CES-AZ-AES-01B-EX (Unicode) System Manual PDF
CES-AZ-AES-01B-EX (Unicode) System Manual PDF
More than safety.
System Manual Safety System CES-AZ-AES-01B-EX
Contents
Correct use 3
Possible combinations for CES components 4
Safety precautions 5
System description 6
Block diagram CES-AZ-AES-01B-EX 7
Installation 8
Electrical connection 9
Connection example CES-AZ-AES-01B-EX 10
LED displays 11
Setup 11
System status table 13
Inspection and service 14
Function test (self-test) 14
Exclusion of liability 14
Technical data 15
Evaluation unit CES-AZ-AES-01B-EX 15
Read head CES-A-LNA-SC-EX 17
Read head CES-A-LMN-SC-EX 19
Read head CEM-A-LE05K-S2-EX 21
Actuator CES-A-BBA-EX 23
Actuator CES-A-BMB-EX 24
Actuator CEM-A-BE05-EX 25
Ordering information and accessories 26
Declaration of conformity 27
System Manual Safety System CES-AZ-AES-01B-EX
Correct use
The Coded Electronic Safety systems CES are safety devices for monitoring mov-
able safety guards so that:
Dangerous work on machines can only be carried out if the safety guards are
closed.
A stop command is triggered if a safety guard is opened while the machine is
running.
Before safety switches are used, a risk assessment must be performed on the
machine in accordance with:
EN 13849-1, Safety of machinery. Safety related parts of control systems.
General principles for design, Annex B
EN ISO 14121, Safety of machinery. Principles for risk assessment
The following applies additionally for evaluation units, read heads and actuators of
the type CES-...-EX and CEM-...-EX :
EN 60079-15, Electrical apparatus for explosive gas atmospheres. Construc-
tion, test and marking of type of protection “n” electrical apparatus
ATEX ratings
For evaluation units
II (3) G [Ex nL] IIC
Not for installation in explosion-hazard areas
System Manual Safety System CES-AZ-AES-01B-EX
Important!
Only components may be used that are permissible in accordance with the
table below.
CEM-A-BE05-EX
CES-A-BMB-EX
CES-A-BBA-EX
Evaluation unit Read head
098 158
098 159
097 178
CES-A-LNA-SC-EX
098 156
CES-AZ-AES-01B-EX CES-A-LMN-SC-EX
105 142 098 157
CEM-A-LE05K-S2-EX
097 176
Combination possible
System Manual Safety System CES-AZ-AES-01B-EX
Safety precautions
The safety system CES-AZ-AES-01B-EX complies with the following safety require-
ments:
Proximity device with self-monitoring type PDF-M according to EN 60947-5-3.
Performance level e according to EN 13849-1: 2007-07
In relation to the structural requirements, category 4 in accordance with EN
13849-1: 2007-07, comparable to category 4 in accordance with EN 954-1, is
achieved.
Redundant design of the circuit in the evaluation unit with self-monitoring. As a
result, the safety system is still effective even if a component fails.
When the safety guard is opened and closed, it is checked whether the safety
system relays open and close correctly.
Monitoring output O1 must not be used as a safety output.
Safety switches fulfill personal protection functions. Incorrect installation or tamper-
ing can lead to severe injuries to personnel.
The number of teach-in and switching operations is saved in the internal memory in
the evaluation unit. If necessary, this memory can be read by the manufacturer.
Check the safe function of the safety guard particularly
after any setup work
after the replacement of a CES component
after an extended period without use
Independent of these checks, the safe function of the safety guard should be
checked at suitable intervals as part of the maintenance schedule.
The year of manufacture of the device can be derived from the serial number on
the rating plate.
Important!
The evaluation unit must be replaced with a new device after 5 years of opera-
tion.
Important!
Prior to use, read the operating instructions and the system manual of the
CES components used, and keep these in a safe place. Ensure the operat-
ing instructions and the system manual are always available during mounting,
setup and servicing. EUCHNER cannot provide any warranty in relation to the
readability of the CD for the storage period required. For this reason you should
archive a printed copy of the system manual. If you should lose the operating
instructions or the system manual, you can download these documents from
www.EUCHNER.de.
System Manual Safety System CES-AZ-AES-01B-EX
System description
The CES non-contact safety system consists of three components:
Coded actuator
Read head
Evaluation unit
1 read head may be connected to the evaluation unit CES-AZ-AES-01B.
It is also possible to connect a start button (monitored start) and a feedback loop
for monitoring external relays and contactors.
The individual configuration is defined by a setup procedure.
Each delivered actuator possesses a unique electronic coding and so is a unique
element in the system used. The code in an actuator cannot be reprogrammed.
The read heads are fastened to the fixed part of the safety guard and are each
connected to the evaluation unit via a two-core screened cable.
The actuator fastened to the movable part of the safety guard is moved towards the
read head by closing the door. When the switch-on distance is reached, power is
supplied to the actuator by the inductive read head and data can be transferred.
The bit pattern read is compared with the code saved in the evaluation unit. If the
data match, the door monitoring output O1 (semiconductor output) on the read
head is set HIGH and the safety outputs (relay outputs) are then enabled. The OUT
LED illuminates.
Optionally, a feedback loop can be connected to the evaluation unit. Then the evalu-
ation unit can only be started with the feedback loop closed. A welded contactor
contact in the release path will thus be detected when a start request is made.
Due to the combination of dynamic polling of the actuators and the redundant,
diverse design of the safety electronics with two safety outputs, the evaluation
unit will enter the safe state with every detectable fault.
When a safety guard is opened, the safety outputs switch off the safety circuit and
the OUT LED goes out. The state of the safety outputs is monitored internally by
positively driven NC contacts (relay output).
Independent of the switching state of the safety circuit, the position of the safety
door can be polled via the output O1.
If an internal fault occurs in the evaluation unit, the safety circuit is switched off,
the diagnostic output (DIA) is set HIGH and the DIA LED illuminates red.
System Manual Safety System CES-AZ-AES-01B-EX
System Manual Safety System CES-AZ-AES-01B-EX
Installation
Warning!
Mounting must be performed only by authorized personnel.
Carry out the work only if there is no ignitable atmosphere and the system is
switched off.
Actuator and read head must be easily accessible for inspection and replace-
ment.
The switching operation must only be triggered by the specific actuator desig-
nated for this purpose.
Actuator and read head must be fitted so that
the front faces are at the minimum switch-on distance 0.8 x Sao or closer (see
technical data) with the safety guard closed.
when the safety guard is opened to the assured switch-off distance Sar, a haz-
ard is excluded.
Note: From the assured switch-off distance Sar, the relay outputs are safely
switched off.
they are positively mounted on the safety guard, e.g. using the safety screws
included (cube-shaped design) or adhesive (cylindrical design M12).
they are not used as a mechanical end stop.
Note: Fit an additional end stop for the movable part of the safety guard.
Pay attention to the maximum tightening torque for the read head or safety
switch and actuator mountings of 1 Nm.
If installed flush, the switching distance changes as a function of the installation
depth and the safety guard material.
The evaluation unit must be mounted in a control cabinet with a minimum de-
gree of protection of IP 54. A snap-in element on the rear of the device is used
for fastening to standard rails.
If several evaluation units are mounted side by side in a control cabinet without
air circulation (e.g. fan), a minimum distance of 10 mm must be maintained
between the evaluation units.
The distance enables heat from the evaluation unit to dissipate.
When mounting several read heads, observe following minimum distance to
avoid mutual interference:
- for CES-A-LNA-SC-EX min. 50 mm
- for CES-A-LMN-SC-EX min. 20 mm
- for CEM-A-LE05K-S2 -EX min. 50 mm
System Manual Safety System CES-AZ-AES-01B-EX
Electrical connection
Warning!
Electrical connection may only be performed by authorized personnel trained
in EMC and with the device and wiring isolated.
Carry out the work only if there is no ignitable atmosphere and the system is
switched off.
System Manual Safety System CES-AZ-AES-01B-EX
M
TST O1 DIA Y1 Y2 S -M1 3~
23 24 13 14
21
-K4
22
21
A1 A1
-K3
-V1 -K3 -V2 -K4 22
A2 A2
feedback loop
GND
Important!
To achieve category 4 according to EN 13849-1 respectively EN 954-1, it is
necessary to monitor the downstream contactors (here contacts of -K3 and -K4
in the feedback loop).
If only one enable path is to be used for control (e. g. of downstream contactors),
failures involving a short circuit between the contacts on the enable path and, for
example, the power supply must be excluded.
With reference to EN 13849-2 Table D.5, this exclusion can be provided if
the cables are inside an electrical installation space and
the installation space meets the related requirements (see EN 60204-1 or
IEC 60204-1).
This example shows only an excerpt that is relevant for connection of the CES
system. The example illustrated here does not show complete system planning.
The user is responsible for safe integration in the overall system.
10
System Manual Safety System CES-AZ-AES-01B-EX
LED displays
STATE Green LED State display (multifunction display using flash-
ing modes)
OUT Yellow LED Safety circuit closed
DIA Red LED - Operating fault or
- External fault (fault in the feedback loop) or
- Invalid teach-in operation or
- Internal device fault or
- TST input activated (function test active)
Setup
During setup, the parameters are set in the evaluation unit by the user using a
teach-in operation (with or without automatic start, with or without feedback loop).
During this process the read head is activated.
These configuration parameters are saved in the non-volatile memory in the evalu-
ation unit.
To trigger a teach-in operation, the user must perform the following actions in the
stipulated order:
1. Prepare for teach-in operation
Switch off power supply UB
Fit a jumper between terminals J and 0V)
. Set required configuration on DIP switches
Switch designation Switch position left (OFF) Switch position right (ON)
5 Automatic start Manual start
(No start button connected) (Start button connected)
6 No feedback loop connected Feedback loop connected
11
System Manual Safety System CES-AZ-AES-01B-EX
Notes
During the teach-in operation the following conditions must be met:
There must be no state change, e.g. opening the safety guard or a change in
the signal on the terminals for the start button and the feedback circuit.
The power supply must not be switched off.
If these conditions are not met, the evaluation unit switches to the safe fault state
(diagnostics LED illuminates) and signals this operating fault with the STATE LED
by 3 short flashes that are repeated every second. The teach-in operation must
be repeated.
The number of teach-in operations is unlimited. The evaluation unit can be re-
configured as often as required.
Actuators cannot be interchanged without a renewed teach-in operation.
An actuator that has not been subjected to teach-in will not be detected by the
read head.
Even if only one new actuator needs to be taught, a complete new teach-in
operation must be carried out as described in the section Setup.
Do not change DIP switches during operation.
12
System Manual Safety System CES-AZ-AES-01B-EX
STATE (green)
Operating mode State
OUT (yellow)
4 Hz DIA (red) Initial setup after delivery without jumper connected to J, 0V.
Setup
1 Hz Teach-in operation
15 Hz
Self-test, duration approx. 10 seconds, is performed after applying the operating voltage UB
(10 s)
Normal operation, monitored door is closed (after pressing the start button, for Manual start operating
mode)
Device-internal component failure or actuator CES-A-BMB-EX in the inadmissible range or excessively high
Fault display
external interference (EMC)
Configuration fault:
Teach-in operation must be performed again
Possible causes:
- State change during the teach-in operation
- During teach-in operation no read head connected or no actuator in the operating distance
3x - The DIP switch setting and the configuration did not match during the teach-in operation
- DIP switch setting has been changed without teach-in operation
- The teach-in jumper (J, 0V) was fitted with power supply switched on
Operating fault - Closed feedback loop (Y1,Y2) present, although a feedback loop was not present during teach-in
- 24 V signal present at the start button input (S) although teach-in was performed with “Automatic start”
operating mode.
Fault in feedback loop
Possible causes:
- Malfunction of the monitored contactor
4x
- Following removal from the operating distance, actuator is not outside the operating distance long enough.
As a result the feedback loop cannot be closed in this short time. Note the release time for the monitored
contactor.
LED is lit
X Any state
13
System Manual Safety System CES-AZ-AES-01B-EX
Exclusion of liability
Exclusion of liability under the following conditions:
incorrect use
non-compliance with safety regulations
installation and electrical connection are carried out by unauthorized personnel
if modifications are made
14
System Manual Safety System CES-AZ-AES-01B-EX
Technical data
Approvals Evaluation unit CES-AZ-AES-01B-EX
Housing for DIN rail mounting, IP 20
Relay output
Approval pending 1 read head can be connected
99
Y
CES-AZ
Unicode
13 O1 Y1 23
14 DIA Y2 24
13 14 13 14
23 24 23 24
24 V O1 24 V O1
15
System Manual Safety System CES-AZ-AES-01B-EX
Technical data
Value
Parameter Unit
min. typ. max.
Housing material Plastic PA6.6
Dimensions 114 x 99 x 22.5 mm
Weight 0.2 kg
Ambient temperature at UB = DC 24 V -20 - +55 °C
Atmospheric humidity, not condensing - - 80 %
Degree of protection acc. to EN 60529 1) IP20
Degree of contamination / material group 2 / IIIa
Installation DIN rail 35 mm according to EN 50022-35
Number of read heads 1 read head per evaluation unit
Connection (plug-in screw terminals/coded) 0.14 - 2.5 mm²
Operating voltage UB (regulated, residual ripple < 5 %) 2) 21 24 27 V DC
For the approval according to the following applies Operation with UL-class 2 power supply only
Current consumption IB (with relay energized) 3) - 150 - mA
External fuse (operating voltage UB) 0.25 - 8 A
Safety contacts 2 (relays with internally monitored contacts)
Switching current (relay outputs)
- At switching voltage AC/DC 21 ... 60 V 1 - 300
mA
- At switching voltage AC/DC 5 ... 30 V 10 - 4000
- At switching voltage AC 5 ... 160 V 10 - 2000
Switching load according to Max. AC 30 V, class 2 / max. DC 60 V, class 2
External fusing (safety circuit) according to EN 60269-1 6 AgG or 6 A circuit breaker (characteristic B or C)
Utilization category according to EN 60947-5-1 AC-12 60V 0.3A / DC-12 60V 0.3A
AC-12 30V 4A / DC-12 30V 4A
AC-15 160V 2A / DC-13 24V 3A
Category according to EN 13849-1 4
Classification acc. to EN 60947-5-3 PDF-M
Rated insulation voltage Ui 250 V
Rated impulse withstand voltage Uimp 4 kV
Rated conditional short-circuit current 100 A
Resilience to vibration According to EN 60947-5-2
Mechanical operating cycles (relays) 10 x 106
Switching delay from state change 4)
- - 210 ms
Time difference (between the switching points of the two
- - 25 ms
relays)
Current via feedback loop Y1/Y2 5 8 10 mA
Permissible resistance via feedback loop - - 600 W
Ready delay 5) - 10 12 s
Dwell time 6) 3 - - s
Switching frequency max. 7) - - 0.25 Hz
Monitoring outputs (diagnostics DIA, door monitoring output
O1, semiconductor output, p-switching, short circuit-protected)
- Output voltage 0.8 x UB - UB V DC
- Max. load - - 20 mA
Start button input S, test input TST
- Input voltage LOW 0 - 2
V DC
HIGH 15 - UB
- Input current HIGH 5 8 10 mA
EMC protection requirements As per EN 60947-5-3
1) The evaluation unit must be mounted in a control cabinet with a minimum degree of protection of IP 54.
2) Supply using a safety transformer according to EN 61558-2-6 is necessary.
3) Without taking into account the load currents on the monitoring outputs.
4) Corresponds to the risk time according to EN 60947-5-3. This is the maximum switch-off delay for the safety outputs following removal of the actuator. In case of EMC interference in excess
of the requirements in accordance with EN 60947-5-3, the switch-off delay can increase to max. 250 ms. After a brief actuation < 0.25 s, the switch-on delay can increase to max. 3 s if this is
followed immediately by further actuation.
5) After the operating voltage is switched on, the relay outputs are switched off and the monitoring outputs are set LOW during the ready delay. For the visual indication of the delay, the green
STATE LED flashes at a frequency of approx. 15 Hz.
6) The dwell time is the time that the actuator must be inside or outside the operating distance.
7) If the current load is > 100 mA, a switching frequency of 0.1 Hz should not be exceeded as this will affect the mechanical life of the relay contacts.
16
System Manual Safety System CES-AZ-AES-01B-EX
8
4,5
CD IP67
CES-A-LNA-SC-EX-098156
10
25
5,5
Active face
I I 3G Ex nL I I C T70°C 3
min.38 5,5 4
Active face
2 safety screws M4 x 14
included
I I 3G Ex nL I I C T70°C
20,1
m Output state
Actuator
Hysteresis
s ON
Read head
OFF
Sao Distance s
20 Switch-off
distance
Distance s [mm]
OFF OFF
15 Hysteresis
Switch-on
distance
10
Side Side
lobe lobe
N 5 N
ON
17
System Manual Safety System CES-AZ-AES-01B-EX
Pin assignment
Read head with plug connector
WH Screen 3
4
BN 1
Technical data
Parameter Value Unit
min. typ. max.
Housing material Fortron, reinforced thermoplastic, fully encapsulated
Dimensions 42 x 25 x 12 mm
Weight (incl. 10 m cable) 0.3 kg
Ambient temperature -25 - +60 °C
Degree of protection IP67/IP69K
Installation position Any
Method of operation Inductive
Power supply Via evaluation unit
Operating distance for center offset m = 0 1)
- Switch-on distance - 15 -
- Assured switch-on distance Sao 10 - -
- Switching hysteresis 0.5 2 -
Connection M8 plug connector (snap-action and screw terminals), 3-pin
Connection cable - - 25 m
1) These values apply for surface installation of the read head and the actuator.
18
System Manual Safety System CES-AZ-AES-01B-EX
4 17
35
connected
19,7
M 12x1
32 1)
EUCHNER
m
I I 3G
T70°C
Centre offset
Active face
M 8x1
5 1)
8
30
37
Note
The read head is allowed to be installed as a maximum up to the clear zone (area
of the active face without metal housing).
OFF
Sao Distance s
8
Distance s [mm]
Switch-off
6 distance
OFF OFF
Hysteresis
4 Switch-on
distance
ON
2
-8 -6 -4 -2 0 2 4 6 8
Centre offset m [mm]
Note
A minimum distance of s = 1.2 mm must be maintained.
19
System Manual Safety System CES-AZ-AES-01B-EX
Pin assignment
Read head with plug connector
WH Screen 3
4
BN 1
Technical data
Parameter Value Unit
min. typ. max.
Housing material Nickel-plated CuZn housing sleeve
Plastic PBT GF20 cap
Dimensions M12 x 1, length 38 mm
Weight (incl. 10 m cable) 0.2 kg
Ambient temperature -25 - +60 °C
Ambient pressure
- - 10 bar
(only of active face in installed condition)
Degree of protection IP67
Installation position Any
Method of operation Inductive
Power supply Via evaluation unit
Operating distance for center offset m = 0 1)
20
System Manual Safety System CES-AZ-AES-01B-EX
14,5
Read head
Actuator
7
± 4°
80
65
49,5
Solenoid
8 ∅ 50
28
OFF
4 Sa0 Distance s
Distance s [mm]
OFF 3
Switch-off OFF
distance
Hysteresis
2
Switch-on
distance Sa0
1
ON ON
-4 -3 -2 -1 0 1 2 3 4
Center offset m [mm]
Wiring diagram
CEM-A-LE05K-S2-EX
S1.4 3
1 2
4
3 4
1
NC
S1.2
Solenoid operating Evaluation unit
voltage S1 S3 CES
S1.1 UON/DC 24 V S3.1 Data line
UON S1.2 - S3.3 Data line
S1.1
YE S1.3 0 V/GND S3.4 SH (screen)
Solenoid
S1.4 y
0V
S1.3
Circuit diagram connection of
solenoid operating voltage S1
A free-wheeling diode is already
integrated into each CEM.
21
System Manual Safety System CES-AZ-AES-01B-EX
Technical data
Value
Parameter Unit
min. typ. max.
General
Housing material Aluminum
Material, read head CES Plastic (PPS)
Solenoid material Galvanized steel
Weight approx. 0.3 kg
Ambient temperature -25 - +50 °C
Degree of protection according to EN 60529 IP67
Installation position Any
Solenoid
Adhesive force in axial direction 500 N
Adhesive force due to remanence 1) approx. 10 ± 25 % N
Solenoid center offset max. ± 2.5 mm
Solenoid operating voltage UB/UON connector S1 24 +10%/-15% V DC
Reverse polarity protection Yes
Free-wheeling diode Yes
Current consumption at terminal connection S1.1 (UON) 100 mA
Power consumption approx. 2.5 W
Switch-off delay 500 ms
Solenoid operating voltage connection M8 plug connector (male socket), 4-pin
Yellow LED integrated in the plug connector (see circuit diagram)
Read head
Operating distance for center offset m = 0
- Assured switch-off distance Sar - - 20
Cable length l = 0 to 25 m
mm
- Switch-on distance - 2 -
- Assured switch-on distance Sao 0 - -
- Switching hysteresis - 0.7 -
Connection evaluation unit plug S3 M8 plug connector (male socket), 3-pin
Connection cable - - 25 m
1) The remanence disappears immediately when the door is opened and over time in de-energized solenoids.
22
System Manual Safety System CES-AZ-AES-01B-EX
ø4,5
ø8
CD IP67
CES-A-BBA-EX-098158
25
I I 3G Ex nL I I C T70°C
I I 3D Ex tD A 22 T70°C
2 safety screws M4 x 14
included
Technical data
Value
Parameter Unit
min. typ. max.
Housing material Fortron, reinforced thermoplastic, fully encapsulated
Dimensions 42 x 25 x 12 mm
Weight 0.02 kg
Ambient temperature -25 - +60 °C
Degree of protection IP67/IP69K
Installation position Active face opposite read head
Power supply Inductive via read head
23
System Manual Safety System CES-AZ-AES-01B-EX
M12x0,75
098159
EUCHNER
11
I I 3G
T70°C
6 Active face
Notes
The actuator can be screwed into the M12 x 0.75 thread provided with the aid
of an insertion tool (Order No. 037 662).
Flush installation of the actuator in steel is allowed.
Technical data
Value
Parameter Unit
min. typ. max.
Housing material Stainless steel
Dimensions M12 x 0.75, depth 6 mm
Weight 0.002 kg
Ambient temperature -25 - +60 °C
Degree of protection IP67
Installation position Active face opposite read head
Power supply Inductive via read head
24
System Manual Safety System CES-AZ-AES-01B-EX
40 ±0,10
8 5,4
Active
face
14,5
7
80
65
49,5
Solenoid
X
4° 4° Ø48
Technical data
Value
Parameter Unit
min. typ. max.
Housing material Aluminum
Material, read head CES Plastic (PPS)
Solenoid mating plate material Galvanized steel
Weight approx. 0.18 kg
Ambient temperature -25 - +50 °C
Degree of protection according to EN 60529 IP67
Installation position Active face opposite read head
Adjustment angle (around point X, see dimension drawing) ±4 °
25
System Manual Safety System CES-AZ-AES-01B-EX
Read heads
Series Cable/connection type Cable length “l” [m] Order No. / Item
098 156
CES-A-LNA-SC-EX M8 plug connector with ATEX rating
CES-A-LNA-SC-EX
098 157
CES-A-LMN-SC-EX M8 plug connector with ATEX rating
CES-A-LMN-SC-EX
097 176
CEM-A-LE05K-S2-EX M8 plug connector with ATEX rating
CEM-A-LE05K-S2-EX
Actuators
Series Comment Version Order No. / Item
098 158
CES-A-BBA-EX 2 safety screws M4 x 14 are supplied with ATEX rating
CES-A-BBA-EX
098 159
CES-A-BMB-EX - with ATEX rating
CES-A-BMB-EX
097 178
CEM-A-BE05-EX - with ATEX rating
CEM-A-BE05-EX
Accessories
Series Comment Version Order No. / Item
Connection set
for evaluation units for evaluation unit CES-AZ-AES-01B Screw terminals 104 756
with plug-in screw terminals
Insertion tool for actuator CES-A-BMB - 037 662
26
System Manual Safety System CES-AZ-AES-01B-EX
Declaration of conformity
Konformitätserklärung
Declaration of Conformity
f: EN 61241-1 Elektrische Betriebsmittel zur f: EN 61241-1 Electrical apparatus for use in the
Verwendung in Bereichen mit presence of combustible dust -
brennbarem Staub – Protection by enclosures “tD”
Schutz durch Gehäuse „tD“
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen Tel. +49/711/ 75 97-0 Fax +49/711/ 75 33 16 www.euchner.de info@euchner.de
077154-14 - Blatt 1
27
System Manual Safety System CES-AZ-AES-01B-EX
CEM-A-L…(-EX)
CET1-AX… a, b, c, d (e) (Ex-Zone 2)
CTK1-AX…
Betätiger
Actuator CES-A-B... (-EX) a, b, c, d (e) (Ex-Zone 2)
CEM-A-B... (-EX)
CES-A-N…
a, b, c, d (e) (Ex-Zone 2)
CET-A-B..
CTK-A-B…
Die Verwendung dieser Produkte in einer Maschine The use of these products within a machine does not
gewährleistet nicht, dass die gesamte Maschine oder guarantee that the entire machine corresponds to the
Anlage den europäischen Richtlinien entspricht. European directives.
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 70771 Leinfelden-Echterdingen Tel. +49/711/ 75 97-0 Fax +49/711/ 75 33 16 www.euchner.de info@euchner.de
077154-14 - Blatt 2
28
System Manual Safety System CES-AZ-AES-01B-EX
29
Euchner GmbH + Co. KG
Kohlhammerstraße 16
D-70771 Leinfelden-Echterdingen
info@euchner.de
www.euchner.de
Issue:
105313-02-04/09
Title:
System Manual Safety System CES-AZ-AES-01B-EX
(Translation of the original operating instructions)
Copyright:
© EUCHNER GmbH + Co. KG, 04/2009