FP-1
Sprinkler Design Data
Project Name: System:
Occupancy: Hazard:
DATE:
Design Summary
System # System # System # System # System #
Design Method
Design Area #
5-1-06
LL
Location
Type of System
W Warren
REVISIONS:
Hazard Class
Criteria From
Design Area
Sprinkler Spacing
Density
K-factor
Hose Allowance
# Design Sprinklers
Requirement @
DESCRIPTION:
Copy of Water Test Data Included with Calculation is required
Certified pump curve required 310 WEST MARTIN ST. RALEIGH, NC 27602
Initial
Secon
-dary
Is system compliant with Chapter 23 (FPC) Is storage area layout, rack, and pile plan included?
ELEVATOR
4'
4'
4'
MACHINE
4'
STORAGE
ROOM 002
9'
9'
10' 5'-8"
2'-3
4'
001
3'8
2'
9'-2"
5'-10"
5'
12'-0"
9'-10"
MECHANICAL 004 OFFICE
003
9'-2"
10'-0"
6'-2" 13' 6'-2"
5'
4'
SPRINKLER REFLECTIVE CEILING PLAN
SCALE: NTS
1"
ELEVATOR
1" 1" 1" 1" 1" 1" CONCRETE BEAMS
MACHINE (TYPICAL)
ROOM 1" 1"
400
6 3
1" 1" 1" 1" 1"
2"
2" 103
4" 4" 4"
SPRINKLER SUPPLY UP
TO SECOND FLOOR
6" DI
4"
2" 2"
1" 1" 2
400 5
1" 1"
102
MECHANICAL OFFICE
399 1"
101
___' ___"
RISER PIPE
CLEAR
12"
CLEAR
18"
12"
CLEAR
36"
36"
36" 36"
NOTE:
APPROACH CLEARANCE
WHEN RISER IS LOCATED IN A
REQUIRED.(BOLLARDS, ETC.)
RISER CLEARANCE
NOT TO SCALE
* 80.4 *
** **
5TH FLOOR 50' ELEV.
* *
** **
4TH FLOOR 38' ELEV.
* *
** **
3RD FLOOR 26' ELEV.
* *
** **
2ND FLOOR 14' ELEV.
**
RPZ
*
**
GROUND FLOOR 2' ELEV.
* *
**
BASEMENT -8' ELEV. **
AND FLOORS. W TE
O O
FL N
4 I EF
TE EL E
O R LV
N VA
TE
5 O
N
TE 2
FIRE
O
N PUMP
Ductile Iorn underground
D/I or Galvanized pipe CONTROLLER
Presure Relief
Valve
Pressure
JOCKEY
SUPPLY Gauge
TEST GAUGE ADJACENT PUMP NOTES:
TEST
TO TEST CONNECTION CONTROLLER
VALVE HYDROSTATIC TEST ALL PIPING PER NFPA 13.
(BUT NOT OFF 2" PIPE)
PUMP TEST HEADER IS REQUIRED.
FLOW METER IS OPTIONAL.
MINIMUM 2" PIPE NOTES 1,2,4&5 SEE NFPA
TO OUTSIDE BLDG. 20, A 2-14
Control Valve
CONTRL
CLEARANCE
24"
24" 24"
FDC
24" MIN.
CLEARANCE
24"
MINIMUN
JOCKEY
PUMP CLEARANCE
TOP VIEW
FULL
SERVICE
CONTRLR
FIRE
PUMP
CONTRL
JOCKEY
FIRE PUMP
PUMP
New Extended Coverage Pendent Semi Recessed 3/4" / 155 / SSP /11.4K/ TOTAL 28 /
New Chrome Pendent Sprinkler Quick Response 1/2" / 155 / QR / 5.5K / TOTAL 10 /
QR
EXISTING PIPE
NEW PIPE
F CONCENTRIC REDUCER
G ECCENTRIC INCREASER
I ORIFICE UNION
C=80CSS?08
FIRESTOP SYSTEMS
Reproducedby HILTI, lno. C<UIesyIi
UnderwIIlarsLaboralorles,lno.
Oecermer10.2004
C=:80bS?08
FIRESTOP SYSTEMS
Reproduoadby HILn. lno.CWtesy Ii
UndarwrIlarsLaboratories.lno.
Deoambar10.2004
Page:
1of2 Page:
2of2
24" MIN.
2"
2 1/2"
8" MIN.
9 1/2" MIN.
8" MIN.
45
°
3 1/2"
48"
12" MIN.
24" MIN.
2"
4" 2 1/2"
45
°
48"
Rounded to All
Nearest Inch Thread
"A"
and Noted Rod
on Plan.
"D"
Top of Beam or Bar
Joist to Center
Line of Pipe
Pipe
"C"
END3
FITTING2
NAME NAME
MATERIAL
FITTING
MATERIAL
SIZE
SIZE
FITTING2
FITTING2
FITTING
MATERIAL
SIZE NAME MATERIAL
FITTING
FITTING2
FITTING NAME
SIZE
MATERIAL
MATERIAL
FITTING
NAME
SIZE
36" TO 42"
ABOVE
FINISHED 5" STORZ CONNECTION
GRADE
30 DEGREE FIXED (NON-SWIVEL)
W/ CAP SECURED W/ CHAIN
4"
GUARDIAN MODEL 6625 RAL (4")
MAX. MODEL 6628 RAL (6") OR EQUAL
QUARTER TURN
BALL VALVE 12"
BALL DRIP
MAX.
END1
NAME
MATERIAL
SIZE
FITTING2
FITTING
END3
NAME
MATERIAL
SIZE
FITTING2
FITTING
BALL DRIP
36" TO 42"
&
FINISHED
FINISHED GRADE Shown for clarity.
ABOVE
GRADE
QUARTER TURN
Run parallel to wall.
BALL VALVE
FINISHED GRADE
TYPICAL NOTES:
FOUNDATION WALL
FOUNDATION WALL
OR D.I. SLEEVE
2"
6" EXTEND RUBATEX INSULATION 2" PAST
LISTED FIRE
PROTECTION PIPING
2"
EXTEND SLEEVE 2"
PAST FOOTING
SLEEVE SIZE
FOOTING
2" TO TOP OF PIPE
NOTE:
2" TO BOTTOM OF PIPE
IF PIPE IS RUN UNDER FOOTING WITH NO PROTECTION
+ PIPE SIZE
MINIMUM CLEARANCE TO TOP OF PIPE IS 3'
= SLEEVE SIZE
12"
PO
NE
C
OL
ES
36"
PO
RISER #2 - IN-RACK SYSTEM
NE
C
OL
ES
HOSE VALVES (RACK AREA)
RISER #4 - DRY SYSTEM
RISER #1 - SYSTEM #4
SPRINKLER
ROOM
FIRE DEPT. CONN.
12"
FOR MAIN DRAIN
O
2" GALVANIZED 45
12" Minimum
RISER ELEVATIONS
nts
Secured in place
5/8" GWB
Secured in place
R-19 Insulation
R-19 Insulation
Blown In Type
Blown In Type
Elevator
Shunt Relay Module
Breaker
SLC
N/O
N/C
SLC
EOL N/O
N/C
Blow off
Drain
INSTALLATION REQUIREMENTS
CONDUIT
INSTALL PER
NATIONAL ELECTRIC CODE
MOUNT AUDIBLE
MOUNT ON A
& VISUAL DEVICES
APPROVED
ON APPROVED
BOX
BOXES.
AIR SUPPLY DIFFUSER OR
RETURN AIR OPENING
SMOKE/ HEAT
DETECTOR
GRAPHIC
HORN SMOKE/ HEAT
ANNUNCIATOR DETECTOR
CONTROL
PANEL
STROBE
96" MAXIMUM
TOP OF DEVICE
3'-8"
(3'-6" MINIMUM,
4'-0" MAXIMUM)
FINISHED
FLOOR
O
MAXIMUM DISTANCE BETWEEN HANGERS
T
S
NOMINAL PIPE SIZE 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 6"
BLAZEMASTER CPVC 5' 6" 6' 0" 6' 6" 7' 0" 8' 0" 9' 0" 10' 0" N/A N/A
THREADABLE LIGHTWALL N/A 12' 0" 12' 0" 12' 0" 12' 0" 12' 0" 12' 0" N/A N/A
STEEL PIPE (10/ 40) N/A 12' 0" 12' 0" 15' 0" 15' 0" 15' 0" 15' 0" 15' 0" 15' 0"
1"-22" Under Obstructed
Construction (Typical)
100 PSI STATIC PRESSURE ON SYSTEM REQUIRES UP-LIFT RESTRAINT WITHIN
12 INCHES HORIZONTALLY OF HEAD FOR ARM-OVERS AND END OF BRANCH LINE
1"Under Obstructed
Construction (Typical)
THE UNSUPPORTED LENGTH BETWEEN THE END SPRINKLER AND THE LAST HANGER
ON THE LINE SHALL NOT EXCEED 36" FOR 1" PIPE, 48" FOR 1 1/4" PIPE AND 60" FOR 1 1/2" PIPE OR LARGER
THE CUMULATIVE HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A SPRINKLER,
SPRINKLER DROP, OR SPRIG-UP SHALL NOT EXCEED 24"
(Schedule 10) 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 6"
1 FT. 6 IN. 1" 1" 1" 1" 1" 1" 1-1/4" 1-1/4"
2 FT. 0 IN. 1" 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2"
2 FT. 6 IN. 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 2"
3 FT. 0 IN. 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/2" 2"
4 FT. 0 IN. 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2" 2" 2" 2-1/2"
5 FT. 0 IN. 2" 2" 2" 2" 2" 2" 2-1/2" 2-1/2"
6 FT. 0 IN. 2" 2" 2" 2" 2" 2-1/2" 2-1/2" 3"
Correct details as required 7 FT. 0 IN. 2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3"
for each installation 8 FT. 0 IN. 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3"
9 FT. O IN. 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 4"
10 FT. 0 IN. 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 3" 4"
12" Minimum
To
FDC