PUPLIC MODE CEILING MOUNTED STROBE

COVERAGE PER NFPA-2007 EDITION * Non COOPER Wheelock Multi-Candela Setting


Minimum Required Light Output, Candela Minimum Required Light Output, Candela Minimum Required Light Output, Candela
(cd) - Effective Intensity (cd) - Effective Intensity (cd) - Effective Intensity
Maximum Area of Maximum Ceiling Maximum Area of Maximum Ceiling Maximum Area of Maximum Ceiling
One Light One Light One Light
Coverage Height Coverage Height Coverage Height
20' x 20' 10' 15 cd 20' x 20' 20' 30 cd 30' x 30' 30' 75 cd
30' x 30' 10' 30 cd 30' x 30' 20' * 45 cd 50' x 50' 30' 95 cd
40' x 40' 10' 60 cd 40' x 40'
44' x 44' 10' 75 cd 44' x 44' 20' 75 cd 53' x 53' 30' * 110 cd
50' x 50' 10' 95 cd 50' x 50' 20' 95 cd 55' x 55' 30' 115 cd
55' x 55' 10' 115 cd 55' x 55' 20' 115 cd 63' x 63' 30' * 150 cd
63' X 63' 10' 150 cd 63' x 63' 20' 150 cd 63' x 63' 30' 150 cd
68' x 68' 10' 177 cd 68' x 68' 20' 177 cd 68' x 68' 30' 177 cd

68' x 68' SCALE: 1/8" = 1'-0"