OPERATING MANUAL

TEMPERATURE CONTROLLER
TC-44

1 2 3 4
1 2 3 4

Technical Specification
Model TC-44
UPPER:- 4 Digit 7 seg .39”,red LED Display
Display
LOWER:- 4 Digit 7 seg .28”,red LED Display
Size 48 X 48 X 70mm
Panel Cutout 44 X 44
Input J, K
Temperature
J: 0 to 600°C / K: 0 to 1200°C
Range
Control Action PID /TP/ON-OFF (selectable)
Output 1 relay, 1 C/O contact, 230V AC, 5A ,1 SSR, 12V DC, 50 mA
Power Supply 110 to 250V AC, 50 / 60 Hz smps
Note :
1) Press + key for 3 sec to go to Factory Setting mode.
2) Press SET key to go to next parameter.
3) Press or to enter value or to select option.
4) Press key for 6 sec to start/stop PID auto-tunning.
5) Every time the instrument is turned ON, following pattern will be
displayed

POWER ON

8. 8. 8. 8.
All digit segment will be turned ON for 3 sec
8. 8. 8. 8.

j Previous or default sensor input will be display for 2 sec


I N P t

0 1 2 3 Process Value
0 1 2 3 Set Value

Page - 1 www.multispanindia.com
0 0 0 0 PROCESS VALUE
SET POINT SETTING

Press ENT key


0 0 0 0 SET VALUE

S E T SET POINT
0 0 0 0
Press SET key for 10 sec to enter
BASIC CONFIGURATION P A S S Password Message
Password parmeter

0 0 0 0

TO ENTER BASIC
CONFIGURATION
SETTING, ENTER “73”

P A S S Password Message
0 0 7 3
SET

I N P T Input ( J / K )
J K

O F S T OFF-SET
0 0 0 0
Press SET key

S L L Set Point Low Limit


0 0 0 0

S H L Set Point High Limit


0 6 0 0

C T R L Control Action
p I D O n O F T P PID/ON-OFF/TP

Press ENT key to Save & Exit

Sr. Parameter Range for J, K


1 PC 00.00 to 99.99
2 IC 0.000 to 9.999
3 DC 0 to 9999
4 CT 4 sec to 99 sec
5 MR -9 to +9
6 PB 2 to 20
7 Hysteresis 1°C to 50°C
8 Off-set correction -20°C to +20°C

Page - 2 www.multispanindia.com
Note :
SET
1) Press key to enter into an internal setting
2) Press SET key to go to next parameter.
3) Press or key to enter value or to
select option.
CONTROL PARAMETER

TO ENTER CONTROL
PARAMETER P A S S Password Message
SETTING, ENTER “37” 0 0 3 7

IF PID SELECTED IF ON-OFF SELECTED IF TP SELECTED

PID p I d O n O F ON-OFF T P TP
Parameters P A R A P A R a Parameters P A R A Parameters

Proportional P C h Y s Hysteresis P b
Constant 0 0 0 0 0 0 0 0 0 0 0 0

I C Press SET key C t


Press SET key

Integral Press ENT key


Constant 0 0 0 0 0 0 0 0
to Save & Exit

Derivative D C m r
Constant 0 0 0 0 0 0 0 0

Cycle Time C T
0 0 0 0
Press ENT key
to Save & Exit
Press ENT key
to Save & Exit

Page - 3 www.multispanindia.com
Note :
1) Press SET key to go to next parameter.
2) Press or key to enter value or to
select option.
FACTORY SETTING
FACTORY SETTING
Process Value 1 2 3 4 SR. PARAMETER VALUES
Set Value 1 2 3 4 Press + key for 3 sec 1 PC 5.000
2 IC 0.225
Factory Setting F C S T 3 DC 25
Y E S n O
4 CT 6 sec
5 MR 0°C
yes : press ENT
key to apply factory set values as shown in table.
nO : press ENT key to escape from factory setting. 6 OFFSET 0°C
7 HYSTERESIS 3°C

Connection Diagram:

-
-

L
T/C

- N
-

NC S.S.R
+
C
NO

Product improvement and upgrade is a constant procedure. So for more updated operating information and support, please
contact our Helpline : 079-22770865 or Email at marketing@multispanindia.com