunction
9. High temp of thermal fin, IPM module
or PFC module
Defining: Temperature of the IPM module is over 95°C
Make sure the IPM module is running under appropriate temperature, and protect it
from damage of over temp.
Overheating protection for IPM module
Drive bpard of
yes compressor is
Check if such malfunction occurs
as soon as the unit is energized. abnormal
which shall be
no replaced.

Check if screws are screwed up no


and if IPM module is spread with
heat dispersion paste

Finish
Analysis of Drive Control Type Malfunction
10. Malfunction of ODU fan
motor drive
Defining: Communication error between fan motor board and master control, data
transfer is abnormal

Make sure the communication between fan motor board and master control is fine.
Analysis of Drive Control Type Malfunction
10. Malfunction of ODU fan
motor drive
Analysis of Drive Control Type Malfunction

11. Current protection of fan motor drive


Defining: Over current of the fan motor being inspected by the fan motor board
When the fan motor is having over current, protect the control board and fan motor.

Over current protection of drive board of fan

Check if resistances among yes


U,V and W are equal or if the Replace fan
earthed circuit is short circuit.

no
Drive board of fan is no
damaged, which shall be
replaced.

Finish
Analysis of Drive Control Type Malfunction

11. Voltage protection of fan motor drive


Defining: VDC voltage is higher than 388V , or lower than 210V
Prevent the fan motor board running from the high or low voltage

Voltage protection of fan motor drive

Adjust the input AC


Check if VDC voltage of power yes voltage to 220V
cord is lower than 210V or and check if the
higher than 388V malfunction will be
cleared.
no
Replace the drive board of fan no
motor drive with a better one.

Finish
Analysis of Drive Control Type Malfunction

12. Overheat protection of fan motor module


Defining: High temp of the IPM module on the fan motor board
Prevent the IPM module running from the high temperature(95°C)

Overheating protection for IPM module

yes Drive board of


Check if such malfunction occurs fan is abnormal
as soon as the unit is energized. which shall be
replaced.
no
Check if screws are screwed up no
and if IPM module is spread with
heat dispersion paste

Finish
Analysis of Drive Control Type Malfunction

13. Overheat protection of fan motor


Defining: High temp of fan motor
Prevent the fan motor running from the high temperature
Overheating protection of fan

Check if resistance for yes Replace


overheating protection of fan motor
is 0; check if earthed circuit of
fan is short circuit.

no
Drive board of fan is damaged, no
which shall be replaced.

Finish
Diagnosis of IMVF Malfunction
A .Use the portable debugger
Diagnosis of GMV Malfunction

B. Use the commission software


Analysis of Part and Device Malfunction

Part and device malfunction mainly includes the error of


temp sensor and pressure sensor. Usually there are 2 ways:
short circuit and open circuit. Solution is to replace the part
and device accordingly.

Use the multimeter and test the value of resistance. If it is 0


ohm, there is a short circuit. If the value is infinite, there is
an open circuit.