Prerequisites

Before using the Installation Builder to install and configure FTE, perform the following:
l Install Experion software including the Installation Builder.

l Create a Master Definition for the node in which all FTE configuration options are defined. If

this is not the case, refer to the Installation Builder User’s Guide.
3.7.2 Checklist
After performing each procedure, return to the checklist to reference the next procedure.
- 28 -
Task Go to Status
Removing non-FTE hardware
Perform these two procedures if the node has an onboard
single NIC.
ATTENTION
If the FTE dual NIC is already installed or you are
using the onboard dual NICs, go to “Installing FTE
software” section of the checklist.
If the Experion node is using the onboard Single adapter,
remove single onboard NIC.
Remove non-FTE
hardware.
Disable non-FTE NIC Disable non-FTE NIC.
Installing FTE hardware.
Verify you the specific vendor’s installation guide is reviewed for
the NICs being used.
Vendor manuals
Obtain the computer user manual for the platform to
determine how to remove the cover.
Vendor manuals
Determine qualified platforms and NIC slot requirements,
Planning, Installation and Service Guide for the Honeywellqualified
platform.
Qualified platforms and
NIC slot requirements.
Determine NIC connection requirements. FTE-qualified NICs.
Install dual port NIC. Install dual port NIC.
Configuring FTE and NICs
Download FTE-configured Master Definition. Download FTE-configured
master definition.
Configure/verify FTE Mux-IM protocol driver properties Configure/verify FTE
Mux-IM protocol driver
properties.
Configure the Honeywell FTE adapter.
ATTENTION
Use this procedure to verify the correct values only.
Configure the Honeywell
FTE adapter.
Verify correct FTE installation. Verify FTE installation.
Connect the network cables to switches if not connected Connect network cables to
switches.
Verify Honeywell FTE driver operation Verify the Honeywell FTE
driver operation.
3.8 Install and configure FTE on domain controllers
3.8.1 Prerequisites
Any one of the following as per your requirement.
l Root or peer Domain Controller running Windows server 2003

l Root, peer or read-only Domain Controller running Windows Server 2008

l Root, peer or read-only Domain Controller running Windows Server 2012

- 29 -
Chapter 3 - FTE Installation and Configuration checklists
Chapter 3 - FTE Installation and Configuration checklists
The following are required.
l Experion Installation media

l Experion PKS System Initialization media

l Fault Tolerant Ethernet Installation and Service Guide for Rxx for Microsoft Windows Server

2003 Domain Controller installation.


l Experion Client/Server Initialization DVD for R3xx, for Windows Server 20032008 R2 Service

PackDomain Controller installation.


3.8.2 Considerations
If you are installing FTE for a domain controller on a Honeywell-qualified platform running
Microsoft Windows Server 2016 Standard, then Honeywell recommends you to use the Experion
PKS System Initialization media for the operating system installation.
During the initialization steps, ensure FTE is selected for the network type and the NIC- FTE Yellow
is configured with at least one IP address, a subnet mask, and a default gateway. When selecting
the installation parameters for a clean operating system installation on the Network and
Input/Output Device Configuration dialog box. This is required while performing operating system
installation.
ATTENTION
Ensure that FTE is configured before promoting the server as a Domain Controller.
3.8.3 Checklist
After performing each procedure return to the checklist to reference the next procedure.
- 30 -
Task Go to Status
Install operating system and FTE
If the domain controller is already up and running proceed to
configuring NICs.
Appropriate checklist
for your system
For example, refer to
the section
Configure NIC
adapters for FTE in
this guide for R410.
If the domain controller is hosted on a Honeywell supported
platform, follow the instructions in Software Installation User’s
Guide for installing Microsoft Windows Server 2016 Standard
operating system only. Ensure to configure the network type as FTE
and specify the FTE settings.
Appropriate checklist
for your system
For example, refer to
the section
Configure FTE in this
guide for R410.
If the domain controller is not hosted on a Honeywell supported
platform or is running Windows Server 2012 operating system,
ensure that a Honeywell supported dual NIC adapter is installed.
Install and configure the domain controller. Based on your
requirement, refer to any of the following domain controller
document.
Windows Domain and Workgroup Implementation GuideFor
operation system migration information, refer the appropriate
operating system-specific implementation guide Windows Domain
Implementation Guide for Windows Server 2016
Appropriate checklist
for your system
For example refer to
the Windows
Domain and
Workgroup
Implementation
Guide.
Remove non-FTE hardware Remove non-FTE
hardware.
Installing FTE hardware if not already installed, otherwise go to
Configure NICs
Verify you have reviewed the specific vendor’s installation guide for
the NICs being used.
Vendor manuals
Obtain the computer user manual for the platform to determine how
to remove the cover.
Vendor manuals
Determine NIC connection requirements. NIC connection
requirements.
Install dual port NIC. Install dual port NIC.
Configuring NICs
Install or update NIC drivers for Experion nodes. Install or update NIC
drivers.
Verify/change physical adapter settings Verify/change
physical adapters
settings.
Verfiy/set NIC adapter TCP/IPV4 properties. Verify/set NIC
adapter TCP/IPV4
properties.
- 31 -
Chapter 3 - FTE Installation and Configuration checklists
Chapter 3 - FTE Installation and Configuration checklists
ATTENTION
Do not change the IP address of the domain controller if it
is already configured as a domain controller. For more
information, refer to the following domain controller
documentation for the release being installed Windows
Domain and Workgroup Implementation Guide. For
planning information, refer to Windows Domain and
Workgroup Planning Guide. For operation system
migration information, refer the appropriate operating
system-specific implementation guide Windows Domain
Implementation Guide for Windows Server
2016/Windows Domain Implementation Guide for
Windows Server 2016
Rename the network physical adapters Rename the network
physical adapters
Installing FTE software
Install FTE software on a domain controller Install FTE software
on a domain
controller
Configure/verify FTE Mux-IM protocol driver properties Configure/verify FTE
Mux-IM protocol
driver properties.
Configure the Honeywell FTE adapter. Configure the
Honeywell FTE
adapter.
Connect the network cables to switches if not connected Connect network
cables to switches.
Verify Honeywell FTE driver operation Verify the Honeywell
FTE driver operation.
Promote the computer to a domain controller Refer to the following
domain controller
guides based on the
operating system you
are running.
l

lWindows
Domain
Implementation
Guide for
Windows Server
2016
- 32 -

CONVERT A SUPERVISORY NETWORK TO AN FTE


NETWORK
Use the information in this section and the appropriate checklist from the sectionFTE Installation
and Configuration checklists to convert a supervisory network to an FTE network.
This conversion must occur before Experion release 4xx is installed on the nodes. Refer to the
procedures available in the Fault Tolerant Installation and Service guide for the Experion release
3xx being migrated from. Use the R3xx version of this guide for all of the steps and
recommendation prior to referencing this document.
l Supervisory network to FTE network considerations

l Identifying the specific conversion scenario

4.1 Supervisory network to FTE network considerations


First convert all nodes within the network to FTE nodes. Before conversion, refer to the Fault
Tolerant Ethernet Overview and Implementation Guide for detailed FTE network planning
information.
l Server and station conversion guidelines

l Special considerations for migrating a single ethernet platform

4.1.1 Server and station conversion guidelines


The following guidelines must be followed for server and station conversion.
l Each server must be converted at the same time as its redundant pair. Stations can be

converted individually.
l Each redundant server that has a dual ethernet configuration must have its links redefined

for a single network.


l Each redundant server must have its host file updated.

4.1.2 Special considerations for migrating a single ethernet


platform
If you are upgrading a platform that currently has a single NIC, replace the single NIC with a dual
NIC before starting a migration. Experion migration software looks specifically for a dual ethernet
configuration and if it is not detected, it stops the migration process. To avoid having a dual NIC
only for the migration process, perform the following:
- 33 -
CHAPTER

4
l Remove the dual NIC from the new platform and install it in the platform that is being replaced.
l Power-up the node being replaced and begin the migration process.
l After all the data on the node being replaced is backed up or migrated, shut it down and

remove the dual NIC.


l Re-install the dual NIC in the new platform and continue with the migration.

4.2 Identifying the specific conversion scenario


l Migration scenarios for single ethernet Experion servers, Console, and Flex stations
l Migration scenarios for dual ethernet Experion servers, Console, and Flex Stations
4.2.1 Migration scenarios for single ethernet Experion servers,
Console, and Flex stations
The following table lists scenarios for migrating single ethernet Experion servers, Console, and
Flex stations currently in a supervisory network to dual ethernet Experion servers, Console, and
Flex stations used in an FTE network.
- 34 -
Chapter 4 - Convert a supervisory network to an FTE network
Chapter 4 - Convert a supervisory network to an FTE network
Current
Honeywell
hardware
platforms
Current
NIC
Is hardware platform
replaced? NIC to use in current hardware platform
l PE16001

l PE2600

series1
Single Yes – with a server that
has onboard NIC
Use card in current platform if it is FTEqualified1
l PE16001

l PE2600

series1
Single Yes – with a server that
has an FTE-qualified dual
NIC
Use card in current platform if it is FTEqualified1
l PE18003

l PE 1430

l PE T105

Single No Must purchase an FTE-qualified Intel Pro


1000 MT PT Dual server NIC2 or ET Gigabit
Dual server NIC2
l PE2850
l PE 2900
l PE2950

l PE R710

l PE T610

l PE T310

l PE R320

l PE T320

l DL 380

Single No Use onboard NIC after enabling it


l WS360-

based
workstation1
l WS370-

based
workstation1
l WS470-

based
workstation1
Single Yes – with current
Windows 7 -based
Honeywell workstation
Use card in new platform (temporarily) or
purchase an FTE-qualified dual NIC2
l WS490

l WS T5400

l WS T5500

l WS T3400

l WS T3500

l WS R55004

l WS T3600

XL
l WS HP

Z6204
Single No Must purchase an FTE-qualified Intel Pro
1000 MT, PT, ET dual server NIC, or ET
Gigabit dual server NIC2
l 1Platforms not supported for Experion R4xx.

l 2Disable onboard NIC for these platforms.

l 3Node types not supported for and above must replace hardware.

l 4These platforms are provided with dual NIC. You need not purchase a separate NIC during

- 35 -
migration.
4.2.2 Migration scenarios for dual ethernet Experion servers,
Console, and Flex Stations
The following table lists scenarios for migrating dual ethernet Experion servers, Console, and Flex
stations currently in a supervisory network to dual ethernet Experion servers, Console, and Flex
stations used in an FTE network.
Current
Honeywell
hardware
platform
Current
NIC
Is hardware platform
being replaced? NIC to use in current hardware platform
l PE 16001

l PE 2600

series 1
Dual Yes – with a server that
has onboard NIC
Use Onboard NIC
l PE 1600

l PE 2600

series 1
Dual Yes – with a server that
has an FTE-qualified dual
NIC
Use card in current platform if it is FTEqualified1,2
l PE 18003

l PE 1430

l PE 2900

l PE 2850

l PE 2950

l PE R710

l PE T610

l PE T310

l T105

l PE R320

l PE T320

l DL 380

Dual No Use card in current platform if it is FTEqualified.


In PE 1800 and PE1430 See Note2.
Use Onboard NIC in platform if it is Dual.
l WS3601

l WS3701

l WS4701

Dual Yes – with current


Windows 7 based
Honeywell-qualified
workstation
Use card in current platform if it is FTEqualified1,2
l WS490

l WS T5400

l WS T5500

l WS T3400

l WS T3500

l WS

R55004
l WS T3600

XL
l WS HP

Z6204
Dual No Use card in current platform if it is FTEqualified2
- 36 -
Chapter 4 - Convert a supervisory network to an FTE network
Chapter 4 - Convert a supervisory network to an FTE network
l 1 Platforms not supported for Experion R4XX

l 2 Refer to FTE-qualified NICs.


l 3 Node types not supported for and above must replace hardware.
l 4These platforms are provided with dual NIC. You need not purchase a separate NIC during
migration.
- 37 -

INSTALL FTE HARDWARE


This section contains procedures for installing and configuring the NIC used with FTE node.
l FTE hardware installation prerequisites

l Remove non-FTE hardware

l Install the NIC

l Install or update NIC drivers

l Configure NIC adapters for FTE

5.1 FTE hardware installation prerequisites


Before installing the FTE hardware, ensure that the following tasks are performed.
l Review the specific vendor’s installation guide for the NICs being used.

l Knowledge of the hardware installation requirements for the specific platform. Refer to FTEqualified

NICs.
l Ensure that the computer user manual is present for your specific platform. Refer to the

manual to remove the cover.


l Review the appropriate, Planning, Installation and Service Guide for the Honeywell-qualified

platform.
5.2 Remove non-FTE hardware
Perform the procedures in this section if you are installing FTE on a node that has a single
integrated onboard NIC.
This section can also be used for removing any unqualified NIC from the computer.
l Remove single onboard NIC

l Disable non-FTE NIC

l FTE-qualified NICs

l Qualified platforms and NIC slot requirements

l NIC connection requirements

5.2.1 Remove single onboard NIC


Use this procedure to disable and remove the integrated onboard NIC.
- 38 -
CHAPTER

5
1.
Perform the following:
For Microsoft Windows 10
Enterprise 2016 LTSB (x64)
a. Right-click the My Computer icon from the
desktop or from the Start menu and choose
Manage.
The Computer Management window is
displayed.
b. In the console tree, open System Tools and
then click Device Manager.
For Microsoft Windows
Server 2016 Standard
a. Right-click the My Computer icon from the
desktop. Or from the Start menu and choose
Manage.
The Computer Management window is
displayed.
b. In the console tree, open Diagnostics and then
click Device Manager.
For Microsoft Windows
Server 2016 Standard
a. On the taskbar, click Server Manager icon
The Server Manager dialog box is displayed.
b. Click Tools > Computer Management.
The Computer Management window is
displayed.
c. In the console tree, open System Tools and
then click Device Manager.
2. Double-click Network adapters to view all installed NICs.
3. Right-click the NIC and choose Uninstall.
4. Click OK to confirm the removal of the device.
5.2.2 Disable non-FTE NIC
Refer to the Planning, Installation and Service Guide for the specific platform on which the FTE is
being installed and for the exact BIOS operation instructions.
Perform the following steps if the single NIC being removed is on the Motherboard (onboard) NIC.
CAUTION
The BIOS setup is an advanced tool; enter the system setup only if you are an experienced
user.
1. Restart the computer and, when prompted during system startup, press the appropriate key(s)
to enter system setup.
2. Select Integrated Devices.
3. If Network Interface Controller is listed, the onboard NIC is present. Change the setting to Off.
- 39 -
Chapter 5 - Install FTE hardware
Chapter 5 - Install FTE hardware
4. Save changes and exit BIOS to continue the system startup and allow your system to detect
new hardware.
5. Restart the system and log on as Administrator.
6. Shut down the system.
Perform the following steps if the single NIC being removed is a separate PCI-x or PCI-e PC card.
1. Turn off the computer.
2. Remove the single PCI NIC from the system and install the dual NIC replacement by following
the steps in the checklist.
3. Reassemble the system per the vendor manual.
4. Turn on the computer.
5.2.3 FTE-qualified NICs
The following is a list of Experion qualified add-on NICs for the use with the Experionand TPS
platforms running Microsoft Windows 10 Enterprise 2016 LTSB (x64), Microsoft Windows Server
2016 Standard, and Microsoft Windows Server 2012 operating systems. This is the available list at
the time of this document creation. If running with a new factory platform review the Planning,
Installation and Service Guide for the specific platform being used as a newer card option may be
available.
NIC PCI type
Intel® PRO 1000 MT dual server adapters PCI-x
Intel® PRO/1000 PT dual server adapters PCI-e
Intel® Gigabit ET dual port server adapters PCI-e
5.2.4 Qualified platforms and NIC slot requirements
The following table provides a list of hardware platforms that qualified for use with FTE. Some
platforms have specific slot requirements, which are indicated in the slot requirement column.
Refer to the following topic in Planning, Installation and Service Guide, if the specific platform is
not listed in the table.
l FTE Slot Requirements in System Planning section.

l Specific Slot Requirements in Workstation Configurations section.

- 40 -
Platform Slot requirement
Dell WS490 PCI-e – slot 1 for PT/ET cards or PCI-X slot 6 for MT card
Dell WS T5400 PCI-e – slot 1 for PT/ET card or PCI-X slot 6 for MT card
Dell WS T5500 PCI-e – slot 1
Dell WS T3400 PCI slot 1 for Intel MT or PCIe slot 3 for Intel PT or ET card
Dell WS T3500 PCIe slot 1 for Intel PT/ET cards
Dell WS R5500 Onboard NIC
Dell WS T3600XL PCIe slot 3 for BroadCom 5720 Dual Port NIC Adapter
HP Z620 Onboard NIC
Dell PE1800 PCI-e slot # 2 for PT/ET card or PCIX 5 slot for MT card For R400.x 32 – bit only
Dell PE 1430 PCI-e – slot 1 for PT/ET Card or PCI-x slot 6 for MT card
Dell PE2850 Onboard NIC
Dell PE2950 Onboard NIC
Dell PE2900 Onboard NIC
Dell PE R710 Onboard NIC – Disable 2 of the four
Dell PE T610 Onboard NIC
Dell PE T105 PCIx slot 3 for Intel dual MT or PCIe slot 1 for Intel PT/ET cards
Dell PE T310 Onboard NIC
Dell PE T320 Onboard NIC
Dell PE R320 Onboard NIC
HP DL380 Onboard NIC
5.2.5 NIC connection requirements
Honeywell recommends you use a consistent strategy when placing the network cards in each
type of computer and when connecting the cables. The initialization and FTE driver software
always assigns the lowest MAC addressed port as the Yellow or A connection. This is also usually
the port labeled 1 or A on the physical connection to the either the dual NIC or the ports located on
the computer backplane. Honeywell recommends that the Yellow or A connection always be
connected to the physical port labeled 1 or A on the computer. This port has the lowest MAC
address.
5.3 Install the NIC
Perform the following procedure for installing the NICs.
l Purpose

l Install dual port NIC

5.3.1 Purpose
If the FTE NIC is not installed at the factory, use the procedures in this section to install and
configure the FTE NICs for your FTE node. For further information, refer to the vendor-specific
documentation.
In addition, refer to the following topics in Planning, Installation, and Service Guide, for further
information about the specific platform being installed.
- 41 -
Chapter 5 - Install FTE hardware
Chapter 5 - Install FTE hardware
l FTE Slot Requirements in System Planning section.

l Specific Slot Requirements in Workstation Configurations section.


5.3.2 Install dual port NIC
Use this procedure to install the NIC in the PCI slot. If necessary, refer to specific platform
hardware manual for information on the available PCI slots.
TIP
Before installing the NIC, review all documentation packaged with the dual port NIC,
including the Quick Start Guide.
1. Identify the “ACT/LINK A” and “ACT/LINK B” ports on the NIC.
ATTENTION
The ACT/LINK A port is closest to the middle of the card.
TIP
Although the next two steps are optional, it is required to know the physical
ethernet address used for each port on the NIC. Based on the physical ethernet
address, review the MAC address table in the Switch Configuration menu to identify
the associated switch and dual adapter ports.
- 42 -
2. Locate and record the NIC’s label containing the 12-digit, hexadecimal physical ethernet
(MAC) address.
ATTENTION
This address applies to Port “A” (ACT/LINK A) on the NIC.
3. Increment the address for port “A” by 1 to derive the physical ethernet (MAC) address for port
“B”, and record the value.
4. Install the dual port NIC in the proper slot using the instructions in the Installation Guide
packaged with the device.
5.4 Install or update NIC drivers
Perform the following procedure for installing or updating the FTE NIC driver.
Honeywell recommends to use the NIC drivers provided in the Experion PKS System Initialization
media or download the latest version from the Honeywellprocess.com website. Refer to the latest
Experion PKS General Release SCN for driver updates.
Determine which manufacture of NICs is installed on the computer and perform either the Intel or
Broadcom procedure for driver installation.
The following table provides a brief list of network interface cards that can be installed on
Honeywell-qualified platform.
- 43 -
Chapter 5 - Install FTE hardware
Chapter 5 - Install FTE hardware
Dell
platform
NIC
manufacturer Onboard/added Remarks
PE1800 Intel Added Platform is only on 32-bit R400.X
PE 1430 Intel Added
PE T105 Intel Added
PE 2850 Intel Onboard
PE 2900 BroadCom Onboard
PE 2950 BroadCom Onboard
PE R710 BroadCom Onboard Has four on-board NICs, disable two NICs only for
FTE.
PE T610 BroadCom Onboard
PE T310 BroadCom Onboard
PE T320 BroadCom Onboard
PE R320 BroadCom Onboard
HP DL380 BroadCom Onboard
WS 490 Intel Added
WS T5400 Intel Added
WS T5500 Intel Added
WS T3400 Intel Added
WS T3500 Intel Added
WS T3500 Intel Added
WS R5500 Intel Onboard
WS
T3600XL
BroadCom Added
HP Z620 Intel Onboard
Perform the following procedure after installing or replacing the dual NIC on the computer.
1. Turn on the computer after installing the dual NIC.
2. Log onto the computer using the Administrator account.
3. If the replaced NIC is the same as the one removed, the Hardware Wizard displays Your new
hardware is ready to use. message.
4. If the Hardware Wizard displays a message that it is required to search for a driver, cancel the
Hardware Wizard and perform one ofthe following procedures.
l Install Intel network driver and PROSet software for the Intel NICs.

l Install or update onboard BroadCom NIC driver.

5. Return to the checklist.


l Install Intel network driver and PROSet software for the Intel NICs

l Install or update onboard BroadCom NIC driver

5.4.1 Install Intel network driver and PROSet software for the
Intel
NICs
Perform the following procedure to install Intel network driver and PROSet software for Intel NICs.
- 44 -
ATTENTION
l Before you begin, ensure that you have used the dual NICs listed in FTE-qualified

NICs, for configuring FTE on computers that do not have the onboard adapters.
l If drivers were downloaded from the Honeywellprocess.com website, ensure that

the instructions included with the drivers are followed instead of this procedure.
CAUTION
If FTE is installed and is operating, disable the FTE by performing the procedure in Unbind
physical adapters from Honeywell FTE adapter, before updating the adapter driver version.
Install Intel drivers
1. Insert the Experion PKS System Initialization media in the DVD drive.
2. In the Honeywell –Experion PKS System Initialization window, click Utilities.
3. On the left pane, click NIC Drivers.
4. Select the Intel NIC driver that applies to your system and then follow the instructions onscreen
to complete the installation.
5. Return to the checklist.
5.4.2 Install or update onboard BroadCom NIC driver
Perform the following procedure to obtain the latest driver.
ATTENTION
l This procedure is for supporting onboard Broadcom NIC cards and the new driver

version that must be updated.


l If drivers were downloaded from the Honeywell Process Solutions website

(http://www.honeywellprocess.com), ensure the instructions included with the


drivers are followed instead of this procedure.
CAUTION
If the FTE is installed and is operating, disable the FTE by performing the procedure in
Unbind physical adapters from Honeywell FTE adapter, before updating the adapter driver
version.
- 45 -
Chapter 5 - Install FTE hardware
Chapter 5 - Install FTE hardware
Install Broadcom drivers
1. Insert the Experion PKS System Initialization media in the DVD drive.
2. In the Honeywell–Experion PKS System Initialization window, click Utilities.
3. In the left pane, select NIC-Drivers.
4. Select BROADCOM 57XX GIGABIT INTEGRATED CONTROLLER.
5. Follow the on-screen instructions to complete the Broadcom driver installation.
6. Return to the checklist.
5.5 Configure NIC adapters for FTE
This section provides the procedures to configure the adapter and IP settings for the network
interface cards that are used for Fault Tolerant Ethernet. It is required to configure these settings
before installing the FTE software to ensure the software package installation picks up the
configuration and transfers them correctly to the Honeywell FTE adapter.
l Rename the network physical adapters

l Verify/set NIC adapter TCP/IPV4 properties

l Verify/change physical adapters settings

5.5.1 Rename the network physical adapters


The NIC must be renamed in the following scenarios.
l If the NICs have been replaced or new NICs are added to the computer.

l If the previous names for these adapters have been deleted and replaced with the Microsoft

default names of Local Area Connections (2).


If you must rename the NICs for any of the previously mentioned scenarios, refer to the naming
conventions mentioned in section, User interfaces and naming conventions.
1. Perform the following steps to determine Green and Yellow adapters.
a. Select Start > All Programs > Accessories, and then select Command Prompt.
Or
Select Start > Run, and type command in the Run dialog box.
The command prompt window is displayed.
b. In the command prompt window, type ipconfig/all and press ENTER.
A list of all the IP configurations are displayed.
c. Examine the Local Area Connections and the physical addresses to determine the lowest
- 46 -
physical address.
d. Determine the lowest physical address associated with the NIC (for example, Local Area
Connection). This adapter is the Yellow adapter.
2. Perform the following:
Click Start > Windows System > Control panel > Network and Internet > Network and Sharing
Center > Change adapter settings.
The Network Connections window appears.
3. Right-click the Local Area Connection that has the lowest physical address and choose
Rename.
Rename the adapter and the Local Area Connection (with Yellow in the name) to meet the
naming convention specified in section Standard naming conventions for NICs.
4. Right-click the Local Area Connection that has the highest physical address and choose
Rename.
Rename the adapter and the Local Area Connection (with Green in the name) to meet the
naming convention specified in Standard naming conventions for NICs.
5. In the command prompt window, type ipconfig/all and press ENTER.
A list of all the IP configurations are displayed.
6. Verify that the lowest physical addresses has Yellow in the adapter name and the next physical
address is labeled Green.
7. Return to the checklist.
5.5.2 Verify/set NIC adapter TCP/IPV4 properties
Perform this procedure before installing the Honeywell FTE Mux driver software. This procedure
can be performed on any computer in the following scenarios.
- 47 -
Chapter 5 - Install FTE hardware
Chapter 5 - Install FTE hardware
l The Experion initialization and automatic software installations are not performed on the

computer (such as Domain Controller).


l The FTE installation and the physical adapters have been unbound from the computer. This is

done to allow network communication while performing NIC driver upgrades.


l FTE adapter settings are changed.

1. Perform the following:


Click Start > Windows System > Control panel > Network and Internet > Network and Sharing
Center > Change adapter settings.
The Network Connections window appears.
2. Perform the following procedure for Yellow network connection.
a. Right-click the Yellow network connection and choose Properties.
The User Account Control dialog box is displayed.
b. Click Continue.
The Yellow Adapter Properties dialog box is displayed.
c. In the Networking tab, select Internet Protocol Version 4(TCP/IPv4) and click Properties.
The Internet Protocol Version 4(TCP/IPv4) Properties dialog box is displayed.
d. Click the General tab and verify/set the IPv4 properties for the Yellow adapter.
e. Set the IP address, Subnet mask and Default gateway assigned to this node. If required,
set the DNS servers.
f. Click OK and click Close.
3. Perform the following procedure for Green network connection.
a. Right-click the Green network connection and choose Properties.
The User Account Control dialog box is displayed.
b. Click Continue.
The Green Adapter Properties dialog box is displayed.
c. In the Networking tab, select Internet Protocol Version 4(TCP/IPv4) and click Properties.
The Internet Protocol Version 4(TCP/IPv4) Properties dialog box is displayed.
d. Click the General tab.
e. Select the Obtain an IP address automatically option.
f. Click OK and click Close.
g. Close Network Connections window.
5.5.3 Verify/change physical adapters settings
Perform the following procedure to update NIC driver for an existing FTE node. This procedure is
used for verifying if the network physical adapter properties are configured correctly after a driver
update.
1. Perform the following:
Click Start > Windows System > Control panel > Network and Internet > Network and Sharing
Center > Change adapter settings.
The Network Connections window appears.
2. Right-click one of the FTE network connections (Yellow or Green) and choose Properties.
The User Account Control dialog box is displayed.
3. Click Continue.
Verify the Adapter Yellow/Green Properties window.
- 48 -
4. In the Networking tab, select Configure.
5. In the Advanced tab, perform the following procedure for Broadcom and Intel adapters .
Broadcom adapters
a. Large send Offload V2 (IPV4) = Disabled.
b. Large send Offload V2 (IPV6) = Disabled.
c. Speed & Duplex = 100Mb Full Duplex.
d. Receive Side Scaling = Disabled.
Intel adapters
a. Jumbo Packet verify/change the value to Disabled.
b. Large Send Offload (IPv4) verify/change the value to Disabled.
c. Large Send Offload (IPv6) verify/change the value to Disabled.
d. Receive Side Scaling verify/change the value to Disabled.
e. Link Speed Tab and verify/change the value to 100Mbps/Full Duplex.
6. Click OK.
7. Click Close from the Adapter Properties window.
8. Repeat this procedure for the second adapter.
- 49 -
Chapter 5 - Install FTE hardware

INSTALL FTE SOFTWARE


Depending on the installation checklist used and options selected, FTE software installation is
performed automatically. This procedure is used for manual FTE installations such as domain
controller installation and adding FTE after an Experion installation has been completed.
ATTENTION
Updates and patches to the FTE software are handled by the General Release Software
Change Notice (SCN) released with the update.
l Install FTE software as an optional component

l Install FTE software on a domain controller

6.1 Install FTE software as an optional component


Prerequisites
Ensure that the following items are available before installing the FTE software.
l Software Installation User's Guide for the release being installed

l Experion PKS Installation media 1

l Experion PKS Installation media 2

l General Release Software Change Notice (SCN) for the release being installed.

Considerations
After the main installation is completed the support media updates must be applied as per the
General Release Software Change Notice (SCN) for the specific release being installed.
1. Insert the Experion PKS Installation media 1 into the DVD drive.
The Install browser is displayed only if auto-play is enabled. If auto-play does not start the
browser, run D:\browser\cdbrower.exe.
The Experion PKS Installer window is displayed.
2. Click Install/Migrate Experion PKS.
The Experion PKS – Dialog Manager window is displayed.
3. In Migration/Clean Install Selection, select Install Clean, and click Next.
The warning message, You have chosen an option that will not Migrate data from a prior
release. Are you sure you want to Continue? is displayed.
4. Click Yes.
The Welcome to the Honeywell Experion PKS Installation Setup wizard is displayed.
- 50 -
CHAPTER

6
5. Read the information and click Next.
The License Agreement page is displayed.
6. Verify the License Agreement and select I accept the terms in the License agreement.
7. Click Next.
The Select Type of Node to Install page is displayed.
8. Choose Optional Features and click Next.
The User and License Information page is displayed.
9. Type the Name and Company Name, and click Next.
The Installation Path(s) Selection page is displayed.
10. Choose Add-on Features and under