Air Conditioner        Edition:2006/1/10

CAUTION
READ THIS MANUAL CAREFULLY TO
DIAGNOSE TROUBLE CORRECTLY
BEFORE OFFERING SERVICE .

SERVICE MANUAL
Air Conditioners MODEL: H2SM-(9+12)H03/R2

THIS MANUAL IS USED BY


QUALIFIED APPLIANCE
TECHNICIANS ONLY. HAIER
DOES NOT ASSUME ANY
RESPONSIBILITY FOR PROPERTY
DAMAGE OR PERSONAL INJURY
FOR IMPROPER SERVICE
PROCEDURES DONE BY ONE
UNQUALIFIED PERSON.
REVISION 0
Air Conditioner        Edition:2006/1/10

IMPORTANT INFORMATION MODEL: H2SM-(9+12)H03/R2

ƽҏFeatures
ƽҏComfortable: wide-angle airflow

ƽhealth air purifying

ƽquiet operation

ƽҏsuper energy efficient

ƽMain Specification

ƽCooling CapacityΚ 2900/3300/5800W

ƽRated Power/Current(cooling)Κ960/1020/2050W/4.6/4.8/9.0A

ƽEER: 3.02/3.23/2.82W/W

ƽHeating CapacityΚ 2800/3300/6000W

ƽRated Power/Current(heating): 900/980/1760W/4.5/4.6/8.0A

ƽCOP: 3.11/3.36/3.4

ƽAir Volume(Indoor): 400/500m3/h


ƽPower: 1PH 220-230V~ 50 Hz
Air Conditioner        Edition:2006/1/10

Safety Information
General Information
This Service Manual describes the operation,disassembly,troubleshooting,and repair of Haier Room Air
Conditioners,etc. It is intended for use by authorized servicers who troubleshoot and repair these units.
NOTE:It is assumed that users of this manual are familiar with the use of tools and equipment used to
troubleshoot and repair electrical,mechanical,and refrigeration systems;and understand the terminology
used to describe and discuss them.

Haier urges you read and follow all safety precautions and warnings contained in this manual. Failure
to comply with safety information may result in severe personal injury or death.

Related Publications
This is a base service manual,covering a range of similar models.It is intended to be used in
conjunction with the Parts Manual and Technical Sheet covering specific model being serviced.

General Precautions and Warnings

WARNING
To avoid risk of personal injury or death due to electrical shock,disconnect electrical power to unit
before attempting to service the unit.

WARNING
To avoid risk of personal injury or death due to electrical shock,DO NOT,under any circumstances,alter
the grounding plug .Air conditioner must be grounded at all times.Do not remove warning tag from power
cord.If a two-prong (non-grounding) wall receptacle is encountered,contact a qualified electrician and
have the receptacle replaced with a properly grounder wall receptacle in accordance with the National
Electrical Code.

WARNING
To avoid risk of personal injury or death due to electrical shock,grounding wires and wires colored like
grounding wires are NOT to be used as current carrying conductors.The standard accepted color coding
for ground wires is green or green with a yellow stripe.Electrical components such as the compressor
and fan motor are grounded through an individual wire attached to the electrical component and to
another part of the air conditioner.Grounding wires should not to be removed from individual components
while servicing,unless the component is to be removed and replaced.It is extremely important to replace
all removed grounding wires before completing service.

WARNING
To avoid risk of heat exposure,which may cause death or severe illness,air conditioner must be
monitored when malfunctions or shuts down.
Air Conditioner        Edition:2006/1/10

CONTENTS

1. SPECIFICATION....................................1

2. ELECTRICAL CONTROL..............................3
3. TROUBLE SHOOTING.................................27
4. INSTALLA TION....................................32 
5. CIRCUIT AND WIRING DIAGRAM.......................42
Air Conditioner        Edition:2006/1/10

SPECIFICATION

1
Air Conditioner        Edition:2006/1/10

Model˖ H2SM-(9+12)H03/R2 Brand Mark˖ -----

Cooling Capacity˖ 2900/3300/5800W Frequency Range˖ 50Hz

Rated Power/Current˖ 960/1020/2050W/9.0A Power 1PH 220-230V~ 50 Hz


Cooling
Max Power/Current˖ 2400W/12.4A --------
Model×Sectional Area˖
EER 3.02/3.23/2.82W/W Power Cord

Heating Capacity˖ 2800/3300/6000W Refer. No.˖ --------


Compressor HUARUN(09)/CRV113
Rated Power/Current˖ 900/980/1760W/8.0A
Heating manufacturer/Type MEIZHI(12)/PA118

Max Power/Current˖         2520W/13.0A Compressor


350/350ml
COP 3.11/3.36/3.40 Oil charge
Power/Current of 850g(09)
----- Type/Net Charge˖ R410A
Electric Heating˖ 1150g(12)

Additional Charge for


Operating temp. range -7OC-43OC Refrigerant 0g
exhausting air.

Charge if over Standrad


H˖ 1180 r/min 50g/m
Pipe Lenth
Indoor
Lenth×Internal/External 2.7*1.4
Velocity M˖ 1050 r/min
Capilary Diametre
0010707668
L˖ 920 r/min Refer No.˖    0010707669

H˖ 840 r/min Height of rising Indoor˖         1.30 mm


H˖ ---- r/min Outdoor˖ 1.37 mm
Outdoor radiator slice
Velocity H˖ ---- r/min Net˖ 8.8kg
Indoor Weight
Gross˖ 10.6kg

Air Net˖ 57kg


Outdoor Weight
Volume Indoor˖ 400(09)/ 500(12) 3
m /h Gross˖ 66kg
(High) Outdoor˖ 795×265×182 mm
3
----- m /h Indoor Dimension(L×W×H)˖
Capacitor of Fan Motor˖ …… Indoor Packaging Dimension(L×W×H) 865x272x330 mm

Class of electric Shock Protection ĉ Outdoor Dimension (L×W×H)˖ 810×288×680 mm

Class of Water Proof˖ IP 24 Outdoor Packaging dimension(L×W×H) 960×405×760 mm

Moisture Removal˖ 1.2/2.4×10-3m 3/h liquid /Gas pipe Diametre ij6.35/9.52 mm


Refrigerant
Remote Model: YR-H10 standard Lenth 5m
Pipe
Controller Refer. No.˖ 0010401628 Max Lenth 15 m
Remote Controller Bracket˖ ----- Lenth/Diametre of Drain Hose ----
Appearance˖ ----- Max. pressure at warm side˖ 4.15 MPa
Climate Type˖ T1 Max.pressure at cool side˖ 4.15MPa

Installation Bracket Type˖ ----- Plug Type(spec.)˖ ---


2
Area available for clooling/heating 15-23 m Ammeter spec.˖ ---
Dry/Wet ball(indoor)˖ 32℃/ 2 3 ć ć --ć
Dry/Wet ball(indoor):27  /
Max.running Max.running
Dry/Wet ball(outdoor)˖43 ć/ 26 ć Dry/Wet ball(outdoor):24℃/18℃
temperature(cooling): temperature(heating):

2
Air Conditioner        Edition:2005/11/18

ELECTRICAL CONTROL

3
Air Conditioner        Edition:2006/1/10

One. Temperature Control Function


In temperature control function, the operation frequency of outdoor unit is determined based on room
temperature and the set temperature.
In automatic fan speed mode, indoor fan is controlled based on the need of temperature control
In heating mode, indoor fan is controlled based on the temperature of coil.
1-1-1.Specification of Indoor Ambient Temperature Sensor
In case of short circuit or open circuit, indicator lamp alarms and indoor fan stops. When normal condition is resumed,
fan will automatically restart and operate normally.
Short Circuit:
o
Temperature: over 126 C, Hexadecimal System: over F8H, Resistance: below 0.65K,Voltage: over 4.85V.
Normal Temperature:
o
Temperature: 25 C, Hexadecimal System: 40H, Resistance: 23K, Voltage: 2.33V.
Open Circuit:
o
Temperature: below -31 C, Hexadecimal System: below 08H, Resistance: below 620K Voltage: below
0.15V.
o
B Parameter = 4200 R (25 C) = 23K
1-1-2 Specification of Indoor Coil Temperature Sensor
o
B Constant Number = 3700 R (25 C) = 10KΩ
1-1-3 When heating operation starts and indoor fan stops or when within 30s of indoor fan starts after
heating operation starts, the resistant of indoor ambient temperature sensor is ignored. (to avoid the
impact of heat exchanger temperature over it.)
When forced operation ends after start-up, temperature zone control begins.
1-2. Set Temperature Correction
Set temperature is corrected according to unit model, operation mode, fan speed and whether it is in
power operation.
Fan speed correction is available only during low and mid heating operation.
1-3. Temperature Zone Control
1-3-1.Error
Temperature zone error is calculated as per the following formula:
In Heating Mode: E = (Remote Control Set Temperature + Correction Value) – Indoor Temperature
In Cooling & Dehumidification Mode: E = Indoor Temperature - (Remote Control Set Temperature +
Correction Value)
1-3-2 Compressor Shutdown
E is negative and |E|>∆T
Heating Cooling
∆T TCHAHL 0.67 TCHACL 0.33
After change of ∆T TCHAHH 0.67 TCHACH 1
∆T Change Condition When operation starts E ≥ 3.0℃,
Compressor shuts down after continuous testing for 120s,
At the beginning of operation, with reference to the conditions given in above table, it operates based
on the parameters after change of ∆T until compressor shuts down for the first time. In the time period
between compressor shutdown and restart, it operates based on ∆T. (except in dehumidification mode)
Compressor starts at the beginning of operation or upon switch of operation mode (except standby ends)
or when E (error) > -∆T.
When compressor is operating, remote control set temperature is changing towards the direction of
compressor shutdown and when it is below –∆T, compressor will shut down.
1-3-3. Compressor Operation
Compressor restarts when E (error) > -△T+0.67℃ and when 3 mins standby is over.
4
Air Conditioner        Edition:2006/1/10

Two. Indoor Fan Control

2-1. Heating
2-1-1. Warm Start
Cold Air Control in Heating Mode
Heat Exchange Temperature:
THHOT3
37.0℃
THHOT2
35.2℃
THHOT1
25.2℃ 4mins
THHOTR
16℃

Stop SLO LO Set LO SLO Stop


Conduct indoor fan control as per the above diagram and the heat exchange temperature.
1. Judge wind speed when heat exchange temperature is rising:
Fan is at super low level when heat exchange temperature is below 35.2℃.(Fan will stop upon
initially energized into heating mode or after defrosting, or when heat exchange temperature is lower
than 25.2℃. Fan is at super low level when temperature is higher than 25.2℃ but lower than
35.2℃.);
Fan is at low level when heat exchange temperature is between 35.2℃ and 37℃;
Fan will operate as per setting when heat exchange temperature is above 37℃.
2. Judge wind speed when heat exchange temperature is falling:
Fan is at low level when heat exchange temperature is below 35.2℃ but above 25.2℃;
Fan is at super low level and will maintain the mode when heat exchange temperature is lower than
25.2℃(Fan is at super low level upon initially energized into heating mode or after defrosting, or
heat exchange temperature is lower than 25.2℃ but higher than 16℃; Fan will stop when heat
exchange temperature falls below 16℃.)
3. Wind speed is at super low or low level when heat exchange temperature is rising. If heat exchange
temperature fails to enter the next temperature zone after 4 mins while wind speed rises to the next
stage, it is necessary to maintain the set wind speed for 4 mins before it is adjusted based on heat
exchange temperature.
4. When heat exchange temperature is falling, wind speed will return to set speed if low wind level is
maintained for over 4 mins.
2-1-2. 3 mins standby period when compressor shutdown.
1. When compressor shuts down(temperature sensor is off), airflow is low for the initial 20s then
reduced to super low (When in silent operation, it is SSLO);
2. Wind is maintained at super low level in the standby period in heating mode(Compressor stops during
mode switch.).
3. Remote control shut down and stop indoor fan.
2-1-3. Compressor Restart
When warm start, airflow is at remote control set level.
When in automatic airflow mode, airflow is determined based on temperature.
Refers to temperature zone control functions.
2-2 Cooling
Airflow is different when airflow is set at high, mid and low level.
When in automatic airflow mode, airflow is determined as per temperature. Refers to temperature control
functions. (Refers to 2-4-8)
2-3. Dehumidification
5
Air Conditioner        Edition:2006/1/10

2-3-1. Compressor is off and is in 3 mins standby.


Fan will stop if compressor stops
Fan is at super low level upon the end of 3 mins standby.
Compressor is on after 3 mins standby.
2-3-2. Compressor is on.
When airflow is set at high, mid or low level, fan will operate as per the setting.
When in automatic airflow mode, airflow is determined as per temperature.

Three. Air Refreshing


Up reception of remote control signal, negative ion generator will start operation to emit negative ion if
fan is operating.
If fan stops, negative ion generator is off.
When negative ion generator is off, if air-refreshing feature is set and fan restarts then negative ion
generator is on.
Four. Timed Operation
Time counting will start based on the difference of timer clock and current clock.
In timed operation, display panel timer lamp is on.
4-1. Timer Off
When timer off is set, panel timer lamp is on and unit will stop operation as per the timing.
4-2. Timer On
If timer on is set, when unit is off, panel timer lamp will be on and unit will resume operation as per the
timing and in set mode.
Execution sequence is based on the setting.
Five. Sleep Operation
When remote control set sleep mode, timer lamp is on.
o
5-1. In cooling/dehumidification mode, set temperature will rise 1 C after 1 hour operation and another
o
1 C after the second hour. The unit will stop after another 6 hours.
o o
5-2. In heating mode, set temperature will fall 2 C after 1 hour and another 2 C after the second hour
o
and will rise 1 C after another 3 hours and the unit will stop after another 3 hours.
5-3 If airflow of indoor fan is high before setting sleep mode, then it will turn into mid level after sleep
mode is set. If airflow of indoor fan is mid before setting, it will turn into low level after setting. If airflow of
indoor fan is low before setting, then it will not change after setting.
Six. Automatic Operation
Automatic operation consists of two features of automatic and full automatic, which can be realized
through EEPROM selection.
6-1. Automatic Operation Mode:
On entering this mode, main control unit will decide the corresponding operation mode as per room
temperature to maintain the set temperature(Set temperature is 23℃in heating mode and 26℃ in
cooling mode.).
Upon initial startup, the unit will enter heating mode if room inlet air temperature is equal to or lower
than 23℃ or it will enter cooling mode if temperature is higher than 23℃.
When entering heating mode, the unit will operate as per heating program(set temperature is 23℃)
Upon reaching temperature where compressor stops operation, compressor will stop and standby for 3
mins. In case it detects that inlet air temperature is higher than 27℃ 15 mins after compressor stops, the
unit will enter cooling mode. Otherwise, the unit will remain in heating mode.
When entering cooling mode, the unit will operate as per cooling program(set temperature is 26℃).
Temperature difference compensation is automatically cancelled. Upon reaching temperature where
compressor stops operation, compressor will stop and standby for 3 mins. In case it detects that inlet air
temperature is equal to or lower than 23℃ 15 mins after compressor stops, the unit will enter heating
mode. Otherwise, the unit will remain in cooling mode.
If the unit changes into automatic mode from any other mode and if the operation mode is changed

6
Air Conditioner        Edition:2006/1/10

(detect before operation), the unit will stop for 3 mins and it will operate based on inlet air temperature
after 3 mins.

Seven. Trial Operation


Trial operation will end after 30 mins, after which unit shuts down. In trial operation, the unit will quit trial
operation mode upon reception of signal.
Low load protection will not start.

Constant Frequency Multi-split Unit ( Single, Double Compressors ) Low Load Protection
(Anti-freeze)Function:
Anti-freeze protection feature is available (Invalid in trial operation and heating mode):
Avoid freeze of indoor heat exchanger(in cooling and dehumidification mode)Compressor will stop
when temperature of indoor coil ≤ 0℃ and when compressor operates for over 5 mins. Compressor will
restart when temperature of indoor coil rises to over 7℃ (It must meet the needs of 3-min delay.).

In case high load protection is actuated twice within 30 mins, high load protection will alarm.
In case heat exchange temperature does not reach "THHEAT[2]", normal temperature zone control will
resume. .
Adopt the lower of either high load frequency or zone frequency as operation data.
Constant Frequency Multi-split Unit(single, double compressor)High Load Protection Control:
1. Fan Stop Protection: Indoor unit only sends A/D value to outdoor unit and outdoor unit exerts control;
2. Compressor Stop Protection:
Eight. Heating Low Temperature Treatment
In case it is unable to switch the four-way valve or in case the temperature of heat exchanger is below
"THHOTLTH"(-4.5℃)for "TMHOTLTH"(90s), compressor will stop and standby for 3 mins. Compressor
will restart when heat exchange temperature is above "THHOTLTH"(-4.5℃).
Fourteen. Communication
8-1 Communication between Indoor & Outdoor Unit
Note: This communication mode is compatible with three unit models of constant frequency
double-compressor multi-split, constant frequency single-compressor multi-split and inverter-controlled
multi-split.
8-1-1 Communication Sequence
Communication starts 2s after power is supplied. Indoor unit will send out signal first and transmission
will maintain at LO of 5ms then it starts to receive signal. In case, signal cannot be received within 2s,
another signal will be sent out. Upon reception of signal, another signal will be sent out after 10ms.
While indoor unit is waiting for signal input, its signal transmission is HI.
Error transmission occurs when indoor unit is unable to receive signal for 10 attempts (20s) after the
previous signal reception. In case of time reduction and shutdown, it is not considered as error
transmission.
Communication treatment will be engaged upon reception of correct HAD signal.
At the end of signal reception, communication data and reverse data will be compared and all the data
will be discarded in case of any error.
Outdoor unit will wait for signal from indoor HEADER HDR (81H) when power is supplied.
When sending signal, signal with header of C3H will be sent first.
During signal transmission, data"1" will output HI of 9MS and LO of 2MS, while data "0" outputs HI of
2MS and LO of 9MS.
Received signal is treated based on the majority of 5, 6 and 7MS.
Signal is only treated when correct HRD signal is received.

Nine. EEPROM Control


When outdoor unit is supplied with power, if there is any inconsistency between EEPROM parameter and

7
Air Conditioner        Edition:2006/1/10

checksum, EEPROM error.


When indoor unit receives EEPROM error signal from outdoor unit, it will display outdoor unit EEPROM error.
At this time, control and emergency operation are not acceptable.
It can only be cancelled through power off.
Ten. Error Record
There is no display when no error code record exists.
Error display mode automatically ends in 10s.
Only stop signal is accepted by remote control. Error record display mode ends corresponding to switch or
remote control stop signal.
For unit with EEPROM, record is saved when power is reset.
Eleven. Error Detect Method
11-1. Indoor Temperature Sensor Error
In operation, an error occurs if the temperature is above 126 oC or below – 31oC.
Operation will resume automatically when temperature is outside the above range.
11-2. Heat Exchange Temperature Sensor Error
In operation, an error occurs if the temperature is above 196 oC or below – 53oC.
Operation will resume automatically when temperature is outside the above range.
In error condition, low load protection is cancelled.
11-3. High Load
After high load and high limit is actuated, if the same operation recurs within 30 mins, a high load and high limit
error occurs.
11-4. Outdoor Temperature Sensor Error
On receiving error code of defrosting, air discharge temperature, base pane or outdoor temperature sensor,
indoor unit will display outdoor temperature sensor error.
Operation will resume automatically when receiving signal of removal of outdoor temperature sensor error.
In the error period, low load protection is cancelled.
11-5. Outdoor Unit Protection & Control Function
Indoor unit will display error when receives the following error codes:
Compressor Discharge Duct High Temperature Protection, DC Over Current, CT Disconnection, AC Over
Current, Power Module High Temperature Protection, Power Module Over Current Protection, Low Voltage
Protection, Outdoor Unit EEPROM Error, Compressor Operation Error.
Error conditions will be cancelled by stopping operation when outdoor unit receives 17654=0001,13=0 error
removal signal.
11-6. Transmission Error
Based on the condition of communication between indoor and outdoor unit, in case outdoor unit fails to
receive signal within 20s after indoor unit sends out signal, transmission is abnormal. (except in the period of
first 2 mins when power is supplied.). It is confirmed as transmission error when outdoor unit receive the error
signal.
Transmission error is removed by stopping operation.
Twelve. Special Function
12-1. Independent Operation of Indoor Unit
a. Entry Condition: First set remote control as heating high wind, 30oC, initial energization, press sleep key 6
times in 7s and there will be 6 sounds.
b. On entering independent operation of indoor unit, indoor unit will operate as per the following procedures:
Indoor unit will operate and communicate as per setting. Communication signal form outdoor unit will not be
treated by indoor unit while it will send signals to outdoor unit continuously.
c. Exit Condition: On receiving remote control or emergency shut down signal, it will exit independent
operation of indoor unit. Furthermore, it will exit independent operation of indoor unit after power off and power
on again. During independent operation of indoor unit, it may simulate outdoor unit and send the following

8
Air Conditioner        Edition:2006/1/10

signals to indoor unit:

12-2. Power-Off Compensation


a Entry Condition: Press sleep key 10 times in 7s and buzzer gives out 4 sounds and save the current status
into indoor unit EEPROM upon the entry.
b. On entering power-off compensation operation, indoor unit operates as per the following procedures:
Remote control emergency signal, and operates as per condition set by remote control and emergency setting
and save the current status into indoor unit EEPROM.
Main unit will operate as per condition set on panel board. And save the current status into indoor unit
EEPROM.
c. Exit Condition: Press sleep key 10 times in 7s and buzzer gives out 2 sounds
d. If timer and sleep features are set under power-off compensation condition, main unit memory is in a state
of shut-off if power is off and on again.

Thirteen. Emergency Switch


When shutdown, press emergency switch down for less than 5s, the unit will start emergency operation.
When shutdown, press emergency switch down for more than 5s but less than 10s, the unit will start trial
operation.
When shutdown, press emergency switch down for more than 10s but less than 15s, it will demonstrate
the previous error.
When shutdown, press emergency switch down, the panel will display automatic operation.
When shutdown, press emergency switch down for less than 15s, or remove hand from emergency
switch, the unit will not accept remote control signal.
Unit enters shutdown condition after 15s.
Unit can receive remote control signal after 15s.
Press emergency switch during operation, air-conditioner will shut down.,
During operation, if error occurs, press emergency switch to shut down the unit to clear error condition.
During error presentation, press emergency switch and error presentation will end.
During operation, if emergency switch is pressed continuously (press and hold) in normal or abnormal
condition (such as tact switch short circuit) or in error presentation condition, the unit can also receive
remote control signal.
Error Record Presentation Mode:
When press and hold switch for 10s it gives out 3 sounds, release switch to enter error record
presentation mode. Press and hold switch for 15s, panel display is off and error record presentation
mode is cancelled.
Previous alarm information will be sent to display panel for status display.
Error record presentation mode is cleared after 10s. (Error record presentation mode is only displayed
for 10s.)
During the presentation, no remote control signal except shutdown signal is accepted.
There is no presentation when no error occurs, only buzzer utters sound.

9
Air Conditioner        Edition:2006/1/10

1. Definition of chip tubes’ pins


Chips are used in this manual and their pins are defined as follows:
Chip’s Pins Definition of Function Chip’s Definition of Function
Pins
GND GND P37AIN5 CTA signal input
XIN XIN P36AIN4 CTB signal input
XOUT XOUT P35AIN3 tube temperature A
TEST GND P34AIN2 tube temperature B
VDD +5V P33 AIN1 Outdoor ambient temperature
P21 Alarm light P32 AIN0 P32 P31 Model selection
(to be connected with pull resistance) 0 0 Model 1
reuse for self-checking/contracting 0 1 Model 2
P22 Serial communication output P31 1 0 Model 3
(to be connected with pull resistance) 1 1 Model 4
RESET Reset P30 EEPROM--SCL
P20 4-way valve A P12 EEPROM--SDA
P00 4-way valve B P11 -INT1 Communication input A
P01 High air flowrate P10 -INTO Communication input B
P02 Mid air flowrate P07 Communication output A
P03 Low air flowrate P06 Communication output B
P04 Compressor B P05 Compressor A

2. Communication format
Note: This communication format is compatible with 3 models, i.e., double-compressor one-drive-two
without converter, single-compressor one-drive-two without converter and one-drive-two with
converter.
2.1. Sequence of communication
Communication begins 2 seconds after the power supply inputs. The indoor unit first gives out a
signal and outputs the LO which remains at 5 ms, then changes to receive signal. If it fails to
receive signal 2 seconds after the signal is given out, it will give out a signal once again. After the
signal is received, it will give out a signal once more 10 ms later. When the indoor unit is waiting
for the signal input, the signal output is HI. If the indoor unit fails to receive signals in normal
condition in times (20 seconds) after the previous signal has been received, the transmission is
abnormal. But time shortage and being halted are not of abnormal transmission. Communication is
carried out when a correct HDA signal is received. After the signal has been received, the
communication data is compared with the inverter data. When incorrect, all the data will be given
up. The outdoor unit waits to receive signal HEADER HDR(81H) from the indoor unit after the
power supply inputs. After the signal has been received, the communication data is compared with
the inverter data. When incorrect, all the data will be given up.
10
Air Conditioner        Edition:2006/1/10

The outdoor unit waits to receive signal HEADER HDR(81H) from the indoor unit after the power
supply inputs. When transmitting signal, HEADER is C3H. When a signal is first transmitted at the
head, data "1" outputs HI of 9MS and LO of 2MS and data "0" outputs HI of 2MS and LO of 9MS.
When receiving signal, the signal reception is carried out depending on the majority of the 5th, 6th
and 7th 5,6,7MS.
The signal reception will not take place until a correct HDR signal is received.

Output 1:

0:

Input 1:

0:

9ms 2ms

2.2. Checkout of errors


The signal reception does not take place until the outdoor unit receive signal HDR from the indoor
unit. At the completion of the signal reception, the data is compared with the inverter data. When
incorrect, all the data is given up. If it is incorrect in 20 seconds of comparison, the compressor,
4-way valve and outdoor fan turn off, giving the abnormal condition and sending out the
corresponding error codes for the abnormalcy of signal delivery and transmission.
2.3. Timer for communication data input /output
After the power supply inputs, the outdoor communication output is HI, waiting for the indoor unit
to send signal.
The timer counter is cleared 0 at the decline of communication, regarding 3 times of 5,6,7 ms.
The status of the communication input PORT determines input signals. When in the next decline of
communication, the timer counter is cleared one again.
HEADER 8 bits, the data and inverter data 48 bits, and the total is 56 bits. After the data has been
received, LO of 10 ms is ready to send signal. The 0 clearance of the timer counter during the
sending takes place in a 1 ms interruption.
HEADER 8 bits, the data and inverter data 48 bits, and the total is 56 bits. After the data has been
sent, Both output LO of 5 ms and output HI of 5ms are ready to receive signal 4 and
communications
11
Air Conditioner        Edition:2006/1/10

A7-6 A5-3 A2-0 C7-0 E7 E6 E5 E4 E3 E2-0


Protocol 82 3 3 8 1 1 1 1 1 3 LSB
MSB
READER Oper Not Section Heat Not Trouble Set Capa Time Abnor
ation in excha in record oper city short mal
mode use nge use ation age informa
temp. tion
HDR A B C D E F
10000001 00000000 11111111 00000000 11111111 00000000 11111111

HDR: READER indoor unit→outdoor unit 81H 10000001

Communic
ation Communication Byte Communication Content Remark
Letter
00 stop 01 cooling
A7, A6 Operation mode
10 dehumidify 11 heating
0: normal 1: trial
A5
operation
0: normal
A4 1: timer on operation in
heating
0 ordinary
A A3 1 timer on operation in
cooling
Variable
000:0 frequency: [set
001:1 temp.- room
A2A1A0 ~ temp.] section
110:6 Fixed frequency:
111:7 000: Off
Other: On
00000000: - infinite
00000001: -53℃ Indoor unit heat
C C7-0 ~ exchange
10000000: 54℃ temperature
11111111:368℃
E E7 Not in use
0: normal
E6 1: trouble record
indication
0: normal
E5
1: set operation
E4 Not in use
12
Air Conditioner        Edition:2006/1/10

0: normal
E3 1: time shortage
operation
00 double-compressor
one-drive-two without
inverter
01 single-compressor
E2 E1
one-drive-two without
inverter
10 One-drive-two with
inverter
E0 Not in use Can not be used
B,D,F: inverter data of A,C and E respectively 8 Bits each

G7-0 I7-4 I3 I21 I0 K76 K54 K3-0


Protocol 8 8 4 1 2 2 2 4 LBS
MSB
HEADER Output Error Err 3 minute Operation Oper Moni
Frequency code or standby mode ation tor
ide sign signa
ndi al l
ty
HDR G H I J K L
11000011 00000000 11111111 00000000 11111111 00000000 11111111
HDA: HEAD 8BIT outdoor unit→indoor unit C3H 11000011
Communi
Communicat
cation Communication Content Remark
ion Byte
Letter
G G7-G0 00000000:OHZ Variable frequency: output
│ frequency
11111111:255HZ

13
Air Conditioner        Edition:2006/1/10

I I7-I4 0000: compressor operation abnormal Black indicates the trouble in the
0001: normal unit with inverter
0010: discharge pipe temperature over-rise Red indicates the trouble in the
protection unit without inverter
0011: DC wave crest current Note:
0100: outdoor EEPROM abnormal 1. Outdoor AC current too high,
0101: AC wave crest current(AC current too i.e., original transformer
high) troubles A and B.
0110: not in use 2. The troubles A and B in the
0111: communication abnormal coil and transformer of previous
1000: CT disconnected outdoor units are separate. Now
1001: undervoltage protection the troubles in the outdoor coil
1010: outdoor thermistor abnormal and transformer are no longer
1011: not in use differentiated by A and B.
1100: outdoor base plate temperature
over-rise protection
1101: outdoor ambient temperature sensor in
trouble
1110: outdoor coil sensor
1111: not in use

I3 0: normal In case of 1, it indicates error.


1: error identity

I2,I1 00: data abnormal In case of 10, the air blower


01: normal control operation during
10: defrosting operation defrosting takes place.
11: not in use

I0 0: normal
1: 3 minute standby
K7,K6 00: stop 01: cooling
10: dehumidifying 11: heating
K5, 0: not double-compressor heating 1:
double-compressor heating
K4 0: normal 1: rated operation
K3 0: normal 1: abnormal operation
K K2-0 000: normal
1**: RC heating at the non-communication
side starts in the timer
*1*: RC cooling at the non-communication
side starts in the timer
**1: both units are in operation

H, J, L: inverter data of G, I and K respectively 8 bits each

14
Air Conditioner        Edition:2006/1/10

3. Single-unit cooling operation


3.1. When the single unit’s indoor unit gives a cooling signal, the corresponding outdoor
compressor carries out cooling operation. During the operation, the outdoor fan operates 1
second before the compressor operates.
3.2. When changed from heating to cooling, the compressor stands by for 3 minutes, the outdoor
fan operates to blow off remaining heat and stops 30 seconds later.
3.3. When the outdoor ambient temperature T1≥38℃, the outdoor fan runs at the high speed.
There is a return difference of 2℃ for the change between high and medium speed.
When the outdoor ambient temperature T1≤26℃, the outdoor fan runs at the low speed. There
is a return difference of 2℃ for the change between low and medium speed.
When the outdoor ambient temperature T1≤8℃, the outdoor fan is in a cycle of 1 minute stop
and 3 minute run. There is a return difference of 2℃ for the change between low speed and run
and stop.
3.4. Once the fan operates in a mode, it must operate for more than 45 seconds.
There is a temperature cut-off protection: when the indoor coil temperature higher than T_CPS (68
℃) and maintains for 10 seconds, both the compressor and outdoor fan stop. The compressor will
not restart in 3 minutes until the coil temperature lower than T_CP R(50℃). The indoor fan is
controlled the same as the thermostat is OFF.

4. Double-unit cooling operation


4.1. When the indoor unit gives out a double unit cooling signal, outdoor compressor A starts
cooling operation. During the operation, the outdoor fan runs 1 second before compressor A
operates, 20 seconds later, outdoor compressor B starts cooling operation.
4.2. Once a compressor starts, the other compressor will not start in 20 seconds from the start.
4.3. When changed from heating to cooling, the compressor stands by for 3 minutes. When both
compressors are in the strand-by status, the outdoor fan stops. Otherwise, it operates. The status
of the fan depends on the number of the compressors that operate.
4.4. When the outdoor ambient temperature T1≥30℃, the outdoor fan runs at the high speed.
There is a return difference for the change between high and medium speed;
When the outdoor ambient temperature T1≤23℃, the outdoor fan runs at the low speed. There
is a return difference for the change between low and medium speed;
When the outdoor ambient temperature T1≤5℃, the outdoor fan is in a cycle of 1 minute stop
15
Air Conditioner        Edition:2006/1/10

and 3 minute run. There is a return difference of 2℃ for the change between low speed and run
and stop.
4.5. Once the fan operates in a mode, it must operate for more than 45 seconds.
4.6. There is a temperature cut-off protection: when a indoor coil temperature higher than T_CPS
(68℃) and maintains for 10 seconds, the corresponding compressor stops. The compressor will
not restart in 3 minutes until the coil temperature lower than T_CP R(50℃). The indoor fan is
controlled the same as the thermostat is OFF.
4.7. In the case of double-unit cooling, one compressor stops and it changes to the single-unit
operation. The fan is controlled in the single-unit operation mode. It stops 30 after blowing off
the remaining heat only if both compressors turn off at the same time.

5. Single unit heating operation:


5.1. When the single unit’s indoor unit gives a heating signal, the corresponding outdoor
compressor carries out cooling operation. During the operation, the outdoor fan and 4-way valve
operate 1 second before the outdoor fan operates.
5.2. When changed from cooling to heating, the compressor stands by for 3 minutes, the outdoor
fan stops.
5.3. When the outdoor ambient temperature T1≤3℃, the outdoor fan runs at the high speed. There
is a return difference of 2℃ for the change between high and medium speed.
When the outdoor ambient temperature T1≥13℃, the outdoor fan runs at the low speed. There is a
return difference of 2℃ for the change between low and medium speed.
5.4. Once the fan operates in a mode, it must operate for more than 45 seconds.
5.5. There is a high temperature protection and a temperature cut-off protection.
High temperature protection: When the indoor coil temperature higher than T_OFS (56℃), the
outdoor fan stops; when the coil temperature falls to T_OFR (52℃), the outdoor fan restarts. The
outdoor fan stops for more than 45 seconds.
High temperature cut-off protection: When the indoor coil temperature higher than T_CPS (68℃)
and maintains for 10 seconds, both the compressor and outdoor fan stop, and the indoor fan operates
as the thermostat is Off. The compressor will not restart in 3 minutes until the coil temperature
lower than T_CP R(50℃).
6. Double-unit heating operation
6.1. When the double-unit’s indoor unit gives out a heating signal, outdoor compressor A starts
16
Air Conditioner        Edition:2006/1/10

heating operation. During the operation, outdoor compressor A and the 4-way valve operate 1
second before the fan starts, 20 seconds later, outdoor compressor B starts heating operation.
6.2. Once an outdoor compressor starts, the other compressor will not start in 20 seconds from the
start.
6.3. When changed from cooling to heating, the compressor stands by for 3 minutes. When both
compressors are in the strand-by status, the outdoor fan stops. Otherwise, it operates. The status
of the fan depends on the number of the compressors that operate.
6.4. When the outdoor ambient temperature T1≤10℃, the outdoor fan runs at the high speed.
There is a return difference for the change between high and medium speed;
When the outdoor ambient temperature T1≥20℃, the outdoor fan runs at the low speed. There
is a return difference for the change between low and medium speed.
6.5. Once a fan operates in a mode, it must operate for more than 45 seconds.

7. Cooling and heating operations take place at the same time:


7.1. When one of the indoor units gives out a cooling signal and another unit gives out a heating
signal at the same time, the outdoor fan operates at the low speed.
7.2. When the indoor unit gives the value of coil temperature, the outdoor fan runs at the low speed if
the heating outdoor unit judges high load.
7.3. When outdoor ambient temperature T1≥28℃, there is no heating operation.
7.4. When outdoor ambient temperature T1≤7℃, there is no cooling operation.
7.5. Once a compressor starts, the other compressor will not start in 20 seconds from the start.

8. Single-unit heating operation with heat load:


8.1. In the single-unit heating operation, the indoor unit gives out the value of the coil temperature,
and the outdoor unit judges whether to start in the high load protection operation based on the
value of the coil temperature it has received. If the conditions for high load protection are met, the
outdoor fan stops immediately. It will restart 45 seconds later if the signal for the outdoor heat load
disappears. Otherwise, the outdoor fan will continue to stop until the signal for the outdoor heat
load disappears. The signal for heat load is as follows:
High temperature protection: When the indoor coil temperature higher than T_OFS (56℃), the
outdoor fan stops; when the coil temperature falls to T_OFR (52℃), the outdoor fan restarts. The
outdoor fan stops for more than 45 seconds.
17
Air Conditioner        Edition:2006/1/10

High temperature cut-off protection: When the coil temperature higher than T_CPS (68℃) and
maintains for 10 seconds, both the compressor and outdoor fan stop, and the indoor fan operates as the
thermostat is Off. The compressor will not restart in 3 minutes until the coil temperature lower than
T_CP R(50℃).
8.2. In the single-unit heating operation, the current in the compressor is larger than 5.8A, and the
outdoor fan stops. 45 seconds later, the current in the compressor is less than 5.3A, and the outdoor fan
operates in normal condition(the compressor does not detect current within 30 seconds after its start),
the current in the compressor is larger than 5.3Aand less than 5.8A, and the outdoor fan does not
restore.

9. Double-unit heating operation with heat load


9.1. In the double-unit heating operation, the indoor unit gives out the value of the coil temperature,
and the outdoor unit judges whether to start in the high load protection operation based on the
value of the temperature it has received. If the conditions for high load protection are met, the
outdoor fan stops immediately. It will restart 45 seconds later if the signal for the outdoor heat load
disappears. Otherwise, the outdoor fan will continue to stop until the signal for the outdoor heat
load disappears. The signal for heat load is as follows:
High temperature protection: When the indoor coil temperature higher than T_OFS (56℃), the
outdoor fan stops; when the coil temperature falls to T_OFR (52℃), the outdoor fan restarts. The
outdoor fan stops for more than 45 seconds.
High temperature cut-off protection: When the coil temperature higher than T_CPS (68℃) and
maintains for 10 seconds, both the compressor and outdoor fan stop, and the indoor fan operates as
the thermostat is Off. The compressor will not restart in 3 minutes until the coil temperature lower
than T_CP R(50℃).
9.2. When the outdoor single-unit gives out the heat load signal, the outdoor fan stops immediately,
45 minutes later, the heat load signal disappears, and the outdoor fan operates.
9.3. In heating operation, any of the current in the compressor is larger than or equal to 5.8A , and
the outdoor fan stops. The current in the compressor is less than or equal to 5.3A, and the outdoor
fan restores (the compressor does not detect current within 30 seconds after its start), the current in
the compressor is larger than 5.3A and less than 5.8A, and the outdoor fan does not restore.

18
10. Current peak protection
Air Conditioner        Edition:2006/1/10

10.1. The current in the compressor is larger than 10 Afor more than 5 seconds, The compressor which
has the highest current will stop(the compressor does not detect current within 10 seconds after its
start) and 3 minutes later it will continue to operate.
10.2. The compressor will no longer operate if overcurrent protection occurs 4 times in a row within
30 minutes, and the output transformer signal fails. In the double-unit operation, if one of the
compressors stops due to the current too high, the other system is a single system.

11. Single-unit defrosting operation (outdoor judgement)


Defrosting control
11.1. Conditions for starting in the defrosting operation
The heating compressor starts and operate continuously for 10 minutes. After the compressor has
been operating for 45 minutes in total (the defrosting operation ends, or when starting in the
cooling mode, the compressor totals the operating time for zero clearance), detecting the
defrosting sensor TE (detecting the frosting of the outdoor heat exchanger) and the outdoor
ambient temperature sensor TA for straight 2 minutes, provided the following conditions are met,
it will start for the defrosting operation: TE≤C×TA-α
Where,

C: TA<0℃

C=0.8

TA≥0℃

C=0.6

αcan be selected according to the data of EEPROM as follows:

Selection of L M H

Jumper

α(℃) 10 8 6

In the place where it tends to frost, it is preferred to choose H. In the place where it does not intend to
frost, it is preferred to choose L. It is set M at delivery.
During the defrosting operation, the temperature control starts -15℃≤C×TA-α≤-2℃
Note: If the result of the calculation from C×TA-α is less than -15℃, -15℃ applies. If the result
of the calculation from C×TA-α is larger than -2℃, -2℃ applies.
11.2. Interval of defrosting
19
Air Conditioner        Edition:2006/1/10

When the result of the calculation from C×TA-α falls in the range of -15℃≤C×TA-α, the
interval between two defrosting operations is 45 minutes.
When the result of the calculation from C×TA-α falls in the range of C×TA-α<-15℃, the
interval between two defrosting operations is 55 minutes.
11.3. Defrosting operation
At the beginning of defrosting, the compressor is halted for the first one minute, but the outdoor fan
operates, 50 seconds later, the 4-way valve is OFF.
During the defrosting operation, such protections as the compressor’s current protection are available.
The compressor may be interrupted for its protection or due to a trouble, and restore after 3 minutes. If
it remains in the defrosting period, it will still start to defrost. The start of the compressor is made by
the rules for the start of the defrosting compressor. (if it cannot restore 3 times in a row, it will be dealt
with as in trouble and cancel defrosting.)
11.4. Once starting to defrost, the compressor must be guaranteed at least 2 minutes of operation
before canceling defrosting. As for the conditions to cancel defrosting, it will restore to the heating
operation from the defrosting operation as long as any of the following conditions is met.
(1) . The outdoor heat exchanger temperature is above 7 degrees for consecutive 80 seconds.
(2) . The outdoor heat exchanger temperature is above 5 degrees for consecutive 12 seconds.
(3) . The defrosting operation has lasted 9 minutes.
11.5. After the conditions for cancellation of defrosting are met, the following operations will follow:
The compressor stops, the outdoor fan starts, 50 seconds later, the 4-way valve is engaged, and 60
seconds later, the compressor operates.

12. Double-unit defrosting operation (outdoor judgement)


After receiving the signal to stop the indoor unit during the defrosting period, the unit must not be
turned off until the outdoor defrosting lasts more than 2 minutes.
When the double units are activated for defrosting, the activation of compressor B is 20 minutes later
than that of compressor A.
Conditions for ending defrosting: It will restore to the heating operation from the defrosting operation
as long as any of the following conditions is met.
(1) . The temperatures on both outdoor heat exchangers are above 7 degrees for consecutive 80
seconds.
(2) . The temperatures on both outdoor heat exchangers are above 5 degrees for consecutive 12
20
Air Conditioner        Edition:2006/1/10

seconds.
(3) . The defrosting operation has lasted 9 minutes.
The starting conditions and control process for the double-unit are same as that for single-unit
defrosting, the only difference is that the activation of compressor B lags that of compressor A.

13. Alarming operation


1. When the whole unit is in normal operation, the alarm light is always on, but does not flash.

2. When the outdoor temperature sensor short-circuited or disconnected, the outdoor fan always

operates at the medium speed and will restore automatically after the sensor comes to normal.
3. When the temperature sensors on the pipes A and B short-circuited or disconnected, the double

unit will not carry out defrosting operation. During heating, this signal is sent to the indoor unit,
but no sending for other operating conditions. When sent to the indoor unit, the whole unit stops.
The signal is sent to the indoor unit which coil is operating abnormally, and the corresponding
indoor unit indicates trouble.
4. When the temperature sensor short-circuited or disconnected or the current transformer fails, the

alarm light flashes in the following manner; when the current transformer fails, the signal is sent
to the indoor unit that operates abnormally, and the corresponding indoor unit indicates trouble:

21
H2SM-14/18C03/R2

Codes and Description


Code indication Outdoor led1
Description
indoor blinks times
Power timer operate
Operate heating cooling
★ ■ ■ Room temperature sensor failure --

★ □ □ Heat-exchange sensor failure --


Indoor
★ □ ★ Indoor EEPROM error ---
Malfunction
■ □ ★ Indoor fan motor malfunction --
■ ■ ★ Communication Error (between indoor and outdoor unit) 3 or 7

Outdoor outdoor EEPROM error 1


Malfunction ★ □ ■ Outdoor Senistor Error 2

outdoor unit A’s coil sensor failure 5


outdoor unit B’s coil sensor failure 9

explanation □on★flash■off

Trouble Shooting
★ ■ ■: Room temperature sensor failure CN8
★ □ □: Heat-exchange sensor failure CN8

whether terminal CN8 on NO Pull out the terminals on the indoor mainboard and
indoor PCB contact wellt? reinsert them

YES

Pull the sensor out of the mainboard


1) Measure the value of resistance Between its two
jumpers
2) Measure the temperature at the room temperature
sensing head.

Check the value of the NO


sensor to see whether the
Sensor is broken,replace it with new sensor

sensor is damaged or not?

YES

The indoor PCB is broken, replace with new indoor PCB

22
H2SM-14/18C03/R2

★ □ ★: Indoor EEPROM error: Replace the PCB of indoor unit

■ □ ★:Indoor fan motor malfunction

whether terminal CN7 YES


Pull out and reinsert the terminals
and CN11 on indoor PCB
well inserted or not?

NO

Electrify the machine again and turn it on in the cooling

operation, Measure voltage between the positions 1 ( red


wire) and 5( black wire) of Terminal CN1 on the indoor PCB

. the voltage is about NO the indoor pcb is damaged and need replace
90-200vac

Yes

NO
check whether motor the indoor motor is damaged and need
can run when replace
turn on the unit

Yes

When motor is running Measure


whether there is voltage NO
pulse(0-5VDC) between the the indoor motor is damaged and need
positions 2 (middle wire) and replace
3( black wire) of Terminal CN7
on the indoor PCB

the indoor pcb is damaged and need replace

23
H2SM-14/18C03/R2

LED1 of outdoor pcb flashes once: outdoor EEPROM error: Replace the PCB of outdoor unit,

★ □ ■
LED1of outdoor pcb flashes twice: Outdoor ambient Sensor failure CN1,

whether terminal CN1 on NO Pull out the terminals on the outdoor mainboard and
outdoor PCB contact well? reinsert them

YES

Pull the sensor out of the mainboard


3) Measure the value of resistance Between its two
jumpers

4) Measure the temperature of Outdoor ambient

Check the value of the NO


sensor to see whether the
Sensor is broken,replace it with new sensor

sensor is damaged or not?

YES

The outdoor PCB is broken, replace a new one

24
H2SM-14/18C03/R2

■ ■ ★ :Communication fault between indoor and outdoor system

Yes
Check whether the linking cable
between the indoor and outdoor Reconnect the linking cable;
is not well connected

NO

If unit A have error , please turn Yes please reverse the outdoor if A is error and B is fine, indoor
on A and B both,check whether B connecting wires A(C) and B (C) unit A PCB is damaged
is fine between unit A and B,

NO
YES
please check whether the
reconnect the L and N wires if A is fine and B has error,the
connecting of L or N is reversed of
outdoor unit main PCB is damaged
the two units

NO

YES
Check whether the LED1 the outdoor PCB is damaged
on the outdoor pcb is on

NO

check whether the voltage of NO check whether fuse of outdoor


YES reaplace the fuse with
CN7 in outdoor pcb is about
pcb is broken T3.15A 250V
198-253VAC

NO

YES check whether the wire from NO Reconnect the linking


terminal block to out pcb is well wire
connected

check whether the voltage of


NO

CN4
the transformer is bad
in outdoor pcb is about 12VAC

YES

the outdoor PCB is damaged

25
H2SM-14/18C03/R2

LED1 of outdoor pcb flashes 5 or 9 times outdoor unit A or B’s coi sensor failure CN2

whether terminal CN2 on NO Pull out the terminals on the outdoor mainboard and
outdoor PCB contact well? reinsert them

YES

Pull the sensor out of the mainboard


5) Measure the value of resistance Between its two
jumpers

6) Measure the temperature of outdoor unit A or


B’s coi

Check the value of the NO


sensor to see whether the
Sensor is broken,replace it with new sensor

sensor is damaged or not?

YES

The outdoor PCB is broken, replace a new one

26
Air Conditioner        Edition:2005/11/18

TROUBLE SHOOTING

27
Air Conditioner        2006/1/10

Trouble shooting
Before asking for service, check the following first.

Phenomenon Cause or check points


The system does not restart When unit is stopped, it won't restart
immediately. immediately until 3 minutes have elapsed
to protect the system.
When the electric plug is pulled out and
reinserted, the protection circuit will work
for 3 minutes to protect the air conditioner.

During unit operation or at stop, a swishing


or gurgling noise may be heard. At first 2-3
Noise is heard minutes after unit start, this noise is more
noticeable. (This noise is generated by
refrigerant flowing in the system.)
Normal During unit operation, a cracking noise may
Performance be heard. This noise is generated by the
inspection casing expanding or shrinking because of
temperature changes
Should there be a big noise from air flow in
unit operation, air filter may be too dirty.

This is because the system circulates smells


Smells are generated. from the interior air such as the smell of
furniture, cigarettes.
Mist or steam are blown out. During COOL or DRY operation, indoor unit
may blow out mist. This is due to the sudden
cooling of indoor air.

Does not work at all.


Is power plug inserted?
Multiple Is there a power failure?
check Is fuse blown out?

Is the air filter dirty? Normally it should be


Poor cooling
cleaned every 15 days.
Are there any obstacles before inlet and outlet?
Is temperature set correctly?
Are there some doors or windows left open?
Is there any direct sunlight through the
window during the cooling operation?(Use
curtain)
Are there too much heat sources or too many
people in the room during cooling operation?

o o
Application temp. range of air conditioner -7 C~43 C.
28
Air Conditioner        Edition:2006/1/10

Abnormality Diagnosing
Trouble Parts that may appear problems Prepared parts Applicable
Number Description
phenomenon and the Cause and tools machine
7805,transformer, piezo
Use the resistance, fuse,remote controller, 7805,transfor
remote receiver. If it can be booted by mer, fuse,
controller to using manual emergency switch, piezo
Not work with invariable
boot that indicate the power cable and resistance,
1 remote frequency
machine wiring board are electriferousˈ remote
controller split unit
and it remote controller or receiver isn’t controller,
doesn’t well˗else check whether piezo receive,avome
work resistance ,fuse and 7805 are ter
wellDŽ
Optical SCR, indoor P.C. board.
Optical SCR,
Check the 2# and 4# terminal
indoor P.C.
Outdoor block of indoor unit, if it has 220V
board ,
fan motor voltage, wiring board is normal,
Outdoor fan outdoor fan invariable
doesn’t run then check whether the optical
2 motor motor frequency
when SCR is good, replace it if it has
doesn’t work capacitor, split unit
cooling or flaw˗else check whether there are
outdoor fan
heating something wrong with connecting
motor,avomet
lineˈoutdoor fan motor capacitor
er
and coil assemblyDŽ
Optical SCRˈindoor P.C. board DŽ
Check whether indoor fan motor Optical SCRˈ
Indoor fan has 80-170V voltageˈif it hasˈ indoor P.C.
motor wiring board is normal, then check board , indoor
Indoor fan invariable
doesn’t run whether the optical SCR is good, fan motor
3 motor frequency
when replace it if it has flaw˗else check capacitor,
doesn’t work split unit
cooling or whether there are something indoor fan
heating wrong with connecting lineˈindoor motor,avomet
fan motor capacitor and coil er
assemblyDŽ
Indoor P.C. board , four-way valve
coil, body of four-way valveˈCheck Indoor P.C.
the 2# and 3# terminal block of board ,
indoor unit, if it has 220V voltage four-way valve invariable
Cooling but
4 Not heating when heating but no when cooling, coil, body of frequency
not heating
then P.C. board is abnormal; else four-way split unit
check whether four-way valve coil valve,
and the body of four-way valve are avometer
damagedDŽ

29
Air Conditioner        Edition:2006/1/10

Drain pan, drain hose. Check


Oriented
whether the indoor unit is installed
wind panel
horizontal, drain hose of indoor invariable
Indoor unit or drain drain pan,
5 unit is leveled off ,the hole is over frequency
make water pan makes drain hose
high ˈfilter and drain hose is dirty split unit
water when
and walled upǃdrain pipe is
used
underwaterDŽ
Indoor P.C. board , startup capacity
Indoor P.C.
running for compressor, overheat protector,
board , startup
indicator compressor. Check the 1# and 2#
capacity for
lights upˈ terminal block of indoor unit invariable
Compressor compressor,
6 but whether it has single AVˈif not then frequency
doesn’t work overheat
compressor examine the power relay of P.C. split unit
protector,
doesn’t board ˈelse check overheat
compressor,av
work protector, startup capacity for
ometer
compressor and compressor itself
Remote controller ǃelectrolytic
capacitor of 2500UFǃ7805ǃ
outdoor heat exchanger sensor Remote
and ambient temperature sensor. controller ,elec
The
Use temperature key of remote trolytic
running
controller to watch how much capacitor of
lamp of air
The outdoor times the timing lamp glitters and 2500UFǃ
conditioner Little split
fan motor judge what’s the trouble .If there is 7805ǃ
lights but unit of
7 and no glitter we should check the outdoor heat
the outdoor frequency
compressor terminal block to see if there is AC exchanger
fan motor conversion
don’t work voltage about 220V.Check the sensor and
and
electrolytic capacitor of 2500UF ambient
compressor
and see if there is current about temperature
don’t run
310V.Examine the output of the sensorǃ
7805 and switch transformer avometer
together with the resistance of the
sensor.
Power modelǃswitch transformerǃ
The running
compressor. Check the temperature key
lamp of air
of remote controller to watch how many
The outdoor conditioner Power modelǃ
times the timing lamp glitters and judge Little split
fan motor lights ,the switch
8 what’s the trouble. Examine the two unit of
runs but the outdoor fan transformerǃ
ends of PN to see if there is DC voltage frequency
compressor motor works, compressorǃ
about 310V.Four group DC power conversion
doesn’t run but the avometer
resource of 15V.Check the triphase coil
compressor
assembly of the compressor and see if
doesn’t work
they are the same.

30
Air Conditioner        Edition:2006/1/10

Outdoor P.C. Boardǃ4 way valve


coilǃ 4 way valve body. Examine
The air the CN204 at Outdoor P.C. Board Outdoor P.C.
conditioner and watch if there is 220V Boardǃ4way Little split
Don’t make can voltage .If there doesn’t have we valve coilǃ 4 unit of
9 heat refrigerate can judge that the P.C. Board is way valve frequency
but can’t bad. If there has, we need to bodyǃ conversion
make heat connect and check the whether the avometer.
4 way valve coil and the 4way
valve body have been damaged .
Multimeter negative generatorǃ Multimeter
indoor P.C. board ǃconnecting and negative
The inserting lines .Check if the generatorǃ The series
machine Multimeter negative generator is indoor P.C. of
10 Show error doesn’t plane and the grounding (CF) is Boardǃ frequency
code E8 work and touching well, then examine not control fixed
shows error only whether the indoor P.C. Board board ǃ cabinet
code E8 and control board have been grounding type
damaged or not but also the (CF)ǃ
connecting lines are good. avometer.
Transformerǃindoor
Transformerǃ The series
microcomputer plateǃfuse. Check
power wave of
The air if the transformer has been
filterǃindoor frequency
11 Can’t start conditioner burned. power wave filterǃ
microcompute fixed
can’t start LX102.Check whether the fuse
r plateǃfuseǃ cabinet
and indoor microcomputer plate
avometer. type
have been damaged.
The system pressureǃoutdoor P.C.
BoardǃPower source voltageǃ
When the
power modelǃthe connecting lines
air
of compressor. The cause is that
conditioner
protective action has been taken outdoor P.C. The
has run
when it runs with large burden, BoardǃPower machine of
Show error about
12 there is more refrigerant than it source frequency
code F11 5minutes
should be .Examine the outdoor voltageǃpower conversion
the indoor
P.C. BoardǃPower source voltageǃ model . split unit
unit shows
power model and see whether they
the error
have been damaged and the
code F11.
connecting lines touch well, if not,
adjust it to be normal.

31
Air Conditioner        Edition:2005/11/18

INSTALLATION

32
Air Conditioner        Edition:2006/1/10

12

12 15

33
Air Conditioner        Edition:2006/1/10

3/8

34
Air Conditioner        Edition:2006/1/10

35
Air Conditioner        Edition:2006/1/10

36
Air Conditioner        Edition:2006/1/10

WHT
1(L) 2(N)

YEL/GRN
BLK
RED
3

3(R)
2

BLK
1

RED YEL/GRN
WHT
WHT
1(L) 2(N)

Indoor unit A YEL/GRN


BLK
RED
3

3(R)
2

BLK
1

RED YEL/GRN
WHT BRN

{
1(L) 2(N)

Indoor unit B
POWER

BLU

YEL/GRN

Outdoor unit

37

5
Air Conditioner        Edition:2006/1/10

38
Air Conditioner        Edition:2006/1/10

9.52
3/8

9.52
3/8

3.The purging Method of the indoor unit B is the same as the indoor unit A.
The unit A and unit B are seperated and disconnected connected for the different compress.

39
Air Conditioner        Edition:2006/1/10

Flare tool for R410A Conventional flare tool


Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)
1.Cut pipe 2.Remove burs
0~0.5mm 1.0~1.5mm 1.5~2.0mm

3.Insert the flare nut

4.Flare pipe

40
Air Conditioner        Edition:2006/1/10

41
Air Conditioner        Edition:2005/11/18

CIRCUIT AND WIRING DIAGRAM

42
H2SM-14/18C03/R2

1 2 3 4 5 6 7 8

+5 +5
BEEP-PKM13EPY-4002

BUZ1 C29
+12v 104/50v R15
10k
R16
10k
R65
R11
10k
10K R17
R49 10k
1N4007
R13 10K R12 100 +5 IC9 +12
D D1-D4 CN3 CN2 FUSE D
Q11 D5
10K R18 7805 3.15A CN4
+5 Q5 104/275V 561K
Q4 2SC2412 C36 4.7k E15 IN4007
C17
2SC2412 C35
2SC2412 104 E8
2 R27 10K 103/50v 470UF/16V
104
2200UF/25V
CN9 1 R66 27 Q1
2SC2412 +12
R30
C12 T1 C40 Z1
10K 102 E9
+12V R59 C42 0-171825-3 RTB-1.5-2P B2P3-VH-A
4.7K 104/50V
R31 100u/25v
10K
+5
+5
R41 1K 02 IRQ VDD 22

R28 1K R9 4.7K 07 C28 E4


C5 102 PTF3/TBCH3 C18 E5 104/50V 100u/16v
Q2 11 104/50V 100u/16v
2SC2412 12
PTF5
PTF6 +5 CN8
48 PTH1/KBD3 36 R45 1K 1
SW1 +5V +5 R29 10K 49 PTB2/ATD2 37
2
R2 10K R54 PTH1/KBD4 PTB3/ATD3 3
680 Q8 R5 10K 08 R44 1K 4
R3 1K 2SB1197 PTF4/TBCH0 C10 C9 R34 E7 4.7UF/50V
102 102 20K 1%
C1 3.3K E6 4.7UF/50V
03 RST C41 R35 3.3K 1% CN5
C 102 C
R43 R51 PTF0/TACH2 04 102
R52 C13 21 R53 1K 1
3.3K 10K VSS GND PTC1 61 R88 560 2
104 45 PTC5 64
AVSS/VRE GND R69 10K 3
56 PTC3 63 R68 10K 4 61 C38
VSSA GND PTC2/MCLK 62
PTD7 53
R67 10K 5 102/50V
60
PTD6/TACLK 52
R70 560
R71 560
+5V 6
7
53 C25
PTC0 PTD5 51 R72 560 102/50V
10 OSC1 59 SJ20-07WX C27

1
R10 10K C2 104 PTF7 +5V 52
+5
57 C47 E13
102/50V
CGMXFC XT1 +5
C26
+5V 09 R1 C4 C3 R87 104/50V 100u/25v 51

+5V R37 10K NC 1M 103 102/50V


R50 51K 8M 10K 1/4W
104
+5 R36 1K 58
4 OSC2 R82 R81
1 R14 1K 13

2
3 PTE0/TXD 55
CN7 2
CN6 2 14 PTE1/RXD VREFH 54 330 1/4W 330K 1/4W
3 VDDA +5 6 D8
C43 C16 1 Q9 1 5 1N4007
103 102 19 C22 2SC2412 1
15 PTE6/MOSI R85 2.2K 1/4W
PTE2/TACH0 102 R86 2 4 CON5
1N4007
+5V
R40 10K 25 PTG2/KBD2 PTE7/SPSCK20 10K 1/4W D6
IC14
R4 4.7K 16 06 TLP371
17 PTE3/TACH1 PTF2/TBCH2 05 R80
220V-L
+5V R38 10K PTE4/SS PTF1/TACH3 +5
Q3 R39 4.7K 18 PTE5/MISO VDDAREF 44 R47 560 1/4W 2.2k 1/4W
C39
220V-N 23
PTG0/KBD0 4
IC12 1
B CN1 2SC2412 R64 10K 24 PTG1/KBD1
PTD3 47 +5 B
2UF 450V +5
PTD2 46 103/50VC49 R83
1 IC10 +5V R93 35 PTB1/ATD1 PTD1 43 3 2
2
R42 C24 10K PTD0 42 C6 C7 TLP421 2.2K
N
3 R57 PTB7/ATD7 41

103/50V

104/50V
220

1
+5 PTD6/ATD6 40 LED1
120 1W 0.01u/275V R21 10K PTB5/ATD5 39
TLP3526 R20 10K R84 6.8K 2W
L1 26 +5
PA0 01
125uH 27 PA1 PTC4

R97
R95
R96
R98
R33
R73 R58 10K +5V GREEN

R6
28 PA2 R24 R7 10K
SW3 10K 29 10K
PA3 R8 10K
5v
D 30 R46
R26
10K
IC2
Q10 31 PA4 5 4
R91 C PA5 5v SDA

10K
10K
10K
10K
10K
10K
B 32 1K C14 6 3
4.7K 33 PA6 C15 104 7
SCL
2
A
PA7 102 5v SW2 8 24C02 1
R89 22K 38 PTB4
8
7
6
5
4
3
2
1

2SC2412 50 PTD4
ZJ1

2
1
34
C19 IC4 PTB0/ATD0
2003
+12
104 MC68HC908AB32 R92
R25 10K
R32 +12 CON1(red)
9
10
11
12
13
14
15
16

10K 10K 1

A A
D7 RL1

220V-N
JQ1A-12V
RLS4148 CON2(white)
1
.
CN13
5
4
3
2
1

1 2 3 4 5 6 7 8

43
Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM

44
38
Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM

W:

45
Air Conditioner        Edition:2006/1/10

Sincere Forever

Haier Group
Haier Industrial Park, No.1, Haier Road

266101, Qingdao, China

http://www.haier.com