8610 MKII Configuration Page 2 of 44
Logging Options
Data Logging
Configuration
Data Logging
about:blank 3/27/2018
8610 MKII Configuration Page 3 of 44
13 -1 1 second
14 -1 1 second
15 -1 1 second
16 -1 1 second
17 -1 1 second
18 -1 1 second
19 -1 1 second
20 -1 1 second
Options
Data Log Options
about:blank 3/27/2018
8610 MKII Configuration Page 4 of 44
Application
ECU (ECM) Options
about:blank 3/27/2018
8610 MKII Configuration Page 5 of 44
Inputs
Analogue Input Configuration
ECU (ECM) Options
Input Configuration
Analogue Inputs
Analogue Inputs
Analogue
Inputs
Flexible Sensor A
The Analogue Input is currently configured as Not Used
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor B
The Analogue Input is currently configured as Not Used
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor C
The Analogue Input is currently configured as a Fuel Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor D
Sensor Description
Input Type
VDO 120 °C
Sensor Alarms
about:blank 3/27/2018
8610 MKII Configuration Page 6 of 44
Digital Inputs
Digital Inputs
Digital
Inputs
Digital Inputs A - C
Digital Input A
Digital Input B
Digital Input C
about:blank 3/27/2018
8610 MKII Configuration Page 7 of 44
Arming
LCD Display Digital Input C
Activation Delay 0s
about:blank 3/27/2018
8610 MKII Configuration Page 8 of 44
Digital Inputs D - F
Digital Input D
Digital Input E
Digital Input F
about:blank 3/27/2018
8610 MKII Configuration Page 9 of 44
Digital Inputs G - I
Digital Input G
Digital Input H
Digital Input I
about:blank 3/27/2018
8610 MKII Configuration Page 10 of 44
Digital Inputs J - L
Digital Input J
Digital Input K
Digital Input L
Analogue Inputs A - C
Analogue Input A (Digital)
Analogue Input D
Analogue Input D (Digital)
about:blank 3/27/2018
8610 MKII Configuration Page 11 of 44
Outputs
Digital Outputs
Relay Outputs (Supplied From Emergency Stop Input)
Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise
Source Polarity
Output C (N/C) Open Gen Output Pulse De-Energise
Output D Close Gen Output Pulse Energise
Source Polarity
Output E Common Alarm Energise
Output F Common Alarm Energise
Output G Audible Alarm Energise
Output H System In Auto Mode Energise
Output I Fuel Pump Control Energise
Output J Fuel Pump Control Energise
Output K Fuel Pump Control Energise
Output L Not Used Energise
Virtual LEDs
LED Configuration
Source Polarity
LED 1 Not Used Lit
LED 2 Not Used Lit
LED 3 Not Used Lit
LED 4 Not Used Lit
LED 5 Not Used Lit
LED 6 Not Used Lit
LED 7 Not Used Lit
LED 8 Not Used Lit
LED 9 Not Used Lit
LED 10 Not Used Lit
LED 11 Not Used Lit
LED 12 Not Used Lit
LED 13 Not Used Lit
LED 14 Not Used Lit
LED 15 Not Used Lit
LED 16 Not Used Lit
LED 17 Not Used Lit
LED 18 Not Used Lit
LED 19 Not Used Lit
about:blank 3/27/2018
8610 MKII Configuration Page 12 of 44
about:blank 3/27/2018
8610 MKII Configuration Page 13 of 44
Timers
Start Timers
Start Delay
Start Timers
Load/Stopping Timers
Load Timers
Stopping Timers
Module Timers
Interface Timers
Page 5m
Scroll 2s
Sleep Timer 5m
about:blank 3/27/2018
8610 MKII Configuration Page 14 of 44
Generator
Generator Options
Generator Options
Enable Yes
Phase Rotation L1-L2-L3
Breaker Control
Generator Voltage
Under Voltage Alarms
Alarm Yes
Action Shutdown
Trip 342V PhPh 90.0%
Pre-Alarm No
Trip 344V PhPh 90.5%
Loading Voltage
Nominal Voltage
381V PhPh
Pre-Alarm No
Return 415V PhPh 109.1%
Trip 417V PhPh 109.5%
Alarm
Trip 419V PhPh 110.0%
about:blank 3/27/2018
8610 MKII Configuration Page 15 of 44
Generator Frequency
Under Frequency Alarms
Alarm Yes
Action Shutdown
Trip 45.0 Hz 89.6%
Pre-Alarm No
Trip 45.1 Hz 89.8%
Loading Frequency
Nominal Frequency
50.2 Hz 100.0 %
Pre-Alarm No
Return 54.0 Hz 107.6%
Trip 54.9 Hz 109.4%
Alarm Yes
Trip 57.5 Hz 114.5%
Generator Current
Generator Current
Generator
Current
about:blank 3/27/2018
8610 MKII Configuration Page 16 of 44
Enable No
Action Shutdown
Trip Level 20 %
Delay 0s
Short Circuit
Enabled Yes
Action Electrical Trip
Trip 200 % 760.0 A
Time Multiplier 0.01
Earth Fault
Enable No
Action Shutdown
Trip Level 10 % 38.0 A
Time Multiplier 0.5
about:blank 3/27/2018
8610 MKII Configuration Page 17 of 44
Generator Power
Generator Rating
Generator Rating
Overload Protection
Overload Protection
Pre-Alarm Yes
Trip 109 % 239 kW
Return 98 % 215 kW
Delay 5s
Alarm Yes
Action Shutdown
Trip 110 % 242 kW
Delay 5s
Load Control
Dummy Load Control
Enable No
Outputs in Scheme 1
Trip 20 % 44 kW
Trip Delay 5s
Return 50 % 110 kW
Return Delay 5s
Enable No
Outputs in Scheme 1
Outputs at Start 1
Trip 80 % 176 kW
Trip Delay 5s
Return 70 % 154 kW
Return Delay 5s
Transfer Time / Load Delay 0.7s
Reverse Power
Reverse Power Alarm
Enabled Yes
about:blank 3/27/2018
8610 MKII Configuration Page 18 of 44
Action Shutdown
Trip 20 kW
Delay 2.0s
Low Load
Low Load Alarm
Enabled No
Description Low Load
Trip 30 %
Delay 1m
about:blank 3/27/2018
8610 MKII Configuration Page 19 of 44
Mains Decoupling
R.O.C.O.F. Alarm
Enable No
Trip 0.13 Hz/s
Enable Yes
Trip 12.0 °
Voltage Alarms
Under Voltage No
Trip 361V PhPh
Delay 0s
Over Voltage No
Trip 438V PhPh
Delay 0s
Frequency Alarms
Under Frequency No
Trip 47.0 Hz
Delay 0s
Over Frequency No
Trip 50.5 Hz
Delay 0s
Synchronising
Synchronising
Sync
Sync Options
Options
Governor
AVR
about:blank 3/27/2018
8610 MKII Configuration Page 20 of 44
MSC Compatibility
MSC Compatibility No
P123 Ramp Enabled No
P123 Frequency Trip 0.1 Hz
Check Sync
Dead Bus
Check Sync
MSC Link
MSC Link
Load Control
Load Options
Ramp
Load Demand
about:blank 3/27/2018
8610 MKII Configuration Page 21 of 44
Insufficient Capacity
Action None
Delay 1s
AVR
Loss Of Excitation
Action None
Delay 0s
Bus
Bus Settings
Enable Yes
Phase Rotation L1-L2-L3
about:blank 3/27/2018
8610 MKII Configuration Page 22 of 44
Engine
Oil Pressure
Input Type
Enable Alarm Open circuit alarm applies to the ECU (ECM) reading
Shutdown
Trip 2 Bar 200 kPa, 29.01 PSI
Pre-Alarm
Trip 2.01 Bar 201 kPa, 29.15 PSI
Return 2.99 Bar 299 kPa, 43.37 PSI
Coolant Temperature
Coolant Temperature
Coolant
Temperature
Enable Alarm Open circuit alarm applies to the ECU (ECM) reading
Pre-Alarm
Trip 50 °C 122 °F
Return 75 °C 167 °F
Pre-Alarm
Return 96 °C 205 °F
Trip 97 °C 207 °F
Electrical Trip
Trip 98 °C 208 °F
Shutdown
Trip 99 °C 210 °F
about:blank 3/27/2018
8610 MKII Configuration Page 23 of 44
Enable No
On 50 °C, 122 °F
Off 55 °C, 131 °F
Enable No
Off 70 °C, 158 °F
On 75 °C, 167 °F
Fan Control
Fuel Level
Fuel Level
Enable Yes
On 30 %
Off 98 %
Fuel Monitoring
Fuel Alarms
Low Fuel Level Alarms
Alarm
about:blank 3/27/2018
8610 MKII Configuration Page 24 of 44
Action None
Trip 25 %
Delay 0s
Pre-Alarm
Trip 75 %
Return 100 %
Delay 0s
Pre-Alarm
Return 125 %
Trip 150 %
Delay 0s
Alarm
Action None
Trip 187 %
Delay 0s
Enable No
Mode Standard Mode
Action Warning Always Latched
Running Rate 10 % / Hr 10 % / Hr
Stopped Rate 10 % / Hr 10 % / Hr
Instrumentation Sources
about:blank 3/27/2018
8610 MKII Configuration Page 25 of 44
DEF Level
Level Alarms
Engine Options
ECU (ECM) Options
Miscellaneous Options
Startup Options
Start Attempts 3
Pre-heat
Enabled Yes
On 50 °C 122 °F
Duration 0s
Post-heat
Enabled Yes
On 50 °C 122 °F
Duration 0s
about:blank 3/27/2018
8610 MKII Configuration Page 26 of 44
Speed Switch
ECU Wakeup
Enable No
Periodic Wakeup Time 1h
Coolant Measurement Persistence No
Droop
Enable No
4.0 %
SPN FMI
1
2
3
4
5
SPN FMI
6
7
8
9
10
Miscellaneous
about:blank 3/27/2018
8610 MKII Configuration Page 27 of 44
Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s
DM1 Signals
ECU Amber
Action None
Arming Always
Activation Delay 0s
ECU Red
Action Shutdown
Arming From Safety On
Activation Delay 0s
ECU Malfunction
Action Warning
Arming Always
Activation Delay 0s
ECU Protect
Action Warning
Arming From Safety On
Activation Delay 0s
Advanced
Water In Fuel
Action Warning
Arming Always
Activation Delay 0s
DPTC Filter
Enabled Yes
Action Warning
Arming From Safety On
HEST Active
about:blank 3/27/2018
8610 MKII Configuration Page 28 of 44
Enabled Yes
Action Warning
Arming From Safety On
DEF Level
Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s
SCR Inducement
Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s
Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s
Cranking
Options
Crank Disconnect
Manual Crank
Speed Sensing
Options
about:blank 3/27/2018
8610 MKII Configuration Page 29 of 44
Speed Settings
Under Speed
Alarm No
Action Shutdown
Trip 1200 RPM
Pre-Alarm No
Trip 1260 RPM
Return 1350 RPM
Over Speed
Pre-Alarm No
Return 1620 RPM
Trip 1650 RPM
Alarm
Trip 1710 RPM
Overspeed Options
Overspeed Overshoot 0 %
Overshoot Delay 0s
Plant Battery
Voltage Alarms
about:blank 3/27/2018
8610 MKII Configuration Page 30 of 44
about:blank 3/27/2018
8610 MKII Configuration Page 31 of 44
Inlet Temperature
Inlet Temperature Alarms
Alarm No
Action Shutdown
Trip 95 °C, 203 °F
Pre-Alarm No
Trip 85 °C, 185 °F
Return 80 °C, 176 °F
about:blank 3/27/2018
8610 MKII Configuration Page 32 of 44
Communications
Communications Options
Module Identification
Site Identity
Genset Identity
RS232 Port
Basic
Serial Port Configuration
Slave ID 10
Baud Rate 115200
Port Usage No Modem
Modem Settings
Alarm numbers
GSM Modem No
SMS Message centre number
SMS Recipient numbers
Advanced
Initialisation Strings
Connection Settings
SMS Control
SMS Module Control
Require PIN No
PIN prefix : 0 0 0 0
about:blank 3/27/2018
8610 MKII Configuration Page 33 of 44
Enabled commands
Start off load (code 1) No
Start on load (code 2) No
Cancel (code 3) No
Stop mode (code 4) No
Auto mode (code 5) No
RS485 Ports
RS485 Port 1
Slave ID 10
Baud Rate 115200
Master inactivity timeout 5s
Inter-frame delay 0 ms
Ethernet Port
Dynamic Host Configuration Protocol
Names
Domain Name
Host Name
Vendor Name
IP Addresses
IP address
0 . 0 . 0 . 0
Subnet Mask
255 . 255 . 255 . 0
Gateway Address
0 . 0 . 0 . 0
DNS Address
0 . 0 . 0 . 0
Modbus
about:blank 3/27/2018
8610 MKII Configuration Page 34 of 44
Scheduler
Exercise Scheduler
Enabled No
Run Mode Off Load
Schedule Period Weekly
about:blank 3/27/2018
8610 MKII Configuration Page 35 of 44
Maintenance Alarm
Maintenance Alarm 1
Enable No
Description Maintenance Alarm 1
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 2
Enable No
Description Maintenance Alarm 2
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 3
Enable No
Description Maintenance Alarm 3
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
about:blank 3/27/2018
8610 MKII Configuration Page 36 of 44
Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options
Advanced
Advanced
Advanced
Advanced Options
Protections
Disable No
Protections Are Disabled Never
Protections Disabled Alarm Action Indication
Coolant Level Protection Override Disabled
Out Of Sync
Other Timers
Synchronisation Delay 3s
Dead Bus Run-on 0s
Mains Decoupling Supervision 1.0s
Enable No
Sync mode Disabled
Excitation speed 1200 RPM
Start Delay 5s
Excitation delay 5.0s
Excitation ramp time 1.5s
AVR
Enable
Enable by Input
Enable by Front Panel
about:blank 3/27/2018
8610 MKII Configuration Page 37 of 44
Number of Resets 1
Time Period 5m
Inhibit Engine Stop
PLC
PLC Logic
PLC Functions 1-4
Function 1
Function 2
Function 3
Function 4
about:blank 3/27/2018
8610 MKII Configuration Page 38 of 44
Function 6
Function 7
Function 8
Function 10
Function 11
about:blank 3/27/2018
8610 MKII Configuration Page 39 of 44
Function 12
Function 14
Function 15
Function 16
about:blank 3/27/2018
8610 MKII Configuration Page 40 of 44
Function 18
Function 19
Function 20
Module Display
Displayed Pages
about:blank 3/27/2018
8610 MKII Configuration Page 41 of 44
Configurable Gencomm
Pages
Page 166
about:blank 3/27/2018
8610 MKII Configuration Page 42 of 44
about:blank 3/27/2018
8610 MKII Configuration Page 43 of 44
about:blank 3/27/2018
8610 MKII Configuration Page 44 of 44