Professional Documents
Culture Documents
Filtro de Mangas
Filtro de Mangas
CAMCORP
Medium
Pressure
Pulse-Jet
Filter Bag
Top & Bottom Load
Dust Collector
Section 1 - SAFETY
Section 2 - RECEIVING
Section 3 - INSTALLATION
Section 4 - OPERATION
Section 7 - MAINTENANCE
Section 8 – APPENDIX
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Section 1 – Safety Recommendations
Because this unit may be under pressure or vacuum do not attempt to open any
device, doors or panels while fans or blowers are running. The unit has air hoses
and valves with a maximum recommended operating pressure of 100 psig. To
eliminate the danger of bursting care must be taken to insure maximum desired
pressure is not exceeded.
Before servicing any portion of the compressed air system the air supply must be
shut off and any pressure relieved.
If your unit is equipped with a discharge auger or an airlock assure that chain
guards are installed before start-up and servicing is attempted only after
electrical power is locked out.
While servicing the filter it is very important that there are no open flames,
welding or grinding sparks. Dust laden air could be highly explosive and extreme
care must be taken. Most filter bags will burn if exposed to sparks, welding or
open flames.
• Run cleaning mechanism 20 minutes with the fan off to clean filter bags.
• Completely discharge dust solids from hopper, if applicable.
• Shut off compressed air supply and relieve pressure in the compressed air
manifold.
• Lock out all electrical power on all equipment especially rotating
equipment.
• On toxic operation, purge collector housing and install a blank in the inlet
duct.
• Install catwalks and safety cables as required.
• Secure access doors in an open position or remove doors.
• Use the buddy system.
• Wear a respirator or appropriate breathing equipment.
• Use common sense.
Follow all current OSHA regulations relative to Lockout / Tag-Out and Confined
Space Entry and any other applicable regulations when servicing your
equipment.
On the following page are examples of safety stickers you will find on Camcorp
equipment. These will help identify potential hazards on the equipment.
1-1
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Examples of Safety Stickers
------DANGER------ -----CAUTION------ -------OTHER-------
Important information
contained on these is
needed by Camcorp when
calling for parts or service.
1-2
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Section 2 - Receiving
Once your claim has been filed with the carrier, contact CAMCORP to
notify us of the problem(s). We will then advise the appropriate repair
procedure or recommend it be returned to our factory, depending on the
extent of the damage.
2-1
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Storage Recommendations
Baghouse, Bin Vent, Filter Receiver, Dirty Air Hopper and Housing
• Filter bags must be stored inside a cool dry area protected from moisture,
rodents and insects.
• For extended storage the boxes for the bags should be wrapped with
plastic wrap or stretch wrap to protect from moisture.
• If the bags get wet for any reason, immediately lay them out with plenty of
ventilation to dry in order to prevent mold and mildew.
• It is recommended to store the cages inside a dry area if at all possible.
• If an inside location is not available the cages can be stored outside as
long as they are covered by a tarp.
• Cages are generally stored horizontally on pallets to keep them off the
ground.
2-2
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Storage Recommendations (continued)
• If cages can be stored horizontally do not stack over three boxes high.
• If the job site is in an area that may receive a significant snow load the
cages must be stored vertically in order to prevent being crushed by the
weight of the snow. Do not stack more than one box high.
Accessory Parts
• This includes all gauges, bag clamps, nylon or copper tubing, valves,
gaskets and other parts not specifically called out.
• These items should be stored inside a cool dry place protected from
moisture, insects, and rodents.
• Fans can be stored outside on a pallet or skid to keep them out of water
and dirt.
• Fan silencers, outlet dampers, and inlet boxes should also be tarped and
stored on a pallet or skid.
• Reference fan IOM manual for long-term storage.
Ducting
• Ducting can be stored outside on a pallet or skid to keep it off the ground.
It should be positioned so that water does not sit on or in the ducting.
• If ducting is unpainted carbon steel it should be at least primed coated
before storage.
• If ducting is already finish coated, it should be tarped to protect the finish.
Knife Gate
• All limit switches, solenoids, and air cylinder ports must be capped and
taped to prevent any moisture or dirt from entering.
• Equipment can sit outside provided it is covered with a tarp and is on a
pallet or skid to keep it out of water and dirt.
• Reference knife gate IOM manual for long-term storage.
2-3
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Storage Recommendations (continued)
Isolation Dampers
• All limit switches, solenoids, and air cylinder ports must be capped and
taped to prevent any moisture or dirt from entering.
• Equipment can sit outside provided it is covered with a tarp and is on a
pallet or skid to keep it out of water and dirt.
Rotary Valve
• Rotor and interior of valve should be well oiled with vegetable oil to
prevent rust and to maintain compatibility with product.
• Unit can be stored outside provided it is covered with a tarp and is on a
pallet or skid to keep it out of water and dirt.
• Reference rotary valve IOM manual for long-term storage.
• All limit switches, solenoids, and air cylinder ports must be capped and
taped to prevent any moisture or dirt from entering.
• Unit can be stored outside provided it is covered with a tarp and is on a
pallet or skid to keep it out of water, dirt and sunlight.
• Reference butterfly valve IOM manual for long-term storage.
Level Indicators
AC Inverters
• Store these items and all other electrical controls inside a protected cool
dry area.
2-4
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Section 3 - Installation
CAMCORP dust collectors are shipped either in one piece, fully assembled,
or in two or more sections depending on the unit size and weight. Before
attempting to move the dust collector or any of its sections review both the
certified general assembly drawing supplied from CAMCORP and the
rigging and lifting guidelines included in this manual. Become familiar with
the size and number of sections to be assembled, the orientation of inlet(s),
outlet(s), access door(s) and compressed air header(s), as well as the
number and location of lifting lugs.
Dust collectors of this type are manufactured from steel sheets or plate and
are quite flexible. Therefore, even though care has been taken to maintain
dimensional accuracy and squareness, some difficulty should be anticipated
and temporary bracing in the field may be required.
STEP 1: Set up the supporting steel for the dust collector level and square.
Precision at this point will greatly help facilitate erection and bolt hole
alignment of the dust collector sections to follow.
STEP 2: Place the hopper with its girth channel on the supporting steel
work. Check for squareness, and for bolthole alignment between the hopper
flange and the girth channel. Apply the appropriate RTV silicone caulk
around the periphery of the hopper flange with one bead on each side of the
boltholes.
STEP 3: Lift the dirty air plenum, with the tube sheet, into place. DO NOT
LOWER THE PLENUM ONTO THE HOPPER FLANGE UNTIL
ALIGNMENT IS ACCOMPLISHED. The silicone caulk makes horizontal
movement very difficult once a load is applied. With the plenum suspended
over the hopper ½” to 1”, begin bolt hole alignment starting at the center of
the plenum and working toward the ends by using tapered drift pins. If the
wall(s) has flexed out of square it will be necessary to pry or pull it back into
alignment. Depending on the size of the unit and the degree of difficulty
hydraulic jacks and come-alongs may be required. When the mating holes
are properly aligned, finish lowering the plenum. Install the remaining bolts,
washers, and nuts and torque to the appropriate specifications.
3-1
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Setting Up Your Unit (continued)
Step 4: Check the top of the dirty air plenum for squareness and bolt hole
alignment between the dirty air plenum and the tube sheet. Make sure that
the silicone caulk has been applied between the top flange of the dirty air
plenum and the underside of the tube sheet flange. Next, apply the caulk
around the periphery of the topside of the tube sheet flange one bead to
each side of the boltholes.
STEP 5: Lift the clean air plenum into place and assemble in the same
fashion as in STEP 3. Again, do not lower the clean air plenum completely
until preliminary alignment is accomplished. Start drift pin alignment at the
center of the plenum on the compressed air header side since the header
makes access to the flange more limited. When alignment is complete install
the remaining bolts, washers, and nuts and torque to the appropriate
specifications.
All CAMCORP dust collectors are provided with lifting lugs for ease in
handling of the units during field erection and installation. The number and
location of these lifting lugs will vary depending on the model, size, and
weight of the dust collector. Before attempting to rig and lift your dust
collector review the certified general assembly drawing supplied from
CAMCORP to verify the number and location of lifting lugs as well as visually
checking this information on the actual unit. Large units are frequently
shipped in several sections so check the lifting lugs provided on each
section. If these cannot be used or there is some question about lifting lug
location consult the engineering staff at CAMCORP for proper location since
proper care must be taken to prevent damage to housing or its components.
Do not lift the dust collector by any attachments other than the lifting lugs
provided.
Use all of the lifting lugs provided on the dust collector on a section of the
dust collector when making a lift.
If the lifting lugs are located below the roofline of the dust collector or
below the top of the section of the dust collector a vertical pull must be
made to avoid crushing the top of the unit. Use spreader beams to
accomplish this vertical pull.
3-2
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Setting Up Your Unit (continued)
Attach tag lines at several locations to help in controlling the unit when
lifted and to prevent spinning or swinging.
The dust collector should be lifted and lowered at a slow, uniform rate
and not allowed to bounce or joggle since this can cause excessive
impact stresses at the lift points.
The NCC pulse timer boards have adjustable pulse duration and interval
(time between valves firing) settings. Before applying power to the timer
always check these settings according to the table below. Since there are
many variances in operations and conditions these are presented only as
initial start-up guidelines. If you experience problems in cleaning of the
filter bags, please contact CAMCORP.
3-3
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Setting Up Your Unit (continued)
The firing sequence of the diaphragm valves on the dust collector should
be set so that no two adjacent rows of bags fire in succession to insure
maximum cleaning and life of the filter media. This can only be achieved
when wiring the pulse timer board to the solenoid valves. If you are
experiencing a high-pressure drop across the filter bags in your dust
collector the pulse interval should be reduced.
Apply electrical power to the timer and make sure that it is cycling
completely through all rows of the unit. In some cases the timer panel
may have more “positions” than required in which case the position
selector cable needs to be attached to the proper numerical value
corresponding to the number of diaphragm valves on the unit.
If your dust collector was shipped via common carrier rather than a
contract hauler there is a possibility that the solenoid enclosure was not
shipped installed on the unit. If this is the case, there is a mounting plate
welded on the housing or the air header with the bolt pattern of the
enclosure already drilled. Bolt the enclosure and install the nylon (or
copper) tubing with the fittings provided making sure that the solenoids
are connected to their corresponding diaphragm valve.
Valves and Piping: After the unit has been installed the diaphragm
valves should be checked to make sure that the port marked “IN” is
assembled to the compressed air manifold. The “IN” connection of the
solenoid valve is connected to the diaphragm valve by means of 3/8”
nylon or copper refrigeration tubing. Each nut on the compression fittings
should be checked for tightness before the compressed air manifold is
pressurized. In most cases a slip fit fitting has been used. The integrity of
the nylon tubing inside each fitting should be checked by pulling gently on
each tube. If the tube pulls out, simply push it back into the fitting until it
will not go any further. The solenoids are shipped with a red plastic plug
in the discharge side of the valve. These plugs must be removed for
proper operation. The medium pressure pulse jet doesn’t generate
enough pressure to blow these out like a high pressure unit.
Pressure Relief Valve: Remove the plastic wrap around the PRV.
3-4
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Gauges: The differential pressure gauge, mounting bracket, fittings and
tubing are usually shipped loose in a box with the dust collector. When
installing these make sure that the high-pressure port of the gauge is
connected below the tube sheet and the low-pressure port is connected
above the tube sheet on the dust collector. There are pipe couplings
welded on the side of the dust collector for these connections. After the
differential pressure gauge is permanently mounted the gauge needs to
be zeroed prior to connecting the tubing to the gauge.
3-5
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
4 3 2 1
Tubing connects to PTC fittings on
Solenoid and Diaphragm Valves
D D
1/8" MNPT to 1/4" FNPT Adapter
3/8" OD Tubing
Default Nylon
Other mat. by request
A A
MEDIUM PRESSURE PULSE-JET HEADER INSTALL INSTRUCTIONS
4 3 2 1
4 3 2 1
Assembles Air Header Tank
Connects to Dust Collector
D D
Air Accumulator Tank
connects to Dust
Collector with
(6) 1/2-13 bolts
with washers and nuts
C C
A A
MEDIUM PRESSURE PULSE-JET HEADER INSTALL INSTRUCTIONS
4 3 2 1
Bag and Cage Installation
Inspect the filter bag cages for any signs of damage, warping, bent wires
or missing welds. Inspect the filter bags for any signs of mold, mildew,
ripped seams or holes.
Be sure the wire cage has a bottom pan. Slip the filter bag over the cage,
centering the seam 1-½” or 2” on either side of the split at the top of the
cage roll band. Seam must be straight (not corkscrewed). Make sure that
the filter bag bottom is tight against the cage bottom pan.
Pull the bag up and over the full length of the cage and fold the entire
extra length over and down inside the top of the cage. Smooth out any
filter bag folds inside the top of the cage.
Slip the assembled filter bag and cage over the outside of the bag cup
(mounted on the tube sheet) making sure to mate the male groove of the
cage roll band top to the female groove of the bag cup.
If you try to move the assembly up and down you will be able to tell if the
grooves are properly aligned.
Install the worm gear bag clamp on the assembly and tighten around the
bag and cage at the point just above the groove on the cage. The clamp
head should be located in the best position for ease in tightening.
Tighten the clamp until secure. You should not be able to rotate the bag-
cage assembly by hand if it is tighten properly.
Close the access door and tighten accordingly. You are ready to begin
start-up procedures if all other preceding tasks and connections are
completed.
3-8
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Bag and Cage Installation (continued)
Inspect the cages for any signs of damage, warping, bent wires or
missing welds. Inspect the filter bags for any signs of mold, mildew,
ripped seams or holes.
Remove the blowpipes inside the clean air plenum by loosening the
bulkhead fitting on the air header end of the blowpipe and then slide the
pipe out of the bulkhead fitting. Some CAMCORP dust collectors use a
retaining clip on the opposite end of the blowpipe and it must be removed
before removal of the blowpipe is possible.
Lower the closed end of the bag through the hole in the tube sheet and
carefully feed the bag in. Assure that the bag doesn’t scrap against the
sides of the tube sheet hole. Excessive scraping can damage filter bags
with special coatings or finishes.
With your hands, “kidney shape” the snap band bag top in order to fit and
align it within the tube sheet hole. Fit the groove of the snap band to the
I.D. of the tube sheet hole and allow it to expand and audibly snap into
place. If the band will not snap into place initially, do not push on the
“dimple” as doing this will permanently damage the snap band. Instead,
kidney shape the snap band from the opposite side of the dimple. Then
you can allow the band to expand and audibly snap into place.
Check the fit of the snap band in the tube sheet hole. It should be even in
height above the tube sheet around the entire circumference, which will
confirm to the installer that the filter bag is centered and well secured in
the tube sheet.
Lower the cage into the bag and press that cage top down into the bag’s
snap band I.D. When in position the rolled flange of the cage top will rest
on the tube sheet and the bag and cage assembly will be rigidly mated.
Replace the blowpipes in the opposite order stated above. Make sure
that the orifices in the blowpipes are properly oriented to blow straight
down the center of the bag and cage assembly before tightening the
bulkhead fitting.
Replace access doors and tighten accordingly. You are ready to begin
start-up procedures if all other preceding tasks and hook-ups are
completed.
3-10
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Snapband
PRODUCT HIGHLIGHT
BEADED SNAPBAND FILTER BAG DESIGN FOR FLAT TUBESHEET HOLE
The snapband was developed to improve sealing efficiency. This design eliminates multiple parts, minimizing labor
expenses. Camcorp provides a uniform double beaded gasket in the cuff assembly. This assures a leakproof seal for flat
plate tubesheet holes. When installing the bags, follow instructions provided.
2. Seat the seam of the cuff into the hole first with
Top View
the tubesheet fitting between the beads, with
one above and one below it .
NOTE: If you are converting to a snapband bag from some other type of sealing method, the tubesheet holes must
be inspected carefully to ensure that proper sealing will result. The surface finish on the inside diameter must be
relatively smooth. Any deep grooves or protrusions will cause leakage. A hole that was flame cut, but not ground
smooth is one example. The tubesheet holes must be consistent in circumference from one hole to another.
If the circumference difference is determined by measuring, the holes should be checked to the nearest 0.001 in.
Slight out-of-roundness is acceptable. Take three measurements for each hole and record the average of these three
measurements. Compare all the hole averages. The difference between the largest average and smallest average hole
size should not exceed 0.020 in. Try sample cuff in largest and smallest hole to confirm proper fit.
When checking the sample snapband in the hole for fit, push on the edge of the snapband slightly with your thumb
to try and move it inward. If a gap occurs easily between the snapband and the edge of the tubesheet hole, leakage
may result. If the inside surface of the hole is smooth, check the cuff fit by trying to spin the cuff in the hole. If it
spins easily, it may leak.
Section 4 - Operation
Operating Principle
A. Solids laden air or gases enter the unit at the hopper or housing inlet.
B. Air passes through the filter media.
C. Solids are retained on the filter media surface.
D. Cleaning cycle consists of a momentary blast of 8-10 psig compressed
air:
1. Momentarily taking a row of bags off stream through
pressure reversal.
2. Flexing filter bags.
3. Solids are released to fall towards hopper and through rotary
valve or other discharge equipment.
4-1
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Start-Up Checklist
Installation
Make sure the unit is secured to the floor or mounting surface. The
ladder(s) and platform(s) must be tightened and set up according to
OSHA requirements. Ducting and piping must be secured and routed out
of the way of traffic whenever possible to avoid injury. Ducting must also
be free of all debris including moisture.
The blowholes in the blowpipes must be centered over the filter bags.
On top bag removal collectors verify that bags and cages are properly
installed.
On top bag removal collectors the bulkhead fittings must be checked for
proper tightness and that the blowpipes are secured at both ends.
Access doors, inspection ports and spring-loaded relief vents should seat
effectively to prevent leakage.
4-2
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Start-Up Checklist (continued)
Inspect explosion relief vents for cracks and that all mounting bolts are
tight.
The pulse timer must be correctly wired and mounted in its enclosure in a
suitable location. Typically, the timer is located near the compressed air
blower. Set the time interval on the timer to 10 seconds.
All the piping connections between the diaphragm and the solenoid valve
must be tight.
The red plugs must be removed from the exhaust port of the solenoid
valve. If these plugs are not removed the diaphragm valves won’t pulse.
Start the compressed air system and check for air leaks in all parts of the
system. With the timer off the blower should build up pressure to at least
10 psig. The relief valve on the compressed air reservoir will prevent over
pressurizing the system. Energize the timer board to begin pulsing. Verify
the solenoid is firing and that the pulses are consistent and at the same
pressure.
4-3
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Start-Up Dust Control Systems
Check dust pickup points for proper suction. Balance airflow in individual
ducts.
Check that all access doors, hatches, ports, and other openings are
closed and latched or bolted.
The main exhaust fan can now be started and brought up to speed.
Start the dust-laden air through the collector. The collector should be
started under partial load to allow the bags to become slowly and evenly
coated with dust particles.
4-4
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Start-Up Dust Control Systems (continued)
Note: If the pressure drop continues to increase over 5” w.g. and does
not stabilize, decrease the timer “off time” to fifteen seconds.
Should adjustment of the timer “off time” fail to cause the pressure
drop to stabilize below 5” w.g., shut down the collector and refer to
“Troubleshooting the Collector” or call your CAMCORP
representative.
When the collector has stabilized the timer “off time” interval may be
slowly increased for the most economical use of compressed air. As the
“off time” is increased, the differential pressure will also increase.
Readings up to 6” w.g. are acceptable, however we recommend
operating at 3”-4” w.g. for maximum filter bag life. The timer “off time”
may be decreased when lower differential pressure readings are desired.
When adjusting the “off time” interval proceed in small steps allowing the
differential pressure to stabilize for several hours between adjustments.
Check the main airflow with a pitot tube or equivalent measuring device
to establish initial conditions. If the main airflow must be adjusted up or
down to suit the process, repeat the steps above.
Shutdown Procedures
Pneumatic systems
4-5
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Section 5 - Component Information
The following pages show details of the mechanical and electrical components of
a typical dust collector. Below is information for identifying each component and
repair kit if applicable.
5-1
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Explosion Vents (if applicable) - Confirm Vent(s) with Camcorp
Camcorp P/N 400068 – 18”x35” Flat Vent, 1.5 PSI Burst
Camcorp P/N 400105 – 18”x35” Domed Vent, 1.5 PSI Burst
Camcorp P/N 400067 – 36”x36” Flat Vent, 1.5 PSI Burst
Camcorp P/N 400096 – 36”x36” Domed Vent, 1.5 PSI Burst
5-2
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
BULLETIN NO. A-27
O P E R AT I N G I N S T R U C T I O N S a n d PA R T S L I S T
Magnehelic ® Differential Pressure Gage
SPECIFICATIONS
Dimensions: 4-3/4" dia. X 2-3/16" deep.
Weight: 1 lb. 2 oz.
Finish: Baked dark gray enamel.
Connections: 1/8 N.P.T high and low pressure
taps, duplicated, one pair side and one
pair back.
Accuracy: Plus or minus 2% of full scale, at
70° F. (Model 2000-0, 3%; 2000-00, 4%).
Pressure Rating: 15 PSI.
Ambient Temperature Range: 20° to 140° F
Standard gage accessories include two 1/8"
N.P.T. plugs for duplicate pressure taps,
two 1/8" pipe thread to rubber tubing
adapters, and three flush mounting
adapters with screws.
1. Select a location free from excessive vibration 5. To zero the gage after
and where the ambient temperature will not installation
exceed 140°F Also, avoid direct sunlight which Set the indicating pointer exactly on the zero
accelerates discoloration of the clear plastic mark, using the external zero adjust screw on the
cover. Sensing lines may be run any necessary cover at the bottom. Note that the zero check or
distance. Long tubing lengths will not affect accu- adjustment can only be made with the high and
racy but will increase response time slightly. Do low pressure taps both open to atmosphere.
not restrict lines. If pulsating pressures or vibra-
tion cause excessive pointer oscillation, consult
the factory for ways to provide additional damp- Operation
ing. Positive Pressure: Connect tubing from source
of pressure to either of the two high pressure
2. All standard Magnehelic gages are calibrated ports. Plug the port not used. Vent one or both
with the diaphragm vertical and should be used low pressure ports to atmosphere.
in that position for maximum accuracy. If gages Negative Pressure: Connect tubing from source
are to be used in other than vertical position, this of vacuum or negative pressure to either of the
should be specified on the order. Many higher two low pressure ports. Plug the port not used.
range gages will perform within tolerance in other Vent one or both high pressure ports to atmos-
positions with only rezeroing. Low range Model phere.
2000-00 and metric equivalents must be used in
the vertical position only. Differential Pressure: Connect tubing from the
greater of two pressure sources to either high
pressure port and the lower to either low pres-
3. Surface Mounting sure port. Plug both unused ports.
When one side of gage is vented in a dirty, dusty
atmosphere, we suggest an A-331 Filter Vent
Plug be installed in the open port to keep inside
of gage clean.
a. For portable use or temporary installation, use
1/8" pipe thread to rubber tubing adapter and
connect to source of pressure with rubber or
Tygon tubing.
b. For permanent installation, 1/4" 0. D., or larger,
copper or aluminum tubing is recommended. See
accessory bulletin S-101 for fittings.
Locate mounting holes, 120° apart on a 4-1/8"
dia. circle. Use No. 6-32 machine screws of
appropriate length.
4. Flush Mounting
Maintenance: No lubrication or periodic servic- Caution: If bezel binds when installing, lubricate
ing is required. Keep case exterior and cover threads sparingly with light oil or molybdenum
clean. Occasionally disconnect pressure lines to disulphide compound.
vent both sides of gage to atmosphere and re-
zero. Optional vent valves, (bulletin S-101), Warning: Attempted field repair may void your
should be used in permanent installations. warranty, Recalibration or repair by the user is not
recommended. For best results, return gage to
Calibration Check: Select a second gage or the factory. Ship prepaid to:
manometer of known accuracy and in an appro-
priate range. Using short lengths of rubber or Dwyer Instruments, Inc.
vinyl tubing, connect the high pressure side of the Attn. Repair Dept.
Magnehelic gage and the test gage to two legs of 55 Ward St.
a tee. Very slowly apply pressure through the Wakarusa, IN 46573
third leg. Allow a few seconds for pressure to Trouble Shooting Tips:
equalize, fluid to drain, etc., and compare read-
ings. If accuracy unacceptable, gage may be • Gage won't indicate or is sluggish.
returned to factory for recalibration. To calibrate in 1. Duplicate pressure port not plugged.
the field, use the following procedure.
2. Diaphragm ruptured due to overpressure.
Calibration:
3. Fittings or sensing lines blocked, pinched, or
1. With gage case, P/N 1, held firmly, loosen leaking.
bezel, P/N 4 by turning counterclockwise. To
avoid damage, a canvas strap wrench or simi- 4. Cover loose or "O" ring damaged, missing.
lar tool should be used.
5. Pressure sensors, (static tips, Pitot tube, etc.)
2. Lift out plastic cover and "O" ring. improperly located.
3. Remove scale screws and scale assembly. Be 6. Ambient temperature too low. For operation
careful not to damage pointer. below 20°F order gage with low temperature,
(LT) option.
4. The calibration is changed by moving the
clamp, P/N. 70-b. Loosen the clamp screw(s) • Pointer stuck-gage can't be zeroed.
and move slightly toward the helix if gage is
1. Scale touching pointer.
reading high, and away if reading low. Tighten
clamp screw and install scale assembly. 2. Spring/magnet assembly shifted and touching
helix.
5. Place cover and O-ring in position Make sure
the hex shaft on inside of cover is properly 3. Metallic particles clinging to magnet and inter-
engaged in zero adjust screw, P/N 230-b. fering with helix movement.
6. Secure cover in place by screwing bezel down 4. Cover zero adjust shaft broken or not properly
snug. Note that the area under the cover is engaged in P/N 230-b adjusting screw.
pressurized in operation and therefore gage
will leak if not properly tightened. We generally recommend that gages needing
repair be returned to the factory. Parts used in
7. Zero gage and compare to test instrument. various sub-assemblies vary from one range of
Make further adjustments as necessary gage to another, and use of incorrect compo-
nents may cause improper operation or failure.
Gages repaired at the factory are carefully cali-
brated and tested to assure "like-new" operation.
After receipt and inspection, we will be happy to
quote repair costs before proceeding.
Consult factory for assistance on unusual appli-
cations or conditions.
Use with air or compatible gases only.
Magnehelic® Gage
EXPLODED VIEW
Series 2000
Ordering Instructions:
When corresponding with the factory regarding Magnehelic® gage problems, refer to the
call-out numbers in this view. Be sure to include model number, pressure range, and any
special options. Field repair is not recommended; contact the factory for repair service
information.
Features
■ R
C
R File #E65038
■ Digital Timing Circuitry:
AC Input, Pulse
Allows for stable timing
from Cleaning of Bag
-40°F to 150°F temperature
range
■ Pulse Time: Line synchro-
House Dust
nized to eliminate 8 mil-
liseconds triac tum off
Collectors
variation
■ 10 Amp-400/600V Output Models DNC-T2003
Triacs: For maximum pro-
tection against output
shorts. 200 VA load rating.
thru DNC-T2032
Operating Logic: The control can function in 2
■ RTV Coating: Conformally modes:
coated for protection
against vibration, humidi- Continuous Mode: The pressure switch termi-
ty and contamination nals are shorted. Upon application of input volt-
■ 2 Modes of Operation: age, the control activates output #1 after the pre-
Can be operated continu- set off time. It will continue to activate outputs
ously or "on demand" via sequentially until input voltage is removed.
external pressure switch On Demand Mode: The pressure switch termi-
■ Field Selectable: For num- nals are connected to an isolated set of contacts of
bers of outputs required a differential pressure switch. The control will
■ LED Indicators: For com- activate the outputs sequentially whenever the
partment being cleaned pressure switch contacts are closed. When the
indication pressure switch contacts open, the output
■ Rugged Timing sequencing stops. Re-closing of the contacts will
Adjustments: Large stable cause the control to resume activating the out-
potentiometers are used puts.
for "on" and "off" time
adjustments Program wire allows the user to select the maxi-
mum number of outputs to be activated.
■ Metal Chassis Provided:
For mounting directly into Note: Controls are shipped with jumper across pressure switch terminals
NEMA-4 box Specifications
■ Timer Life Tested for 24
4 Hours: To eliminate field
failures
Time Delay
On-Time: Adjustable from 50 to 500 millisec-
Output
Type: Solid-state switch (Triac)
■ Input Protection: 30 joule onds Switch Rating: 200 VA maximum per output
metal oxide varistor Off-Time: Range A - adjustable from 1.5 to 30
■ One Year Warranty: seconds; Range B - adjustable from 8.5 to 180 Protection
Warranted to be free from seconds Transient Voltage: 30 joule metal oxide varistor
defects in materials or Short Circuit Protection: 3 Amp. fuse
Note: Range S designates customer specified time
workmanship for One
range. Consult factory for parameters Environmental
Year from date of purchase
■ Made in USA Repeatability: ± 3% over temperature and volt- Operating Temperature: -40°C to 66°C
age ranges
Storage Temperature: -40°C to 70°C
Input
Operating Voltage:
120 ± 10%, 220 ±10% VAC
Frequency: 50/60 Hz
Power Consumption: 2 VA Max. Pressure Alternate action
switch TIMER #1 dual coil latching relay.
Contacts shown with
Wiring diagram to Facilitate reset coil energized last.
Expanded Output Mode L1 L2 C 1 2 3 4 5 6 7 8 9 10
10 5 1
OFF ON
Program Wire-
Determines number
of outputs to be
activated
# 6 screw typ.
D
B
3 AMP
AC C 1 2
L1
.31 Voltage .625
(4250-2 10/92) Input L2
2.0 Max.
Solenoid Valve
Features
■ Field Selectable from 2 to
10 Outputs
DC Input, Pulse
■ Completely Solid-state
Timing and Switching Cleaning of bag
Logic
■ 300% Overrated Solid-
state Switch
House Dust
■ Pressure Switch Control
Option On Board
Collectors Model
■ 12 to 24 Volts D.C. Input
Voltage
DNC-T2010-ADC
■ Adjustable "On" and "Off" Operating Logic: The control can function in 2
Times modes:
■ High Quality Locking Continuous Mode: The pressure switch terminals
Bushing Potentiometers are shorted. Upon application of output voltage,
for Timing Adjustment the control activates output #1 after the preset off
■ Very Low Power time. It will continue to activate outputs sequen-
Consumption tially until input voltage is removed.
■ RTV Protective Coating
for Corrosion and On Demand Mode: The pressure switch termi-
Moisture Resistance nals are connected to an isolated set of contacts of
a differential pressure switch. The control will acti-
■ LEDs Show
vate the outputs sequentially whenever the pres-
Compartment Being
sure switch contacts are closed. When the pressure
Cleaned
switch contacts open, the output sequencing stops.
■ Metal Chassis Provided Re-closing of the contacts will cause the control to
For Mounting Directly resume activating the outputs.
Into NEMA-4 Enclosure
Program wire allows the user to select the maxi-
mum number of outputs to be activated.
Specifications
4-12
Previous
National Controls
Contents Corporation
Phone 800-323-2593
Next
630-231-5900
Fax 630-231-1377
OFF ON
Program Wire-
Determines number
of outputs to be
activated
6.250
6.875
OUTPUTS (-)
+ - (+)
3 AMP
12-24VDC ONLY
.31
#6 screw typ.
.625
4
C 1 2 3 4 5 6 7 8 9 10
(4250-3 10/92)
DC + 2.0 Max.
Voltage
Input
-
Solenoid Valve Important Notice to Users:
Our timers are capable of use in a
wide array of devices and in various
applications. Any device or system
incorporating a timer should be so
designed that, in the event of failure,
malfunction or normal wear-out of
the timer, the system will become
inoperative in a manner which will
prevent property damage or bodily
Injury.
Caution:
1. Do not mount controls in high
vibration areas without shock
mounts.
2. Do not mount controls in areas of
high dust or corrosive atmospheres
without a protective enclosure.
Accessories: 3 Do not use a converter or inverter
for the power source.
Description Dimensions Part Number 4. Do not mount control in high
NEMA-4 BOX 10” x 8” x 4” BOX-A1008-CHNF transient voltage areas without an
NEMA-4 BOX 12” x 10” x 5” BOX-A1210-CHNF isolation transformer
On/Off Switch NEMA-4 Rated w/Legend Plate MSW-0DPST-011
5. Do not leave control box open.
6. Do not allow a local repair shop to
repair the controls, as we employ
National Controls Corporation offers NEMA 4 type enclosures for mounting our controls. These enclosures are made of heavy gauge steel and have a some very sophisticated components
continuous hinge cover. All seams are continuously welded. The finish is gray hammer-tone enamel inside and out, over phosphatized surfaces. that could be further damaged. For
service, call us directly: 800-323-2593
Note. In order to keep abreast of the latest technology, National Controls Corporation reserves the right to change components and/or design of
controls without notice.
4-13
BULLETIN E-97
Series DCT1000 Dust Collector Timer Controller
Thank you for purchasing the DCT1000 Dust Collector Timer PHYSICAL DATA
Controller. You have selected a state of the art dust collector Storage Temperature: -40˚F to 176˚F (-40˚C to 80˚C).
timer control that will provide years of dependable operation Operating Ambient Temperature: -40˚F to 140˚F (-40˚C to
and service. 60˚C).
Weight: 1 lb. 3.0 oz. (538.6 grams).
The DCT1000 Dust Collector Timer Controller was designed Power: 50 or 60 Hz, 85 to 270 VAC input.
to be used with pulse-jet type dust collectors for on-demand Power input: 270 VAC RMS max., transients: 80 Joule @
or continuous cleaning applications. The DCT1000 consists 1000 msec/50 Joule @ 2 msec.
of three basic modules: the master controller, the optional Fuse: 3A @ 250 VAC.
channel expander (slave board) and the pressure module Low voltage control circuitry is isolated from the line voltage for
(DCP100/200). This manual is limited to the installation and system safety.
operation of the master controller and optional channel Output Channels: up to 22 on one module, expandable to
expander. For installation requirements on the pressure mod- 255 using additional expansion modules.
ule, please refer to the installation and operating instructions Solenoid supply: 300 VA max.
for the DCP100/200. On-time: 10 msec to 600 msec, 10 msec steps.
Continuous cleaning applications do not require external On-time Accuracy: ±10 msec.
inputs and can be used for time based “on-demand” clean- Off-time: 1 to 255 seconds, in 1 second steps.
ing through use of the cycle delay feature. Off-time Accuracy: ±1% of the value or ±50 msec, which
For on-demand applications, the plug-in pressure modules ever is greater.
(DCP100/200) can be used to take full advantage of all the Default Settings:
features the DCT1000 offers, or an external pressure switch Channels: All installed channels
(such as the Dwyer Photohelic®) can be used for High/Low Time-off: 10 seconds
limit control. Time-on: 100 msec.
Down-time Cycles: 1 minute
As with traditional Dwyer products, the Dwyer DCT1000 was Cycle Delay: 0 minutes.
designed so that it is easy to use, thus allowing for a quick Low Alarm: 1.0″ w.c. [0.25 kPa]
and easy start up for your dust control applications. The con- High Alarm: 6.0″ w.c. [1.49 kPa]
tents inside this installation and operating manual will guide Low Limit: 3.0″ w.c. [0.75 kPa]
you through the features of the DCT1000 and how they can High Limit: 5.0″ w.c. [1.24 kPa]
be applied to get the most out of your dust control require- Auto Alarm Reset: 5 seconds.
ments.
2
Normally Open Contacts
Low
Limit
Pressure
Limit High
Switches Limit
4-20 mA Connections
Receiver 4-20 mA High Low Alarm Man Dt
Com Mode Ovr Cln Alarm
+ - Limit Com Limit Reset Com
Connections
TB3
TB3
Using DCT1000
Daisy Chain
In Out
24V Supply
Receiver TB4
Master Controller
+ - Input MUST NOT
+ Optional Connection Be Connected
Supply
- Using External Master Controller
Power Supply TB5
Alarm To
Relay Additional
Daisy Chain
In Out
Contacts
Expander
Supply Alarm (Internally Connected) Modules
Load TB1 (10 Channel Shown)
Sol
L1 L2 Com 1 2 3 4 5 6 7 8 9 10
Sol
L1 L2 Com 1 2 3 4 5 6 7 8 9 10
Figure 1
Switch Connections
Line
Input Solenoids
5
3.6 High Alarm Setup The display will indicate a 10-second countdown, at the end
The operation of the High Alarm Setup is identical to the High of which all parameters will be restored to factory defaults.
and Low Limit Setup and is only available when a pressure Releasing the switches prior to the end of the count will stop
module is installed. The High Alarm default is 6.0″ w.c. [1.49 the process and no modification will be made. Likewise, in
kPa]. The upper settable value is the calibration pressure of each of the parameter setup modes, pressing and holding
the pressure module and the lower limit is zero. Pressing the UP and DOWN buttons simultaneously will reset the indi-
Select will change the system to the Low Alarm Setup mode. vidual default value, leaving other settings unchanged.
6
4.4 Error Codes 5.0 Glossary of Terms
Error codes will be displayed on the three-digit display when
certain faults occur. Most of these indicators are associated • Run Mode: The term used when the timer board is firing
with the daisy chain communication, but certain error codes the solenoids.
pertain to single board operation also. These codes are:
• Modules: A major system component such as the
DCT1000 master controller or a DCP100 pressure module.
Display Meaning Action Required
• Pressure Module: The pressure measurement subsys-
This is a “watchdog” Make sure all electrical tem that includes the software and hardware for on-demand
reset that is enabled connections are appro- cleaning, alarms and signal retransmission of the process
Err 1 when the master con- priately shielded so the variable (i.e., the differential pressure across the dust bags).
troller isn’t able to cycle master controller is not
through its operation. disrupted by noise. • Master Controller: The primary timer board that contains
all of the major features, connections for external inputs and
The pressure module The master controller will power to drive the DCT1000 Dust Collector Timer Controller
Err 2 has failed to respond try to recover from the system.
to the request of the fault. If unsuccessful, • Power Guard: A plastic shield that covers the output tri-
master controller. replace the pressure acs and other line voltage circuitry.
module.
• Demand Cycle Mode: A process in which the run mode
Communication error in Make sure the control is enabled through the on-board pressure module or an
the daisy chain inter- cable used in the daisy external switch such as the Dwyer Photohelic®.
face. This will only chain interface is proper-
appear when the mas- ly shielded from noise. • Euro Connector: A “caged” connection used to termi-
Err 3
ter controller is used in nate solenoids, incoming power, or external switches on the
conjunction with a DCT1000.
slave board. • Continuous Cycle Mode: A time based cycling mode
dependent on solenoid time on/off settings and time set
The master controller Reinstall all modules in between complete cycles.
has detected a change accordance with the
Err 4 in module configuration instructions in the factory • Manual Override: Allows the user to override the
or a fault in one of the IOM. DCT1000 remotely or from the master controller panel
modules. through use of a switch or a wire jumper.
• Slave Board: A channel expander that is used in con-
If the fault described in Reinstall all modules. junction with the master controller to accommodate addi-
“Err 4” is not corrected, Contact factory if the tional solenoids on larger dust collection systems. It can be
the master controller problem persists. recognized easily as it does not have the on-board display
Err 5 will reconfigure the panel or the power supply present. A master controller may
modules that are also be used as a slave board.
responding properly
and operate at a
degraded condition.
PROCESS {IN 0}
LAST OUTPUT
TIME OFF (SEC)
TIME ON (MSEC)
HIGH LIMIT
UP
RUN LOW LIMIT
6-1/4
[158.75]
6-7/8
[174.62]
8-1/4 1/16
[209.55] 1-13/16 [1.59]
8-3/4
[46.04]
[233.25]
Still need help? Please feel free to contact one of our customer service representatives at
219-879-8000 or visit us on the web at www.dwyer-inst.com or www.dust-controls.com.
Again, we thank you for selecting the Dwyer DCT1000.
ROOTS
™
J Check shipment for damage. If found, file claim with J Read starting check points under OPERATION. Run
carrier and notify ROOTS. equipment briefly to check for installation errors and
make corrections. Follow with a trial run under normal
J Unpack shipment carefully, and check contents against operating conditions.
Packing List. Notify ROOTS if a shortage appears.
J In event of trouble during installation or operation, do
J Store in a clean, dry location until ready for installation. not attempt repairs of ROOTS furnished equipment.
Lift by methods discussed under INSTALLATION to Notify ROOTS, giving all nameplate information plus an
avoid straining or distorting the equipment. Keep covers outline of operating conditions and a description of the
on all openings. Protect against weather and corrosion if trouble. Unauthorized attempts at equipment repair may
outdoor storage is necessary. void ROOTS warranty.
J Read OPERATING LIMITATIONS and INSTALLATION sec- J Units out of warranty may be repaired or adjusted by the
tions in this manual and plan the complete installation. owner. Good inspection and maintenance practices
should reduce the need for repairs.
J Provide for adequate safeguards against accidents to NOTE: Information in this manual is correct as of the date of
persons working on or near the equipment during both publication. ROOTS reserves the right to make design or
installation and operation. See SAFETY PRECAUTIONS. material changes without notice, and without obligation to
make similar changes on equipment of prior manufacture.
J Install all equipment correctly. Foundation design must For your nearest ROOTS Office, dial our Customer Service
be adequate and piping carefully done. Use recommend- Hot Line toll free; 1 877 363 ROOT(S) (7668) or direct 281-
ed accessories for operating protection. 966-4700.
J Make sure both driving and driven equipment is correct-
ly lubricated before start-up. See LUBRICATION.
ISRB-2002 rev.0106
(formerly IOM-180-205)
ROOTS® products are sold subject to the
current General Terms of Sale, GTS-5001
and Warranty Policy WP-5020. Copies are
available upon request.
Contact your local ROOTS Office
or ROOTS Customer Service
Hot Line 1-877-363-ROOT(S) (7668) or
direct 281-966-4700.
2
Safety Precautions
It is important that all personnel observe safety precautions • Stay clear of the blast from pressure relief valves and the
to minimize the chances of injury. Among many considera- suction area of vacuum relief valves.
tions, the following should be particularly noted:
• Use proper care and good procedures in handling, lifting,
• Blower casing and associated piping or accessories may installing, operating and maintaining the equipment.
become hot enough to cause major skin burns on con-
tact. • Casing pressure must not exceed 25 PSI (1725 mbar)
gauge. Do not pressurize vented cavities from an external
• Internal and external rotating parts of the blower and source, nor restrict the vents without first consulting
driving equipment can produce serious physical injuries. ROOTS.
Do not reach into any opening in the blower while it is
operating, or while subject to accidental starting. Protect • Do not use air blowers on explosive or hazardous gases.
external moving parts with adequate guards.
• Other potential hazards to safety may also be associated
• Disconnect power before doing any work, and avoid with operation of this equipment. All personnel working
bypassing or rendering inoperative any safety or protec- in or passing through the area should be trained to exer-
tive devices. cise adequate general safety precautions.
Operating Limitations
A ROOTS blower or exhauster must be operated within cer- • Measured temperature rise must not exceed listed val-
tain approved limiting conditions to enable continued satis- ues when the inlet is at ambient temperature. Ambient
factory performance. Warranty is contingent on such opera- is considered as the general temperature of the space
tion. around the unit. This is not outdoor temperature unless
the unit is installed outdoors.
Maximum limits for pressure, temperature and speed are
specified in TABLE 1 for various models & sizes of blowers &
exhausters. These limits apply to all units of normal con- • If inlet temperature is higher than ambient, the listed
struction, when operated under standard atmospheric condi- allowable temperature rise values must be reduced by
tions. Be sure to arrange connections or taps for instru- 2/3 of the difference between the actual measured inlet
ments, thermometers and pressure or vacuum gauges at or temperature and the ambient temperature.
near the inlet and discharge connections of the unit. These,
along with a tachometer, will enable periodic checks of oper- • The average of the inlet and discharge temperature must
ating conditions. not exceed 250°F. (121°C).
PRESSURE – The pressure rise, between inlet and discharge,
• The ambient temperature of the space the blower/motor
must not exceed the figure listed for the specific unit frame
is installed in should not be highter than 120°F (48.8°C).
size concerned. Also, in any system where the unit inlet is at
a positive pressure above atmosphere a maximum case rat- SPEED – These blowers & exhausters may be operated at
ing of 25 PSI gauge (1725 mbar) should not be exceeded speeds up to the maximum listed for the various frame sizes.
without first consulting the ROOTS. Never should the maxi- They may be direct coupled to suitable constant speed driv-
mum allowable differential pressure be exceeded. ers if pressure/temperature conditions are also within limits.
At low speeds, excessive temperature rise may be a limiting
On vacuum service, with the discharge to atmospheric pres-
factor.
sure, the inlet suction or vacuum must not be greater than
values listed for the specific frame size. Special Note: The listed maximum allowable temperature
rise for any particular blower & exhauster may occur well
TEMPERATURE – Blower & exhauster frame sizes are
before its maximum pressure or vacuum rating is reached.
approved only for installations where the following tempera-
This may occur at high altitude, low vacuum or at very low
ture limitations can be maintained in service:
speed. The units’ operating limit is always determined by the
maximum rating reached first. It can be any one of the three:
Pressure, Temperature or Speed.
For your nearest ROOTS office contact information, please consult the last page of this document. 3
Installation
ROOTS blowers & exhausters are treated after factory tures by tapping with a hammer. In lifting, keep the direction
assembly to protect against normal atmospheric corrosion. of cable pull on these bolts as nearly vertical as possible. If
The maximum period of internal protection is considered to lifting lugs are not available, lifting slings may be passed
be one year under average conditions, if shipping plugs & under the cylinder adjacent to the headplates. Either method
seals are not removed. Protection against chemical or salt prevents strain on the extended drive shaft.
water atmosphere is not provided. Avoid opening the unit
until ready to start installation, as corrosion protection will Packaged Units: When the unit is furnished mounted on a
be quickly lost due to evaporation. baseplate, with or without a driver, use of lifting slings pass-
ing under the base flanges is required. Arrange these slings
If there is to be an extended period between installation and so that no strains are placed on the unit casing or mounting
start up, the following steps should be taken to ensure corro- feet, or on any mounted accessory equipment. DO NOT use
sion protection. the lifting lugs in the top of the unit headplates.
Before starting the installation, remove plugs, covers or seals
J Coat internals of cylinder, gearbox and drive end bearing from unit inlet and discharge connections and inspect the
reservoir with Nox-Rust VCI-10 or equivalent. Repeat interior completely for foreign material. If cleaning is
once a year or as conditions may require. Nox-Rust required, finish by washing the cylinder, headplates and
VCI-10 is petroleum soluble and does not have to be impeller thoroughly with an appropriate solvent. Turn the
removed before lubricating. It may be obtained from drive shaft by hand to make sure that the impellers turn
Daubert Chemical Co., 2000 Spring Rd., Oak Brook, Ill. freely at all points. Anti-rust compound on the connection
60521. flanges and drive shaft extension may also be removed at
this time with the same solvent. Cover the flanges until
J Paint shaft extension, inlet and discharge flanges, and all ready to connect piping.
other exposed surfaces with Nox-Rust X-110 or equiva-
lent. Mounting
Care will pay dividends when arranging the unit mounting.
J Seal inlet, discharge, and vent openings. It is not rec- This is especially true when the unit is a “bare-shaft” unit
ommended that the unit be set in place, piped to the furnished without a baseplate. The convenient procedure
system, and allowed to remain idle for extended periods. may be to mount such a unit directly on a floor or small con-
If any part is left open to the atmosphere, the Nox-Rust crete pad, but this generally produces the least satisfactory
VCI-10 vapor will escape and lose its effectiveness. results. It definitely causes the most problems in leveling
and alignment and may result in a “Soft Foot” condition.
J Protect units from excessive vibration during storage. Correct soft foot before operation to avoid unnecessary load-
ing on the casing and bearings. Direct use of building struc-
J Rotate shaft three or four revolutions every two weeks.
tural framing members is not recommended.
For blowers without a base, it is recommended that a well
J Prior to start up, remove flange covers on both inlet and anchored and carefully leveled steel or cast iron mounting
discharge and inspect internals to insure absence of plate be provided. The plate should be at least 1 inch (25
rust. Check all internal clearances. Also, at this time, mm) thick, with its top surface machined flat, and large
remove gearbox and drive end bearing cover and inspect enough to provide leveling areas at one side and one end
gear teeth and bearings for rust. after the unit is mounted. It should have properly sized
studs or tapped holes located to match the unit foot drilling.
Because of the completely enclosed unit design, location of Proper use of a high quality machinist’s level is necessary for
the installation is generally not a critical matter. A clean, dry adequate installation.
and protected indoor location is preferred. However, an out-
door location will normally give satisfactory service. With the mounting plate in place and leveled, set the unit on
Important requirements are that the correct grade of lubricat- it without bolting and check for rocking. If it is not solid,
ing oil be provided for expected operating temperatures, and determine the total thickness of shims required under one
that the unit be located so that routine checking and servic- foot to stop rocking. Place half of this under each of the
ing can be performed conveniently. Proper care in locating diagonally-opposite short feet, and tighten the mounting
driver and accessory equipment must also be considered. studs or screws. Rotate the drive shaft to make sure the
impellers turn freely. If the unit is to be direct coupled to a
Supervision of the installation by a ROOTS Service Engineer driving motor, consider the height of the motor shaft and the
is not usually required for these units. Workmen with experi- necessity for it to be aligned very accurately with the unit
ence in installing light to medium weight machinery should shaft. Best unit arrangement is directly bolted to the mount-
be able to produce satisfactory results. Handling of the ing plate while the driver is on shims of at least 1/8 inch
equipment needs to be accomplished with care, and in com- (3mm) thickness. This allows adjustment of motor position
pliance with safe practices. Unit mounting must be solid, in final shaft alignment by varying the shim thickness.
without strain or twist, and air piping must be clean, accu-
rately aligned and properly connected. Aligning
Bare-shaft Units: Two methods are used to handle a unit When unit and driver are factory mounted on a common
without base. One is to use lifting lugs bolted into the top of baseplate, the assembly will have been properly aligned and
the unit headplates. Test them first for tightness and frac- is to be treated as a unit for leveling purposes. Satisfactory
4
installation can be obtained by setting the baseplate on a con- the coupling.
crete slab that is rigid and free of vibration, and leveling the
top of the base carefully in two directions so that it is free of When a unit is BELT DRIVEN, the proper selection of sheave
twist. The slab must be provided with suitable anchor bolts. diameters will result in the required unit speed. When select-
The use of grouting under and partly inside the leveled and ing a sheave to be fitted to the blower shaft ROOTS recom-
shimmed base is recommended. mends a taper lock style sheave to insure proper contact with
the blower shaft. This flexibility can lead to operating tem-
It is possible for a base-mounted assembly to become twist- perature problems caused by unit speed being too low. Make
ed during shipment, thus disturbing the original alignment. sure the drive speed selected is within the allowable range for
For this reason, make the following checks after the base has the specific unit size, as specified under Table 1.
been leveled and bolted down. Disconnect the drive and
rotate the unit shaft by hand. It should turn freely at all Belt drive arrangements usually employ two or more V-belts
points. Loosen the unit foot hold-down screws and deter- running in grooved sheaves. Installation of the driver is less
mine whether all feet are evenly in contact with the base. If critical than for direct coupling, but its shaft must be level
not, insert shims as required and again check for free and parallel with the unit shaft. The driver should be mount-
impeller rotation. Finally, if unit is direct coupled to the driv- ed on the inlet side of a vertical unit (horizontal piping) and
er, check shaft and coupling alignment carefully and make on the side nearest to the shaft on a horizontal unit. SEE
any necessary corrections. PAGE 6 - Acceptable Blower Drive Arrangement Options.
The driver must also be mounted on an adjustable base to
In planning the installation, and before setting the unit, con- permit installing, adjusting and removing the V-belts. To
sider how piping arrangements are dictated by the unit position the driver correctly, both sheaves need to be mount-
design and assembly. Drive shaft rotation must be estab- ed on their shafts and the nominal shaft center distance
lished accordingly and is indicated by an arrow near the known for the belt lengths to be used.
shaft.
CAUTION: Drive couplings and sheaves (pulleys) should have
Typical arrangement on vertical units has the drive shaft at an interference fit to the shaft of the blower (set screw types
the top with counterclockwise rotation and discharge to the of attachment generally do not provide reliable service.) It is
left. Horizontal units are typically arranged with the drive recommended that the drive coupling or sheave used have a
shaft at the left with counterclockwise rotation and discharge taper lock style bushing which is properly sized to provide the
down. See Figure 4 for other various unit arrangements and correct interference fit required. Drive couplings, that require
possible conversions. heating to fit on the blower shaft, should be installed per cou-
pling manufacturer recommendations. A drive coupling or
When a unit is DIRECT COUPLED to its driver, the driver RPM sheave should not be forced on to the shaft of the blower as
must be selected or governed so as not to exceed the maxi- this could affect internal clearances resulting in damage to
mum speed rating of the unit. Refer to Table 1 for allowable the blower.
speeds of various unit sizes.
Engine drive applications often require special consideration
A flexible type coupling should always be used to connect the to drive coupling selection to avoid harmful torsional vibra-
driver and unit shafts. tions. These vibrations may lead to blower damage if not
When direct coupling a motor or engine to a blower you must dampened adequately. It is often necessary to install a fly-
insure there is sufficient gap between the coupling halves and wheel and/or a torsionally soft elastic element coupling
the element to prevent thrust loading the blower bearings. based on the engine manufacturer recommendations.
When a motor, engine or blower is operated the shafts may The driver sheave should also be mounted as close to its
expand axially. If the coupling is installed in such a manner bearing as possible, and again should fit the shaft correctly.
that there is not enough room for expansion the blower shaft Position the driver on its adjustable base so that 2/3 of the
can be forced back into the blower and cause the impeller to total movement is available in the direction away from the
contact the gear end headplate resulting in damage to the unit, and mount the assembly so that the face of the sheave
blower. The two shafts must be in as near perfect alignment is accurately in line with the unit sheave. This position mini-
in all directions as possible, and the gap must be established mizes belt wear, and allows sufficient adjustment for both
with the motor armature on its electrical center if end-play installing and tightening the belts. After belts are installed,
exists. Coupling manufacturer’s recommendations for maxi- adjust their tension in accordance with the manufacturer’s
mum misalignment, although acceptable for the coupling, are instructions. However, only enough tension should be
normally too large to achieve smooth operation and maxi- applied to prevent slippage when the unit is operating under
mum life of the blower. load. Excessive tightening can lead to early bearing concerns
The following requirements of a good installation are recom- or shaft breakage.
mended. When selecting a coupling to be fitted to the blower Before operating the drive under power to check initial belt
shaft ROOTS recommends a taper lock style coupling to tension, first remove covers from the unit connections. Make
insure proper contact with the blower shaft. If the coupling sure the interior is still clean, then rotate the shaft by hand.
must have a straight bore the coupling halves must be fitted Place a coarse screen over the inlet connection to prevent
to the two shafts with a line to line thru .001” interference fit. anything being drawn into the unit while it is operating, and
Coupling halves must be warmed up per coupling manufac- avoid standing in line with the discharge opening. Put oil in
turer’s recommendations. Maximum deviation in offset align- the sumps per instructions under LUBRICATION.
ment of the shafts should not exceed .005” (.13 mm) total
indicator reading, taken on the two coupling hubs. Maximum Piping
deviation from parallel of the inside coupling faces should not
Before connecting piping, remove any remaining anti-rust
exceed .001” (.03 mm) when checked at six points around
compound from unit connections. Clean pipe should be no
For your nearest ROOTS office contact information, please consult the last page of this document. 5
Acceptable Blower Drive Arrangement Options
ACCEPTABLE UNACCEPTABLE
Top Shaft Top Shaft
Motor On Inlet Side of Blower (Top Shaft) Motor On Discharge Side of Blower (Top Shaft)
Motor On Inlet Side of Blower (Bottom Shaft) Motor On Discharge Side of Blower (Bottom Shaft)
INLET
INLET
DISCHARGE
DISCHARGE
smaller than unit connections. In addition, make sure it is or sandy locations. A discharge silencer is also normally
free of scale, cuttings, weld beads, or foreign material of any suggested, even though Whispair units operate at generally
kind. To further guard against damage to the unit, especially lower noise levels than conventional rotary blowers. Specific
when an inlet filter is not used, install a substantial screen of recommendations on silencing can be obtained from your
16 mesh backed with hardware cloth at or near the inlet con- local ROOTS distributor.
nections. Make provisions to clean this screen of collected
debris after a few hours of operation. It should be removed Discharge piping requires a pressure relief valve, and should
when its usefulness has ended, as the wire will eventually include a manual unloading valve to permit starting the unit
deteriorate and small pieces going into the unit may cause under no-load conditions. Reliable pressure/vacuum gauges
serious damage. and good thermometers at both inlet and discharge are rec-
ommended to allow making the important checks on unit
Pipe flanges or male threads must meet the unit connections operating conditions. The back-pressure regulator shown in
accurately and squarely. DO NOT attempt to correct mis- Figure 3 is useful mainly when volume demands vary while
alignment by springing or cramping the pipe. In most cases the unit operates at constant output. If demand is constant,
this will distort the unit casing and cause impeller rubbing. but somewhat lower than the unit output, excess may be
In severe cases it can prevent operation or result in a broken blown off through the manual unloading valve.
drive shaft. For similar reasons, piping should be supported
near the unit to eliminate dead weight strains. Also, if pipe In multiple unit installations where two or more units operate
expansion is likely to occur from temperature change, instal- with a common header, use of check valves is mandatory.
lation of flexible connectors or expansion joints is advisable. These should be of a direct acting or free swinging type, with
one valve located in each line between the unit and header.
Figure 3 represents an installation with all accessory items Properly installed, they will protect against damage from
that might be required under various operating conditions. reverse rotation caused by air and material back-flow through
Inlet piping should be completely free of valves or other an idle unit.
restrictions. When a shut-off valve can not be avoided, make
sure a full size vacuum relief is installed nearest the unit inlet. After piping is completed, and before applying power, rotate
This will protect against unit overload caused by accidental the drive shaft by hand again. If it does not move with uni-
closing of the shut-off valve. form freedom, look for uneven mounting, piping strain,
excessive belt tension or coupling misalignment.
Need for an inlet silencer will depend on unit speed and pres-
sure, as well as sound-level requirements in the general sur- DO NOT operate the unit at this time unless it has been lubri-
roundings. An inlet filter is recommended, especially in dusty cated per instructions.
6
Technical Supplement for URAI® Gas Blowers
Technical Supplement for 32, 33, 36, 42, 45, 47, 53, 56, 59, purge gas pressure must be maintained one psi above the
65, 68, 615 Universal RAI-G blowers discharge gas pressure. Also, there exists a possibility of
gear end oil and drive end grease leakage into the gas
ROOTS Universal RAI-G rotary positive gas blowers are a stream.
design extension of the basic Universal RAI blower model.
URAI-G blower uses (4) mechanical seals in place of the The lubricants selected must be compatible with the gas.
standard inboard lip seals to minimize gas leakage into the
atmosphere. The seal vent chambers are plugged. These
units are intended for gases which are compatible with cast URAI GAS Blower Oil and Grease Specifications
iron case material, steel shafts, 300/400 series stainless steel
The specified oil should be ROOTS synthetic P/N 813-106- of
and carbon seal components, viton o-rings and the oil/grease
the proper viscosity.
lubricants. If there are any questions regarding application or
operation of this gas blower, please contact factory. When servicing drive end bearings of a Gas blower, use the
specified NLGI #2 premium grade aluminum complex*
Precaution: URAI-G blowers: Care must be used when
grease, ROOTS P/N T20019001, with 300°F (149°C) service
opening the head plate seal vent chamber plugs (43) as
temperature and moisture resistance and good mechanical
some gas will escape–if it is a pressure system, or the
stability.
atmospheric air will leak in-if the system is under vacuum.
There is a possibility of some gas leakage through the
mechanical seals. This leakage on the gear end will escape
*ROOTS Synthetic Oil & Grease is superior in performance to
through the gear box vent, and on the drive end, through the petroleum based products. It has high oxidation stability, excellent corrosion
grease release fittings. If the gas leakage is undesirable, protection, extremely high film strength and low coefficient of friction. Typical
each seal chamber must be purged with an inert gas oil change intervals are increased 2-3 times over petroleum based lubricants.
through one purge gas hole (43) per seal . There are two Also, ROOTS Synthetic Oil is 100% compatible with petroleum based oils.
plugged purge gas holes(1/8 NPT) provided per seal. The Simply drain the oil in the blower and refill the reservoirs with ROOTS Synthetic
Oil to maintain optimum performance of your ROOTS blower.
For your nearest ROOTS office contact information, please consult the last page of this document. 7
Lubrication
For Units with a Grease Lubricated Drive End and is drained downward.
A simple but very effective lubrication system is employed on Oil sumps on each end of the blower are filled by removing
the drive shaft end bearings. Hydraulic pressure relief fittings top vent plugs, Item (25), and filling until oil reaches the mid-
are provided to vent any excess grease, preventing pressure dle of the oil level sight gauge, Item (45 or 53), or the over-
build-up on the seals. A restriction plug and metering orifice flow plug (see pages 14 and 15).
prevent loss of lubricant from initial surges in lubricant pres- Initial filling of the sumps should be accomplished with the
sure but permit venting excess lubricant under steadily rising blower not operating, in order to obtain the correct oil level.
pressures. Approximate oil quantities required for blowers of the various
When servicing drive end bearings of Non Gas blower, use models and configurations are listed in Table 3. Use a good
the specified NLGI #2 premium grade microgel grease with grade of industrial type non-detergent, rust inhibiting, anti-
250°F (121°C) service temperature and moisture resistance foaming oil and of correct viscosity per Table 2. *ROOTS syn-
and good mechanical stability. ROOTS specifies Shell Darina thetic oil (ROOTS P/N 813-106-) is highly recommended.
EP NLGI Grade 2. Product Code 71522. ROOTS does not recommend automotive type lubricants, as
they are not formulated with the properties mentioned above.
URAI GAS Blower Oil and Grease Specifications
The oil level should not fall below the middle of the site gauge
The specified oil should be ROOTS synthetic P/N 813-106- of or overflow plug on URAI (ref. pages 14 & 15) when the
the proper viscosity. blower is idle. It may rise or fall on the gauge during opera-
When servicing drive end bearings of a Gas blower, use the tion, to an extent depending somewhat on oil temperature
specified NLGI #2 premium grade aluminum complex* and blower speed.
grease, ROOTS P/N T20019001, with 300°F (149°C) service Proper lubrication is usually the most important single con-
temperature and moisture resistance and good mechanical sideration in obtaining maximum service life and satisfactory
stability. operation from the unit. Unless operating conditions are quite
NOTE: Lithium based greases are not compatible with the severe, a weekly check of oil level and necessary addition of
ROOTS Synthetic grease used when assembling a Gas blow- lubricant should be sufficient. During the first week of opera-
er or the non-soap base grease used when assembling a tion, check the oil levels in the oil sumps about once a day,
standard URAI blower. Lithium based grease is not and watch for leaks. Replenish as necessary. Thereafter, an
approved for any ROOTS blowers. occasional check should be sufficient. It is recommended that
the oil be changed after initial 100 hours of operation.
Using a pressure gun, slowly force new lubricant into each Frequent oil changing is not necessary unless the blower is
drive end bearing housing until traces of clean grease comes operated in a very dusty location.
out of the relief fitting. The use of an electric or pneumatic
grease gun could force the grease in too rapidly and thus Normal life expectancy of petroleum based oils is about 2000
invert the seals and should not be used. hours with an oil temperature of about 180°F (82°C). As the
oil temperature increases by increments of 15-18°F (8°C -
After a long shutdown, it is recommended that the grease fit- 10°C), the life is reduced by half. Example: Oil temperatures
tings be removed, the old grease flushed out with kerosene of 210-216°F (99°C - 102°C) will produce life expectancy of
or #10 lubricating oil, drained thoroughly, and bearings 1/4 or 500 hours. Therefore, it is considered normal to have
refilled with new grease. Be sure grease relief fittings are oil change periods of 500 hours with petroleum based oils.
reinstalled. Grease should be added using a hand operated
grease gun to the drive end bearings at varying time intervals Normal life expectancy of ROOTS™ Synthetic Oil is about 4000
depending on duty cycle and RPM. Table 4 has been pre- to 8000 hours with an oil temperature of about 180°F (82°C).
pared as a general greasing schedule guide based on average As the oil temperature increases by increments of 15-18°F
operating conditions. More frequent intervals may be neces- (8°C - 10°C), the life is reduced by half. Example: Oil temper-
sary depending on the grease operating temperature and atures of 210-216°F (99°C - 102°C) will produce life
unusual circumstances. expectancy of 1/4 or 1000 to 2000 hours.
For Units with Splash Lubrication on Both Ends NOTE: To estimate oil temperature, multiply the discharge
temperature of the blower by 0.80. Example: if the discharge
Bearings and oil seals are lubricated by the action of the tim- air temperature of the blower is 200° F, it is estimated that
ing gears or oil slingers which dip into the main oil sumps the oil temperature is 160° F.
causing oil to splash directly on gears and into bearings and
*ROOTS™ Synthetic Oil & Grease is superior in performance to petroleum based prod-
seals. A drain port is provided below each bearing to prevent ucts. It has high oxidation stability, excellent corrosion protection, extremely high film
an excessive amount of oil in the bearings. Seals located strength and low coefficient of friction. Typical oil change intervals are increased 2-3
inboard of the bearings in each headplate effectively retain oil times over petroleum based lubricants. Also, ROOTS™ Synthetic Oil is 100% compatible
within the sumps. Any small leakage that may occur should with petroleum based oils. Simply drain the oil in the blower and refill the reservoirs
the seals wear passes into a cavity in each vented headplate with ROOTS™ Synthetic Oil to maintain optimum performance of your ROOTS™ blower.
8
Operation
Before operating a blower under power for the first time, close the discharge unloading valve to apply working pres-
recheck the unit and the installation thoroughly to reduce the sure. At this point it is recommended that a pressure gauge
likelihood of avoidable troubles. Use the following procedure or manometer be connected into the discharge line if not
check list as a guide, but consider any other special condi- already provided, and that thermometers be in both inlet and
tions in the installation. discharge lines. Readings from these instruments will show
whether pressure or temperature ratings of the blower are
J Be certain that no bolts, tools, rags, or debris have been being exceeded.
left in the blower air chamber or piping. During the final run, check operating conditions frequently
and observe the oil levels at reasonable intervals. If excessive
J If an outdoor intake without filter is used, be sure the noise or local heating develops, shut down immediately and
opening is located so it cannot pick up dirt and is pro- determine the cause. If either pressure rise or temperature
tected by a strong screen or grille. Use of the temporary rise across the blower exceeds the limit specified in this
protective screen as described under INSTALLATION is manual, shut down and investigate conditions in the piping
strongly recommended. system. Refer to the TROUBLESHOOTING CHECKLIST for
suggestions on various problems that may appear.
J Recheck blower leveling, drive alignment and tightness The blower should now be ready for continuous duty opera-
of all mounting bolts if installation is not recent. If belt tion at full load. During the first few days make periodic
drive is used, adjust belt tension correctly. checks to determine whether all conditions remain steady, or
at least acceptable. This may be particularly important if the
J Turn drive shaft by hand to make sure impellers still blower is supplying air to a process system where conditions
rotate without bumping or rubbing at any point. can vary. At the first opportunity, stop the blower and clean
the temporary inlet protective screen. If no appreciable
J Ensure oil levels in the main oil sumps are correct. amount of debris has collected, the screen may be removed.
See comments under INSTALLATION. At this same time, ver-
J Check lubrication of driver. If it is an electric motor, be ify leveling, coupling alignment or belt tension, and mounting
sure that power is available and that electrical overload bolt tightness.
devices are installed and workable. Should operating experience prove that blower capacity is a
little too high for the actual air requirements, a small excess
J Open the manual unloading valve in the discharge air may be blown off continuously through the manual unload-
line. If a valve is in the inlet piping, be sure it is open. ing or vent valve. Never rely on the pressure relief valve as
an automatic vent. Such use may cause the discharge pres-
J Bump blower a few revolutions with driver to check that sure to become excessive, and can also result in failure of
direction of rotation agrees with arrow near blower the valve itself. If blower capacity appears to be too low, refer
shaft, and that both coast freely to a stop. to the TROUBLESHOOTING CHECKLIST.
After the preceding points are cleared, blower is ready for Vibration Assessment Criteria
trial operation under “no-load” conditions. The following With measurements taken at the bearing locations on the
procedure is suggested to cover this initial operation test housings, see chart below for an appropriate assessment
period. guide for rotary lobe blowers rigidly mounted on stiff foun-
dations.
a. Start blower, let it accelerate to full speed, then shut off.
Listen for knocking sounds, both with power on and as In general, blower vibration levels should be monitored on a
speed slows down. regular basis and the vibration trend observed for progres-
sive or sudden change in level. If such a change occurs, the
cause should be determined through spectral analysis.
b. After blower comes to a complete stop, repeat above,
but let blower run 2 or 3 minutes. Check for noises, As shown on the chart below, the level of all pass vibration
such as knocking sounds. will determine the need to measure discrete frequency vibra-
tion levels and the action required.
c. After blower comes to a complete stop, operate blower
for about 10 minutes unloaded. Check oil levels. All Pass Vibration Discrete Frequency Action
Observe cylinder and headplate surfaces for develop- (in/sec) Vibration (in/sec)
ment of hot spots such as burned paint, indicating 0.45 or less N/R Acceptable
impeller rubs. Be aware of any noticeable increase in Greater than 0.45 0.45 or less @ Acceptable
vibration. but 1.0 or less any frequency
Assuming that all trials have been satisfactory, or that neces- Greater than 0.45 @ Investigate
any frequency
sary corrections have been made, the blower should now
have a final check run of at least one hour under normal Greater than 1.0 Less than 1.0 Investigate
operating conditions. After blower is restarted, gradually Greater than 1.0 Investigate
For your nearest ROOTS office contact information, please consult the last page of this document. 9
Troubleshooting Checklist
10
Inspection & Maintenance: Universal RAI® series blowers
A good program of consistent inspection and maintenance is any reason. Some oil seal leakage may occur since an oil film
the most reliable method of minimizing repairs to a blower. A under the lip is required for proper operation. Periodically
simple record of services and dates will help keep this work leaked oil should be wiped off from surfaces. Minor seal
on a regular schedule. Basic service needs are: leakage should not be considered as indicating seal replace-
ment.
• Lubrication Timing gear wear, when correct lubrication is maintained,
should be negligible. Gear teeth are cut to provide the correct
• Checking for hot spots amount of backlash, and gears correctly mounted on the
shafts will accommodate a normal amount of tooth wear
• Checking for increases or changes in vibration and noise without permitting contact between lobes of the two
impellers. However, too high an oil level will cause churning
• Recording of operating pressures and temperatures and excessive heating. This is indicated by unusually high
temperature at the bottom of the gear housing. Consequent
Above all, a blower must be operated within its specified rat- heating of the gears will result in loss of tooth-clearance ,
ing limits, to obtain satisfactory service life. backlash and rapid wear of the gear teeth usually will devel-
op. Continuation of this tooth wear will eventually produce
A newly installed blower should be checked often during the
impeller contacts (knocking), and from this point serious
first month of full-time operation. Attention there after may
damage will be unavoidable if blower operation is continued.
be less frequent assuming satisfactory performance.
A similar situation can be produced suddenly by gear tooth
Lubrication is normally the most important consideration and
fracture, which is usually brought on by sustained overload-
weekly checks of lubricant levels in the gearbox and bearing
ing or momentary shock loads.
reservoirs should be customary. Complete oil change sched-
ules are discussed under LUBRICATION. Problems may also develop from causes other than internal
parts failure. Operating clearances within a blower are only a
Driver lubrication practices should be in accordance with the
few thousandths of an inch. This makes it possible for
manufacturer’s instructions. If direct connected to the blower
impeller interference or casing rubs to result from shifts in
through a lubricated type coupling, the coupling should be
the blower mounting, or from changes in piping support. If
checked and greased each time blower oil is changed. This
this type of trouble is experienced, and the blower is found
will help reduce wear and prevent unnecessary vibration. In a
to be clean, try removing mounting strains. Loosen blower
belted drive system, check belt tension periodically and
mounting bolts and reset the leveling and drive alignment.
inspect for frayed or cracked belts.
Then tighten mounting again, and make sure that all piping
In a new, and properly installed, unit there is no contact meets blower connections accurately and squarely Foreign
between the two impellers, or between the impellers and materials in the blower will also cause trouble, which can
cylinder or headplates. Wear is confined to the bearings only be cured by disconnecting the piping and thoroughly
(which support and locate the shafts) the oil seals, and the cleaning the blower interior.
timing gears. All are lubricated and wear should be minimal
A wide range of causes & solutions for operating troubles
if clean oil of the correct grade is always used. Seals are sub-
are covered in the TROUBLE SHOOTING CHECKLIST. The
ject to deterioration as well as wear, and may require replace-
remedies suggested should be performed by qualified
ment at varying periods.
mechanics with a good background. Major repairs generally
Shaft bearings are designed for optimum life under average are to be considered beyond the scope of maintenance, and
conditions with proper lubrication and are critical to the serv- should be referred to an authorized ROOTS distributor.
ice life of the blower. Gradual bearing wear may allow a shaft
Warranty failures should not be repaired at all, unless specif-
position to change slightly, until rubbing develops between
ic approval has been obtained through ROOTS before start-
impeller and casing. This will cause spot heating, which can
ing work. Unauthorized disassembly within the warranty peri-
be detected by observing these surfaces. Sudden bearing
od may void the warranty.
failure is usually more serious. Since the shaft and impeller
are no longer supported and properly located, extensive gen-
eral damage to the blower casing and gears is likely to occur.
Oil seals should be considered expendable items, to be
replaced whenever drainage from the headplate vent cavity
becomes excessive or when the blower is disassembled for
For your nearest ROOTS office contact information, please consult the last page of this document. 11
Figure 2 - Allowable Overhung Loads for V-Belt Drives Universal RAI®/URAI®-J Units
252100 • Motor HP
Belt Pull lbs =
Blower RPM • Sheave Diameter
Sheave Width
Shaft Load (lb.in) = Belt Pull • (A + 1/4” + )
2
ACCEPTABLE UNACCEPTABLE
Motor On Inlet Side of Blower (Top Shaft) Motor On Discharge Side of Blower (Top Shaft)
Motor On Inlet Side of Blower (Bottom Shaft) Motor On Discharge Side of Blower (Bottom Shaft)
INLET
INLET
12
Figure 3a - Air Blower Installation with Accessories
For your nearest ROOTS office contact information, please consult the last page of this document. 13
Figure 4
14
Drive End Breather Orientation for U-RAI series - DSL with Oil Lube
Table 1 - Universal RAI series, Universal URAI-DSl & URAI-G gas blower,
Maximum Allowable Operating Conditions
For your nearest ROOTS office contact information, please consult the last page of this document. 15
Table 2 - Recommended Oil Grades URAI GAS Blower Oil and Grease Specifications
The specified oil should be ROOTS synthetic P/N 813-106- of
Ambient ISO
Temperature °F (°C) Viscosity No.
the proper viscosity.
These capacities are provided to assist in stocking the correct amount of oil. Exact sump capacities may differ slightly. See
“Lubrication” section for proper filling instructions.
UNIVERSAL URAI series-DSL Splash Lubricated Drive End
UNIVERSAL RAI, URAI-J, URAI-G
Note that the gear end sump capacity is provided on the adjacent table.
Frame Size Gear End Capacity Fl. Oz. (Liters) Frame Size Drive End Capacity Fl. Oz. (Liters)
Vertical Horizontal Vertical Horizontal
22 3.4 (.1) 6.1 (.18) 32 4.0 (.12) 6.5 (.19)
24 3.4 (.1) 6.1 (.18) 33 4.0 (.12) 6.5 (.19)
32 8.5 (.25) 16.0 (.47) 36 4.0 (.12) 6.5 (.19)
33 8.5 (.25) 16.0 (.47) 42 5.5 (.16) 10.8 (.32)
36 8.5 (.25) 16.0 (.47) 45 5.5 (.16) 10.8 (.32)
42 12.7 (.37) 22.8 (.67) 47 5.5 (.16) 10.8 (.32)
45 12.7 (.37) 22.8 (.67) 53 7.5 (.22) 14.8 (.44)
47 12.7 (.37) 22.8 (.67) 56 7.5 (.22) 14.8 (.44))
53 16.0 (.47) 27.6 (.82) 59 7.5 (.22) 14.8 (.44)
56 16.0 (.47) 27.6 (.82) 65 16 (0.47) 31 (0.91)
59 16.0 (.47) 27.6 (.82) 68 16 (0.47) 31 (0.91)
65 28.3 (.84) 52.1 (1.54) 615 16 (0.47) 31 (0.91)
68 28.3 (.84) 52.1 (1.54)
615 28.3 (.84) 52.1 (1.54)
76 32.3 (.96) 59.5 (1.76)
711 32.3 (.96) 59.5 (1.76)
718 32.3 (.96) 59.5 (1.76)
See page 14 and 15 for illustration of vertical and horizontal configurations.
Table 4 - Universal URAI series with Grease Lubricated Drive End: Specified Bearing The specified grease for servicing drive
Greasing Intervals end bearings of a Gas blower, use a NLGI
#2 premium grade aluminum complex*
Speed In RPM Operating Hours Per Day grease, ROOTS P/N T20019001 with
8 16 24 300°F (149°C) service temperature and
Greasing Intervals in Weeks moisture resistance and good mechanical
stability.
750-1000 7 4 2
When servicing drive end bearings of Non
1000-1500 5 2 1
Gas blower, use a NLGI #2 premium
1500-2000 4 2 1 grade microgel grease with 250°F (121°C)
2000-2500 3 1 1 service temperature and moisture resist-
2500-3000 2 1 1 ance and good mechanical stability.
3000 and up 1 1 1 ROOTS specifies Shell Darina EP NLGI
Grade 2. Product Code 71522.
NOTE: Lithium based greases are not
compatible with the ROOTS Synthetic
grease used when assembling a Gas
blower or the non-soap base grease used
when assembling a standard URAI blower.
Lithium based grease is not approved for
any ROOTS blowers.
16
1 2 3 4 5 6 7 8 9 10 11
No. PATT. No.
REQ'D. PART NAME PART No.
MAT'L.
17
14
C
38 C
SEE NOTE
"F" 5
SEE NOTE 37
8 "B"
18
SEE NOTE "A"
(DO NOT DRILL
SEE TABLE 19 42
THRU)
20 11.2378
D D
SEE NOTE
"E"
9
40
45
SEE NOTE
SEE NOTE "G" "C" 18
For your nearest ROOTS office contact information, please consult the last page of this document.
35
E E
3 33
23
15 39 39
21
F F
Assembly of UNIVERSAL RAI Series, Air Blowers, 2-1/2” Through 5” Gear Diameter
17
18
Assembly of UNIVERSAL RAI Blowers, 6” and 7” Diameter
1 2 3 4 5 6 7 8 9 10 11
No. PATT. No.
REQ'D. PART NAME PART No.
MAT'L.
14
45
5
26
4
17
38
C C
SEE NOTE 43
"F"
SEE NOTE
8 "B"
18
A
20 19 37
44
D D
SEE NOTE
" E"
A
9
40
SEE NOTE
"C" & "E"
3
For your nearest ROOTS office contact information, please consult the last page of this document.
E E
33
23
39
15
21
F F
7 2
32
CONFIDENTIAL DR. vc
THIS DOCUMENT CONTAINS CONFIDENTIAL INFORMATION OF CHKD.
SECTIONAL ASSEMBLY
G ROOTS DIVISION, DRESSER INDUSTRIES, INC. IT SHALL G
APP.
3-1/2 THRU 5" U-RAI GAS BLOWERS
BE HELD IN STRICTEST CONFIDENCE, AND BE USED ONLY
IN CONJUNCTION WITH ROOTS DIVISION BUSINESS.
D ADD ITEMS 8 & 20 (NAMEPLATE & SCREW) RK 08/16/02 T129 RK AGP DBV
DIMENSIONAL TOLERANCES UNLESS OTHERWISE SPECIFIED
FINISHED DIMENSIONS
12 35 REF: EP938 CONCENTRICITY C ADD LIFTING LUG ITEM # 46 RK 04/12/02 T122 RK AGP SCALE TWO PLACE DECIMALS (.XX)---.015 FRACTIONAL--1/64
FULL
FLATNESS PERPENDICULARITY ADD 33 URAI-G TO NOTE E AND THREE PLACE DECIMALS (.XXX)--.005
19
1 2 3 5 6 7 8 9 10 11
20
No. PATT. No.
REQ'D. PART NAME PART No.
MAT'L.
A A
A
0.1980
1 11 13
27
26
42
29
VIEW "X"
B B
27
25
44
34
45 32
31
14 37
2
38
C 3 C
5
B B
18
20
19
B B
D D
8 43
"X"
9 33
36
15 35
SEE NOTE "C" 17
30
E E
39
21 32
23
7
F F
16 12
NOTES
For your nearest ROOTS office contact information, please consult the last page of this document. 21
22
Assembly of UNIVERSAL RAI Series - DSL with Splash Lubricated Drive End 6” Gear Diameter
Universal RAI Series Blowers Parts List Universal RAI Series Blowers Parts List Universal RAI-DSL Series Blowers Parts List
2-1/2” – 5” Gear Diameter 6” & 7” Gear Diameter 3-1/2” – 5” Gear Diameter
(Refer to drawing #64720023) (Refer to drawing #64792023) (Refer to drawing #T30356023)
Item # Part Name Qty. Item # Part Name Qty. Item # Part Name Qty.
For your nearest ROOTS office contact information, please consult the last page of this document. 23
Universal RAI Series Gas Blowers Parts List Universal RAI Series Gas Blowers Parts List
3-1/2” & 5” Gear Diameter 6” Gear Diameter
(Refer to drawing #T30099023) (Refer to drawing #T3011023)
24
Basic Connection & Drive Shaft Information
For your nearest ROOTS office contact information, please consult the last page of this document. 25
Basic Connection & Drive Shaft Information
URAI-J METRIC WHISPAIR AIR BLOWERS (with Grease Lubed Drive End)
BOM # * FRAME INLET/DISCH SHAFT BARE
SIZE CONN. DIAMETER WEIGHT
TBD 33J 2" BSP 19 mm 84
740860M0 36J 2.5" BSP 19 mm 112
TBD 45J 2.5" BSP 24 mm 119
TBD 47J 3" BSP 24 mm 138
TBD 56J 4" BSP 28 mm 180
Refer to Specification Sheet XXXXXX
URAI-J-DSL METRIC WHISPAIR AIR BLOWERS (with Dual Splash Lubrication DSL )
BOM # * FRAME INLET/DISCH SHAFT BARE
SIZE CONN. DIAMETER WEIGHT
TBD 33J 2" BSP 19 mm 87
T304660M0 36J 2.5" BSP 19 mm 115
TBD 45J 2.5" BSP 24 mm 122
T304550M0 47J 3" BSP 24 mm 141
TBD 56J 4" BSP 28 mm 185
Refer to Specification Sheet XXXXX
Universal RAI-J air blowers incorporate the patented WhispairTM design in addition to the
same features as the original URAI blowers. The URAI-J's are center timed, however the
WhispairTM benefits can only be realized when the jet is located in the discharge position.
26
Basic Connection & Drive Shaft Information
NOTE: METRIC URAI product has metric shaft diameter and connection sizes
URAI-METRIC AIR BLOWERS (with Grease Lubricated Drive End)
FRAME INLET/DISCH SHAFT BARE
BOM # *
SIZE CONN. DIAMETER WEIGHT
651020M0 22 1" BSP 16 mm 32
651030M0 24 2" BSP 16 mm 43
710480M0 32 1 1/4" BSP 19 mm 69
651050M0 33 2" BSP 19 mm 74
651060M0 36 2 1/2" BSP 19 mm 102
651080M0 42 1 1/2" BSP 24 mm 88
651090M0 45 2 1/2" BSP 24 mm 109
651100M0 47 3" BSP 24 mm 128
651120M0 53 2 1/2" BSP 28 mm 143
651130M0 56 4" BSP 28 mm 170
651140M0 59 4" BSP 28 mm 204
T30392060 65 3" BSP 32 mm 245
T30394060 68 5" BSP 32 mm 285
T30390060 615 150 NP10 32 mm 425
T30396060 76 4" BSP 38 mm 400
T30398060 711 150 NP10 38 mm 530
T30400060 718 200 NP10 38 mm 650
Refer to Specification Sheet XXXXX
Universal RAI air blowers include detachable mounting feet which permit vertical or horizontal installation.
The units are center timed for rotation in either direction. The bearings on the URAI are grease lubricated
on the drive end and splash lubricated on the gear end. The URAI-DSL is splash lubricated on BOTH ends.
For your nearest ROOTS office contact information, please consult the last page of this document. 27
Contact List
CUSTOMER SERVICE
Dresser Rooots
16240 Port Northwest Drive
Houston, TX 77041
Toll Free Hot Line: 1-877-363-ROOT(S) (7668)
Direct Line: 832-590-2600
Toll Free Fax: 1-877-357-7238
Direct Fax: 832-590-2325
©2006 Dresser, Inc. all rights reserved. • WHISPAIR is a trademark of Dresser, Inc. • ROOTS and Universal RAI are registered trademarks of Dresser, Inc.
Material Safety Data Sheet
I. Product Name: Dresser Roots ISO-VG 320 Date Issued/Revised: August 10, 2006
Chemical Family: S yn t h e t i c b a s e d l u b r i c a t i n g o i l
Use: Lu b r i c a n t a n d c o r r o s i o n i n h i b i t o r
Manufacturer: R o ya l P u r p l e , L t d .
Address: 1 R o ya l P u r p l e La n e , P o r t e r , T e x a s 7 7 3 6 5 U S A
Phone: 2 8 1 - 3 5 4 - 8 6 0 0 Emergency Phone: 2 8 1 - 3 5 4 - 8 6 0 0 Fax: 2 8 1 - 3 5 4 - 7 6 0 0
II. Components:
B a s e O i l ( s yn t h e t i c ) — S y n t h e t i c a d d i t i v e s w i t h i s o - p a r a f f i n i c d i l u e n t s .
T h e p r e c i s e c o m p o s i t i o n o f t h i s o i l i s p r o p r i e t a r y. A m o r e c o m p l e t e d i s c l o s u r e wi l l b e p r o v i d e d t o a p h ys i c i a n o r
n u r s e i n t h e e v e n t o f a m e d i c a l e m e r g e n c y.
A l l c o m p o n e n t s o f t h i s p r o d u c t a r e l i s t e d o n t h e U . S . T S C A i n v e n t o r y .
T h i s p r o d u c t c o n t a i n s n o h a z a r d o u s s u b s t a n c e s w i t h i n t h e d e f i n i t i o n o f O S H A R e g u l a t i o n 2 9 C F R 1 9 1 0 . 1 2 0 0 .
R o ya l P u r p l e c e r t i f i e s t h a t t h i s p r o d u c t h a s b e e n e v a l u a t e d f o r R C R A c h a r a c t e r i s t i c s a n d d o e s n o t m e e t t h e c r i t e r i a o f a
hazardous waste if discard ed in its purchased form.
V. Extinguishing Media:
®
Suitable: F o a m , d r y p o wd e r , H a l o n , c a r b o n d i o x i d e , s a n d , e a r t h a n d wa t e r m i s t .
Unsuitable: W a t e r j e t .
Protective Equipment for Fire Fighting: S e l f - c o n t a i n e d b r e a t h i n g a p p a r a t u s .
IX. Physical and Chemical Properties: Evaporation Rate (Butyl Acetate = 1): Negligible
Physical State: Li q u i d Vapor Pressure (kPa): < 0 . 1
Color: L i g h t A m b e r Percent Volatiles: N o n e
3
Odor: Lu b e O i l Density (g/cm ): 0 . 88
pH: N e u t r a l Flammability: N o t f l a m m a b l e a t a m b i e n t t e m p .
º º
Boiling Range / Point F ( C): > 7 0 0 ( > 3 7 1 ) OAR Value: U N
º º
Pour Point F ( C): -35 ( -37 ) Oxidizing Properties: N o n e
º º
Flash Point (COC) F ( C): >450 (>232 ) Water Solubility: In s o l u b l e
º º
Autoignition Temperature F ( C): > 6 0 0 ( > 3 1 5 ) Vapor Density: G r e a t e r t h a n a i r
Product Name: Dresser Roots ISO-VG-320
LEGEND
I. Identification of the Substance / Preparation and Company NFPA SYMBOL
II. Composition Information on Ingredients FIRE
III. Hazards Identification
IV. First Aid Measures
V. Fire Fighting Measures
VI. Accidental Release Measures
VII. Handling and Storage
Signature: ____________________________________
VIII. Exposure Control / Personal Protection
IX. Physical and Chemical Properties
Prepared By: A. J. Gustavsen. Ph. D. X. Stability and Reactivity HMIS SYMBOL
XI. Toxicological Information HEALTH 0
Date Issued/Revised: August 10, 2006 XII. Ecological Information
FLAMMABILITY 1
As of issue date, the information contained herein is accurate and reliable to the XIII. Waste Disposal
bestofRoy alPur ple’skn owl edge .Roy alPur pl
edoe sn otwa r
ran
torguarante
ei ts REACTIVITY 0
XIV. Transport Information
accuracy or reliability and shall not be liable for any loss or damage arising out of
theus et he reof .Itist heus e r’sr espon sibilityt os at
isfyi ts e
lftha
tth
einforma ti
on XV. Regulatory Information PPI B
offered for its consideration is suitable for its particular use. XVI. Other Information
Section 6- Troubleshooting
Pressure Gauge
Check the differential pressure gauge or manometer and the tubing
leading to the dust collector for proper operation. Disconnect the lines at
the gauge or manometer and clear with compressed air. Look for loose
fittings, cracked, broken or pinched tubing. Make sure that the gauge is
zeroed or that the manometer is level, zeroed and contains the correct
fluid.
If none of the solenoid valves are operating check the timer using the
“Troubleshooting the Timer” section.
Check the air pressure at the compressed air manifold. It should recover
to 10 psig before each pulse. If not, check to make sure that the
compressed air supply system is in good operating condition. Listen for
the sound of compressed air flowing continuously through one or more
diaphragm valves. This is an indication of a valve or valves “stuck” in the
pulsing position. The usual causes for this condition are either a leak in
the tubing between the solenoid and diaphragm valves or dirt in the
solenoid and/or diaphragm valves.
Check to see that all solenoid valves are firing by holding a finger over
each solenoid exhaust port as described in the “Start Up Checklist”
section.
6-1
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Troubleshooting the Dust Collector (continued)
Visually inspect the bags for heavy caking. If caking is evident see the
note below and take the necessary action to clean the bags. Next,
measure the main airflow with a pitot tube or equivalent device and
compare with the original volume for which the unit was designed. If the
flow is too high, cut back the main fan to prevent a recurrence of the
problem.
Water Leaks
Inspect the dust collector housing and ductwork for holes, cracks or
loose gasketing where water could enter the collector.
6-2
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Troubleshooting the Dust Collector (continued)
Condensation
If moisture has been condensing inside the collector check the dew point
temperature of the incoming air stream. It may be necessary to insulate
the collector and/or the ductwork leading to the collector to keep surface
temperatures above the dew point and prevent condensation inside the
dust collector.
NOTE: Collectors that have blinded bags can possibly be put into
service by running the pulsing air system for 15 to 30 minutes with a 10
second “off time” and without the main fan or blower running. If the
pressure drop is not lower when the main fan is started again remove
the filter bags from the collector and replace. Make sure the timer “off
time” has been reset to specifications prior to re-start. Information
pertaining to filter bag cleaning may be obtained by calling your
CAMCORP sales representative.
6-3
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Troubleshooting the Dust Collector (continued)
Residual dust
If dust has migrated into the clean air plenum because of a dropped filter
bag, torn filter bag or a hole in tube sheet, etc., the pulsing air may stir
up the dust and allow it to escape into the clean air exhaust after each
pulse. Residual dust may also be driven down inside the filter bags by
the pulsing air. If the filter bags are filled with several inches of dust
clean both the clean air plenum and the filter bags to avoid further
problems.
Temperature
Operating Temperature above the recommended limit of the filter bag
material.
6-4
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Troubleshooting the Dust Collector (continued)
Chemical attack
Bag material degrades due to attack from certain chemicals in the dust
or gasses in the air stream.
High moisture
High moisture content in the collector may cause certain filter bag
material to shrink, degrade (more rapidly at elevated temperatures) or
blind off.
Localized abrasion
Abrasion of the filter bags where high velocity dusty air hits the filter
bags. A dust impingement baffle may be required to be installed on the
inlet of the dust collector.
If the “Power On” indicator is not on, check for 120 VAC power input.
The “hot” line connection must be connected to terminal “L1”, as this is
the fused terminal.
Check the wiring from the timer to the solenoids for open or short
circuits.
After performing the steps above, if the timer is still not functioning
properly (no output voltage, sequencing problems, etc.) please contact
your CAMCORP representative.
6-5
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Troubleshooting the Compressed Air System
Ruptured diaphragm
Disassemble valve in question and inspect diaphragm(s). Replace with a
repair kit if necessary.
6-6
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Troubleshooting the Cleaning System
6-7
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Symptom Possible Causes Possible Sources
Poor Restricted Inlet Clogged Filter Element
Performance Collapsed Inlet Hose
Underrated Fuses
6-8
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Symptom Possible Causes Possible Sources
Overheating Excessive Pressure Clogged Filter Element
Ratio Collapsed Inlet Hose
Clogged Dust Vent Filter
Undersized Dust Vent Filter
Clogged Diffusion Pads
Insufficient Rotor Wrong Sheave Set
Speed Wrong Motor Speed
Slipping Belts
6-9
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Section 7 – Routine Maintenance
Inspection
Frequency will vary as widely as there are operating conditions. In
general proceed as follows:
Weekly – Check pulse timer board and solenoid valves for function.
This usually is only listening to check uniform time in intervals between
blasts.
Monthly – Lubricate fan, rotary valve and screw conveyor. Check seals
on latter two for dust loss.
Repairs
7-1
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Section 8 – Appendix
Air-to-Cloth Ratio – Ratio of the volume of gas filtered (in ACFM) to the amount
of filter media (in square feet).
Bag Blinding – A condition where dust particles become embedded in the fabric
over time and are not removed by the cleaning mechanism. This results in an
increased pressure drop across the filter bag media.
Bleed Through – Small particles of dust that are able to migrate through the
filter bags.
Can Velocity – The upward velocity of air through a cross section of the dust
collector.
Clean Air Plenum – The area of the dust collector where the air passes through
after being filtered by the filter media.
Dirty Air Plenum – The area of the dust collector where the filter media hangs
and the air has dust particulate in it.
Dust Cake – The normal build up on the outside of the filter media. A dust cake
is needed to provide the maximum filtering efficiency.
Filter Media – An air permeable material that provides a means to separate the
particulate from the air. This is usually a felt or woven bag or a pleated cartridge.
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com
Magnehelic Gauge – A standard devise used to measure differential pressure.
Pressure Drop – Another term for differential pressure or the drop in pressure
between two measured points.
Re-Entrainment – The re-depositing of dust on the filter media after it has been
cleaned off. This can be caused by turbulence in the hopper (or dirty air plenum)
or by excessive airflow through the dust collector.
Smart Timer Board – A timer that senses the differential pressure and only
cleans (pulses) the filter media when differential pressure is high (when the bags
/ cartridges are dirty). This provides for more economical use of compressed air.
The Smart Timer also provides additional features not available on a standard
timer. See Section 5 on Smart Timers for more details.
Timer Board – An electrical device that provides the electrical signal to the
solenoids to pulse the diaphragm valves.
Tubesheet – The steel plate that supports the filter media (bags or cartridges).
This plate separates the dirty air plenum from the clean air plenum.
8-2
CAMCORP, INC.
Phone: 913-831-0740 Fax: 913-831-9271
www.camcorpinc.com