Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

pcs 20/7/04 9:41 PM Page 1

Conditions influencing
coke formation
Hotspots in fired heaters can lead to accelerated rates of coking and tube failure.
Two examples show how integrating fireside and oil-side calculations can help
identify and correct conditions leading to high localised peak flux rates
Tony Barletta
Process Consulting Services Inc

Rate of coke formation


H
igh tube metal temperatures equipment, there is no free lunch.
(TMTs) and coking in fired Fundamental principles cannot be Coke forms because the oil film
heaters continue to reduce run violated without paying the temperature and residence time exceed
lengths and in some instances cause consequences. In fired heaters, rapid the oil’s thermal stability. The oil film
tube failure. High TMTs are the result of coke formation and high TMTs are often temperature depends on the heat flux
non-uniform heat flux distribution in the outcome. and oil mass velocity. Raising the heat
the firebox and tube-side conditions Specific heater design will determine flux increases the oil film temperature at
that lead to accelerated rates of coke the severity of non-uniform heat flux a fixed mass flux, while a higher mass
formation. Several factors including the distribution. Hence, typical evaluation flux lowers the film temperature at a
number of burners, burner layout, criteria such as average radiant section given heat flux. The oil residence time
burner flame length, burner to tube heat flux or maximum duty can be depends on the oil’s mass velocity and
spacing, firebox height to width (L/D) misleading. For instance, design the amount of coil steam or condensate
and non-ideal flue gas flow patterns guidelines for vacuum heaters may added to each heater pass (vacuum and
influence heat flux distribution. specify that the average radiant heat flux coker heaters). A lower residence time
2
Moreover, tube-side conditions that should not exceed 10 000 btu/hr-ft -ºF. reduces the rate of coke formation.
affect the rate of coke formation such as In one instance, a vacuum heater Radiant section heat flux varies from
2
tube size, oil mass velocity and oil operating at only 9000 btu/hr-ft -ºF was the combustion zone where the fuel/air
residence time need to be considered. decoked every two years. Whereas mixture is burned to the flue gas outlet
When local conditions generate high another operates reliably for four years from the radiant section. In the
TMT, determining the root cause is at an average heat flux of approximately combustion zone, the maximum heat
2
essential. Otherwise, the problem 12 000 btu/hr-ft -ºF. Fireside design flux is controlled by direct flame or hot
cannot be fixed. In some instances, it is problems that cause very high, localised gas radiation. Direct flame radiation
more cost effective to improve fireside heat flux will produce elevated TMTs depends on the number of burners,
performance. In others, tube-side even when there is no coke in the tubes. flame size, distance between the burners
changes are needed. This often raises the film temperature and burner-to-tube spacing. In some
Two cases will illustrate how local above the oil’s thermal stability and instances, direct flame radiation
conditions can lead to high TMT, high causes coke to form. At very high, controls the maximum heat flux in the
rates of coke formation and short run localised heat flux, even a small amount combustion zone. Talmor’s (Talmor, E,
lengths. In each example, revamp of coke results in very high TMTs. In “Combustion Hot Spot Analysis for Fired
modifications increased run length by these instances, tube metallurgy limits Process Heaters,” Gulf Publishing, 1982)
reducing heat flux variability or can be exceeded. combustion zone heat flux calculation
improving tube-side operation. Even when localised heat flux is not should be used to identify the specific
extremely high, coke can form because location of the hotspots.
Hotspots – local conditions the tube-side conditions result in oil film In many heaters, the highest heat flux
Hotspots exist in all fired heaters’ temperature and residence time above is outside the combustion zone. Here,
radiant sections; the magnitude depends the oil’s thermal stability limits. Tube the flue gas temperature determines the
on the specific heater design. Since size (oil mass velocity) and the location maximum heat flux. These hotspots can
many heaters have been purchased of the outlet tubes are important be determined by measuring the TMTs
solely on lowest initial installed cost, the considerations affecting the rate of coke when the heater is clean, through direct
low bidder is forced to supply an formation. It is not unusual to have the heat flux measurements with a flux
“inferior” design. Lowering cost may pass outlet tubes routed through the probe or calculation using a proprietary
include reducing the number of burners, highest heat flux zone. Furthermore, program such as HTRI that performs a
decreasing the distance between the outlet tubes for heaters such as vacuum zone analysis and considers burner type,
burners, lowering the distance between heaters are often larger diameter. The location, flame size and distance from
the burner centreline to tube face, larger diameter results in lower mass burner centreline to tube face.
stacking the tubes passes along the wall, flux, higher oil film temperature and Coking occurs when the oil film
increasing the L/D or several other cost- increased oil residence time, and can temperature is too high for too long. The
saving considerations. However, many lead to high rates of coke formation if film temperature (at a fixed heat flux)
of the techniques that lower cost also the tubes are located in the highest heat depends on the tube-side heat-transfer
cause large heat flux variability flux zone. In summary, localised coefficient. Increasing the mass flux by
throughout the firebox or degrade tube- hotspots can be caused by fire- or tube- decreasing the tube size raises the heat-
side operation. As with most process side design shortcomings, or both. transfer coefficient and lowers the film

00
P T Q REVAMPS & OPERATIONS
pcs 20/7/04 9:41 PM Page 2

temperature. Conversely, when the tube film temperature and residence times 10–12 ft of the radiant section showed
size is increased (such as heater outlet are established from the heater model, damage from high temperature.
tubes), the heat-transfer coefficient the oil’s thermal stability can be Interestingly, burner flame lengths were
decreases, thereby increasing the oil film assessed. A lower oil residence time approximately 10–12 ft.
temperature and residence time. permits a higher allowable temperature Combustion zone problems occur
Furthermore, when the pass outlet tubes for a given level of thermal stability. when the localised heat flux from direct
are routed through the highest heat flux While thermal stability depends on the flame radiation exceeds that calculated
zone, the oil film temperature and oil type and upstream processing, it can from hot gas radiation. The maximum
residence time often exceed the oil’s be represented as an exponential heat flux in the combustion zone
thermal stability, rapidly forming coke function of oil film temperature and depends on the number of burners,
inside the tubes. When coke residence time. For instance, even burner layout, heat release per burner,
accumulates inside the tubes, it acts as though the coker heater’s operating burner volume and burner-to-tube
an insulator, raising TMTs. In some temperatures cause thermal cracking to spacing. In this case, very high, localised
instances, TMTs exceed the maximum occur inside the heater tubes, it is the oil heat flux in three areas of the
temperature for the tube metallurgy for residence times and film temperature combustion zone was evident from
extended periods, causing the tube to that dictate the rate of coke lay-down infrared TMT measurements and tube
rupture. inside the tube. The TMTs will increase metallurgical evaluation. Infrared scans
as coke forms inside a tube, to the point showed TMTs highest in the area
Fired heater models where the heater must be decoked. predicted by Talmor’s peak heat flux
Various models are used to design and Reducing the rate of coke formation to method for combustion zones.
predict the operation of fired heaters. increase heater run length requires Furthermore, one of the three hot zones
These make several assumptions about either lower oil residence time or lower had even higher heat flux than the
the actual heater’s performance. Some oil film temperature, and sometimes other two.
assume that the radiant section is a well- both.
stirred isothermal zone or that the flue Burner layout
gas flows upwards, with the radiant Case study 1 Burner configuration plays a significant
section heat flux determined by hot gas Poor burner layout role in combustion zone heat flux and
radiation alone. Some models take into In Case study 1, a vertical cylindrical flue gas flow patterns. Burner layout,
account direct flame radiation in the hydrotreater reactor heater that had number of burners, distance between
combustion zone, while others ignore operated well for years began to have burners and heat release per burner all
the specific burner system design problems when the fired duty was affect the localised heat flux. Figure 1
completely. Rarely will a fired heater’s increased. Very high, localised heat flux shows the heater floor with three
model default match the operation of a raised the oil’s film temperature above burners installed on an equilateral
specific heater design. Thus, most the thermal stability limit of the oil, triangular pitch. Visual inspection of the
models fail to predict local conditions forming a thin coke layer inside the burner locations inside the heater (and
without the user manipulating them. tubes. Since the thin layer of coke raised from the heater drawings) shows three
Since actual heater design is so variable, the resistance to heat transfer at a very areas where the distance from the
the model user must have significant high heat flux, TMTs increased above burner to the tube face is small. Heat
know-how concerning fire- and tube- the metallurgical limits, causing a tube flux from direct flame radiation
side operations. Field measurements and to fail. Although tube failure was increases as the distance from a flame to
observations are critical. Simple localised, several tubes in the bottom a tube decreases. Infrared measurements
techniques like throwing baking soda of TMTs showed the three areas
into the burners to observe flame closest to the burners had the highest
behaviour may be used to identify TMTs and one of the three higher
One of four
flame impingement. Heater models than the other two.
passes
can be powerful tools, but they can Distributing heat in the
also easily give answers that do not combustion zone requires a balance
represent true heater performance. between heat release per burner,
Understanding fired heater distance from the burner to the tube
operation and design requires that face and distance between the
both the fire- and process side be burners. Ultimately, the heater
evaluated together. Correctly designer (engineering contractor or
predicting the oil film temperature heater vendor) determines the
and residence time in each coil is number of burners and the diameter
essential to specify design changes of the heater floor. While more
during a revamp to avoid problems or burners distribute the heat better, this
to establish the root cause of rapid requires a larger footprint. Figure 2
coking when local conditions are non- shows a schematic of three potential
ideal. In one case, the heater model burner layouts using three, four and
Large burner,
assumed the radiant section was a high heat six burners. The hatched area
well-stirred box. Thus, it predicted a release represents the location of the
2 Short
peak heat flux of 25 000 btu/hr-ft -ºF, convection section inlet relative to
distance
but the actual peak heat flux in the the different burner configurations.
combustion zone was closer to 42 000 In a cylindrical heater, good heat
2
btu/hr-ft -ºF. Each model makes Three (3) burner distribution is easier when six or
simplifying assumptions that equilateral layout more burners are designed in a circle,
influence the model results, so the but this increases total installed cost.
user needs to be aware of these. Increasing the number of burners
Once an individual heater’s tube oil Figure 1 Burner layout – three large burners would have reduced the heat release

00
P T Q REVAMPS & OPERATIONS
pcs 20/7/04 9:41 PM Page 3

One of four
One of four passes
passes
Six (6)
burners
Colder gas
flows
down

Convection section
Hot gas
opening

Four (4)
burners

Hot
Hot Burner location & area Very hot
Convection section area flue gas flow area
opening patterns combine
to make very Hot
Hot hot area area
area
Three (3) burner
Three (3) equilateral layout
burners
Figure 3 Flue gas flow pattern – three large burners Figure 4 Hotspots – three large
burners

Although this equation makes several shows these flow patterns with three
Figure 2 Alternative burner layout – three, assumptions to simplify what happens burners. Furthermore, when baking
four and six burners in an actual heater, it highlights that soda is thrown into the firebox to better
radiant heat transfer is controlled by observe flame patterns, the two burners
per burner and helped distribute the flue gas and process fluid temperature lined up on one side of the convection
heat. However, the floor diameter must differences. Since the flue gas absolute section opening were forcing the single
be large enough to accommodate temperature is so much higher than the flame closer to the tubes. Tube failures
additional burners while maintaining process fluid, the localised flue gas occurred in this very hot area of the
the proper distance between them to temperature largely determines how heater (Figure 4). Heater flue gas flow
allow for stable flame operation and the much heat is transferred at any location patterns have a large effect on flame
correct distance from the burner to tube within the firebox. Thus, large interaction and burner stability.
face, to reduce the peak heat flux caused variations in flue gas temperature Flame stability problems are
by direct flame radiation to an throughout the firebox (Tg) result in increasing because of the use of low and
acceptable level. An acceptable level is large heat flux differences. ultra-low NOX burners. Thus, high heat
when the heat flux from direct flame flux variability is becoming more
radiation is at or less than that caused by Flue gas flow patterns common. In the high flux areas, TMT
hot gas radiation alone. However, when Localised heat flux is also influenced by and oil film temperature are high, which
the lowest initial installed cost is the flue gas flow patterns. Flue gas does not raises the rate of coke formation. Field
basis for purchasing a heater, cost- flow uniformly upwards in the firebox. measured heat flux and infrared
cutting methods such as decreasing the Burner location relative to the measurements of TMTs show that flame
number of burners and reducing the convection section inlet and cold flue stability and flue gas recirculation
floor diameter will almost always be the gas flowing downward are some of the problems are increasingly common
result. While heater OEMs are often factors influencing flue gas today.
blamed for poor heater design, it is the recirculation. In a vertical cylindrical
purchaser that is truly at fault for heater, ideally hot flue gas flows Heater revamp
allowing fundamental principles to be upwards in a circular pattern, while cold Ideally, six burners should have been
violated. In this case, the number of flue gas flows downward behind and used to better distribute heat in the
burners could not be increased due to around the tubes. In practice, burner firebox and to improve flue gas flow
the existing floor diameter. layout, burner type and convection patterns. But in this instance, the burner
Heat exchange from hot gas radiation section opening play a major role in flue floor was too small to maintain a proper
can be calculated from Equation 1 gas flow patterns. distance between the centreline of the
(Lobo-Evans method) as a function of In the three-burner arrangement, two burner and the tube face with the six-
flue gas temperature (Tg), tube metal burners are located below one edge of burner layout. Increasing the distance
temperature (Tt) and the radiant section the convection section, requiring flue between the burners and the tubes
surface area (αAcp). gas from these two burners to flow would have reduced the heat flux due to
towards the middle of the convection direct flame radiation, but the floor was
Radiant section Qr= 0.173 (α Acp) (F) section inlet area. This pushes the flue not large enough in diameter. Therefore,
4 4
[(Tg/100) -(Tt/100) ] (Equation 1) gas from the single burner at the other the only practical solution was to install
edge of the convection section toward one large burner with multiple gas tips
Duty = Btu/hr the tubes (Figure 3). Modelling this with in the middle of the heater floor (Figure
a computational fluid dynamics (CFD) 5).

00
P T Q REVAMPS & OPERATIONS
pcs 20/7/04 9:41 PM Page 4

the effect was to increase


One of four the oil’s film temperature
passes and residence time and
Condensate thereby raise the rate of
Hot
Cold gas Cold
flue flue
31/2 OD tubes
冦 Steam out
coke formation.

gas gas G (mass flux) = Mass rate of


Oil in Oil in oil/inside cross-sectional
冦 4 OD tubes area of heater tube
4 OD tubes (Equation 2)



2
= lb/sec-ft

31/2 OD tubes Coke forms because the


oil flowing on the inside
tube is cracking. The
temperature throughout
More uniform
heat distribution
eliminates
4 OD tubes
冦 the radiant section of a
coker heater is above the
Oil out Oil out oil-cracking temperature,
hot spots
so coke always forms. The
key is to minimise the rate
of formation and increase
the duration between
Figure 5 Reduced localised heat flux – single Figure 6 Coker heater – before revamp decokes. Maximising the
large burner inside tube’s heat-transfer
coefficient minimises the
low and oil residence film temperature and increases the
time very high. heater’s run length. Since the outlet
Moreover, fireside com- tubes’ mass velocity was well below 200
31/2 OD tubes bustion zone evaluation lb/sec-ft2, these tubes needed to be


on 2 to 1
centerline
spacing
High heat
showed the local heat changed from 4” to 3.5”. By reducing
flux was highest where the tube size to 3.5,” the process heat-
the radiant section tube transfer coefficient (Equation 3) would


flux zone size changed from 3.5” be increased and the oil’s film
4 OD tubes in heater to 4”. This was temperature reduced.
on 3 to 1
centerline confirmed with infrared
spacing measurements of TMTs. Inside tube heat (h i) = (0.023) k/D
Figure 6 shows the (DG/µ) (cpµ/k) (µ/µw) (Equation 3)
0.8 0.33 0.14

2
cabin heater prior to Transfer coefficient = Btu/hr-ft -ºF
making modifications.
The convection section
Figure 7 Location of highest heat flux was designed with both Localised oil film
oil and steam coils. temperature
When this solution is implemented, Convection section oil coils were 4”, Lowering film temperature reduces the
it will reduce combustion zone heat flux while the steam tubes were 3.5”. Radiant rate of coke formation. Equation 4
from direct flame radiation to below section coils were down-flow, with 4” shows how the temperature drop across
that from hot gas radiation, thereby tubes on the roof section, 3.5” tubes on the oil’s film is calculated. The Do and Di
reducing peak heat flux in the bottom of the majority of the wall and the last six are the outside and inside tubes’
the heater by 40%. This will tubes were 4”. All radiant section tubes diameters, respectively. Combustion
dramatically lower the oil film were on two-to-one spacing except the zone direct flame radiation or flue gas
temperature and rate of coke formation, last six 4” outlet tubes that were spaced temperature largely determines the
but it will also raise the bridge wall at three-to-one. Coke was forming in the amount of heat transferred locally
temperature and the convection section 4” tubes at the bottom of the heater, (Qlocal).
heat flux. When revamping heaters, causing very short run lengths. Low oil
existing configurations force the revamp mass flux and high oil residence time
engineer to make compromises. were the two main reasons for this short ∆tf = Temperature drop across the oil
run length. film (Equation 4)
Case study 2 = Qlocal Do/Di h i
Coker heater revamp Oil mass flux = ºF
In Case study 2, a coker heater had run Oil mass flux (Equation 2) is a measure
lengths of less than two months of the flow of oil through the tube cross- For a given heat flux (Qlocal), the
between decokes, although the average sectional area. Increasing mass flux temperature drop through the oil’s film
radiant section heat flux was less than lowers the oil film temperature and temperature is set by the process fluid
2
9500 btu/hr-ft -ºF. However, oil reduces the rate of coke formation. inside the film coefficient (h i). Reducing
residence time was very high and the Conversely, lowering the mass flux the tube size lowers the oil’s film
oil’s mass velocity low throughout the raises the oil film temperature. By temperature and reduces the rate of coke
radiant section tubes. In the larger 4” increasing the outlet tube size, the formation in a heater.
outlet tubes, mass flux was extremely designer reduced the pressure drop. Yet, Fireside calculations showed that the

00
P T Q REVAMPS & OPERATIONS
pcs 20/7/04 9:41 PM Page 5

highest heat flux (Qlocal)


occurred in the area where the Oil in Oil in
Oil in Flue

tube size changed from 3.5” to Convert steam
gas
4” (Figure 7). Since the 4” Condensate in coils to oil
tubes were spaced at three-to-
once spacing, installing 3.5” Convert 4 tubes
tubes on the same tube Convection
section
to 31/2 OD tubes 冦
hangers reduced the peak heat
flux, further reducing the oil’s
film temperature. Cross over Bridgewall


temperature temperature Eliminate
4 tubes
Oil residence time Radiant 31/2 OD tubes
Oil residence time is section
controlled by the radiant
section’s tube length, tube size,

Oil out Replace with
oil mass flow rate and
Fuel/air 31/2 OD tubes
condensate injection. Decreas-
Oil out Oil out
ing the radiant section’s oil
residence time lowers the rate
of coke formation. In this Figure 8 Simplified heater schematic Figure 9 Coker heater – after revamp
example, the heater operated
less than 60 days between decokings due less than 30 seconds without
to the high rate of coke formation. The exceeding the condensate
radiant section’s oil residence time was pump’s capacity. The outlet Oil in Oil in
more than one minute and had to be tube sizes were changed to 3.5”
reduced to less than 30 seconds to to reduce the oil’s film
Convert steam

coils to oil
Add three rows
materially improve run length. temperature and lower the oil’s of 31/2 OD tubes 冦
Increasing condensate injection residence time.
would have been the easiest way to The convection section’s
Convert 4 tubes
to 31/2 OD tubes 冦
decrease oil residence time, but raising duty was increased by
the rate would increase the heater’s converting the steam coils to


firing because condensate must be oil, and the 4” convection Eliminate
vapourised. Another alternative was to section’s oil tubes were reduced 4 tubes
reduce all the radiant section’s 4” tube from 4” to 3.5” to reduce 31/2 OD tubes
sizes to 3.5”. Although this reduced oil residence time and oil film
residence time, it was not enough to temperature. The oil


materially increase run length and it convection section’s surface Replace with
also increased the pressure drop so area was increased by more 31/2 OD tubes
much that the charge and condensate than 600%. Since the revamp Oil out Oil out
pumps were no longer able to provide needed to be completed as fast
sufficient head to overcome the as possible, the radiant section’s
additional pressure drop. Therefore, modifications were minimised. Figure 10 Coker heater – increased convection
other means to increase run length were The 4” roof tubes were removed surface area
needed. and the 4” outlet tubes were
changed to 3.5” tubes. The heater run true heater performance.
Convection/radiant section length has increased dramatically.
duty After startup, the skin temperatures
Figure 8 is a simplified representation of were still higher in the highest heat flux Tony Barletta is a chemical engineer with
a fired heater. Total duty is supplied by section of the heater compared to the Process Consulting Services in Houston,
the convection and radiant sections. In other tubes, but the lower residence Texas, USA. His primary responsibilities are
this instance, the majority of the time and lower film temperature have conceptual process design (CPD) and
convection section’s surface area was dramatically reduced the rate of coke process design for refinery revamps.
used to make steam. Thus, most of the formation. In the longer term, the Previous positions include production
heat added to the oil was radiant section convection section has unused space to planner at BP’s Alliance refinery and
duty. It was clear that increasing the add more tubes to further lower the technical service engineer at Hess Oil St.
convection section’s oil duty would radiant section’s heat flux (Figure 10). Croix refinery. Barletta has authored
decrease the radiant section’s flux and Identifying the local conditions that numerous technical papers on revamping
enable some of the 4” tubes to be lead to rapid coke formation is the key refinery units and holds a BS degree in
replaced with 3.5” tubes. to increasing heat run length. chemical engineering from Lehigh
Figure 9 shows the revamp Quantifying the radiant section’s heat University. Email: tbarletta@revamps.com
modifications. The convection section’s flux variability and minimising it is
surface area was added for the oil, and essential. Since the oil’s film
the radiant section’s surface area was temperature and residence time have a
reduced by removing some tubes and dramatic influence on coke formation
replacing others with smaller tubes. rates, properly evaluating each coil to
These changes, in addition to a higher establish the locations of hotspots is
condensate flow injection, reduced the essential. Fireside and oil-side
radiant section’s flux rate and reduced calculation methods must be integrated
the radiant section’s residence time to and calibrated with plant data to predict

00
P T Q REVAMPS & OPERATIONS

You might also like