Professional Documents
Culture Documents
Cooling Tower
Cooling Tower
INTRODUCTION
Treatment programs have been applied to cooling
water systems for many years. The treatment program
contains active components (“actives”) that serve to
minimize performance problems, such as scaling, cor-
rosion, fouling, and microbiological growth. Table 1
lists a variety of treatment actives and their func-
tions.1–6 The control of treatment programs is impor-
tant to ensure that the desired amount of actives is
present. A previous paper discussed using an inert
tracer within the treatment program to control the
product dosage to the cooling water system.7 Using
Figure 1 — Generalized representation depicting the
an inert tracer, the amount of product added to the correlation between performance problems and
cooling system is accurately known; however, this does treatment actives consumption (as scale/deposits
not insure that, under stressed conditions, system form due to high stress conditions).
problems will not occur. If the correct amount of prod-
uct has been fed and active residual levels are low, it is and adsorbing onto solids/surfaces in the system,
likely that the system has responded to a stress.1–6,10–13 thereby acting to prevent growth of scale/deposits and
This also provides an opportunity to take corrective enhancing performance of corrosion inhibitors (Fig-
action to reduce the system stress or modify the treat- ure 1).10 In the process of preventing scale/deposits/
ment program. corrosion, a limited amount of scale inhibitor con-
Scale inhibitors are pivotal to the performance of sumption will naturally occur [Table 2 (“Normal” col-
many treatment programs.8–9 Scale inhibitors function umn) and Figure 1(left half)].1–6 As scale/deposits form
by adsorbing onto suspended solids/scaling particles
2
Table 3 — Operating conditions for pilot cooling Table 4 — Composition of make-up waters used in pilot
tower tests cooling tower testing
3
methods have suffered from one or more of the fol-
lowing problems:18–21
(1) complicated methods requiring separation, extrac-
tion, and/or adsorption/washing to remove the
polymer from the sample matrix
(2) complicated analysis methods with long time
period for development of test response (e.g.,
15 minutes for Hyamine turbidity test)
(3) interferences that give false-positive response
(indicating polymer is present at a significant
level, when it is not)
(4) subjective analysis based on visual comparisons
Figure 3 — Water analyses from a PCT test using an (5) limited dynamic range of polymer levels that re-
All-Organic program; standard make-up water, 2-5 quire extra steps for sample dilution or prepara-
cycles of concentration, 35°C return temperature. tion to measure low or high dosages
Polymer consumption is related to the Mg-Ca
concentration cycle split (PCT Test 5). (6) complicated statistical analysis and equipment
calibration procedures that require extensive
number of samples to help reduce interferences
tion, this represents 24% of the total HEDP in the
bulk water. However, only a very small percentage of In order to address all of these needs, a new active
calcium (0.8%) and alkalinity (1.2%) from the bulk polymer test method has been developed for measure-
water would be consumed during the formation of that ment of polymeric scale inhibitors/ dispersants in
same deposit. Based on the magnitude of these water systems.22–25 The new analysis method is used
changes, measurement of HEDP or polymer consump- for grab sample testing and can be measured by fluo-
tion is analytically more feasible than measurement rescence or colorimetric techniques. The new active
of calcium or alkalinity consumption. This also indi- polymer test method (grab samples) also complements
cates that consumption of the actives is a sensitive the on-line monitoring/control capabilities of a new
indicator of the formation of deposits. generation of fluorescent tagged polymers, which are
subsequently described in this paper. The new active
In PCT Test 5 (an All-Organic treatment program at
polymer test method addresses application needs on
pH 9), the conductivity was increased incrementally,
the lower-half of the diagram describing system moni-
thus increasing the concentration cycles. Magnesium
toring/control hierarchy (Figure 4), whereas the new
cycles remained at theoretical levels, but calcium pre-
generation of fluorescent tagged polymers addresses
cipitated. Results in Figure 3 show the loss of dis-
needs in the upper-half of Figure 4.
persant polymer as calcium carbonate precipitates.
The X-axis is “Delta Cycles” or “Cycle Splits”, defined The new active polymer test method utilizes the fol-
as the difference in Mg and Ca concentration cycles. lowing grab-sample analysis procedure:
The farther out of balance the program operates, the
(1) specified amount of dye/buffer reagent is added
greater the actives consumption. Thus if we can mea-
to cuvette
sure the actives consumption and provide a corrective
action to the system, we should be able to improve
performance of the cooling water system.
Continuous direct control
➞
analysis of treatment actives can lead to serious mis- Regular testing/Data collection/Manual adjustment
interpretation and response to system stresses and
performance problems. Historically, it has been very Irregular testing frequency/Limited data collection/Irregular adjustment
difficult to provide an accurate, general analysis of
polymeric dispersants.17 Existing polymer analysis Figure 4 — Hierarchy of treatment dosage monitoring/
control
4
(2) defined amount (1 mL) of filtered water sample is in specific applications by changing the ratio of re-
added to reagent solution agent solution to water sample. This new polymer
analysis test provides very linear/predictable re-
(3) after 30 seconds, sample is analyzed (colorimetric
sponse (Figure 5) throughout the 0–20 ppm dosage
or fluorescence methods)
range. The high ppm dosage range can be extended
(4) analyzer readout indicates ppm dosage of active or a high-resolution low polymer dosage can be de-
polymer termined by changing the ratio of reagent solution
volume to water sample volume. Chemical compat-
Polymer consumption and treatment product dosage
ibility guidelines for this new method are listed in
are obtained from inert tracer reading/treatment com-
Table 7. A more extensive list of application guide-
position and comparing those results with active poly-
lines has also been published.
mer remaining in the system (step 4).
Application guidelines (dissolved ions and operating
conditions) for the new active polymer test method is CASE HISTORY
listed in Table 7.22–24 These guidelines can be extended A North American refinery cooling water system was
experiencing high-stress operating conditions due to
very high temperature heat-exchangers. The treat-
Table 7 — Chemical compatibility guidelines for new
active polymer test
ment product was a Stabilized-Phosphate type pro-
gram. Although the treatment program worked in
Preferred Analysis most of the cooling water system, deposit formation
Range *,** was occurring in the high-temperature exchangers.
Alkalinity (HCO3– as CaCO3) 0 – 1,800 mg/L Polymeric dispersant consumption averaged 72%
Calcium (as CaCO3) 0 – 1,700 mg/L (Figure 6), which corresponded to heat exchanger
fouling that was confirmed by visual inspections.
Conductivity 0 – 6,000 µS/cm
Polymer consumption was determined from the poly-
Iron (soluble, as Fe) 0 – 90 mg/L mer dosage added (from inert tracer readings) and
Magnesium (as CaCO3) 0 – 1,700 mg/L the level of active polymer remaining (using the new
Manganese (as Mn) 0 – 860 mg/L Active Polymer Test).
Orthophosphate (as PO4) 0 – 2,100 mg/L A new treatment program was implemented, which
pH 4.5 – 11 included a high-stress polymeric dispersant capable
of operating effectively under high-temperature con-
Silicate (as SiO2) 0 – 530 mg/L
ditions. The polymeric dispersant consumption was
Sodium (as Na) 0 – 2,000 mg/L dramatically reduced (72% –>10%) upon implemen-
Sulfate (as SO4) 0 – 1,700 mg/L tation of the new treatment program, as shown in
Turbidity 0 – 120 NTU Figure 6. The reduction in polymer consumption also
correlated to a significantly reduced level of fouling
**Upper limit of operating range is based on the concentration of in the high-stress heat exchangers.
chemical species required to produce a 10% change in response
of analysis method (using reference dosage of 10 ppm polymer
actives).
** Adjusting ratio of reagent:water sample can be used to extend
upper limit of these guidelines
5
Overall benefits of the high-stress polymer program 2. The polymer must fluoresce in the visible wave-
and the new Active Polymer Test are as follows: length region (λex >370 nm, λem >420 nm) and
the fluorescence of the polymer must be not
• 3-fold increase in active polymer level for a com-
interfere with inert fluorescent tracers.
parable level of polymer added to the system
3. The polymer must be stable to oxidizing biocides
• Reduced % polymer consumption correlates with
at pH between 6.5 and 9, but at least above pH 8.0.
improved results in high-stress exchangers
4. The polymer must have stable fluorescence over
• % polymer consumption can be used as a very valu-
the pH range 6.5 – 9.5.
able indicator of system performance and to opti-
mize system operation 5. The polymer must be stable in cooling water sys-
tems for at least 24 hrs. (hydrolytic stability, ther-
• High-stress polymer program allowed only a light
mal stability to 70°C).
dusting of easy-to-remove powder to form in high-
stress exchangers 6. The fluorescence of the polymer should be free of
interferences under standard cooling water con-
• Significantly improved results were obtained even
ditions (i.e., Ca, Mg, alkalinity, etc.).
though cycles increased from 3.2 –>5.7 (and hold-
ing time increased) 7. The polymer must be capable of being formulated
in products. Some cooling water products are for-
• % polymer consumption increased as short-term
mulated at low pH (1 – 2), while other products
operating stresses increased (hydrocarbon leak and
are formulated at high pH (13).
reduced level of polymer added)
8. The polymer should be photostable and when for-
Even with doubling the concentration cycles, a hydro-
mulated in products have no undesirable color.
carbon leak and 18% reduction in the level of poly-
mer actives added, the high-stress polymer program 9. Unreacted fluorescent starting material and any
had better performance and much lower polymer con- small molecule fluorescent by-products must have
sumption (<1/2 of polymer consumption in original distinct fluorescence properties from the fluores-
treatment program). Use of the Active Polymer Test cent polymer.
method made corroboration of these results easy,
10. The polymer must meet all safety and environ-
quick, and accurate. The use of % polymer consump-
mental regulations.
tion also provides a means to quickly confirm if im-
provements made in the system are being maintained Two general approaches for the synthesis of a fluo-
over long time periods. rescent polymer were considered in the development
of new fluorescent water-soluble polymers (Figure 7).
USE OF FLUORESCENT POLYMERS • Modification of an existing polymer with a fluores-
cent dye after polymerization. This is the method
The new Active Polymer test method provides an easy,
by which an existing tagged polymer is prepared.3
quick and accurate method to determine polymer con-
sumption. However, the current method was not • Polymerization of the polymer with a small amount
developed to be an on-line method. In order to use of a fluorescent monomer.
polymer consumption as a way to continuously con-
Both methods have been used to prepare fluorescent-
trol a cooling water system, the method must be on-
tagged polymers. However, in order to prepare a fluo-
line. Although it would be possible to automate the
rescent polymer with fluorescence in the visible or
Active Polymer test method, the use of a fluorescent
near visible wavelength region (λex >370 nm), the
water-soluble polymer was chosen. The development
use of a fluorescent monomer has been more success-
of fluorescent water-soluble polymers for use in cool-
ful. The polymers used in these studies have been
ing water systems is known.3,26,27 However, previously
prepared with fluorescent monomers and meet the
available fluorescent water-soluble polymers did not
requirements given above. In testing a variety of fluo-
meet all the requirements given below.
rescent polymers, a number of the requirements given
1. The fluorescent polymer should be similar in struc- above are worth mention. First, the fluorescent poly-
ture and activity to existing polymers used in cool- mer should be similar in activity to the existing dis-
ing water systems, since it will replace the current persant polymers used in cooling water systems, since
untagged polymer in cooling water products. The they will be replacing the existing dispersants. In bench
fluorescence of the polymer must be correlated with testing of calcium phosphate dispersancy, tagged dis-
activity. persant polymers were equal to the untagged versions
of the dispersant polymer.
6
Postmodification of Existing Polymer
( CH2–CH )x ( CH2–CH )y + z NH2 ⇒ ( CH2–CH )x' ( CH2–CH )y' ( CH2–CH )z'
C=O C=O C=O C=O C=O
F
OH NH2 OH NH2 NH
Another important requirement was that the poly- forming scale. This is referred to as a concentration
mer needed to have an excitation wavelength above cycle split. To use concentration cycle splits reliably,
370 nm. This made the use of solid-state light-emit- Ca and Mg analyses must be performed on both the
ting diodes (LEDs) and photodiodes possible, thus tower water and the make-up water, for a total of
decreasing the size while increasing the functional- four analyses for each point in time.
ity of the measurement instrumentation. Thus, the
Concentration cycle splits cannot be accurately used
same type of instrumentation described in a previous
if any of the following conditions occur:
paper can be used with these new fluorescent poly-
mers. This was a substantial improvement over • If magnesium silicate formation occurs;
existing fluorescent dispersant polymers.3,26,27
• If the make-up water is variable or there are mul-
Finally, any loss of the fluorescence of the fluores- tiple sources of make-up water;
cent polymer must be related to its activity. Specifi-
• If there are interconnected systems;
cally, laboratory testing showed that pH, oxidizing
biocides or other species present in a cooling water • If there are interferences with the analysis of Ca
system did not affect the fluorescence of the polymer. or Mg; and/or
• If extra Ca is added to the system to increase
METHODS USED TO MONITOR SCALE hardness.
For several years, consumption has been discussed If any of the above circumstances occur, the use of
in relation to the performance of the cooling water concentration cycle splits will not provide meaningful
system.3,13 We believe that the consumption of treat- information on scaling in the cooling water system.
ment actives actually “PRE-cedes” the formation of
In addition, it is not possible to measure Ca and Mg
deposits, and allows one to “PRE-act” by changing
on-line with enough accuracy and precision using
the system operating conditions in order to “PRE-vent”
current technology. Thus, analyses must be done off-
serious performance problems. The increase in poly-
line using grab samples. There will always be a sig-
mer consumption with increasing concentration cycles
nificant lag time between the sampling and analysis
has been demonstrated.3 In addition, polymer con-
time, which could cause difficulties in situations
sumption and fouling monitor friction factors were
where conditions change rapidly. Finally, the analy-
shown to increase in a case history from a chemical
sis of Ca and Mg must be accurate and precise, which
processing plant.3 However, additional experimental
requires analytical laboratory analysis. Because of
information was desirable to determine how the poly-
the time-consuming nature of performing four analy-
mer consumption is related to commonly used methods to
ses, and the need for accuracy and precision, this is
determine the onset of scaling events.
an approach that is best suited for laboratory use.
Several methods are commonly used to determine if
A second method that is useful to show that scaling
scaling is occurring. In All-Organic Programs, which
is occurring is measurement of filtered and unfiltered
consist of organophosphonates, copper corrosion in-
total phosphate, orthophosphate or zinc. This method
hibitors and polymeric dispersants, the difference
is used in stabilized phosphate, alkaline phosphate
between magnesium concentration cycles and calcium
and zinc-containing treatment programs. Again, as
concentration cycles is a good method to determine if
with concentration cycle splits, analytical methods
calcium-containing species are precipitating and
7
Figure 8 — Comparison of scale onset as determined Figure 9 — Comparison of scale onset as determined
by concentration cycle splits and heat transfer by concentration cycle splits and polymer con-
resistance. Data from a Pilot Cooling Tower test using sumption. Data from a Pilot Cooling Tower test using
an All-Organic program; standard make-up water, an All-Organic program; standard make-up water,
2-5 cycles of concentration. (PCT Test 6) 2-5 cycles of concentration. (PCT Test 6)
8
% Polymer Consumption = Table 8 — Potential limitations of using conductivity
for control of cycles of concentration in cooling water
Product Dosage (from Inert Tracer) – Fluorescent Polymer systems
Product Dosage (from Inert Tracer) • No direct measure of scaling tendency
x 100 (higher conductivity can occur at lower scaling
tendency and vice versa)
As shown in Figure 9, the % polymer consumption
and the concentration cycle splits (based on Ca and • No direct measure that scaling is occurring
Mg measurements in the make-up and recirculating • Conductivity signal is temperature dependent
water), track each other very well. Thus, % polymer (temperature coefficient (1-2%/°F or more)
consumption can be used as an early indicator that • Temperature coefficient varies based on changes in
PRE-cedes the onset of scaling in a cooling water sys- water composition
tem. Additionally, as the % polymer consumption is
determined on-line, it can be used in advanced con- • Fouling of electrodes affects results
trol strategies to help prevent problems from occur- • Changes in make-up water composition affects
ring. Polymer consumption actually can be a more accuracy of cycles control
sensitive/reliable performance indicator than concen- • Multiple make-up sources, process leaks, and pH
tration cycle splits because polymer consumption can control acid feed can interfere with accurate measure-
be measured continuously on-line, requires fewer ment of cycles
measurements, and does not require a high level of
consistency in the concentration cycle levels in the • “Cycles of conductivity” often does not equal “cycles
make-up water. As shown in Figure 9, the polymer of concentration” of dissolved ions (individual or total)
consumption consistently trends upward (an indicator based on interferences listed above
of increase in scaling), before it is clear from the • Can fail destructively (scaling causes reduced con-
concentration cycle splits (because there is more ductivity, which causes system to further concentrate
statistical variability) that a change is occurring. So and cause more scaling)
polymer consumption and concentration cycle splits • Conductivity control is often run much lower than
are a much more direct indicator of scaling processes optimum – which leads to inefficient cost/performance
than fouling simulators (e.g., fouling monitor). Since system operation
polymer consumption measurements can be done con-
tinuously on-line with an inert fluorescence tracer and
tagged polymer, this method offers the unique advan- system using conductivity control may be run ineffi-
tage of providing an immediate response to system ciently or still be subject to scaling even if conductiv-
changes. ity is tightly controlled and the conductivity meter
well maintained.
Use of Conductivity to Control Blowdown — The
previous results that measuring on-line polymer con- For example, if the make-up water quality is vari-
sumption provides an excellent warning indicator for able (or any of the other limiting conditions listed in
the onset of scaling. Polymer consumption can also Table 8 apply), conductivity does not provide as good
be used to gauge the magnitude of scaling and to a representation regarding concentration cycles of the
determine that corrective actions have eliminated the cooling tower. Two specific examples of make-up wa-
problem. Beyond basic system characterization and ter upsets are: (1a-b) increase/decrease in overall con-
problem-solving, the next step is to provide a higher ductivity or (2) change in composition of the dissolved
level of system control compared to other methods ions. If conductivity control were used under those
(e.g., conductivity) using polymer consumption. conditions, several possible outcomes can occur:
In cooling water systems utilizing All-Organic pro- 1a. Assume that make-up water conductivity is
grams (without pH control), the main control methods 600 µS/cm and that conductivity control is used for
used to prevent scaling are treatment product dos- setpoint control of blowdown control at 2400 µS/cm
age and adjusting concentration cycles through (4 X make-up water conductivity). If the make-
blowdown. Concentration cycle adjustment has his- up water conductivity increases from 600 µS/cm
torically been done (sometimes indirectly) using con- to 1100 µS/cm, then blowdown control will be acti-
ductivity. Some of the limitations of using conductiv- vated much sooner (at 2.2 X make-up water con-
ity for cycles control are listed in Table 8. Even if the ductivity). This will result in larger amounts of
recirculating cooling water/make-up water systems make-up water being used, result in more treated
are not impacted by one or more of these limitations, cooling water being discharged from the system,
conductivity does not directly measure scaling pro- and result in inefficient operation and still does
cesses or the scaling tendency of the water. Thus, a not guarantee that scaling will not be a problem.
9
Figure 10 — Use of polymer consumption instead of Figure 11 — Use of polymer consumption instead of
conductivity to control blowdown. Data from a Pilot conductivity to control blowdown. Data from a Pilot
Cooling Tower Test 7 using an All-Organic program; Cooling Tower Test 7 using an All-Organic program.
standard make-up water (Make-up water upset condition at about 150 hours.)
1b. Alternatively, assume that make-up water con- was determined using on-line measurement of an
ductivity decreases from 600 µS/cm to 300 µS/cm, inert fluorescent tracer and a fluorescent tagged dis-
then blowdown control in the example above will persant polymer. A new controller provided on/off control
be activated much less often (at 8X make-up water of the treatment product feedpump and controlled the
conductivity). This will result in a significant blowdown valve based on polymer consumption.
increase in holding time index, still not guaran-
Figure 11 shows the % polymer consumption and con-
tee that a change in conductivity will match a
ductivity during an upset in make-up water compo-
change in scaling tendencies, and may result in
sition (after 150 hours elapsed operating time), which
increased operating costs.
caused an increase in system conductivity. Although
2. A change in chemical composition of make-up the 2nd make-up water composition (given in Table 4)
water may or may not coincide with conductivity contained twice as much calcium, because of the
changes. For example, the level of magnesium presence of the more soluble calcium sulfate, the
may decrease and calcium may increase; but the amount of CaCO3 precipitated may be less. The new
overall level of conductivity may be unchanged. controller maintained the polymer consumption at a
In this case, the scaling tendency of the water constant level and prevented any scaling increase,
increases, even though no apparent change in con- but allowed the tower to operate more efficiently at a
ductivity control of blowdown would occur. This higher level of cooling water conductivity.
can lead to many of the same problems previously
The results above were corroborated by concentra-
described.
tion cycle splits, which showed no change after the
Use of Polymer Consumption to Control Blow- upset in make-up water composition occurred. The
down — A Pilot Cooling Tower test (PCT test 7) was predicted effects of using conductivity control in this
used to determine the benefits of polymer consump- upset condition of make-up water composition were
tion control of cycles of concentration, as compared corroborated in additional PCT testing. When the
to conductivity method. In the initial work, concentra- cooling tower blowdown was controlled by conductiv-
tion cycles were controlled using conductivity. Scaling ity, the upset in make-up water composition resulted
was controlled by maintaining the non-scaling water in a much greater level of blowdown, and increased
chemistry, and the polymer consumption was found system operating costs with no guarantee that scal-
to be approximately 15%. ing was being prevented. A comparison of the blow-
down rates and make-up rates required during the
After testing the operation of the PCT using conduc-
make-up water upset under consumption control and
tivity control, the control of the tower was changed
under conductivity control are given in Table 9. Using
so that the blowdown was controlled by polymer con-
polymer consumption to control blowdown and cycles
sumption. During this stage of testing, it was demon-
of concentration, blowdown, make-up water usage,
strated that a PCT could be consistently controlled at
and associated system operating costs were reduced
a tagged polymer consumption level of 15% (Figure 10),
compared to using conductivity control.
with good control of scaling. Polymer consumption
10
Table 9 — Comparison of cooling tower operation
under consumption and conductivity control during
a make-up water upset (PCT test 7)
11
Figure 13 — Comparison of scale onset as determined by heat transfer resistance and
polymer consumption in PCT Test 10 during iron upsets using a stabilized phosphate
treatment program; pH = 7; standard make-up water, 4-5 cycles of concentration
A. Under Conductivity Control
gram was performed (PCT Test 9). When a loss of new controller responded as expected by increasing
acid feed occurred in the test using polymer consump- blowdown rate. This action helped prevent scaling/
tion to control blowdown, the new controller responded deposit formation in the system (no increase in HTR)
to the pH upset by initiating blowdown, thus reduc- and maintained the polymer consumption level until
ing the cycles of concentration. Phosphate splits the upset condition was corrected.
remained small and scale control was maintained.
Even more advanced forms of system control could The ability of a new controller to provide on/off con-
be implemented by inputting additional signals (such trol of treatment product feedpump and the blowdown
as pH) from the system to provide more detailed prob- valve was demonstrated. Also, the ability of the new
lem-solving and also additional automatic corrective controller to respond to severe upset conditions (loss
actions (e.g., activating a 2nd acid feedpump to com- of acid feed and iron upset) was demonstrated. Under
pensate for the loss of acid feed). normal conditions, polymer consumption-based con-
trol of blowdown allowed operation of the cooling
Since Stabilized Phosphate programs utilize acid feed water system at higher cycles than usually encoun-
and operate at a lower pH than other treatment pro- tered, while still minimizing scale formation. This
grams, corrosion and iron upsets can also occur. An iron allowed system performance to be maintained while
upset would result in fouling of the heat exchanger, reducing overall operating costs due to increased
but no change in the conductivity of the cooling sys- cycles of concentration and reduced blowdown rate.
tem. In another PCT test (PCT Test 10), an iron upset When an upset condition occurred, the new controller
was initiated by feeding an iron-containing solution responded by increasing blowdown rate. This action
directly into the basin to represent the upset condition. helped prevent scaling/deposit formation in the sys-
When conductivity was used to maintain cycles of tem until the upset conditions could be corrected.
concentration, only about 50% of the added iron was
recovered in the recirculating water. The fouling moni- CONCLUSIONS
tor on the system showed an increase in HTR (heat-
transfer resistance on the heat-exchanger tube) and 1. The measurement of on-line polymer consumption
deposits were visually observed (Figure 13A). At the and concentration cycle splits are direct indicators
same time, a 10–20% increase in polymer consump- of scaling processes and are more sensitive indica-
tion indicated that an increase in scaling/deposition tors of scaling processes than fouling simulators
was occurring. Even losses of 0.5 mg/L of iron or less (e.g., fouling monitors).
were readily detectable using polymer consumption 2. Since polymer consumption measurements can be
methods in this PCT test, which shows the high sensi- done continuously on-line with an inert fluores-
tivity of polymer consumption method as a monitor of cence tracer and tagged polymer, this method
system performance. When the iron upset was repeated offers the unique advantage of providing an
under polymer consumption control (Figure 13B), the immediate response to system changes.
12
3. It has been demonstrated that the dispersant 6. S. J. Armitage, J. E. Hoots, “Problem-Solving
polymer in cooling water treatment programs is Tools for Improved Performance of Treatment
consumed by scaling events and several types of Programs in Cooling Water Systems,” Official Pro-
active treatment components are present at ceedings – 57th International Water Conference,
enriched levels in deposits. Paper No. IWC-96-5, 1996.
4. The farther out of cycle balance the program oper- 7. J. E. Hoots, B. E. Moriarty, B. F. Pesigan, J. P.
ates, the greater the actives consumption. Rasimas, “Latest Methods of Performance Opti-
mization and Control in Cooling Water,” CORRO-
5. A new rapid and easy colorimetric test was devel-
SION/2001, National Association of Corrosion
oped to measure the amount of active polymer.
Engineers, Houston, Texas, 2001.
Polymer consumption, as measured by the new
test, can be used as a very valuable indicator of 8. P. R. Puckorius, S. D. Strauss, “Special Report –
system performance and for overall optimization Cooling Water Treatment,” Power, 139, No. 5,
of system operation. p. 17, 1995.
6. The development of a new fluorometric dispersant 9. Air Force Civil Engineering Support Agency,
polymer using a new fluorescent tag makes it fea- “Industrial Water Treatment Primer,” U.S.
sible to measure polymer actives online without Department of Commerce, Publication ADA 262
reagents. 698, March 1, 1992.
7. Polymer consumption was used as the basis for 10. K. P. Fivizzani, R. W. Cloud, J. E. Hoots, “Influ-
blowdown control in both All-Organic and Stabi- ence of Mechanistic Studies on the Development
lized Phosphate programs. This control was shown of New Cooling Water Programs,” CORROSION/
to save water under normal conditions and mini- 89, Paper No. 175, National Association of Corro-
mize scale under upset conditions. sion Engineers, Houston, Texas, 1989.
11. U.S. Patent 5,171,450 (assigned to Nalco Chemi-
REFERENCES cal Company), J. E. Hoots, December 15, 1992.
1. J. E. Hoots, “Methods for Improving Performance 12. U.S. Patent 5,435,969 (assigned to Nalco Chemi-
of Water Treatment Programs in Cooling Sys- cal Company), J. E. Hoots, M. R. Godfrey, July
tems,” International Association of Corrosion 25, 1995.
Engineers, Calgary, Alberta (Canada), 1999.
13. J. E. Hoots, D. A. Johnson, J. D. Lammering, D.
2. J. C. Horne, N. M. Rao, J. E. Hoots, “Develop- A. Meier, B. Yang, “High Cycle Cooling Tower
ment of a Mechanistic Understanding of Aromatic Operation: Hurdles and Solutions,” 60th Inter-
Triazole Consumption in Cooling Water,” Official national Water Conference, Paper No. IWC-99-
Proceedings - 60th International Water Confer- 48, 1999.
ence, 303-311, 1999.
14. Z. Amjad, “Factors to Consider in Selecting a Dis-
3. J. E. Hoots, “Water Treatment Dosage Control persant for Industrial Water Systems,” Ultrapure
and Relationship to Performance,” CORROSION/ Water, Vol. 16(7), 17,18,20,22-24, 1999.
95, Paper No. 260, National Association of Corro-
15. Ondeo Nalco Company, “Ondeo Nalco High Stress
sion Engineers, Houston, Texas, 1995.
Polymer,” Bulletin 425, 1999, and “Ondeo Nalco
4. S. J. Armitage, E. W. Ekis, J. E. Hoots, J. M. High Stress Polymer improves performance of
Johnston, “Actives-Based Chemical Control for A-Z-Lite program in heat stressed system,” Case
Recirculating Cooling Water Systems,” Official Study CH-438, 1999.
Proceedings - 56th International Water Confer-
16. J. E. Hoots, G. A. Crucil, “Role of Polymers in the
ence, 37-43, 1995.
Mechanisms and Performance of Alkaline Cool-
5. S. J. Armitage, J. E. Hoots, “New Methods for ing Water Programs,” CORROSION/86, Paper
On-Line Monitoring/Control of Corrosion Inhibi- No. 13, National Association of Corrosion Engi-
tors & Performance Relationships,” Proceedings neers, Houston, Texas, 1986.
of the 8th European Symposium on Corrosion
17. Hach Water Analysis Handbook, “Polyacrylic
Inhibitors (8 SEIC), Vol. 1, p. 533, 1995.
Acid: Absorption-Colorimetric Method, Method
8107,” 3rd Edition, 1059, 1997.
13
18. J. Richardson, M. G. Trulear, “Monitoring and 23. Ondeo Nalco Company, “Ondeo Nalco Active
Control of Polymeric Scale Inhibitors,” American Polymer Test – DR/2010 Procedure,” Analytical
Chemical Society (Book of Abstracts), 218th ACS Procedure (AP-116/2010), 1999.
National Meeting, COLL 226, 1999.
24. Ondeo Nalco Company, “Ondeo Nalco Active
19. W. M. Hann, T. W. Sanders, N. Pugliano, “Adsorp- Polymer Test – DR/890 Procedure,” Analytical
tion Studies of Tagged Polyelectrolytes on Crys- Procedure (AP-116/890), 1999.
tal Surfaces: Industrial Implications,” American
Chemical Society (Book of Abstracts), 218th ACS 25. Ondeo Nalco Company, “Ondeo Nalco Active
National Meeting, COLL 228, 1999. Polymer Test – Pocket Colorimeter Procedure,”
Analytical Procedure (AP-116/PC), 2000.
20. S. Patel, P. J. Sullivan, F. O’Brien, M. T. Muldoon,
D. V. Onisk, J. W. Stave, “Is There Enough Poly- 26. U.S. Patent 5,635,575 (assigned to Kurita Water
mer in the Tower,” CORROSION/2000, Paper No. Industries, Ltd.), M. Kira, N. Kobayashi, June 3,
329, National Association of Corrosion Engineers, 1997.
Houston, Texas, 2000. 27. U.S. Patent 5,948,268 (assigned to Nippon
21. W. A. Mitchell, G. A. Small, M. A. Reinsalu, D. O. Shokubai Co., Ltd. and Kurita Water Industries,
Veil, “The Use of Novel Monitoring and Control Ltd.), S. Yamaguchi, T. Fujisawa, Sep. 7, 1999.
Technology in Cooling Water Systems to Lower 28. P. J. Sullivan and J. F. Garey,” Effectiveness of
Operating Costs,” CORROSION/95, Paper No. Polymer Phosphonate Blends for Inhibition of
263, National Association of Corrosion Engineers, CaCO 3 Scale,” Industrial Water Treatment,
Houston, Texas, 2000. December 1996.
22. U.S. Patent 5,389,548 (assigned to Nalco Chemi-
cal Company), J. E. Hoots, C. C. Pierce, M. R. R.
W. Kugel, Feb. 14, 1995.