Professional Documents
Culture Documents
Multi V 2 Trouble Shooting Guide Book
Multi V 2 Trouble Shooting Guide Book
Guide Book
No part of this publication may be reproduced, stored in or introduced into a retrieval
system, or transmitted, in any form, or by any means (electronic, mechanical, photocopying,
or otherwise), without prior permission of the LG Electronics Inc. Air-Conditioning Division
Contents
Search with Error Code number
1. Basic Part
1.1 Unit conversion (Energy / Pressure)
1.2 NOMENCLATURE
1.3 LGMV Guideline
1.4 Temperature vs. pressure of refrigerant
1.5 P-h Diagram
1.6 Cycle Circuit & Sensor
1.7 Outdoor Wiring Diagram
4. Solution Check
- PC central controller
- Simple central controller and CNU
- LG utility setting
- TeraTerm setting
- PI485 check
- PDI check
- One point service manual
R: Reserved
4
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.2.2 Multi V Plus Outdoor Unit (R410A)
1.2.1 Multi V Indoor Unit (R410A)
5
1.2 NOMENCLATURE
1.2.3 Multi V Plus II Outdoor Unit (R410A)
6
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.2.5 Multi V Space Outdoor Unit (R410A)
7
1.2.6 Multi V Sync Outdoor Unit (R410A)
8
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.2.8 Multi V Plus Outdoor Unit (R22)
9
1.2.7 Multi V Indoor Unit (R22)
1.3 LGMV Guideline
Abnormal Abnormal
No Item Unit R22,407C 410A Cause & Check Point
condition condition
Overcharging(30Hz),Fan Lock
above 2200 above 3200
1 High Pressure kPa 1100~1800 2000 ~ 3000 Overchaning(25Hz:Plus II)
below 900 below 1800 Ref. Leakage or Ref. Shortage
Low Pressure above 600 above 1300 Overcharging
2 kPa 300~500 600 ~ 1000
(Cooling) below 250 below 400 Ref. Leakage or Ref. Shortage
above 1000 above 1000 Ref. Leakage or Ref. Shortage
3 Indoor LEV Pulse 200~600 200~600
below 200 below 200 Overcharging
4 Outdoor LEV Pulse 1944 - 1344 - Full Open
Indoor pipe Overcharging
5 ఁ above 0ఁ below -1ఁ above 0ఁ below -1ఁ
[Outlet-inlet] LEV fault
Indoor pipe Ref. Leakage,
6 ఁ 8ఁ~15ఁ above 17ఁ 6ఁ~15ఁ above 17ఁ
Inlet,Outlet Indoor Path. Clogging
Overcharging
High Pressure above 2300 above 3300
7 kPa 1600~2000 2500 ~ 3200 Fan Lock
(Heating)
below 1400 below 2300 Ref. Leakage or Ref. Shortage
above 800 above 1200 LEV fault
8 Low Pressure kPa 200~600 200 ~ 1200
below 120 below 120 Ref. Leakage or Ref. Shortage
10
1.4 Temperature vs. pressure of ref.
Basic Part
Saturation temperature vs. saturation pressure table for
each refrigerant
Absolute pressure = Guage pressure + 101.325 kPa
kPa = kgf/cm2 X 101.97
R-22 R-407C
Troubleshooting
Guide for each
Error Code
Relative ۀۑۄۏڼۇۀڭ
Temp. ډۋۈۀگ Relative pressure(kPaG) Temp.()
Pressure ۀۍېێێۀۍۋ
ڿۀۏڼۍېۏڼڮ ڿۀۏڼۍېۏڼڮ ڿۀۏڼۍېۏڼڮ
kPaG ێڼڢٻڿۀۏڼۍېۏڼڮ kPaG
ڿۄېیۄڧ ڿۄېیۄڧ ێڼڢ
-30 62.56 -30 86.75 37.87 50 -35.26 -28.35
-25 100.11 -25 129.50 72.67 100 -28.52 -21.75
-20 143.99 -20 179.43 113.92 150 -22.99 -16.34
-15 194.87 -15 237.28 162.41 200 -18.25 -11.71
Component Check
-10 253.46 -10 303.86 218.96 250 -14.09 -7.64
Electrical
-5 320.48 -5 378.98 284.43 350 -6.98 -0.69
0 396.66 0 466.50 359.72 400 -3.87 2.35
5 482.78 5 564.29 445.77 500 1.71 7.78
10 579.62 10 674.25 543.56 600 6.63 12.57
15 687.99 15 797.30 654.12 750 13.09 18.85
20 808.69 20 934.41 778.51 850 16.94 22.59
25 942.59 25 1086.55 917.87 1000 22.17 27.67
30 1090.55 30 1254.72 1073.36 1150 26.91 32.24
Solution Check
35 1253.46 35 1439.97 1246.28 1300 31.23 36.42
40 1432.25 40 1643.37 1437.87 1550 31.23 36.42
45 1627.89 45 1866.04 1649.67 1750 42.42 47.18
50 1841.36 50 2109.14 1883.24 2000 47.78 52.30
55 2073.75 55 2373.87 2140.33 2250 52.69 56.97
60 2326.16 60 2661.51 2422.98 2550 58.09 62.08
65 2599.83 65 2973.36 2733.60 2850 63.05 66.74
70 2896.07 70 3310.77 3075.22 3200 68.38 71.69
Test functions
R-410A
Relative
Temp. Relative pressure(kPaG) Temp.()
pressure
Saturated Saturated Saturated
Saturated Gas kPaG
Liquid Liquid Gas
-30 169.62 168.91 170 -30.09 -30.02
-25 229.70 228.81 230 -25.08 -25.01
-20 299.57 298.46 300 -20.06 -19.99
-15 380.23 378.87 380 -15.09 -15.01
-10 472.75 471.09 470 -10.21 -10.12
-5 578.21 576.21 580 -4.98 -4.89
0 697.76 695.38 700 0.04 0.13
5 832.60 829.77 830 4.86 4.96
10 983.94 980.63 980 9.84 9.94
15 1153.09 1149.25 1150 14.88 14.98
20 1341.39 1336.98 1350 20.18 20.29
25 1550.25 1545.26 1550 24.96 25.08
30 1781.19 1775.59 1800 30.36 30.47
35 2035.78 2029.59 2000 34.30 34.42
40 2315.76 2309.03 2300 39.71 39.82
45 2623.00 2615.82 2600 44.62 44.73
50 2959.61 2952.13 2950 49.84 49.95
55 3328.02 3320.49 3400 55.91 56.01
60 3731.18 3724.00 3700 59.61 59.70
65 4173.11 4166.98 4200 65.28 65.34
70 4746.09 4706.31 4700 70.17 70.17
11
1.5 P-h Diagram
R22
R410A
12
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.6.1.1 Main Outdoor Unit(5/6 HP)
13
1.6 Cycle Circuit & Sensor
1.6.1 Multi V Plus, Plus II
1.6.1.2 Main Outdoor Unit (Plus II 8HP)
14
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.6.1.3 Main Outdoor Unit (Plus 8~14HP, Plus II 10~16HP)
15
1.6.1.4 Sub Outdoor Unit (Plus 8/10/12/14 HP)
16
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
17
1.6.2.1 Cooling Mode
1.6.2 Multi V Sync
1.6.2.2 Heating Mode
18
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.6.2.3 Cooling Oriented Simultaneous Operation
19
1.6.2.4 Heating Oriented Simultaneous Operation
20
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
21
1.6.3 Multi V Space (10HP)
1.. Outdoor Wiring Diagram
1.7.1 Multi V Plus
1.7.1.1 Multi V Plus Main Unit
22
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.7.1.2 Multi V Plus II Sub 5,6HP(UY2)
23
1.7.1.3 Multi V Plus II 8HP(UW1)
24
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
1.7.1.4 Multi V Plus II 10,12,14,16HP(UW1)
25
1.7.1.5 Multi V Plus II 10,12HP(UW1)
26
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
27
1.7.1.6 Multi V Plus Sub Unit
1.7.2 Multi V Space
28
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
29
1.7.3.1 Multi V Sync Main Unit
1.7.3 Multi V Sync
1.7.3.2 Multi V Sync Sub Unit
30
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
31
1.7.4 HR Unit
MEMO
2. Troubleshooting
Guide for each
Error Code*
* Includede model :
Plus, Sync, Plus II (Tropical)
Error code Error Contents Meaning Main Causes
Is sensor properly No
Connect properly to PCB
connected to PCB?
Yes
Yes
* In case the value is more than 100 ༮ (open) or less than 100 ȳ(short), Error occurs
34
Error code Error Contents Meaning Main Causes
Basic Part
1. Remote controller fault
The remote controller did not 2. Indoor unit PCB fault
No transmission between cabled remote
03 receive the signal from indoor 3. Connector fault, Wrong
controller & indoor unit
unit during specific time connection
4. transmission cable problem
Troubleshooting
Guide for each
Error Code
Does the error happens No
Replace cabled remote
again if the remote
controller
controller is replaced?*
Yes
Component Check
No
Does the error occurred
Electrical
Check connection &
when the cable of remote
transmission cable **
controller is replaced?
Yes
Solution Check
* If there is no remote controller to replace : Use another unit’s remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
˧ make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
Test functions
CN-REMO : Remote controller connection
35
Error code Error Contents Meaning Main Causes
Yes
Yes
Replace Indoor PCB or
reconnect the connector
No
Drain pump blocked by Check the drain head height
foreign particles? and slope***
Yes
Checking float
switch
Remove it & clean the pump (Low position short 0 ohm )
float
Condensate water
36
Basic Part
float
Troubleshooting
Guide for each
Error Code
***Indoor PCB drain pump connector
Component Check
A:Point to check rotating
(Check input of 220V)
Electrical
(Marked as CN-DPUMP)
Solution Check
Float switch Housing (CN-FLOAT)
Test functions
MAX 450
37
Error code Error Contents Meaning Main Causes
* If the DC voltage between transmission terminal A, B ** If the DC voltage between transmission terminal A, B
of outdoor unit is fluctuate within (-9V~+9V) then of indoor unit is fluctuate within (-9V~+9V) then
transmission from indoor unit is normal transmission from outdoor unit is normal
38
Error Code Error Contents Meaning Main Causes
Basic Part
Indoor unit outlet pipe Indoor unit outlet pipe temperature
06 Refer to CH02
temperature sensor error sensor open or short
Troubleshooting
Guide for each
Error Code
Error diagnosis and countermeasure flow chart
Is error code
Is operation mode of No No
disappeared
outdoor & Indoor units Replace Indoor PCB****
Component Check
after set operation
same?
mode same?***
Electrical
Yes Yes
END
Solution Check
* Check mode select setting of wired remote controller.
** Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error
Test functions
may be occurred because the operation mode is fixed by dip switch setting.
**** After replacing the indoor unit PCB, it should be done to do Auto addressing and input the address of central control
39
Error Code Error Contents Meaning Main Causes
- Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control
40
Error Code Error Contents Meaning Main Causes
Basic Part
1. Motor connector connection fault
Indoor unit BLDC fan motor Indoor BLDC fan motor feedback
10 2. Indoor PCB fault
failure signal is absent (for 50 sec.)
3. Motor fault
Troubleshooting
Guide for each
Error Code
Is connector No
Connect properly
connection proper?
Yes
Is fan motor No
Component Check
Replace indoor unit fan motor
normal?*
Electrical
Yes
Solution Check
* It is normal when check hall sensor of indoor fan motor as shown below
Test functions
hundreds kȳ hundreds kȳ
hundreds kȳ hundreds kȳ
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control
(Notice: The connection of motor connector to PCB should be done under no power supplying to PCB)
41
Error Code Error Contents Meaning Main Causes
Yes Yes
END
42
Error Code Error Contents Meaning Main Causes
Plus :21
Basic Part
1. Over current detection at the inverter
Plus II:
compressor (U,V.W)
211,212,213,214
2. IPM overheating.
3. Insulation damage of the compressor
S IPM fault of inverter Defective inverter compressor,
N1 Right / compressor motor damage
Inverter element (IPM) defect
P 21 Comp. compressor 4. Low input voltage at the outdoor
A 5. Inverter compressor terminal disconnected
C or loose.
E N2 Left
6. Inverter PCB / IPM PCB defect
Troubleshooting
21 Comp.
Component Check
of Inverter compressor normal ?
[refer electric component part]
Electrical
Yes
Yes
Solution Check
Is IPM normal? No
Replace IPM
[refer electric component part]
Yes
Is capacitor normal? No
Replace capacitor
[refer electric component part]
Yes
Test functions
normal? *
Yes
No
Is it Multi V Space? Multi V Plus, Multi V Sync
Yes
Yes
Is magnetic switch No
Replace Magnetic switch
Normal?
Yes
43
Point Checking
Plus
Comp.
Running
Current
(COMP
start)
Coil resistance INV, const. speed comp. resistance :INV COMP ˧ 1.2˟·10%(Plus), 0.35˟·10%(plus II)
(No power) :Constant speed COMP : (U-V)1.96˟/(V-W)1.91˟/(U-W)1.99˟·10%)
Insulation
resistance Insulation resistance : INV COMP ˧ above ༯, const. comp : above ༯
(No power)
Compressor
connector
Comp. connector Comp. conector Cooling fan connector Cooling fan operation
(Plus II)
44
Part Check
(Function) points
Basic Part
INV 2. Power & 3. High pressure 4. DC-Link 6. transmission 5. Checking circuit
COMP start-relay switch & sensing & circuit to main for reverse phase
PCB drive circuit power-relay display circuit PCB of input power
drive circuit
(INV
COMP
part)
Troubleshooting
Guide for each
Error Code
(plus)
7. On-board
writing
connector
1. MICOM
circuit
Component Check
Electrical
8. CT sensing
circuit
9. PWM driving
signal output
circuit
Solution Check
Phenomena Check point How to check? Counter-measure
No power 2.Power -Input voltage should be 220V. - Check & replace fuse(3.15A),
at PCB (when power is supplied) T-N voltage (220V)
-Input resistance should be more than a few ༮ - If resistance value is
(when power is not supplied) 0~100˟ ,
replace PCB
Test functions
No transmission 6.Transmiss -Yellow LED should blink. - Check yellow LED blinks or
ion circuit not
to main - When is OFF, check
PCB transmission
with main PCB and replace
Inverter compressor Red LED -When red LED blinks. -Check error code displayed at
PCB Error Error displays about inverter compressor PCB main PCB
45
Part
Check point
(Function)
(Plus)
Sub PCB
Heat sink
cooling fan
(Plus)
46
Part Check
(Function) How to check? Counter-measure
points
Basic Part
Capacitor Electric capacity. -Electricity capacity of capacitor must be - Replace capacitor
(To charge DC (when power is 2600~2800༲ and the resistance of capacitors when value is more or
voltage for not supplied) should be more than a few ༮ less than normal spec.
inverter
compressor)
(Plus)
Troubleshooting
Guide for each
Error Code
* Check values at both
terminal of capacitor
DC charging - Charged voltage of between terminals of capacitor - Check input voltage
Component Check
voltage (= between IPM P-N terminal = DC link terminals) and
(When power is should be more than 450V replace capacitor
Electrical
supplied) (At the moment of inverter compressor start)
Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is
Switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟,
(When power is not supplied) Replace Magnet
(Plus) switch
Solution Check
-When magnet switch is on, voltage should be 220V
(When power is not supplied) -When voltage is not
220V, magnet switch
is melt down
- Replace magnet
switch
Test functions
** check point of 1st coil of magnet switch
Magnet switch - While pressing green button of magnet switch, -Replace magnet
connection Voltage of each connectors should be 0V or switch
check Resistance should be 0~1˟
(In case power (Warning: power should not be supplied)
is not supplied)
47
Part Check
(Function) points
(Plus II)
U terminal
7. On-board
V terminal writing connector
8. CT sensing circuit
9.Power relay
W terminal
10.Comm port
& LED
12. PWM LED 11. PWM driving signal output circuit
Inverter compressor 12. PWM -When red LED is on. -Check error code displayed at
PCB Error LED PWM is normal main PCB
48
Part
Check point
(Function)
Basic Part
IPM Check voltage
& resistance of
each phases
(CH21, (When power
- - -
CH22) is not supplied) + + +
Troubleshooting
Guide for each
Error Code
(Plus II) P-U :28kȳ·10% P-V :28kȳ·10% P-W : 28kȳ·10%
+ + +
Component Check
- - -
Electrical
N-U :28kȳ·10% N-V :28kȳ·10% N-W : 28kȳ·10%
Reverse: N-U :Open N-V :Open N-W : Open
Solution Check
Check power
Heat sink supplay and
cooling fan operation
status
(Plus II)
Test functions
Position of cooling fan Heat sink cooling fan
drive connector in main PCB
(220V output)
49
Part Check
How to check? Counter-measure
(Function) points
Capacitor DC charging - Charged voltage of between terminals of capacitor - Check input voltage
(To charge DC voltage (= between IPM P-N terminal = DC link terminals) and replace capacitor
voltage for (When power is should be more than 450V
inverter supplied) (At the moment of inverter compressor start)
compressor)
(Plus II)
Magnet Magnet switch When magnet switch is on, output voltage should be When output voltage is
Switch 380V (Running) not 380V, Replace PCB
(Plus II)
50
Error code Error Contents Meaning Main Causes
Basic Part
Plus:22 1. Compressor damage
Plus II: 2. Current sensing sensor (CT) damage
221,222,223,224 3. Low input voltage
The current flowing at the CT 4. compressor terminal is disconnected or loose
Over current of
N1 Right sensing circuit is more than the 5. Abnormality at the outdoor / indoor unit fan
S inverter
22 Comp. allowable maximum value of the 6. Cover or clogging
P compressor
A current (Outdoor unit covering during cooling mode
Troubleshooting
Guide for each
C / Filter clogged at the indoor during heating
N2 Left
Error Code
E mode )
22 Comp.
7. Defective inverter PCB/IPM PCB
Component Check
Are the resistance between No
Electrical
each phase and insulation resistance
Replace INV COMP
of Inverter compressor normal ?
[refer electric component part]
Yes
Is fuse normal? No
Replace FUSE
[refer electric component part]
Solution Check
Yes
Test functions
[refer electric component part]
Yes
Yes
51
Part Check
(Function) points How to check? Counter-measure
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within Standard·10% -Check supply power
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within and connection
Block, Input 220V·10%. condition
power) - Voltage fluctuation should be within 10V
- While stand-by and in operation,
Voltage drop should be within 10V
FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
loaded FUSE Replace FUSE
current) (when power is
supplied)
(plus)
Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
(Noise emit & (When power is be within 0~40V It is disconnected
protect) supplied) Replace noise filter
(Plus) (Plus II)
52
Part Check
(Function) points
Basic Part
INV PCB
(Plus) * Measure the CT current with clamp meter -Multi V SPACE : U(+), U(-), V(+), V(-)
The current difference among
* Multi V PLUS
- Multi / Sync
V PLUS / Sync : R phase phases is less than 0.5A ·10%
Troubleshooting
Guide for each
Error Code
Component Check
Electrical
U(+) U(-) V(+) V(-)
Solution Check
3ɐ DIODE
(Plus)
Test functions
P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
53
Part Check
(Function) points
INV PCB
* Measure the CT current with clamp meter
(Plus II)
*Current < 25A
3ɐ DIODE
(Plus II)
-In case the measured value is different from the table, set multi tester to resistance mode
and measure. If the value is small (0 ȳ) or high (hundreds M ȳ), PCB needs to be
replaced.
- In case that bridge diode is damaged, check if inverter PCB assembly(IPM) is needed to be
replaced.
54
Error Code Error Contents Meaning Main Causes
Basic Part
23(plus)
23(1~4,Plus II) 1. Looseness of DC link terminal
S N1 Right DC voltage charging for 2. Damage in starting relay
Problem in DC charging voltage
P 23 Comp. inverter compressor driving 3. Capacitor damage
after starting relay turned on
A defect 4. Defective sensing circuit of the
C N2 Left inverter PCB
E 23 Comp.
Troubleshooting
Guide for each
Error diagnosis and countermeasure flow chart
Error Code
Is noise filter and
No
fuse normal? Replace Noise Filter or Fuse
[refer electric component part]
Yes
Component Check
Is capacitor normal? No
Electrical
Replace Capacitor
[refer electric component part]
Yes
Solution Check
Yes * After indoor unit turned on and the compressor is not operated,
just before magnetic switch is turned on
the voltage between the 2 terminal as below is more than 270V
Check whether all the
connections and terminals
is normal and reconnect
Test functions
Plus / Sync Plus II
Part Check
How to check? Counter-measure
(Function) points
55
Part Check
How to check? Counter-measure
(Function) points
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power and
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within connection condition
Block, Input 220·10%.
power) - Voltage fluctuation should be within 10V
- While stand-by and in operation,
Voltage drop should be within 10V.
FUSE Check -Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
loaded FUSE Replace FUSE
current) (when power is
(plus) supplied)
Nose filter Check voltage -Voltage (R-R,S-S,T-T) < 0~10V - In case of 220V
(Noise emit & (When power is If voltage is higer than 10~40V, check resistance It is disconnected
protect) Supplied) (Plus) (Plus II) Replace noise filter
56
Error Code Error Contents Meaning Main Causes
Basic Part
24(Plus Main) 1. High pressure switch defect
24(1~4,Plus II) 2. Fan defect of indoor unit or outdoor unit
3. Check valve of compressor clogged
S N1 Right 4. Pipe distortion due to the pipe damage
P 24 Comp. 5. Refrigerant overcharge
A Excessive rise of Compressor off due to 6. LEV defect at the indoor or outdoor unit .
C N2 Left discharge pressure in the high pressure 7. Covering or clogging
E 24 Comp. outdoor compressor switch in outdoor unit (Outdoor covering during the cooling mode /
Indoor unit filter clogging during the heating mode)
Troubleshooting
Guide for each
(plus) 8. SVC valve clogging
Error Code
109 (Sub1) 9. Outdoor PCB defect
140 (Sub2) 10. HR unit valve coil defect(Multi V Sync)
154 (Sub3) 11. HR unit PCB defect(Multi V Sync)
Component Check
Is high pressure switch
No
Electrical
connector connected Connect securely
to PCB?*
Yes
Solution Check
Yes
Yes
Replace connecting cable
No
Is SVC valve open? Open SVC valve
Test functions
Yes
Yes
Yes
Is high pressure of No
LGMV similar as Replace high pressure sensor
at manifold gauge?
Yes
Yes
Next page
57
Is it Multi V Sync?
Yes
Is HR unit valve No
Connect HR unit valve connector
connector normal ?
Yes
Yes
Yes
Yes
Yes
Yes
58
* Plus : Connector location of high pressure switch at PCB(Refer electrical component part for Multi V Space)
Basic Part
Inverter compressor PCB SUB outdoor unit PCB
Troubleshooting
Guide for each
Error Code
Component Check
Checking short or not at connector of high Checking short or not at connector of high
Electrical
pressure switch pressure switch
Solution Check
**** Check resistance of HR unit valve coil : 1.85 k˟(·10%)
Test functions
- HR unit PCB-
59
* Plus II: Connector location of high pressure switch at PCB(Refer electrical component part for Mult V Space)
** Checking short or not at connector of high *** Checking short or not at connector of high
pressure switch pressure switch
60
Error Code Error Contents Meaning Main Causes
Basic Part
Plus:
25(Main)
147 (Sub1)
The power supply input voltage
149 (Sub2) Low / over voltage 1. Input voltage is abnormal(T-N)
tolerance is more or less than
171 (Sub3) of main PCB input 2. Outdoor unit main PCB defect
allowable standard
Plus I:,
251,252,253,
254
Troubleshooting
Guide for each
Error Code
Error diagnosis and countermeasure flow chart
Component Check
Yes
Electrical
Replace main PCB
Solution Check
Test functions
* Check voltage at outdoor T/Block(220V)
61
Error code Error Contents Meaning Main Causes
Plus II:
261,262,
263,264 1. U,Vㇵ connect orCOMP fault
S N1 Right At below min.Hz, 2. DC CT sensor fault
Compressor start failure
P 26 Comp. U,V current is lower than 1A 3. INV PCB fault
A 4. IPM component or connector fault
C N2 Left
E 26 Comp.
No
Is IPM normal ?
Replace IPM
[electric component part]
Yes
Is COMP normal? No
Replace COMP
[electric component part]
Yes
Yes
U(+)U(-)V(+)V(-)
62
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
63
Error diagnosis and countermeasure flow chart
Error diagnosis and countermeasure flow chart
64
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
65
Error Code Error Contents Meaning Main Causes
33 (Plus Main)
Plus II :
331,332,
333,334 Compressor is off 1. Temperature sensor defect of constant
Over-increase discharge
because of over-increase (Space:Inv.) compressor discharge pipe?
temperature of constant
Left discharge temperature of 2. Refrigerant shortage/leak
SPACE (Space:Inv.) compressor at
Comp.(N2) constant (Space:Inv.) 3. LEV defect
main constant outdoor and
compressor at main and 4. Liquid injection valve defect
plus sub constant outdoor unit
sub outdoor unit 5. Check solenoid valve defect(Sync)
100,101(Sub1)
102,103(Sub2)
152,153(Sub3)
Yes
Yes
Check another
No No components
Is it cooling mode of Is there pipe
and operation
Multi V Sync ? (strainer etc.) clogging?
conditions
Yes / Take measures
Yes
66
Is it cooling mode of No
Multi V Sync ?
Basic Part
Yes
Troubleshooting
Guide for each
Yes
Error Code
Is the outdoor unit No
check sol valve measure ~220V? Replace outdoor unit PCB
[electric component part]
Yes
Component Check
Electrical
Check for bent or blocked pipe
* Error is generated if the resistance is more than 5Mȳ (open) and less than 2 ༮ (short)
Solution Check
Note: Standard values of resistance of sensors at different temperatures (·5% variation)
10 = 362༮ : 25= 200༮ : 50= 82༮ : 100= 18.5༮
Test functions
Check the resistance
of constant compressor
discharge temperature
sensor
67
Check
Check points
Loc.
Check outdoor
unit LEV
Connector
resistance
1.85 k˟(·10%)
Liquid by pass
valve
Connector
resistance
1.85 k˟(·10%)
68
Check
Check points
Loc.
Basic Part
Hot gas by pass
Valve
Connector
resistance
1.85 k˟(·10%)
Troubleshooting
Guide for each
Error Code
Component Check
Electrical
Liquid by pass
valve
Connector
resistance
1.85 k˟(·10%)
Solution Check
Test functions
69
* Calculation of additional refrigerant amount
Multi V
Plus,
Plus II
Multi V
Space
Multi V
Sync
70
* Calculation of additional refrigerant amount
Basic Part
R22 Multi V Plus
Troubleshooting
Guide for each
Error Code
Component Check
Electrical
Solution Check
* R22 Correction Factor(CF)
HP 5 6 8 10 12 14 16 18 20
Test functions
Pump CF(kg) 0 0 -3 -2 -1 -1 -2 -2 -2
6(380V)
Product(kg) 4 4.5 10 10 10 20 20 20
Cool 10(220V)
Only 0(380V)
CF(kg) 0 0 -2 -1 -1 -2 -2 -2
-3(220V)
HP 22 24 26 28 30 32 34 36 38 40
30(50Hz)
Product(kg) 20 20 30 30 30 30 30 30 30
Heat 20(60Hz)
Pump 0(50Hz)
CF(kg) -2 -2 0 0 0 1 1 2 2
-1(60Hz)
30(50Hz)
Product(kg) 20 20 30 30 30 30 30 30 30
Cool 20(60Hz)
Only 0(50Hz)
CF(kg) -2 -2 0 0 0 1 1 2 2
-1(60Hz)
71
Error Code Error Contents Meaning Main Causes
-Plus, Sync
1. High pressure sensor defect
34
2. Indoor or outdoor unit fan defect
(Main)
3. Deformation because of damage of refrigerant pipe
143
Error happens because of 3 4. Over-charged refrigerant
(Sub1)
Over-increase of times successive 5. Indoor / outdoor unit LEV defect
145
discharge pressure of compressor off due to over- 7. When blocked
(Sub2)
compressor increase of high pressure - Outdoor unit is blocked during cooling
169
by high pressure sensor - Indoor unit filter is blocked during heating
(Sub3)
8. SVC valve is clogged
Plus II:
9. PCB defect of outdoor unit
341,342,
10. Indoor unit pipe temperature sensor defect
343,344
No
Is service valve opened ? Open service valve
Yes
Yes
Yes
Is filter blocked
(Heating:indoor, No Clean indoor filter (heating)
Cooling:outdoor /outdoor heat exchanger (cooling)?
heat exchanger)?
Yes
Yes
Next page
72
Is it Multi V Sync?
Basic Part
Yes
Troubleshooting
Guide for each
Yes
Error Code
is the outdoor unit No
Check sol valve Replace outdoor unit PCB
measure ~220V in port?
Yes
Component Check
Is HR unit valve No
Replace HR unit valve connector
connector normal ?
Electrical
Yes
Solution Check
Yes
Yes
Test functions
Is HR unit valve LED turns on
No
when connected indoor unit Replace HR unit PCB
start to operate?
Yes
Yes
Yes
73
Error No. Error Contents Meaning Main Causes
No
Is service valve
Open service valve
opened?
Yes
No
Are transmission cable/ check transmission/
piping normal? piping correction.
Yes
No
Is there pipe crack
or trace of leakage?
Yes
Is fan normal? No Check and replace related parts
(in heating outdoor fan,
Weld / reconnect the (error 105~108 reference)
in cooling indoor fan)
cracked portion and
recharge refrigerant Yes
No
Is strainer Ok?* Replace the strainer
Yes
Yes
Next page
74
Is it Multi V Sync?
Basic Part
Yes
Yes Yes
Troubleshooting
Guide for each
Error Code
is the outdoor unit No
Check sol valve Replace outdoor unit PCB
measure ~220V in port?
Yes
Component Check
No
Is HR unit valve
Replace HR unit valve connector
Electrical
connector normal ?
Yes
Solution Check
Yes
Yes
Test functions
Is HR unit valve LED turns on No
when connected indoor unit Replace HR unit PCB
start to operate?
Yes
No
Is the resistance value of
Replace HR unit valve coil
HR unit valve coil normal?**
Yes
Check HR unit coil * In case of frost and high temperature difference between inlet and
assembly location outlet of strainer, strainer blocking may happen
(Caution: frost on the outlet area (afterward after half of body)
Yes
Check for bent or blocked ** Check sol valve coil resistance value : 1.85 k˟(·10%)
from connected pipes
Check blocked HR Unit HR unit valve coil resistance value : 1.85 k˟(·10%)
75
Error code Error contents Meaning Main causes
Plus:40
Plus II:
401,402,403,404 1. Fuse failure
Low current at CT While inverter compressor 2. Defective noise filter
SP N1 Right or operation R phase current 3. R phase connection problem
A 40 Comp. CT sensor defect drops below 1A or CT short 4. CT sensor failure (inverter PCB
C failure)
N2 Left
E
40 Comp.
Yes
Yes
Yes
* Measure the CT current with clamp meter -Multi V SPACE : U(+), U(-), V(+), V(-)
The current difference among
- Multi V PLUS / Sync : R phase phases is less than 0.5A ·10%
76
FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
Basic Part
loaded FUSE Replace FUSE
current) (when power is
supplied)
(plus)
Troubleshooting
Checking points of R ɐ fuse
Component Check
Electrical
Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
(Noise emit & (when power is be within 0~40V It is disconnected
protect) Supplied) Replace noise filter
(Plus) (Plus II)
Solution Check
Test functions
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is
(When power should be within 0~10˟ ˳, noise filter is
Is not supplied) disconnected.
Replace noise filter
77
Error code Error contents Meaning Main causes
Plus:
47 (Main constant compressor) 1. Connection of the compressor defect
Compressor
121 (Sub1 constant compressor 1) Sensor measurement discharge pipe temperature sensor
discharge pipe
122 (Sub1 constant compressor 2) valve is abnormal 2. Discharge pipe compressor sensor
temperature
133 (Sub2 constant compressor 1) (Open/Short) of the compressor (open/short) defect
sensor error
134 (Sub2 constant compressor 2) 3. Outdoor PCB defect
162 (Sub3 constant compressor 1)
163 (Sub3 constant compressor 2)
Plus II:
471,472,473,474
(Constant compress)
Yes
Is the resistance of No
Replace sensor
sensor normal?*
Yes
Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes
* Error is generated if the resistance is more than 5Mȳ (open) and less than 2 ༮ (short)
78
Basic Part
Troubleshooting
Guide for each
Error Code
Check the resistance inverter
compressor discharge
temperature sensor
Check the resistance
of constant compressor
discharge temperature
sensor
Component Check
Electrical
Solution Check
Test functions
79
Error code Error contents Meaning Main causes
Plus:
42 (Main)
117 (Sub1)
Abnormal value of 1. Bad connection of low pressure connector
129 (Sub2) Sensor error of low
sensor 2. Low pressure connector defect (Open/Short)
158 (Sub3) pressure
(Open/Short) 3. Outdoor PCB defect
Plus II:
421,422,423,42
4
Plus:
43 (Main)
116 (Sub1)
Abnormal value of 1. Bad connection of high pressure connector
128 (Sub2) Sensor error of high
sensor 2. High pressure connector defect(Open/Short)
157 (Sub3) pressure
(Open/Short) 3. Outdoor PCB defect
Plus II:
431,432,433,43
4
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?
Yes
After replacement of No
Replace corresponding
outdoor unit main PCB
pressure sensor
is the system normal?
Yes
END
High pressure
sensor
Low pressure
sensor
Pressure sensor
connection
Plus model on main PCB
Plus II model
80
Error code Error contents Meaning Main causes
Plus:
Basic Part
44 (Main)
1. Bad connection of air temperature
118 (Sub1)
connector
130 (Sub2) Sensor error of outdoor air Abnormal value of
2. Air temperature connector
159 (Sub3) temperature sensor (Open/Short)
defect(Open/Short)
Plus II:
3. Outdoor PCB defect
441,442,
443,444
Troubleshooting
Guide for each
Plus:
Error Code
45 (Main H/E A)
48 (Main H/E B)
123 (Sub1 H/E A)
124 (Sub1 H/E B)
1. Bad connection of air temperature
135 (Sub2 H/E A) Piping temperature sensor error
connector
136 (Sub2 H/E B) of heat exchanger in Abnormal value of sensor
2. Air temperature connector
164 (Sub3 H/E A) main & sub outdoor unit heat (Open/Short)
defect(Open/Short)
165 (Sub3 H/E B) exchanger (A,B)
Component Check
3. Outdoor PCB defect
Plus II:
451,452,
Electrical
453,453(H/E A)
481,482,
483,484(H/E B)
Plus:
46 (Main)
1. Bad connection of air temperature
120 (Sub1)
connector
132 (Sub2) Compressor suction Abnormal value of
Solution Check
2. Air temperature connector
161 (Sub3) temperature sensor error sensor (Open/Short)
defect(Open/Short)
Plus II:
3. Outdoor PCB defect
461,462,
463,464
Plus:47
(constant compressor
of main outdoor unit)
Plus II: Discharge piping temperature
Test functions
471,472,473,474 Abnormal value of sensor
sensor error of constant(Space: Refer to CH41
(Open/Short)
Inv.) compressor (Main unit)
Left
SPACE
Comp.(N2)
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
81
Measure resistance of outdoor air temperature Measure resistance of outdoor suction pipe
sensor temperature sensor
Plus II model
82
Error Code Error Contents Meaning Main Causes
(plus)
Basic Part
49 (Main) The measured value of the 1. Abnormal input voltage
Outdoor voltage
148(Sub1) sensor is not 2. Outdoor line fuse damage
sensing error
150(Sub2) normal(Open/Short) 3. Outdoor main PCB defect
172(Sub3)
Troubleshooting
Guide for each
Error Code
is the power input normal? No
(3 phase =380V·10%, Check power supply
single phase =220V·10%)
Yes
Component Check
220V·10% ?
Yes
Electrical
Change main PCB of outdoor
* Check Line Fuse of MAIN PCB(Plus) * Check Line Fuse of MAIN PCB(Plus II)
Solution Check
Test functions
Part Check
How to check? Counter-measure
(Function) points
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power and
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within connection condition
Block, Input 220·10%.
power) - Voltage fluctuation should be within 10V
- While stand-by and in operation,
Voltage drop should be within 10V
83
Error Code Error Contents Meaning Main Causes
Check
No R~S/S~T/T~R phase voltage is 380V · 10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V · 10%
Check connection condition and wiring if power is
abnormal
Yes
No
Is main PCB assembly normal? Replace Main PCB assembly
Yes
84
Error Code Error Contents Meaning Main Causes
Basic Part
1. 130% more than outdoor unit rated capacity
Over-Capacity Sum of indoor unit capacity 2. Wrong connection of transmission cable/piping
Plus:51
(Sum of indoor unit capacity is exceed outdoor unit 3. Control error of sub outdoor unit DIP switch
Plus II:511
more than outdoor capacity) capacity specification 4. Power supply defect of Sub unit PCB
5. Outdoor unit PCB defect
Troubleshooting
Guide for each
Error Code
Is capacity sum of
No Are quantity and capacity No Check transmission cables
indoor units less than
of indoor units installed between indoor and outdoor
130% of outdoor unit
same as the data of LGMV? units
capacity at LGMV?
Yes Yes
Component Check
Adjust the capacity of indoor
and outdoor unit
Electrical
Is SUB DIP switch No
5(SUB1), 6(SUB2) Adjust corresponding DIP switch
ON?*
Yes
Solution Check
Is power of SUB PCB No Is main power really supplied? No Supply main
On? (Check LED blinking) (Terminal Block T-N) power again
Yes Yes
Is transmission
No
Test functions
cables between outdoor units Re-connect
connected correctly?**
Yes
Yes
End
85
* Dip switch setting of SUB unit(Plus)
SUB 1 SUB 2
ON ON
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
1 1
2 2
86
* Dip switch setting of SUB unit (Plus II)
Basic Part
SUB1 SUB2
Troubleshooting
Guide for each
Error Code
Component Check
Electrical
Solution Check
** In order to check transmission
cables between outdoor units,
check in order as below
: PCB connectors ˧
terminal block ˧
transmission cables
Test functions
1 1
2 2
87
Error Code Error Contents Meaning Main Causes
Plus:52
Plus II:521,522,
523,524
Main controller can’t 1. Power cable or transmission cable is not connected
S N1 Right Transmission error between receive signal from 2. Defect of outdoor Main fuse/Noise Filter
P 52 Comp. (Inverter PCB ˧ Main PCB ) inverter controller 3. Defect of outdoor Main / inverter PCB
A
C N2 Left
E 52 Comp.
Is transmission
LED (Yellow) of inverter No Is noise filter or fuse No
Replace noise filter or fuse
compressor normal?
PCB on?
Yes
Yes
No
Is transmission cable
Re-connect transmission cable
connected correctly?
Yes
No
Is MAIN PCB normal? Replace MAIN PCB
Yes
* The method of checking MAIN PCB and inverter compressor PCB (If normal, transmission LED blinks)
( Refer electrical component part for Multi V Space)
- Transmission connector & LED in inverter compressor PCB - Transmission connector & LED in MAIN PCB
(Plus) (Plus)
88
Basic Part
Error code Error Contents Meaning Main Causes
Troubleshooting
Guide for each
Error Code
Error diagnosis and countermeasure flow chart
Component Check
Yes
Electrical
Yes
End
No
Is power supplied
Supply power
Solution Check
to indoor units?
Yes
Test functions
In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with same
method of CH05. and additionally check as shown as below and above flow chart
- Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with which
the number of transmission is not increased with LGMV
- Although the quantity of indoor units installed is not same as LGMV data, and if transmission of the indoor unit
displayed at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at LGMV)
may have following problems
ྙ wrong connection of transmission cable or power cable
ྚ fault of power / PCB / transmission cable
ྛ duplication of indoor unit number
- If transmission is not doing well wholly then the Auto Addressing is not done
- The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be duplicated
*After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then
the central control address also should be input.
in case that only transmission PCB is replaced above process is not needed
89
Error code Error Contents Meaning Main Causes
Plus:
54 (Main)
110 (Sub1) 1. Inverter PCB defect
Wrong connection of 3Ȱ Wrong connection of 3Ȱ power
141 (Sub2) 2. No power of R, S, T supplied
power supply cable (Reverse supply cable (Reverse direction /
155 (Sub3) 3. Wrong connection of R, S, T cables
direction / missing a phase) missing a phase)
Plus II: 4. Main fuse defect
541,542,
543,544
Yes
Is CH 54 occurred again No
after reset MAIN End
circuit breaker?
Yes
Is 3Ȱ Fuse normal? No
[refer electric Replace Fuse
component part]
Yes
Check the diode of inverter
fan PCB and in case of fault
replace inverter fan PCB
[refer electric component part]
Is noise filter
normal? No
Replace NOISE FILTER
[refer electric
component part]
Yes
* Check power cable connection state, **Check power cable connection state, phase order, power
phase (R-S-T) order, power supply state supply state in distribution panel
in control box of product
90
FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
Basic Part
loaded FUSE Replace FUSE
current) (when power is
supplied)
(plus)
Troubleshooting
Checking points of R ɐ fuse
Component Check
Electrical
Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
(Noise emit & (when power is be within 0~40V It is disconnected
protect) Supplied) Replace noise filter
(Plus) (Plus II)
Solution Check
Test functions
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is
(When power should be within 0~10˟ ˳, noise filter is
Is not supplied) disconnected.
Replace noise filter
91
Error code Error Contents Meaning Main Causes
No
Installed 3 UNIT or more? Recheck power and installation condition
Yes
Yes
No
Is Super Sub Unit
Recheck power and installation condition
installed ?
Yes
92
Error code Error Contents Meaning Main Causes
Basic Part
EEPROM Access error
Plus II: Inverter PCB EEPROM and 1. EEPROM contact defect/wrong insertion
601,602, error Check SUM error 2. Different EEPROM Version
603,604 3. ODU inverter PCB assembly damage
Troubleshooting
Guide for each
Error Code
No 1.Check EEPROM insert direction/connection condition
Is EEPROM insertion
2.Check EEPROM Check SUM
normal?
Replace if abnormality found
Yes
Component Check
Is inverter PCB assembly No
Replace inverter PCB assembly
normal?
Electrical
Yes
Solution Check
Inverter EEPROM
Test functions
93
Error code Error Contents Meaning Main Causes
Is resistance value
Does cooling fan No No
of cooling fan coil correct?
rotate while compressor Replace cooling fan
[refer electric
operation?
component part]
Yes Yes
No
Is value of sensor
Replace sensor
resistance normal?*
Yes
* Heat sink temperature sensor (·5% tolerance) : 10 = 20.0༮ : 25= 10.0༮ : 50= 3.5༮ : 85= 1.0༮
- Position of cooling fan drive connector in main PCB - Heat sink cooling fan
94
Error code Error Contents Meaning Main Causes
Basic Part
Heat sink temperature 1. Loose connection of temperature sensor connector
Plus: Abnormal value of sensor
sensor error of inverter 2. Temperature sensor defect (Open/Short)
65 (Open/Short)
control PCB 2. Fan Main PCB defect
Troubleshooting
Guide for each
Error Code
Is sensor connected No
Connect PCB to sensor
to PCB correctly?
Yes
Component Check
Is value of sensor No
Replace sensor
Electrical
resistance normal?*
Yes
Solution Check
* If value is 100 ༮ ˦(open) or 100 ȳ ˨(short), error occurs
NB: Resistance value of temperature sensor change according to temperature
It is normal if value shown as below (·5% error)
Heat sink sensor(·5% tolerance) : 10 = 20.0༮ : 25= 10.0༮ : 50= 3.5༮ : 85= 1.0༮
Test functions
- Temperature sensor location of Heat sink - Measure the resistance of heat sink temperature sensor
95
Error code Error Contents Meaning Main Causes
S N1 Right
After FAN drive signal
P 67 Fan 1. Motor connection defect
If the HALL SENSOR signal
A 2. FAN PCB defect
does not come on for 4 sec.
C N2 Left 3. Motor defect
E 67 Fan
Yes
No
Is the motor normal?* Replace FAN motor
Yes
96
Error diagnosis and countermeasure flow chart(Plus II)
Basic Part
Is ODU Fan Motor Assemble No
Reconnect motor connector
condition normal?
Yes
Troubleshooting
Guide for each
Is ODU Fan Motor normal? 2. Check insulation resistance between ODU fan motor
Error Code
terminal(U,V,W)
Replace fan motor if abnormality found
Yes
Component Check
Yes
Electrical
No
Is Fan PCB assembly normal? Replace Fan PCB assembly
Yes
Solution Check
Test functions
resistance
* Check Hall sensor of LGDC FAN motor
19.0ȳ·7% (75)
97
Error code Error Contents Meaning Main Causes
Yes
98
Error code Error Contents Meaning Main Causes
Basic Part
Inverter input current Micom input voltage isn't 1. Input voltage abnormal (T-N)
Plus II:
CT within 2.5V ·0.3V at initial 2. ODU inverter PCB damage
711,712,713,714
sensor error state of power supply (CT sensing part)
Troubleshooting
Guide for each
Error Code
Check
No R~S/S~T/T~R phase voltage is 380V ·10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V ·10%
Check connection condition and wiring if power is
abnormal
Yes
Component Check
No
Is inverter PCB assembly normal? Replace inverter PCB assembly
Electrical
Yes
Solution Check
Test functions
99
Error code Error Contents Meaning Main Causes
Check
No R~S/S~T/T~R phase voltage is 380V · 10%
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V · 10%
Check connection condition and wiring if power is abnormal
Yes
Yes
100
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
101
Error code Error Contents Meaning Main Causes
Check
No R~S/S~T/T~R phase voltage is 380V · 10%
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V · 10%
Check connection condition and wiring if power is abnormal
Yes
Yes
Is inverter PCB No
Replace inverter PCB assembly
assembly normal?
Yes
102
Error code Error Contents Meaning Main Causes
Basic Part
Offset of micom which senses
Plus II: the 1.Input voltage is abnormal(not 15V)
Fan CT sensor error
751.752,753,7544 fan motor phase current is not 2.Fan PCB assembly defect
2.5V
Troubleshooting
Guide for each
Error Code
No Check 15V wire connection
Is input voltage normal?
Reassemble or manage if abnormality found
Yes
No
Is Fan PCB assembly normal? Replace Fan PCB assembly
Component Check
Electrical
Yes
Solution Check
Test functions
103
Error code Error Contents Meaning Main Causes
Plus II: Fan DC Link High Fan PCB DC link voltage 1.Input power abnormal
761,762,763,764 Voltage Error supplied over 780V 2.Fan PCB assembly defect
Check
R~S/S~T/T~R phase voltage is 380V · 10%
Is input voltage normal? No R~N/S~N/T~N phase voltage is 220V · 10%
Check connection condition and wiring if power is
Yes abnormal
No
Is Fan PCB assembly normal? Replace Fan PCB assembly
Yes
104
Error code Error Contents Meaning Main Causes
Basic Part
1.Overload operation
Plus II: Fan Over Current Output current is over 5A for
2.Fan Motor defect
771,72,773,774 Error 40ms
3.Fan PCB assembly defect
Troubleshooting
Guide for each
Error Code
Is installation No No Check ODU fan motor assemble condition and locking
condition normal? Reassemble or replace if abnormality found
Yes
Component Check
(19.0ȳ·5% at 75¶C)
Between each phase and insulation
2. Check insulation resistance between ODU fan motor
resistance of motor output
terminal (U,V,W) and pipe (over 100Mȳ )
Electrical
terminal normal?
Replace fan motor if abnormality found
Yes
Solution Check
Yes
Yes
Test functions
Recheck power and
installation condition
105
Error code Error Contents Meaning Main Causes
Is fan motor assemble No Check ODU fan motor assemble condition and locking
condition normal? Reassemble or replace if abnormality found
Yes
No
Is wiring between fan motor Recheck f an motor hall sensor connection
and PCB normal? Reassemble if abnormality found
Yes
Yes
106
Error code Error Contents Meaning Main Causes
Basic Part
1.Fan motor defect/ assemble
condition abnormal
Plus II: Fan Starting Failure 2.Fan motor connector
Fan Motor initial starting failure
791,792,793,794 Error misconnection(Hall sensor,
U,V,W ouput)
3.Fan PCB defect
Troubleshooting
Error diagnosis and countermeasure flow chart
Yes
Component Check
1. Check resistance between each motor output terminal
Are the resistance No No (19.0 ȳ ·7% at 75¶C)
Electrical
Between each phase and insulation
2. Check insulation resistance between ODU fan motor terminal
resistance of motor output
(U,V,W) and pipe (over 100Mȳ)
terminal normal?
Replace fan motor if abnormality found
Yes
Solution Check
condition normal? 2. Check wire disconnection and wiring
Reassemble or replace if abnormality found
Yes
Yes
Test functions
Recheck power and
installation condition
107
Error code Error Contents Meaning Main Causes
Yes
No
Is EEPROM 24C16? Replace EEPROM with 24C16
Yes
108
Error code Error Contents Meaning Main Causes
Basic Part
Error occurs when checking 1.EEPROM bad contact/wrong
Plus II: Fan PCB EEPROM the EEPROM checksum as insertion
871,872,873,874 Error initializing after power is 2.EEPROM Version is different
supplied 3.ODU fan PCB assembly damage
Troubleshooting
Guide for each
Error Code
1.Check EEPROM insertion direction/connection condition
Is EEPROM insertion normal? No 2.Check EEPROM checksum
Replace EEPROM if abnormality found
Yes
No
Component Check
Is Fan PCB assembly normal? Replace fan PCB assembly
Electrical
Yes
Solution Check
Test functions
109
Error code Error Contents Meaning Main Causes
plus:
Over-increase of constant Compressor is off because of
100,101 (Sub1)
compressor discharge Over-increase of constant compressor discharge Refer to CH33
102,103 (Sub2)
temperature of Sub outdoor temperature of Sub outdoor unit
152,153 (Sub3)
110
Error code Error Contents Meaning Main Causes
Basic Part
Plus:
104 (Main)
111 (Sub1)
142 (Sub2) Transmission 1. Loose connection of power cables
Master displays ODU number
156 (Sub3) Error /transmission cables (Open/Short)
which is not communicated.
Plus II: Between 2. Each outdoor unit PCB defect
Slave displays own error number
011˧041 Outdoors 3. Defect of PCB power
011˧042
011˧043
Troubleshooting
Guide for each
011˧044
Error Code
Error diagnosis and countermeasure flow chart(Plus)
Component Check
Sub PCB blinks? [refer electric normal? [refer electric Input power
component part] component part]
Electrical
Yes Yes
Solution Check
Is transmission cables
No
of outdoors connected
Re-connect transmission cables
correctly? [refer electric
component part]
Yes
Test functions
Replace MAIN PCB
LED 8 7 6 5 4
LED 3
LED 2
LED 1
111
Error diagnosis and countermeasure flow chart(Plus II)
112
Error code Error Contents Meaning Main Causes
Basic Part
-Plus
1. Loose connection of transmission cables
Plus:Transmission error Plus:Transmission error between 2. Transmission cables are open/sort
Plus:105
between outdoor unit Main PCB outdoor Main PCB and fan Main 3. Outdoor Main PCB PCB defect
Plus II:
and fan Main PCB PCB (Fan ˧ outdoor main) 4. Fan Main PCB defect
11˧051
11˧52
Plus II:Transmission error Plus:Transmission error between -Plus II
11˧53
between outdoor unit Inv PCB outdoor Inv PCB and fan PCB 1. Wrong connection between Inverter and
11˧54
and fan PCB (Fan ˧ inv) Fan PCB
Troubleshooting
Guide for each
2. Fan PCB power not supplied
Error Code
3. ODU Inv/Fan PCB defect
Component Check
No
(yellow) of inverter fan normal ? [refer electric Replace noise filter or fuse
PCB on?* component part]
Electrical
Yes
Yes
Solution Check
Are transmission cables No
of Main PCB / Fan PCB Re-connect transmission cables
connected normally?
Yes
No
Is green LED of
Replace Main PCB
Main PCB blinks?**
Test functions
Yes
113
114
Error code Error Contents Meaning Main Causes
Basic Part
Plus:106
Plus II:
11˧061 1. Overload operation (Pipe
12˧062 clogging/Covering/EEV
13˧063 IPM protection circuit defect/Ref. overcharge
14˧064 Over current of Main outdoor activation 2. ODU fan motor assemble condition abnormal
fan motor (inverter fan IPM fault) (over current / (Coil disconnection/Short/Insulation damage)
S N1 Right overheating) 3. Fan PCB heatsink assemble condition
Troubleshooting
P 106 Fan abnormal
Error Code
4. Fan PCB assembly defect
C N2 Left
E 106 Fan
No
Component Check
Is it Multi V Space ? Multi V Plus & Sync
Electrical
Yes
Yes
Yes
Solution Check
Is inverter fan PCB No
Normal? [refer electric Replace inverter fan PCB
component part]
Yes
Test functions
component part]
Yes
Vcc
Gnd
1 Hb
2 Ha
3 4
115
Part Check
How to check? Counter-measure
(Function) points
Inverter fan
IPM PCB
4. IPM
2. DC supply terminal
(DC310V)
DIODE㽕㥉(P-U : 0.5V)
116
Part Check
How to check? Counter-measure
(Function) points
Basic Part
No power
on PCB
10. Comm. circuit
Troubleshooting
1. MICOM LED
Error Code
9. On-boarding 3. In/Output connector
connector of reactor
8. Heat sink
temperature 4. DC-Link output voltage
sensor connector
Component Check
7. PWM
Electrical
drive circuit
5. DC-Link electrolytic
capacitor
6. SMPS power
circuit
Solution Check
2.3 power -Input voltage of 3ɐ 4 wires should be -Check supply voltage,
Input circuit 3ɐ 380V, 1ɐ 220V noise
- Check half wave rectifying circuit diode filter, fuse
(R-Reactor1: 0.6V, S-Reactor1: 0.6V: -Replace inverter fan
T-Reactor1: 0.6V) PCB
Test functions
R, S, T, N Reactor 1
Red LED -When red LED blinks, error code happens -Check error code at
about inverter fan PCB main PCB
117
Multi V Space BLDC FAN PCB
4.SW_SEL 6.CN_COMM
LED01M : PWM Enable 5.SW_DIR [MAIN PCB >FAN PCB] :5,6,8HP
[louver
LED02M : display error [FAN direction] [FAN >COMP PCB] : 10HP
selection]
7.CN_POWER2
3.Power supply [louver power supply]
LED01K
(FAN >INV
communication)
8.SW01M,02M,03M
[PCB JIG check]
9.CN_WIRTE
[on boarding
light]
10.CN_M1S,M2S
[louver signal input]
13.CN_FAN
[FAN signal output)
Power does not turn 1.CN POWER -AC voltage measure 220V -Input voltage (220V)
on -Replace related parts
3. Power supply - ZNR01D( barrister ),FUSE burn out
(CH105) checkup
FAN motion disabled 2.CN_DC LIINK -DC 470V~520V displays - Check and replace
-DC 380V and above are normal CAPACITOR
- Replace PCB
13.CN_FAN - U,V,W electric flow measurement - Check up and replace
(CH106) stabilize connection and motor
11.CN_SENSOR -Check connectors
(CH67)
Louver does not 4.SW_SEL Check if connector is connected -connect connectors (if there
work -DC24V display check are no louver)
7.CN_POWER2
-Connection status check -Check and Replace trance and
10.CN_M1S,M2S power supply
Connection status check
12.CN_MOTOR1,2 -Check and replace louver
motor and connection part
118
Error diagnosis and countermeasure flow chart (Plus II)
Basic Part
No
Is fan motor assemble Check ODU fan motor assemble condition and locking
condition normal? Reassemble or replace if abnormality found
Yes
Troubleshooting
1.Check fan motor U,V,W connector connection condition
Error Code
condition normal? 2.Check fan motor wire disconnection
Replace ODU fan motor if abnormality found
Yes
Component Check
condition normal? 2.Check assemble condition between fan PCB and Heatsink
Reassemble heatsink if abnormality found
Electrical
Yes
No
Is fan PCB assembly normal? Replace fan PCB assembly
Solution Check
Yes
Test functions
(FAN PCB)
119
Multi V Plus II LGDC FAN PCB
CN Micom N
Write
V 2. CN FAN Right
1. CN DC Link
CN Heat Sink
6. CN Inverter
Communication
4. CN Hall Sensor
(Right) P
5. CN Hall Sensor
(Left)
FAN motion disabled 1.CN_DC LIINK -DC 470V~520V displays - Check DC Voltage at FAN PCB
-DC 380V and above are normal terminal (more than 380V—
Normal)
2/3. CN_FAN - U,V,W electric flow measurement - Replace PCB
(CH106) stabilize - Check up and replace
-Check connectors connection and motor
4/5. CN_HALL
SENSOR(CH67)
120
Error code Error Contents Meaning Main Causes
Basic Part
Plus:107
Plus II:
11˧071
12˧072
13˧073 DC voltage charging Low voltage of Main 1. Bad connection of voltage lead cable of main PCB DC link
14˧074 failure of inverter fan outdoor fan motor 2. Fan main PCB capacitor defect
S N1 Right motor drive (below 380V) 3. Fan main PCB defect
P 107 Fan
Troubleshooting
Guide for each
A
Error Code
C N2 Left
E 107 Fan
Component Check
Electrical
Is DC LINK cable No
Adjust DC LINK cables
Normal?*
Yes
Solution Check
Replace inverter fan PCB
Test functions
No 1. Check DC_Link Wire connection
Is wiring between fan motor
2. DC_Link
and PCB normal?
Replace wire if abnormality found
Yes
No
Measure DC_Link voltage
Is DC_Link voltage normal?
Check inverter PCB if voltage is below 380V
Yes
No
Is Fan PCB assembly normal? Replace fan PCB assembly
Yes
121
- Inverter fan main PCB - Inverter fan IPM PCB
(Plus)
(Plus II)
122
Error code Error Contents Meaning Main Causes
Basic Part
Plus:
Excessive rise of high pressure in Compressor Off due to the high pressure switch
109 Refer to CH24
outdoor unit in outdoor unit
(Sub1)
Troubleshooting
(Sub1) phase)
Component Check
Electrical
Solution Check
Test functions
123
Error code Error Contents Meaning Main Causes
Plus:
113 (Main)
125 (Sub1)
Outdoor unit
137 (Sub2)
liquid pipe Abnormal sensor 1. Defective temperature sensor connection
166 (Sub3)
(condenser) resistance value 2. Temperature sensor defect(Open / Short)
Plus II:
temperature (Open/Short) 3. Outdoor unit main PCB defect
11˧131
sensor error
12˧132
13˧133
14˧134
Plus:
114 (Main sub-cool inlet)
115 (Main sub-cool outlet)
126 (Sub1 sub-cool inlet)
127 (Sub1 sub-cool outlet)
138 (Sub2 sub-cool inlet)
139 (Sub2 sub-cool outlet)
167 Sub3 sub-cool inlet)
Outdoor unit sub- 1. Defective temperature sensor connecter
168 (Sub3 sub-cool outlet) Abnormal sensor
cooling inlet / outlet connection
resistance value
temperature sensor 2. Temperature sensor defect(Open / Short)
Plus II: (Open/Short)
error 3. Outdoor unit main PCB defect
11˧141(sub-cool inlet)
12˧142
13˧143
14˧144,
11˧151(sub-cool outlet)
11˧152
11˧153
11˧154
Is temperature sensor No
connector connections Check and correct connection
are normal?
Yes
Yes
* Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error (Plus II)
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (·5% tolerance)
Air temperature sensor: 10 = 20.7༮ : 25= 10༮ : 50= 3.4༮
Pipe temperature sensor: 10 = 10༮ : 25= 5༮ : 50= 1.8༮
- Liquid pipe temp sensor - Sub-cool inlet temp sensor - Sub-cool outlet temp sensor
124
Error code Error Contents Meaning Main Causes
Basic Part
116 Sensor measured value of resistance is
High pressure sensor Refer CH43
(Plus Sub1) abnormal (Open / Short)
Troubleshooting
Guide for each
118 Outdoor unit air temperature Sensor measured value of resistance is
Refer to CH44
Error Code
(Plus Sub1) sensor error abnormal (Open / Short)
Component Check
121 (Plus Sub1
constant compressor 1) Compressor discharge pipe Sensor measured value of resistance is
Electrical
Refer to CH41
122 (Plus Sub1 temperature sensor error abnormal (Open/Short)
constant compressor 2)
123 (Plus Sub1 HEX A) Sub outdoor unit heat exchanger Sensor measured value of resistance is
Refer to CH45
124 (Plus Sub1 HEX B) (A,B) pipe sensor error. abnormal (Open/Short)
Solution Check
125 Outdoor liquid pipe (condenser) Sensor measured value of resistance is
Refer to CH113
(Plus Sub1) sensor error abnormal (Open/Short)
Test functions
128 Sensor measured value is abnormal
High pressure sensor error Refer to CH43
(Plus Sub2) (Open/Short)
125
Error Code Error Contents Meaning Main Causes
140 Excessive rise in outdoor high Compressor Off due to the high pressure
Refer to CH24
(Plus Sub2) pressure switch in outdoor unit
126
Error Code Error Contents Meaning Main Causes
Basic Part
Plus:
151
Function error of 4way 1. Wrong operation of 4way valve because of sludge etc. inflow
Plus II: Function error of
(reversing valve) in 2. No pressure difference because of compressor fault
11˧511 outdoor 4way
Main or Sub outdoor 3. Wrong installation of In/outdoor common pipe
11˧512 (reversing valve)
units 4. 4way valve defect
11˧513
11˧514
Troubleshooting
Guide for each
Error diagnosis and countermeasure flow chart
Error Code
Is 4-Way valve connecter No
connection are properly Reconnect it
connected?
Yes
Component Check
Electrical
Is 4 Way valve coil No
Change 4 Way valve coil
resistance normal?*
Yes
Solution Check
Yes
Yes
Test functions
After reset, can we
check supply voltage at PCB No
Replace outdoor unit PCB
when starting heating
mode operation****
Yes
After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes
127
(Plus)
**** Check the output voltage of terminal socket ***** Checking method for outdoor unit of 3unit system
during heating operation : 220V (·10%) ྙ Close all the SVC valves of high / low pressure common pipe
ྚ Operate system
ྛ Check the difference of high and low pressure
with LGMV for each unit (Main, Sub1, Sub2)
ྜ If there is a unit in which the difference is not increased
then the 4way valve of that unit is defective
128
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
129
Main PCB
(Plus ȤȤ)
Error Code Error Contents Meaning Main Causes
152,153 Excessive rise of the constant Constant speed compressor Off due to the
Refer to CH33
(Plus Sub3) compressor discharge temperature excessive rise in discharge temp
164 (Plus Sub3 HEX A) Pipe sensor error of the main and Abnormal resistance value of sensor
Refer to CH45
165 (Plus Sub3 HEX B) sub units heat exchanger (A,B) measurement ( Open / Short )
130
Error Code Error Contents Meaning Main Causes
Plus:
Basic Part
173
(MAIN constant)
174, 175 1. Constant compressor defect
Over-increase of
(sub1 constant 1,2) 2. Discharge temperature sensor defect
temperature
176, 177 Abnormal staring of 3. Outdoor temperature sensor defect
after constant
(sub2 constant 1,2) constant compressor 4. Outdoor main PCB defect
compressor
Plus II: 5. Magnet switch defect
starts
11˧731 6. Wrong connection of constant compressor cables
Troubleshooting
11˧732
Is resistance value
Component Check
(insulation & phase to phase)
of corresponding constant No
Replace constant compressor
Electrical
compressor normal ?
[refer electric
component part]
Yes
No
Is cables’ connection
Adjust connection of cables
Solution Check
of compressor normal? *
Yes
Is discharge temperature
No
sensor of compressor Replace discharge
normal? [refer electric temperature sensor
component part]
Test functions
Yes
Is magnet switch No
normal? [refer
㜼 electric Replace magnet switch
component part]
Yes
Yes
* cables connection between constant compressor
and magnetic switch
Replace outdoor unit PCB
131
Error Code Error Contents Meaning Main Causes
Plus II:
11˧931 Heat sink
Fan PCB heatsink 1. Heatsink temperature sensor defect
11˧932 temperature is
temperature high 2. Fan PCB assembly defect
11˧933 over 95¶C
11˧934
Yes
No
Is temperature sensor Check connection condition of
attached to heat sink? heat sink and temperature sensor
Yes
No
Is fan PCB assembly
㜼 normal? Replace fan PCB assembly
Yes
132
Error
Error Code Meaning Main Causes
Contents
Basic Part
1. HR unit’s power cable or transmission cable connection defect
After the Auto operation,
2. After Auto-Addressing, wrong address setting of the indoor
if the number of the indoor
Pipe detection unit (Defective indoor power / transmission error and PCB
200 units detected is different
error defect)
from the number
3. Wrong setting of the HR unit’s rotary switch or dip switch
communicating indoor unit
4. HR unit PCB defect
Troubleshooting
H1 01…H1 04
Error Code
H2 01…H2 04
connected to HR unit valve 2. After Auto-Addressing, wrong address setting of the indoor
H3 01…H3 04 Pipe
of marked number unit
H4 01…H4 04 detection
(Ex : H1 02 no.2 valve (Defective indoor power / transmission error and PCB defect)
. error
pipe of no.1 HR unit failed 3. Wrong setting of the HR unit’s rotary switch or dip switch
.
to search) 4. HR unit PCB defect
.
Component Check
Error diagnosis and countermeasure flow chart
Electrical
H.R. unit green No
LED (communication LED) blinks Check H.R. unit input power (220V·10%)
periodically ?
Yes
Yes
Solution Check
Check installation status of communication line
Check H.R. unit Rotary switch and and connected pipe
Dip Switch setting outdoor unit ˩HR unit ˩outdoor unit
Yes Yes
Test functions
Operate auto pipe detection after the H.R. unit on (Refer to CH05)
pipe is sufficiently refrigerated
after resetting outdoor unit
and HR unit 30 minutes before
Yes
Yes
Finish
[NB] If Indoor units/transmission cables of HR unit and cables of power 220V has been changed each other,
transmission parts and indoor will be burnt
133
ඖ Auto addressing
<SW02M> <SW01M>
134
ඖ Auto pipe detection
Basic Part
Confirm the IDU auto addressing setting
Troubleshooting
Guide for each
Error Code
Check the proper setting of
No. 2 & 3 of SW02M of the HRU
(Model of HRU & number of IDU)
Component Check
Confirm the No. 5 DIP S/W of SW03M
Electrical
of the ODU PCB
- Outdoor temp is over 15 : ON
- Outdoor temp is below 15 : OFF
Solution Check
Wait for 3 minute
Test functions
The number of HRU connected is displayed
at 7-seg of the ODU main PCB, and
then ’88’ is displayed
After ODU stopped, the number of IDU Display error on the ODU PCB / HRU PCB
detected is displayed at 7-seg of the ODU - ODU PCB : HR unit No. Valve No.
main PCB for 30 seconds (Example: H1 01)
- HRU PCB : ‘200’
Yes
135
ඖ Manual pipe detection
No
Equal number of
“IDU and Displayed one”?
Yes
Turn off “No.6 DIP S/W of SW03M of ODU Check the central control address of IDU
PCB” and HRU
136
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
137
ඖ Switch setup of HR Unit
ඖ HR Unit PCB
Basic Part
(with SW01M, SW03M, SW04M)
Troubleshooting
Guide for each
Error Code
Component Check
Electrical
Solution Check
T vaGu
T k aGu
SW01M SW03M SW04M
Test functions
No.1 of SW01M
T v aGuUXGGz~WXtGGGGGJX
T k GaGlGGGGllwyvtGG
G^TzlnU
SW01M SW03M SW04M
T v azGGGGXWGGGGG
nGoGGGGGGG
GGGGGGGG
SW03M
GJXG GGz~WZtGzV~
SW01M SW04M
T k GaGkGGGGGGG
SW03M z~WZtGzV~GG GGG^Tzln SW03M
TvGaGzGGGGXGGGGG
nGsGGGGGGG
GGGGGGGG
GJXG GGz~W[t SW04M
SW01M SW03M Tk GaGkGGGGGGG
SW04M z~W[tGzV~GG GGG^Tzln SW04M
No.1 of SW01M
TvGaGuUGXGGz~WXtGGGGG
GGGJX
Tk GaG“XX” GG^TzlnG
SW01M SW03M SW04M
139
Error Code Error Contents Meaning Main Causes
HR unit
202(HR unit1) 206(HR unit2)
Sub-cooling 1. Defective temperature sensor connection
210(HR unit3) 214(HR unit4) Abnormal value of sensor
inlet pipe 2. Temperature sensor defect(Open/Short)
218(HR unit5) 222(HR unit6) measurement ( Open / Short )
temperature 3. Outdoor unit main PCB defect
226(HR unit7) 230(HR unit8)
sensor error
HR unit
203(HR unit1) 207(HR unit2)
Sub-cooling Abnormal value of sensor 1. Defective temperature sensor connection
211(HR unit3) 215(HR unit4)
discharge pipe measurement 2. Temperature sensor defect(Open/Short)
219(HR unit5) 223(HR unit6)
temperature ( Open / Short ) 3. Outdoor unit main PCB defect
227(HR unit7) 231(HR unit8)
sensor error
yes
yes
* Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (·5% tolerance)
Air temperature sensor: 10 = 20.7༮ : 25= 10༮ : 50= 3.4༮
Pipe temperature sensor: 10 = 10༮ : 25= 5༮ : 50= 1.8༮
140
Error Code Error Contents Meaning Main Causes
Basic Part
1. Defective connection in HR unit power supply and
204(HR unit1) 208(HR unit2) transmission transmission
transmission connection
212(HR unit3) 216(HR unit4) error between error between
2. Wrong setting of the HR unit Rotary switch and
220(HR unit5) 224(HR unit6) the HR unit and the HR unit and
Dip switch
228(HR unit7) 232(HR unit8) outdoor unit outdoor unit
3. Defective HR unit PCB
Troubleshooting
Guide for each
Error Code
H.R. unit green No
LED (communication LED) blinks Check H.R. unit input power (220V·10%)
periodically ?
Yes
Yes
Component Check
Check installation status of communication line
Electrical
Check H.R. unit Rotary switch and and connected pipe
Dip Switch setting outdoor unit ˩HR unit ˩outdoor unit
Yes Yes
Solution Check
[NB] If Indoor units/transmission cables of HR unit and cables of power 220V has been changed each other,
transmission parts and indoor will be burnt
Test functions
141
Error Code Error Contents Meaning Main Causes
1. Defective CNU
Central controller data Central controller to CNU data
241 2. Center controller initialization
transmission error (Sending error) transmission failure
failure
Central controller receive Error CNU to Central controller on time 1. Defective CNU
242
(Data receiving error ) data receiving error 2. Central controller initialization error
1. Defective CNU
Central controller receive time out transmission failure
244 2. Initialization failure of central
(Receiving time : 3sec ˦) between central controller and CNU
controller
142
Error Code Error Contents Meaning Main Causes
Basic Part
1. NOISE occurs
2. CNU defect
Central controller Received check sum is different from 3. Temporary error of Timing mismatch
250
Check sum Error calculated check sum data 4. A/C product defect
5. PI485 communication cable open or
connection defect
1. NOISE occurs
Troubleshooting
Guide for each
2. CNU defect
Error Code
Central controller 3. Temporary error of Timing mismatch
251 Length of received data : 0
Receive Zero Error 4. A/C product defect
5. PI485 communication cable open or
connection defect
1. NOISE occurs
2. CNU defect
Component Check
Central controller Setting address and actual address 3. Temporary error of Timing mismatch
252
Wrong Address Error are different each other 4. A/C product defect
Electrical
5. PI485 communication cable open or
connection defect
1. NOISE occurs
2. CNU defect
Central controller 3. Temporary error of Timing mismatch
253 No response from air conditioner
Disconnection Error 4. A/C product defect
Solution Check
5. PI485 communication cable open or
connection defect
1) Check system setting address of central controller and actual address is matched or not
Test functions
2) Re-start service program(engine) of central controller
3) Replace CNU
143
MEMO
3. Electric
Component Check
3.1 How to check main control box?
(a) Plus
2 6
4
3
5
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within 220·10%. and connection
Block, - Voltage fluctuation should be within 10V condition
Input - While stand-by and in operation,
power)
Voltage drop should be within 10V
2 FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect disconnection Fuse is disconnected.
over- of FUSE Replace FUSE
loaded (when power
current) is supplied)
146
(a) Plus
Basic Part
No. Part Check
How to check? Counter-measure
(Function) points
3 Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
(Noise emit & (When power be within 0~40V It is disconnected
protect) is Replace noise filter
Supplied)
Troubleshooting
Guide for each
Error Code
Component Check
Plus Plus II
Electrical
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is
(In case power should be within 0~10˟ ˳, noise filter is
Is not supplied) disconnected.
Replace noise filter
4 Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is
Solution Check
switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟,
(When power is not supplied) Replace Magnet
When magnet switch is on, voltage should be 220V switch
(When power is not supplied)
-When voltage is not
220V, magnet switch
is melt down
- Replace magnet
switch
Test functions
** check point of 1st coil of magnet switch
Magnet switch -While pressing green button of magnet switch, - Replace magnet
connection Voltage of each connectors should be 0V or switch
check Resistance should be 0~1˟
(In case power (Warning: power should not be supplied)
is not supplied)
147
(a) Plus
16. Auto-Addressing
148
(a) Plus
Basic Part
No. Part Check
How to check? Counter-measure
(Function) points
Troubleshooting
and
Component Check
Electrical
42 ˟
Solution Check
Test functions
149
(b) Plus ȤȤ
2 4
1 4
3
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within 220·10%. and connection
Block, - Voltage fluctuation should be within 10V condition
Input - While stand-by and in operation,
power)
Voltage drop should be within 10V
150
Basic Part
(b) Plus ȤȤ
No. Part Check
How to check? Counter-measure
(Function) points
2 Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
Troubleshooting
Guide for each
(Noise emit & (When power be within 0~40V It is disconnected
Error Code
protect) is Replace noise filter
Supplied)
Component Check
Electrical
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is
(In case power should be within 0~10˟ ˳, noise filter is
Solution Check
Is not supplied) disconnected.
Replace noise filter
3 Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is
switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟,
(Constant (When power is not supplied) Replace Magnet
speed When magnet switch is on, voltage should be 220V switch
compressor) (When power is not supplied)
-When voltage is not
Test functions
220V, magnet switch
is melt down
- Replace magnet
switch
151
(b) Plus ȤȤ
Const. Comp.
High Pr. Switch Central controller
Sub-cooling
sensor
220V Power
Input
No power 2.Power terminal -Input voltage should be 220V. -Check fuse(3.15A), T-N voltage
at PCB (when power is supplied) -If resistance is 0~100˟ , replace
2.Power terminal -Input resistance should be more than PCB
a few ༮(when power is not supplied)
152
3.2 How to check inverter control box?
Basic Part
(a) Plus
Troubleshooting
Guide for each
3
Error Code
4 2
Component Check
1
Electrical
7 5
8 6
Solution Check
No. Part Check
How to check? Counter-measure
(Function) points
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% - Check supply voltage
(Terminal (When power - Voltage of 1ɐ(R-N,S-N,T-N) should be within & connection points
block, Power is supplied) 220·10%. Check noise filter,
Test functions
input) - Voltage fluctuation should be within 10V fuse
- While standby and in operation,
Voltage drop should be within 10V
153
(a) Plus
Loc. Part Check
How to check? Counter-measure
(Function) points
4 INV compressor 2. Power & 3. High pressure 4. DC-Link 6. transmission 5. Checking circuit
PCB start-relay switch & sensing & circuit to main for reverse phase
drive circuit power-relay display circuit PCB of input power
drive circuit
7. On-board
writing connector
1. MICOM
circuit
9. PWM driving
signal output
circuit 8. CT sensing circuit
Inverter Red LED -When red LED blinks. -Check error code displayed at
compressor Error displays about inverter compressor PCB main PCB
PCB Error
154
(a) Plus
Basic Part
Loc. Part Check
How to check? Counter-measure
(Function) points
Troubleshooting
lighting connector DC rectifying circuit
7. PWM
drive circuit 4. DC-Link output voltage
Component Check
6. SMPS power
circuit
Electrical
5. DC-Link electrolytic
capacitor
No power 2.3ɐ power - Input voltage of 3ɐ 4 wires should be -Check supply voltage, noise
on PCB Input circuit 3ɐ 380V, 1ɐ 220V Reactor 1 filter, fuse
R, S, T, N
- Check half wave rectifying circuit diode -Replace inverter fan PCB
Solution Check
(R-Reactor1: 0.6V, S-Reactor1: 0.6V:
T-Reactor1: 0.6V)
Test functions
No 10. Transmission -Yellow LED should blink. -Check yellow LED blinks or not
transmission circuit with main -When is OFF / ON continuously,
PCB check transmission with main PCB
Inverter fan Red LED -When red LED blinks, error code happens -Check error code at main PCB
PCB error about inverter fan PCB
155
(a) Plus
2. DC supply terminal
(DC310V)
Inverter fan 1.PWM signal - Check 9pin connectors - Replace cables & check
is not rotating 2.Fan DC power - DC voltage should be charged of 310V soldering condition of PCB
3.Outdoor - While Fan operating, in case voltage of - Replace connectors & inverter
fan connector connectors(U-V,V-W,U-W) is 100~300V PCB if not charging
˧ Normal
4. IPM - Check Diode(P-N : 0.95V, - Replace inverter IPM PCB
P-U,P-V,P-W: 0.55V
N-U,N-V,N-W: 0.55V
156
(b) Plus ȤȤ
Basic Part
2
Troubleshooting
3
Component Check
Electrical
Solution Check
Phenomena Check point How to check? Counter-measure
Test functions
condition - Voltage between terminals of reactor should
be within 0~1V (When power is supplied)
157
(b) Plus ȤȤ
700 DC
Link
DC 15V
Output N- Phase
terminal Terminal
PFC
R- Phase
On-boarding
(To Diode)
terminal
R- Phase
Terminal
(From Noise
filter)
T- Phase
Terminal
(From Noise
filter)
Inverter 12. PWM LED -When red LED blinks. -Check error code displayed
compressor PCB PWM is normal at main PCB
Error
158
(b) Plus ȤȤ
Basic Part
Loc. Part Check
How to check? Counter-measure
(Function) points
4 Inverter
fan PCB
Troubleshooting
Guide for each
Error Code
Component Check
Electrical
Solution Check
Phenomena Check point How to check? Counter-measure
Test functions
disconnecting
all connector
No 10. Transmission -Yellow LED should blink. -Check yellow LED blinks or not
transmission circuit with -When is OFF / ON continuously,
Inverter PCB check transmission with main
PCB
Inverter fan Red LED -When red LED blinks, error code happens -Check error code at main PCB
PCB error about inverter fan PCB
159
3.3 How to check Multi V Space control box?
* MUTLI V SPACE 10HP C/BOX
10 11
10 11 12 6 12
9
5 8 7
7 8 5
4
3 6 3
2
1 1
2
1 T/BLOCK 3 phase 4 line power input 1 T/BLOCK 3 phase 4 line power input
3 Noise filter Block and discharge noise 3 Noise filter Block and discharge noise
5 FAN PCB BLDC FAN control 5 FAN PCB BLDC FAN control
6 COMP PCB BLDC COMP control 6 COMP PCB BLDC COMP control
12 Magnet S/W BLDC COMP switch 12 Magnet S/W BLDC COMP switch
160
Basic Part
Multi V SPACE COMP PCB
Troubleshooting
Guide for each
Error Code
1.CN06
[MAIN >COMP
Communication]
12. LED01,02K
5.CN04
Component Check
11. Function key [high pressure switch
& Power-Relay]
Electrical
6.Power supply
Solution Check
9.CN02 8.CN IIPM 7.CN GATE1,2
[DC LINK sensor]
10.CN14
[COMP output sensor]
Test functions
Monitoring
Situation How to check? Counter-measure
Location
PCB power does not 4.CN01 -input voltage must be 220V (power on) -LINE FUSE(3.15A)
turn on (CH52) manage after checking input
-input resistance is over ༮.(power off) voltage 220V
-replace PCB if the resistance is
0~100˟
Communication does 1.CN06 -yellow LED(LED01,02K)must flick. -check communication and FAN
not work 2.CN09 PCB and MAIN PCB if the yellow
(CH52) LED is flick or OFF (check
connection and replace PCB)
COMP malfunction 10.CN14 -constant COMP output U(-),V(-),W -replace after checking PCB and
COMP if the difference is over 2A
9.CN02 -DC voltage within 470V~520V
-replace after checking CAPACITOR
8.CNIPM -check connection status and PCB
7.CN_GATE
(CH21 Replace and check motor and
connection
CH22
CH23)
Deficiency error 3.CN05 -3 point power line (noise filter latter part) - Readjust and Replace after
(CH54) over 380V checking FUSE, input power ,
connection line
161
Multi V SPACE BLDC FAN PCB
4.SW_SEL 6.CN_COMM
[louver 5.SW_DIR [MAIN PCB!>FAN PCB] :5,6,8HP
selection] [FAN direction] [FAN!>COMP PCB] : 10HP
LED01M : PWM Enable
LED02M : display error
7.CN_POWER2
3.Power supply [louver power supply]
LED01K
(FAN!>INV
communication)
8.SW01M,02M,03M
[PCB JIG check]
9.CN_WIRTE
[on boarding light]
10.CN_M1S,M2S
2.CN_DC LINK [louver signal input]
[DC power
11.CN_SENSOR
supply sensor)
[FAN signal input]
1.CN_POWER
[PCB power 12.CN_MOTOR1,2
supply) [louver signal output]
13.CN_FAN
[FAN signal output)
Power does 1.CN POWER -AC voltage measure 220V -Input voltage (220V)
not turn on
3. Power supply (CH105) - ZNR01D( barrister ),FUSE burn out -Replace related parts
checkup
FAN motion 2.CN_DC LIINK -DC 470V~520V displays - Check and replace CAPACITOR
disabled -DC 380V and above are normal - Replace PCB
Louver does 4.SW_SEL -Check if connector is connected - connect connectors (if there are no
not work louver)
Vcc Gnd
Hb Ha
162
Basic Part
3.4 How to check indoor unit PCB?
3.CN_FLOAT
[Drain pump
13.CN_POWER 1.CN_MOTOR 2.CN_CC3 sensor]
[power supply_220V] [indoor motor] [DRY CONTACT
boarding]
4.CN_OPTION
Troubleshooting
[additional function]
6.CN_REMO
[remote control
power &
communication]
Component Check
7.CN_HVB
12.CN_DRAIN [plasma]
Electrical
[Drain pump 11.CAPACITOR 9.CN_VANE1,2 8.CN_DISP
Output part_220v] [internal$ external]] [louver operation] [reception part PCB
10.CN_LEV connection port]
[indoor LEV operation]
* Outdoor unit communication PCB front side Outdoor unit communication PCB backside
* When there is
communication error(U01Y)
Solution Check
1 8
2 7
14.CN_A5 3 6
[indoor PCB 4 5
connection] DIODE MODE measurement
8-1,2,3,4 : 1.2V
5-1,2,3,4 : 0.7V
Communication
Connection (A,B)
Test functions
Monitoring
Situation How to check? Counter-measure
Location
PCB, remote control 13.CN_POWER -input voltage must be 220V.(power on) -manage and check input voltage 220V
power does not come - Barrister (ZNR01N),FUSE,,PCB check -replace and check relate parts
on
Outdoor unit motor 1.CN_MOTOR -Error CH10(FAN LOCK) when it does not -replace and check motor and
does not work operate after remote control operation connection
11.CAPACITOR -DC 310V is recharged Replace CAPACITOR
Outdoor unit sensor 5. sensor -is LG MV sensor value normal? -replace and check connection and
error (CH01,02,06) sensor part
Outdoor unit front 8.CN_DISP -check indoor unit front panel LED -reception PCB and connection part
panel reception defect operation reception PCB and connection part
and remote control - Wireless remote control and forced
does not work operation switch operation
163
3.5 How to check other electric components?
(a) Plus
Name Check
Check points
Loc.
25 Normal state
Others : PCB checking mode
22 In case of R22 refrigerant
R410A: 41
Outdoor
sub unit
PCB display
Value Sub PCB
(When power
is supplied) LED 8 7 6 5 4
display
condition) LED 3
LED 2
LED 1
164
(a) Plus
Basic Part
Name Check point
Troubleshooting
Guide for each
Error Code
ON
1. Main unit
1 X Cooling operation control No. 1 ON push RED button 3 times for 3 sec.
Component Check
display 01, 0F by turns (#1 indoor unit OFF)
Push BLACK button for 3 sec.
Electrical
display 01,0P by turns
A few sec. later display 01, 0N by turns (#1 indoor unit ON)
Push RED button for 1 sec.
display 02, 0F by turns (#2 indoor unit OFF)
(go on…)
Solution Check
/ Target high pressure down, target low pressure up
Test functions
4 O Constant No.4 ON RESET
compressor 1 BACKUP operation / while constant compressor failure, operate more than indoor unit
capacity (SINGLE:70K,SERIES:110K)
3,4 O MAIN UNIT BACKUP No.3, No.4 ON RESET / when MAIN unit failure
7 X Forced oil return operation No.7 ON Push BLACK button for 2 sec. display 01(Oil return)
2. Sub unit
DIP RE Function Method / description
s/w SET
165
(b) Plus ȤȤ
Name Check
Check points
Loc.
Initial setup
There are 4 initial setup steps before running.
All DIP switch setting must be completed before initial setup.
1) Step 1 : factory setting value display
Factory setting value is displayed in 7 segment on PCB for 24sec.
All dip switches must be set properly before step 1.
166
Troubleshooting Electrical
Basic Part Guide for each Solution Check Test functions
Error Code Component Check
167
(b) Plus ȤȤ
(b) Plus ȤȤ
Outdoor unit
PCB DIP ሲ Dip switch Setting ሲ
switch
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON
8 7 6 8 7 6
OFF
1. Main unit
10 0 Snow No.8 ON
168
(b) Plus ȤȤ
Basic Part
Name Check point
Troubleshooting
8 7 6 8 7 6
Component Check
1 0 Slave 1 No.5, No.7, ON
Electrical
2 0 Slave 2 No.6, No.7, ON
Solution Check
No. RESET Function Dip Switch
Test functions
169
(b) Plus ȤȤ
- Driving current fluctuation of Inv. compressor should be less than 2A(Plus II)
170
(C) Plus, Plus ȤȤ
Basic Part
Name Check location and method
Troubleshooting
Guide for each
Error Code
ྙ - ྛ : around 300˟ ྚ - ྜ : around 300˟ ྙ - ྜྷ : around 150˟
Component Check
Electrical
Solution Check
ྛ - ྜྷ : around 300˟ ྚ - ྞ : around 300˟ ྜ - ྞ : around 150˟
Outdoor unit main LEV Outdoor unit sub cooling LEV Indoor unit LEV
Test functions
171