CIAC IMVF Troubleshooting 2010
CIAC IMVF Troubleshooting 2010
TRAINNING
D.C. Inverter VRF
:
Main Board
Transfer Board
Compressor Board
• filter
• rectifier
• Cement
resistance
• AC contactor
• electrolytic
capacitor
• module
Drive DC fan
Category of IMVF Malfunction
Defining:
High pressure switch: Higher than a specific level (e.g. 4.2MPa)
High pressure sensor:4.4Mpa
The system pressure has a lot to do with the compressor running load.
Thus it has a direct influence on the operating life of the compressor. To
control the high pressure is to protect the compressor.
2 Ways to Achieve
High Pressure High Pressure
Sensor Switch
Analysis of Refrigeration System Type Malfunction
Yes
No
No
Are the operational modes
refer to specification of indoor unit
of the indoor unit set correctly?
No
Are the gas and liquid completely open the valve
valves open?
Yes
Analysis of Refrigeration System Type Malfunction
Yes
Is the ventilation No
for the indoor and outdoor remove obstacles
units smooth?
Yes
No
Are the fans of the indoor and measure the fan motor and the signal input
outdoor units working?
Yes
No
Are the swing blades Check the swing motor and the signal input
completely open?
Yes
Analysis of Refrigeration System Type Malfunction
Yes
Yes
No
Does the electronic expansion make sure the valve body meshs with the valve coil
valve works properly?
Yes
No
the system pipes are jammed check the inlets and outlets of the main pipes that are connected with the indoor unit and the electronic
expansion valve of the outdoor unit. Replace the expansion valve and the dryer filter.
Analysis of Refrigeration System Type Malfunction
Defining:
When exhaust temperature (or the shell) of the compressor is higher than a specific level (e.g.
118°C), the system would automatically shuts down
Influence
Bad radiating of Bad lubricating
the compressor property of the
winding, cause refrigeration oil,
the damage of the even cause the
compressor charring
Analysis of Refrigeration System Type Malfunction
Cause by:
Lack of refrigerant
Over current of compressor
High outdoor ambient temp.
Less refrigerant flow (blockage )
Analysis of Control & Communication Type Malfunction
5. Communication Protection E6
Cause:
1) Connection of the ODU and IDU
2) Connection of the ODU and ODU
3) Wrong setting of the main board switch and
address DIP switch
5. Communication Protection E6
6. Sensor malfunction
Temperature sensors:
1) 15K: Ambient temp sensor of IDU/ODU
2) 20K: Inlet/middle/outlet temp sensor of heat
exchanger
3) 50K: Discharge temp or shell temp
Analysis of Control & Communication Type Malfunction
6. Sensor malfunction
Temperature sensors:
1) 15K: Ambient temp sensor of IDU/ODU
Analysis of Control & Communication Type Malfunction
6. Sensor malfunction
Temperature sensors:
2) 20K: Inlet/middle/outlet temp sensor of heat
exchanger
Analysis of Control & Communication Type Malfunction
6. Sensor malfunction
Temperature sensors:
3) 50K: Discharge temp or shell temp
Analysis of Control & Communication Type Malfunction
6. Sensor malfunction
Pressure sensors:
1) High pressure sensor
2) Low pressure sensor
Analysis of Drive Control Type Malfunction
1. E5 Protection
There are several kinds of causes for
Compressor is running, but E5.
the discharge temp. is lower Please write down the LED display
than the high-pressure. on the main board (both master
Check the wiring or board and drive board) to confirm it.
compressor
Fix frequency
Malfunction of fan Malfunction of the drive
compressor over
board board for compressor
current
Check the led Check the led display and
Check the current and
display and confirm confirm
confirm
Analysis of Drive Control Type Malfunction
1. E5 Protection
Analysis of Drive Control Type Malfunction
1. E5 Protection
How to check: Drive board or DC inverter compressor
Analysis of Drive Control Type Malfunction
2. Ultra-low Voltage of DC Input
Defining: When the voltage of VDC is lower than 375V(205V), drive board shows error,
system shuts down
Avoid compressor running under the ultra low voltage, which would cause the high
current, to protect the compressor
Low-voltage protection of DC bus-bar
Adjust the voltage
Check if input voltage of power yes to 380V(220V) and
check if the
cord is lower than 320V(180V) malfunction will be
cleared.
no
Finish
Analysis of Drive Control Type Malfunction
Voltage Meter
Filter Board
Commutating
Bridge
voltage Meter
Analysis of Drive Control Type Malfunction
Finish
Analysis of Drive Control Type Malfunction
Defining: When the current of IPM module on the drive board is too high, or
temperature is too high, it would show this malfunction.
It’ s a kind of hardware protection.
Turn off the unit and wait for the capacitor to discharge until the voltage is under
36V.Use the multimeter, turn to diode testing point, release the U V W wire of the
compressor and start testing. Measure the diode voltage between U-P, V-P, W-P , N-U,
N-V, N-W
Analysis of Drive Control Type Malfunction
4. Abnormal IPM Module
Inside structure of IPM and test conclusion
DC+
M1 M2 M3
DC-
5. Less Phase
Defining: The phase sequency wire U,V,W is not connected.
Make sure the U,V,W wire is connected well before the compressor runs.
Finish
Analysis of Drive Control Type Malfunction
no
Drive board of compressor no
is damaged and shall be
replaced.
Finish
Analysis of Drive Control Type Malfunction
Finish
Analysis of Drive Control Type Malfunction
8. Communication error from Inverter
driver to master control
Defining: communication fault between the drive board and master board, the data
transfer between them is abnormal
Make sure the communication between drive board and master board is fine.
Analysis of Drive Control Type Malfunction
8. Communication error from Inverter
drive to master control
Analysis of Drive Control Type Malfunction
9. High temp of thermal fin, IPM module
or PFC module
Defining: Temperature of the IPM module is over 95°C
Make sure the IPM module is running under appropriate temperature, and protect it
from damage of over temp.
Overheating protection for IPM module
Drive bpard of
yes compressor is
Check if such malfunction occurs
as soon as the unit is energized. abnormal
which shall be
no replaced.
Finish
Analysis of Drive Control Type Malfunction
10. Malfunction of ODU fan
motor drive
Defining: Communication error between fan motor board and master control, data
transfer is abnormal
Make sure the communication between fan motor board and master control is fine.
Analysis of Drive Control Type Malfunction
10. Malfunction of ODU fan
motor drive
Analysis of Drive Control Type Malfunction
no
Drive board of fan is no
damaged, which shall be
replaced.
Finish
Analysis of Drive Control Type Malfunction
Finish
Analysis of Drive Control Type Malfunction
Finish
Analysis of Drive Control Type Malfunction
no
Drive board of fan is damaged, no
which shall be replaced.
Finish
Diagnosis of IMVF Malfunction
A .Use the portable debugger
Diagnosis of GMV Malfunction