8610 MKII Configuration Page 1 of 44

8610 MKII Configuration


Module
Module Options
Description

1
2
3
4

LED Indicators

Insert Card Text


1 Fuel Pump Control Lit
2 Digital Input F Lit
3 Close Gen Output Pulse Lit
4 Common Alarm Lit

Miscellaneous Options

Enable Fast Loading Feature No


Audible alarm prior to starting No
All warnings are latched No
Enable Sleep Mode No
Enable Manual Fuel Pump Control
Support Right-to-Left Languages In Module Strings No
Power Up In Mode Stop
Enable Cool Down In Stop Mode No
Enable maintenance reset on module front panel No
Show Active DTC
Show Inactive DTC

Configurable Status Screens


Home Page

Home Page Mode

Displayed Pages

Page 1 Summary Screen Page 6 Not Used


Page 2 Not Used Page 7 Not Used
Page 3 Not Used Page 8 Not Used
Page 4 Not Used Page 9 Not Used
Page 5 Not Used Page 10 Not Used

Event Log
Display Options

Module display Date and time

about:blank 3/27/2018
8610 MKII Configuration Page 2 of 44

Logging Options

Log the following events to the event log

Log Fuel Level Yes


Power-Up Yes Log When At Rest No
ECU Shutdown alarms Yes Engine starts Yes
Engine stops Yes
'Repeat SMS' requires a GSM modem to be configured on the
Communications/Basic page
Shutdown Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Electrical Trip Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Latched warnings Yes
Unlatched warnings Yes
Repeat SMS No
Repeat delay 12h
Repeats 2

Maintenance Alarms Yes


Repeat SMS No
Repeat delay 12h
Repeats 2

Data Logging
Configuration
Data Logging

Logged data Log Interval


1 -2147483384 1 minute
2 1536 1 second
3 1044 1 second
4 1032 1 second
5 -1 1 second
6 -1 1 second
7 -1 1 second
8 -1 1 second
9 -1 1 second
10 -1 1 second
11 -1 1 second
12 -1 1 second

about:blank 3/27/2018
8610 MKII Configuration Page 3 of 44

13 -1 1 second
14 -1 1 second
15 -1 1 second
16 -1 1 second
17 -1 1 second
18 -1 1 second
19 -1 1 second
20 -1 1 second

Options
Data Log Options

Only Log When Engine is Running Yes


Log to USB drive No
Keep Oldest Data No

about:blank 3/27/2018
8610 MKII Configuration Page 4 of 44

Application
ECU (ECM) Options

Engine Type Deutz EMR3


Enhanced J1939 No
Alternative Engine Speed No
Modbus Engine Comms Port RS485 Port

Auto Voltage Sensing

Enable Auto Voltage Sensing No


Over Voltage During Auto Sensing Trip 277 V PhN

about:blank 3/27/2018
8610 MKII Configuration Page 5 of 44

Inputs
Analogue Input Configuration
ECU (ECM) Options

Oil pressure is read from the ECU


Use Module to Measure Oil Pressure
(ECM)
Use Module to Measure Coolant Engine temperature is read from the
Temperature ECU (ECM)

Input Configuration

Analogue Input A Not Used


Analogue Input B Not Used
Analogue Input C Fuel Sensor
Flexible
Analogue Input D
Analogue
'Flexible Analogue' selections are configured on the
'Inputs/Analogue Inputs' pages
'Digital Input' selections are configured on the 'Inputs/Digital
Inputs' pages
Oil/Temperature/Fuel selections are configured on the 'Engine'
pages

Analogue Inputs
Analogue Inputs

Analogue
Inputs

Flexible Sensor A
The Analogue Input is currently configured as Not Used
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor B
The Analogue Input is currently configured as Not Used
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor C
The Analogue Input is currently configured as a Fuel Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor D
Sensor Description

Sensor Name Oil Temperature

Input Type

VDO 120 °C

Sensor Alarms

Alarm Arming Always

about:blank 3/27/2018
8610 MKII Configuration Page 6 of 44

Low Alarm Enable No


Action None
Low Alarm 47 °C 117 °F

Low Pre-alarm Enable


Low Pre-alarm Trip 60 °C 140 °F
Low Pre-alarm Return 73 °C 163 °F
Low Alarm String Flexible Sensor D Low

High Pre-alarm Enable


High Pre-alarm Return 99 °C 210 °F
High Pre-alarm Trip 111 °C 232 °F

High Alarm Enable No


Action None
High Alarm 137 °C 279 °F

High Alarm String Flexible Sensor D High

Digital Inputs
Digital Inputs

Digital
Inputs

Digital Inputs A - C
Digital Input A

Function Remote Start On Load


Polarity Close to Activate
Action
Arming
LCD Display Digital Input A
Activation Delay 0s

Digital Input B

Function User Configured


Polarity Close to Activate
Action Shutdown
Arming Always
LCD Display Digital Input B
Activation Delay 0s

Digital Input C

Function Generator Closed Auxiliary


Polarity Close to Activate
Action

about:blank 3/27/2018
8610 MKII Configuration Page 7 of 44

Arming
LCD Display Digital Input C
Activation Delay 0s

about:blank 3/27/2018
8610 MKII Configuration Page 8 of 44

Digital Inputs D - F
Digital Input D

Function User Configured


Polarity Close to Activate
Action Indication
Arming From Safety On
LCD Display Digital Input D
Activation Delay 0s

Digital Input E

Function User Configured


Polarity Close to Activate
Action Warning
Arming Never
LCD Display Digital Input E
Activation Delay 0s

Digital Input F

Function Mains Parallel Mode


Polarity Close to Activate
Action
Arming
LCD Display Digital Input F
Activation Delay 0s

about:blank 3/27/2018
8610 MKII Configuration Page 9 of 44

Digital Inputs G - I
Digital Input G

Function User Configured


Polarity Close to Activate
Action Shutdown
Arming Never
LCD Display Digital Input G
Activation Delay 0s

Digital Input H

Function User Configured


Polarity Close to Activate
Action Indication
Arming From Safety On
LCD Display Digital Input H
Activation Delay 0s

Digital Input I

Function User Configured


Polarity Close to Activate
Action Electrical Trip
Arming Never
LCD Display Digital Input I
Activation Delay 0s

about:blank 3/27/2018
8610 MKII Configuration Page 10 of 44

Digital Inputs J - L
Digital Input J

Function Duty Select


Polarity Close to Activate
Action
Arming
LCD Display Digital Input J
Activation Delay 0s

Digital Input K

Function External Panel Lock


Polarity Close to Activate
Action
Arming
LCD Display Digital Input K
Activation Delay 0s

Digital Input L

Function User Configured


Polarity Close to Activate
Action Warning
Arming Never
LCD Display Digital Input L
Activation Delay 0s

Analogue Inputs A - C
Analogue Input A (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input B (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input C (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input D
Analogue Input D (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

about:blank 3/27/2018
8610 MKII Configuration Page 11 of 44

Outputs
Digital Outputs
Relay Outputs (Supplied From Emergency Stop Input)

Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise

Relay Outputs (Volts Free)

Source Polarity
Output C (N/C) Open Gen Output Pulse De-Energise
Output D Close Gen Output Pulse Energise

Relay Outputs (DC Supply Out)

Source Polarity
Output E Common Alarm Energise
Output F Common Alarm Energise
Output G Audible Alarm Energise
Output H System In Auto Mode Energise
Output I Fuel Pump Control Energise
Output J Fuel Pump Control Energise
Output K Fuel Pump Control Energise
Output L Not Used Energise

Virtual LEDs
LED Configuration

Source Polarity
LED 1 Not Used Lit
LED 2 Not Used Lit
LED 3 Not Used Lit
LED 4 Not Used Lit
LED 5 Not Used Lit
LED 6 Not Used Lit
LED 7 Not Used Lit
LED 8 Not Used Lit
LED 9 Not Used Lit
LED 10 Not Used Lit
LED 11 Not Used Lit
LED 12 Not Used Lit
LED 13 Not Used Lit
LED 14 Not Used Lit
LED 15 Not Used Lit
LED 16 Not Used Lit
LED 17 Not Used Lit
LED 18 Not Used Lit
LED 19 Not Used Lit

about:blank 3/27/2018
8610 MKII Configuration Page 12 of 44

LED 20 Not Used Lit

about:blank 3/27/2018
8610 MKII Configuration Page 13 of 44

Timers
Start Timers
Start Delay

Remote Start Off Load 5s


Remote Start On Load 5s
Telemetry Start 5s

Start Timers

Engage Attempt 2.0s


Engage Rest 1.6s
Delay Crank 0.1s
Cranking 10s
Cranking Rest 16s
Smoke Limiting 0s
Smoke Limiting Off 0s
DPF Ramp 5.0s
Safety On Delay 10s
Warming 0s
Sensor Fail Delay 2.0s

Load/Stopping Timers
Load Timers

Transfer Time / Load Delay 0.7s


Breaker Close Pulse 1.5s
Breaker Trip Pulse 0.5s

Stopping Timers

Return Delay 30s


Cooling 1m
ETS Solenoid Hold 0s
Fail to Stop Delay 30s
Generator Transient Delay 2.5s

Module Timers
Interface Timers

Page 5m
Scroll 2s
Sleep Timer 5m

about:blank 3/27/2018
8610 MKII Configuration Page 14 of 44

Generator
Generator Options
Generator Options

Alternator Fitted Yes


Poles 4
AC System 3 Phase, 3 Wire
VT fitted No
Primary 111 V PhPh Secondary 110 V PhPh

Generator Phase Rotation

Enable Yes
Phase Rotation L1-L2-L3

Breaker Control

Enable Breaker Alarms Yes


Fail to Open Delay 1.0s
Fail to Close Delay 2.0s

Generator Voltage
Under Voltage Alarms

Alarm Yes
Action Shutdown
Trip 342V PhPh 90.0%
Pre-Alarm No
Trip 344V PhPh 90.5%

Loading Voltage

Loading Voltage 370V PhPh 97.3%


Enable Alarm Yes
Action Electrical Trip

Nominal Voltage

381V PhPh

Over Voltage Alarms

Pre-Alarm No
Return 415V PhPh 109.1%
Trip 417V PhPh 109.5%
Alarm
Trip 419V PhPh 110.0%

about:blank 3/27/2018
8610 MKII Configuration Page 15 of 44

Generator Frequency
Under Frequency Alarms

Alarm Yes
Action Shutdown
Trip 45.0 Hz 89.6%
Pre-Alarm No
Trip 45.1 Hz 89.8%

Loading Frequency

Loading Frequency 47.0 Hz 93.6%


Enable Alarm Yes
Action Electrical Trip

Nominal Frequency

50.2 Hz 100.0 %

Over Frequency Alarms

Pre-Alarm No
Return 54.0 Hz 107.6%
Trip 54.9 Hz 109.4%
Alarm Yes
Trip 57.5 Hz 114.5%

Generator Current
Generator Current

Generator
Current

Generator Current Options


Generator Current Options

CT Primary (L1,L2,L3,N) 400 A


CT Secondary 5 Amp
Full Load Rating 380 A
Earth CT Primary 400 A

about:blank 3/27/2018
8610 MKII Configuration Page 16 of 44

Generator Current Alarms


Overcurrent Alarm

Immediate Warning Yes


IDMT Alarm Yes
Trip 100 % 380 A
Time Multiplier 36
Action Electrical Trip

Negative Phase Sequence

Enable No
Action Shutdown
Trip Level 20 %
Delay 0s

Short Circuit

Enabled Yes
Action Electrical Trip
Trip 200 % 760.0 A
Time Multiplier 0.01

Earth Fault

Enable No
Action Shutdown
Trip Level 10 % 38.0 A
Time Multiplier 0.5

about:blank 3/27/2018
8610 MKII Configuration Page 17 of 44

Generator Power
Generator Rating
Generator Rating

kW Rating 220kW 267kVA


-kVAr Rating 0kVAr -1.00pf
kVAr Rating 151kVAr 0.82pf

Overload Protection
Overload Protection

Pre-Alarm Yes
Trip 109 % 239 kW
Return 98 % 215 kW
Delay 5s
Alarm Yes
Action Shutdown
Trip 110 % 242 kW
Delay 5s

Load Control
Dummy Load Control

Enable No
Outputs in Scheme 1

Trip 20 % 44 kW
Trip Delay 5s

Return 50 % 110 kW
Return Delay 5s

Load Shedding Control

Enable No
Outputs in Scheme 1
Outputs at Start 1
Trip 80 % 176 kW
Trip Delay 5s
Return 70 % 154 kW
Return Delay 5s
Transfer Time / Load Delay 0.7s

Reverse Power
Reverse Power Alarm

Enabled Yes

about:blank 3/27/2018
8610 MKII Configuration Page 18 of 44

Action Shutdown
Trip 20 kW
Delay 2.0s

Low Load
Low Load Alarm

Enabled No
Description Low Load
Trip 30 %
Delay 1m

about:blank 3/27/2018
8610 MKII Configuration Page 19 of 44

Mains Decoupling
R.O.C.O.F. Alarm

Enable No
Trip 0.13 Hz/s

Vector Shift Alarm

Enable Yes
Trip 12.0 °

Voltage Alarms

Under Voltage No
Trip 361V PhPh
Delay 0s
Over Voltage No
Trip 438V PhPh
Delay 0s

Frequency Alarms

Under Frequency No
Trip 47.0 Hz
Delay 0s
Over Frequency No
Trip 50.5 Hz
Delay 0s

Synchronising
Synchronising

Sync

Sync Options
Options

Enable Synchronising Yes

Governor

Interface Internal Analogue


Output Reversed No
Action Adjust To Nominal Frequency

AVR

Output Internal Analogue


Output Reversed No

about:blank 3/27/2018
8610 MKII Configuration Page 20 of 44

Action Adjust To Nominal Voltage

MSC Compatibility

MSC Compatibility No
P123 Ramp Enabled No
P123 Frequency Trip 0.1 Hz

Check Sync
Dead Bus

Voltage 51V PhPh 51V PhPh

Check Sync

Low Frequency -0.1 Hz


High Frequency 0.2 Hz
Voltage 3V PhPh 3V PhPh
Phase Angle 5°

Fail To Sync Alarm

Action Electrical Trip


Delay 1m

MSC Link
MSC Link

MSC Failure Action Warning


MSC Alarms Disabled Action None
Too few modules action None
Minimum modules on MSC link 1

Load Control
Load Options

Load Control Mode kW Share


Reactive Load Control Mode kVAr Share

Ramp

Ramp Speed 3.0 % %/s

Load Demand

Starting options Start all sets initially


Start next set on Warning No
Allow set to start with warning No
Balance engine hours No
Hours 167
Calling for less sets 70 %

about:blank 3/27/2018
8610 MKII Configuration Page 21 of 44

Calling for more sets 80 %

Insufficient Capacity

Action None
Delay 1s

AVR
Loss Of Excitation

Arming Active from Parallel


Pre-Alarm No
Trip 25.0 % %
Return 20.0 % %
Alarm No
Action Shutdown
Trip 35.0 % %
Delay 1s

AVR Trim Alarm

Action None
Delay 0s

Bus
Bus Settings

AC System 3 Phase, 3 Wire


Phase Rotation L1-L2-L3

Bus Phase Rotation

Enable Yes
Phase Rotation L1-L2-L3

about:blank 3/27/2018
8610 MKII Configuration Page 22 of 44

Engine
Oil Pressure
Input Type

Oil pressure is read from the ECU (ECM)

Sensor Open Circuit Alarm

Enable Alarm Open circuit alarm applies to the ECU (ECM) reading

Low Oil Pressure Alarms

Shutdown
Trip 2 Bar 200 kPa, 29.01 PSI
Pre-Alarm
Trip 2.01 Bar 201 kPa, 29.15 PSI
Return 2.99 Bar 299 kPa, 43.37 PSI

Coolant Temperature
Coolant Temperature

Coolant
Temperature

Coolant Temperature Alarm


Input Type

Engine temperature is read from the ECU (ECM)

Sensor Open Circuit Alarm

Enable Alarm Open circuit alarm applies to the ECU (ECM) reading

Low Coolant Temperature Alarms

Pre-Alarm
Trip 50 °C 122 °F
Return 75 °C 167 °F

High Coolant Temperature Alarms

Pre-Alarm
Return 96 °C 205 °F
Trip 97 °C 207 °F
Electrical Trip
Trip 98 °C 208 °F

Shutdown

Trip 99 °C 210 °F

about:blank 3/27/2018
8610 MKII Configuration Page 23 of 44

Coolant Temperature Control


Coolant Heater Control

Enable No
On 50 °C, 122 °F
Off 55 °C, 131 °F

Coolant Cooler Control

Enable No
Off 70 °C, 158 °F
On 75 °C, 167 °F

Disable when set not available No

Fan Control

Fan Overrun Delay 0s

Fuel Level
Fuel Level

Fuel Control and Monitoring


Input Type

FUEL SENSOR NEW

Fuel Pump Control

Enable Yes
On 30 %
Off 98 %

Fuel Monitoring

Fuel Tank Size 500


Litres
Logging Interval 8h
Dial Out On Logging No
SMS Enabled Yes
SMS interval every 1 logs
Stable Timer 0.5s
Change Indicating Filling 1%
Change Indicating Stable 1%

Fuel Alarms
Low Fuel Level Alarms

Alarm

about:blank 3/27/2018
8610 MKII Configuration Page 24 of 44

Action None
Trip 25 %
Delay 0s

Pre-Alarm
Trip 75 %
Return 100 %
Delay 0s

High Fuel Level Alarms

Pre-Alarm
Return 125 %
Trip 150 %
Delay 0s
Alarm
Action None
Trip 187 %
Delay 0s

Fuel Usage Alarm

Enable No
Mode Standard Mode
Action Warning Always Latched
Running Rate 10 % / Hr 10 % / Hr
Stopped Rate 10 % / Hr 10 % / Hr

Fuel Use and Efficiency


Engine Efficiency Curve

Engine Type Not used


Specific Gravity 0.89

Instrumentation Sources

Instantaneous Fuel Consumption Not Used


Trip Average Fuel Consumption Not Used
Trip Fuel Usage Not Used
Accumulated Fuel Usage Not Used
Instantaneous Efficiency Not Used
Trip Average Efficiency Not Used
Accumulated Average Efficiency Not Used
Estimate Run Time to Empty Not Used

Run Time Until Empty

about:blank 3/27/2018
8610 MKII Configuration Page 25 of 44

Fuel Tank Run Time 8h 0m 8h 0m


Fuel Tank Run Time Load Level Percentage 100 %

DEF Level
Level Alarms

Low Alarm Enable No


Action None
Trip 10 %
Delay 0s

Low Pre-alarm Enable No


Trip 30 %
Return 40 %
Delay 0s

Engine Options
ECU (ECM) Options

Engine Type Deutz EMR3


Enhanced J1939 No
Alternative Engine Speed No
Modbus Engine Comms Port RS485 Port
Disable ECM Speed Control No

Miscellaneous Options

J1939-75 Instrumentation Enable No


J1939-75 Alarms Enable No
CAN source address (instrumentation) 44

Startup Options

Start Attempts 3

Pre-heat

Enabled Yes
On 50 °C 122 °F
Duration 0s

Post-heat

Enabled Yes
On 50 °C 122 °F
Duration 0s

ECU (ECM) Options


Engine Hours

about:blank 3/27/2018
8610 MKII Configuration Page 26 of 44

Module to Record Engine Hours No

DPF Regeneration Control

Allow Non-Mission Regeneration No

Speed Switch

Enable Default Dataset ECU

ECU Wakeup

Enable No
Periodic Wakeup Time 1h
Coolant Measurement Persistence No

Engine CAN Termination

Engine CAN Termination Disable

Droop

Enable No
4.0 %

SPN Ignore List

SPN FMI
1
2
3
4
5

SPN FMI
6
7
8
9
10

Miscellaneous

CAN source address (engine messages) 3

about:blank 3/27/2018
8610 MKII Configuration Page 27 of 44

ECU (ECM) Alarms


ECU (ECM) Data Fail
ECU (ECM) Data Fail

Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s

DM1 Signals
ECU Amber

Action None
Arming Always
Activation Delay 0s

ECU Red

Action Shutdown
Arming From Safety On
Activation Delay 0s

ECU Malfunction

Action Warning
Arming Always
Activation Delay 0s

ECU Protect

Action Warning
Arming From Safety On
Activation Delay 0s

Advanced
Water In Fuel

Action Warning
Arming Always
Activation Delay 0s

DPTC Filter

Enabled Yes
Action Warning
Arming From Safety On

HEST Active

about:blank 3/27/2018
8610 MKII Configuration Page 28 of 44

Enabled Yes
Action Warning
Arming From Safety On

DEF Level

Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s

SCR Inducement

Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s

Gas Engine Options


Gas Engine Timers

Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s

Cranking
Options

Crank Disconnect on Oil Pressure


Check Oil Pressure Prior to Starting

Crank Disconnect

Generator Frequency 21.0 Hz


Engine Speed 600 RPM
Oil Pressure 2 Bar
Charge Alternator No
6.0 V DC
Generator Voltage No
322V PhPh

Manual Crank

Hold Start Button To Crank No


Manual Crank Limit 30s

Speed Sensing
Options

about:blank 3/27/2018
8610 MKII Configuration Page 29 of 44

Disable ECM Speed Sensing No


Magnetic Pickup Fitted No
Flywheel Teeth 190
Enable Multiple Engage Attempts No
Engage Attempts 2
Loss of Sensing Signal Shutdown
Disable under speed alarms if sensor fails No
Magnetic pickup open circuit Shutdown

Speed Settings
Under Speed

Alarm No
Action Shutdown
Trip 1200 RPM
Pre-Alarm No
Trip 1260 RPM
Return 1350 RPM

Over Speed

Pre-Alarm No
Return 1620 RPM
Trip 1650 RPM
Alarm
Trip 1710 RPM

Overspeed Options

Overspeed Overshoot 0 %
Overshoot Delay 0s

Plant Battery
Voltage Alarms

Under Voltage Yes


Pre-Alarm 10.0 V DC
Return 10.5 V DC
Delay 1m
Over Voltage Yes
Return 29.5 V DC
Pre-Alarm 30.0 V DC
Delay 1m

Charge Alternator Alarm

about:blank 3/27/2018
8610 MKII Configuration Page 30 of 44

Use Module for Charge Alternator No


Alarm Disabled
Trip 4.0 V DC
Delay 5s
Pre-Alarm Enabled
Trip 6.0 V DC
Delay 5s

about:blank 3/27/2018
8610 MKII Configuration Page 31 of 44

Inlet Temperature
Inlet Temperature Alarms

Alarm No
Action Shutdown
Trip 95 °C, 203 °F
Pre-Alarm No
Trip 85 °C, 185 °F
Return 80 °C, 176 °F

about:blank 3/27/2018
8610 MKII Configuration Page 32 of 44

Communications
Communications Options
Module Identification

Site Identity
Genset Identity

RS232 Port
Basic
Serial Port Configuration

Slave ID 10
Baud Rate 115200
Port Usage No Modem

Modem Settings

Alarm numbers

GSM Modem No
SMS Message centre number
SMS Recipient numbers

Send extended instrumentation No


Send as flash message No

Advanced
Initialisation Strings

Init (not auto answer) E0S7=60S0=0&S0&C1&D3


Init (auto answer) E0S7=60S0=2&S0&C1&D3
Hangup H0

Connection Settings

Master inactivity timeout 5s


Connect delay 60s
Retries 4
Retry delay 5s
Repeat cycle delay 10s
Inter-frame delay 0 ms

SMS Control
SMS Module Control

Require PIN No

PIN prefix : 0 0 0 0

about:blank 3/27/2018
8610 MKII Configuration Page 33 of 44

Enabled commands
Start off load (code 1) No
Start on load (code 2) No
Cancel (code 3) No
Stop mode (code 4) No
Auto mode (code 5) No

RS485 Ports
RS485 Port 1

Slave ID 10
Baud Rate 115200
Master inactivity timeout 5s
Inter-frame delay 0 ms

Ethernet Port
Dynamic Host Configuration Protocol

Obtain IP Address Automatically Yes

Names

Domain Name
Host Name
Vendor Name

IP Addresses

IP address
0 . 0 . 0 . 0

Subnet Mask
255 . 255 . 255 . 0

Gateway Address
0 . 0 . 0 . 0

DNS Address
0 . 0 . 0 . 0

Preferred Connection Address


0 . 0 . 0 . 0

Modbus

Modbus Port Number 502

about:blank 3/27/2018
8610 MKII Configuration Page 34 of 44

Scheduler
Exercise Scheduler

Enabled No
Run Mode Off Load
Schedule Period Weekly

Week Day Start Time Duration


Monday 00:00 00:00
Week Day Start Time Duration
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00
Monday 00:00 00:00

about:blank 3/27/2018
8610 MKII Configuration Page 35 of 44

Maintenance Alarm
Maintenance Alarm 1

Enable No
Description Maintenance Alarm 1
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Maintenance Alarm 2

Enable No
Description Maintenance Alarm 2
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Maintenance Alarm 3

Enable No
Description Maintenance Alarm 3
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

about:blank 3/27/2018
8610 MKII Configuration Page 36 of 44

Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options

Default Configuration Main Configuration

Advanced
Advanced

Advanced

Advanced Options
Protections

Disable No
Protections Are Disabled Never
Protections Disabled Alarm Action Indication
Coolant Level Protection Override Disabled

Out Of Sync

Out Of Sync Angle 16 °


Out Of Sync Timer 0.2s

Other Timers

Synchronisation Delay 3s
Dead Bus Run-on 0s
Mains Decoupling Supervision 1.0s

Dead Bus Synchronising

Enable No
Sync mode Disabled
Excitation speed 1200 RPM
Start Delay 5s
Excitation delay 5.0s
Excitation ramp time 1.5s

AVR

Allow live nominal voltage adjust


WARNING : Ensure the generator system is adequately designed to cater for voltage
adjustment.

Reset Electrical Trip


Reset Electrical Trip

Enable

Enable by Input
Enable by Front Panel

about:blank 3/27/2018
8610 MKII Configuration Page 37 of 44

Number of Resets 1
Time Period 5m
Inhibit Engine Stop

PLC
PLC Logic
PLC Functions 1-4
Function 1

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 1
Activation Delay 0s

Function 2

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 2
Activation Delay 0s

Function 3

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 3
Activation Delay 0s

Function 4

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 4
Activation Delay 0s

PLC Functions 5-8


Function 5

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always

about:blank 3/27/2018
8610 MKII Configuration Page 38 of 44

LCD Display PLC Function 5


Activation Delay 0s

Function 6

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 6
Activation Delay 0s

Function 7

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 7
Activation Delay 0s

Function 8

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 8
Activation Delay 0s

PLC Functions 9-12


Function 9

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 9
Activation Delay 0s

Function 10

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 10
Activation Delay 0s

Function 11

about:blank 3/27/2018
8610 MKII Configuration Page 39 of 44

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 11
Activation Delay 0s

Function 12

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 12
Activation Delay 0s

PLC Functions 13-16


Function 13

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 13
Activation Delay 0s

Function 14

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 14
Activation Delay 0s

Function 15

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 15
Activation Delay 0s

Function 16

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always

about:blank 3/27/2018
8610 MKII Configuration Page 40 of 44

LCD Display PLC Function 16


Activation Delay 0s

PLC Functions 17-20


Function 17

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 17
Activation Delay 0s

Function 18

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 18
Activation Delay 0s

Function 19

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 19
Activation Delay 0s

Function 20

Function User Configured


Polarity Close to Activate
Action Warning
Arming Always
LCD Display PLC Function 20
Activation Delay 0s

Module Display
Displayed Pages

Page 1 Not Used Page 5 Not Used


Page 2 Not Used Page 6 Not Used
Page 3 Not Used Page 7 Not Used
Page 4 Not Used Page 8 Not Used

Configurable Gencomm Pages


Configurable Gencomm Pages

about:blank 3/27/2018
8610 MKII Configuration Page 41 of 44

Configurable Gencomm
Pages

Page 166

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 167

about:blank 3/27/2018
8610 MKII Configuration Page 42 of 44

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 168

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1

about:blank 3/27/2018
8610 MKII Configuration Page 43 of 44

6-7 -1 70-71 -1 134-135 -1 198-199 -1


8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 169

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1

about:blank 3/27/2018
8610 MKII Configuration Page 44 of 44

12-13 -1 76-77 -1 140-141 -1 204-205 -1


14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Configurable Editor Screens
User Editable Module Parameters

Editable Item 1 Not Used


Editable Item 2 Not Used
Editable Item 3 Not Used
Editable Item 4 Not Used
Editable Item 5 Not Used
Editable Item 6 Not Used