Designwall™ 2000 Flat Wall Panels: 2" thick, ISO core, 30" module width.
Single Span Double Span Triple Span
Wind Load (psf) Maximum Span Limiting Factor Maximum Span Limiting Factor Maximum Span Limiting Factor
20 10' -3'' (D) 11' -8'' (N) 10' -0'' (L)
25 9' -1'' (D) 9' -6'' (N) 10' -0'' (L)
30 8' -2'' (D) 8' -0'' (N) 8' -6'' (N)
35 7' -5'' (D) 7' -0'' (N) 7' -4'' (N)
40 6' -9'' (D) 6' -2'' (N) 6' -6'' (N)
45 6' -3'' (D) 5' -7'' (N) 5' -9'' (N)
50 5' -10'' (D) 5' -1'' (N) 5' -3'' (N)
55 5' -5'' (D) 4' -8'' (N) 4' -9'' (N)
60 5' -1'' (D) 4' -4'' (N) 4' -5'' (N)
65 4' -9'' (D) 4' -0'' (N) 4' -1'' (N)
70 4' -6'' (D) 3' -9'' (N) 3' -9'' (N)
75 4' -3'' (D) 3' -6'' (N) 3' -6'' (N)
80 4' -0'' (D) 3' -4'' (N) 3' -4'' (N)
85 3' -10'' (D) 3' -1'' (N) 3' -2'' (N)
90 3' -8'' (D) 2' -11'' (N) 3' -0'' (N)
Notes:
1. Wind Load charts based on L/180 deflection limit. 4. Limiting factor: (N) Negative Load / Connection Strength, (S) Core Shear,
2. Exterior face 22 gauge steel, Interior face 24 gauge steel. (B) Flexural Bending, (D) Deflection, (L) Maximum Fabrication Length.
3. Spans may be governed by other factors including deflection due to 5. Values based on single #14 fastener into 3/16" steel thickness to achieve full
temperature differential, unequal span conditions, and fastener pullout limits spanning capacity of panel. For lighter gauge supports spans may be further
in lighter gauge supports. Consult Kingspan for specific project applications. limited by fastener pullout. See Fastener Section following these Wind Load
charts.
SPECIFICATION
85 3' -10'' (D) 2' -11'' (N) 2' -11'' (N)
DATA
90 3' -8'' (D) 2' -9'' (N) 2' -9'' (N)
Designwall™ 4000 Flat Wall Panels: 2" thick, ISO core, 24" module width.
Single Span Double Span Triple Span
Wind Load (psf) Maximum Span Limiting Factor Maximum Span Limiting Factor Maximum Span Limiting Factor
20 11' -8'' (D) 14' -0'' (B) 10' -0'' (L)
25 10' -7'' (D) 12' -8'' (D) 10' -0'' (L)
30 9' -8'' (D) 10' -10'' (S) 10' -0'' (L)
35 9' -0'' (D) 9' -4'' (S) 9' -6'' (S)
40 8' -5'' (D) 8' -3'' (S) 8' -4'' (S)
45 7' -10'' (D) 7' -5'' (S) 7' -5'' (S)
50 7' -5'' (D) 6' -9'' (S) 6' -9'' (S)
55 7' -1'' (D) 6' -2'' (S) 6' -2'' (S)
60 6' -6'' (S) 5' -8'' (S) 5' -8'' (S)
65 6' -0'' (S) 5' -4'' (S) 5' -3'' (S)
70 5' -7'' (S) 5' -0'' (S) 4' -11'' (S)
75 5' -3'' (S) 4' -8'' (S) 4' -7'' (S)
80 4' -11'' (S) 4' -5'' (S) 4' -4'' (S)
85 4' -7'' (S) 4' -2'' (S) 4' -1'' (S)
90 4' -4'' (S) 4' -0'' (S) 3' -11'' (S)
Notes:
1. Wind Load charts based on L/180 deflection limit. 4. Limiting factor: (N) Negative Load / Connection Strength, (S) Core Shear,
2. Exterior face 22 gauge steel, Interior face 24 gauge steel. (B) Flexural Bending, (D) Deflection, (L) Maximum Fabrication Length.
3. Spans may be governed by other factors including deflection due to 5. Values based on single #14 fastener into 3/16" steel thickness to achieve full
temperature differential, unequal span conditions, and fastener pullout limits spanning capacity of panel. For lighter gauge supports spans may be further
in lighter gauge supports. Consult Kingspan for specific project applications. limited by fastener pullout. See Fastener Section following these Wind Load
charts.
Designwall™ 4000 Flat Wall Panels: 2" thick, ISO core, 36" module width.
Single Span Double Span Triple Span
Wind Load (psf) Maximum Span Limiting Factor Maximum Span Limiting Factor Maximum Span Limiting Factor
20 11' -8'' (D) 13' -6'' (N) 10' -0'' (L)
25 10' -6'' (D) 10' -11'' (N) 10' -0'' (L)
30 9' -8'' (D) 9' -3'' (N) 10' -0'' (L)
35 8' -11'' (D) 8' -0'' (N) 8' -8'' (N)
40 8' -4'' (D) 7' -1'' (N) 7' -7'' (N)
45 7' -10'' (D) 6' -4'' (N) 6' -9'' (N)
50 7' -5'' (D) 5' -9'' (N) 6' -1'' (N)
55 7' -0'' (D) 5' -4'' (N) 5' -7'' (N)
60 6' -6'' (S) 4' -11'' (N) 5' -2'' (N)
65 6' -0'' (S) 4' -7'' (N) 4' -9'' (N)
70 5' -7'' (S) 4' -3'' (N) 4' -5'' (N)
75 5' -3'' (S) 4' -0'' (N) 4' -2'' (N)
80 4' -11'' (S) 3' -9'' (N) 3' -11'' (N)
85 4' -7'' (S) 3' -7'' (N) 3' -8'' (N)
90 4' -4'' (S) 3' -5'' (N) 3' -6'' (N)
Notes:
1. Wind Load charts based on L/180 deflection limit. 4. Limiting factor: (N) Negative Load / Connection Strength, (S) Core Shear,
2. Exterior face 22 gauge steel, Interior face 24 gauge steel. (B) Flexural Bending, (D) Deflection, (L) Maximum Fabrication Length.
3. Spans may be governed by other factors including deflection due to 5. Values based on single #14 fastener into 3/16" steel thickness to achieve full
temperature differential, unequal span conditions, and fastener pullout limits spanning capacity of panel. For lighter gauge supports spans may be further
in lighter gauge supports. Consult Kingspan for specific project applications. limited by fastener pullout. See Fastener Section following these Wind Load
charts.
SPECIFICATION
85 2' -2'' (D) 2' -2'' (D) 2' -2'' (S)
DATA
90 2' -0'' (D) 2' -0'' (D) 2' -0'' (S)
Designwall™ 3000 Wall Panels: 11/4" thick, Paper core, module width to 36".
Single Span Double Span Triple Span
Wind Load (psf) Maximum Span Limiting Factor Maximum Span Limiting Factor Maximum Span Limiting Factor
20 9' -7'' (D) 10' -8'' (B) 10' -0'' (L)
25 8' -10'' (D) 9' -7'' (B) 10' -0'' (L)
30 8' -4'' (D) 8' -9'' (B) 9' -8'' (B)
35 7' -10'' (D) 8' -1'' (B) 9' -0'' (B)
40 7' -5'' (B) 7' -7'' (B) 8' -5'' (B)
45 7'-0" (B) 7' -2'' (B) 7' -8'' (S)
50 6' -8'' (B) 6' -8'' (S) 6' -10'' (S)
55 6' -4'' (B) 6' -1'' (S) 6' -3'' (S)
60 6' -1'' (B) 5' -7'' (S) 5' -9'' (S)
65 5' -10'' (B) 5' -2'' (S) 5' -4'' (S)
70 5' -8'' (B) 4' -9'' (S) 4' -11'' (S)
75 5' -5'' (B) 4' -6'' (S) 4' -7'' (S)
80 5' -2'' (S) 4' -2'' (S) 4' -4'' (S)
85 4' -10'' (S) 4' -0'' (S) 4' -1'' (S)
90 4' -7'' (S) 3' -9'' (S) 3' -10'' (S)
Notes:
1. Wind Load charts based on L/180 deflection limit. 4. Limiting factor: (N) Negative Load / Connection Strength, (S) Core Shear,
2. Exterior face 22 gauge steel, Interior face 24 gauge steel. (B) Flexural Bending, (D) Deflection, (L) Maximum Fabrication Length.
3. Spans may be governed by other factors including deflection due to 5. Values based on single #14 fastener into 3/16" steel thickness to achieve full
temperature differential, unequal span conditions, and fastener pullout limits spanning capacity of panel. For lighter gauge supports spans may be further
in lighter gauge supports. Consult Kingspan for specific project applications. limited by fastener pullout. See Fastener Section following these Wind Load
charts.
pullout check
Tributary area: tributary width x tributary height.
One screw in 16 gauge = 238 lb. – Allowable where panel joint and
support intersect
300 lb. exceeds 238 lb. – Allowable (no good)
Wall panels
Two screws in 16 gauge = 357 lb. – Allowable 25 psf wind load Supports
300 lb. < 357 lb. – OK perpendicular
to panel joints
Consider 14 gauge supports:
■ One screw in 14 gauge = 353 lb. – Allowable
300 lb. < 353 lb. – OK