Professional Documents
Culture Documents
EEE 101 Experiment 2: Feedback Implementation and Error Signals
EEE 101 Experiment 2: Feedback Implementation and Error Signals
EEE 101 Experiment 2: Feedback Implementation and Error Signals
Abstract—The main objective of this experiment is to errors that were measured, and the implementation of each
construct a closed-loop system with an additional system gain to controller is discussed in the succeeding sections.
the first-order, type-0 plant developed in the previous
experiment. The error signal to variable controller values was A. Closing the loop
tested and observed. The variable controllers used are the
The plant obtained from experiment 1, with modelled
proportional controller and the integral controller. The error
results and step responses are shown in this paper. transfer function, G(s), was implemented in a closed-loop
system shown in Fig. 1.
I. INTRODUCTION
A closed-loop control system, also known as a feedback
control system is a control system which uses the concept of
an open loop system as its forward path but has one or more
feedback loops or paths between its input and its output. The
reference to “feedback” simply means that some portion of the
output is returned to the input to form part of the system’s Fig. 1. Closed-loop system
excitation. [1] Vdesired is a DC voltage input with value equal 0.8*(V TEMP-
Closed-loop systems are designed to automatically achieve ), where VTEMP-MAX is the stop condition value taken from
MAX
and maintain the desired output condition by comparing it the data in experiment 1. In this case, V desired = 0.8*(4.54) = 3.6
with the actual condition. It does this by generating an error V. A UA741 single op-amp was used to implement the
signal which is the difference between the output and the summing block in the closed-loop system. The schematic
reference input. [1] diagram of the operational amplifier for the unity gain
When the closed-loop system is properly designed, the feedback (i.e. E(s)= Vdesired - VTEMP) is shown in Fig. 2.
output will be less sensitive to disturbances, less sensitive to
plant changes, and will have a lesser steady-state error with
respect to a desired value.
Another way to get a more accurate output (i.e. smaller
steady-state error) is to increase the system type of the plant.
This technique was examined using an integral controller,
wherein given an input step function, the steady state error
theoretically must approach zero.
The error signals for each gain that were obtained are
plotted in Fig. 4.
C. Integral Controller
The proportional controller was replaced with an integral
controller since the constant of proportionality (k p) needed is
only 1. A UA741 op-amp, a 1MΩ resistor and a 1µF capacitor
was used. An inverter was cascaded to the integral controller
to compensate for the negating effect of the integrating. The
inverter was implemented by also using a UA741 op-amp.
The schematic diagram of integral controller is shown in Fig.
8.
Fig. 9. Step Response of the Integral Controller
1
Fig. 8. Integral Controller (Integrator and Inverting Amplifier)
0.5
The output voltage (VTEMP) was measured every 30 seconds.
The results are shown in Table 2. 0
0 90 180 270 360 450 540 630 720 810 900 990
TABLE III -0.5
OUTPUT VOLTAGES WITH RESPECT TO TIME
Time in Seconds
TIME
TIME VTEMP
VTEMP (V) (min:sec
(min:sec) (V)
)
0:00 2.43 8:30 3.25 Fig. 10. Error Results of the Integral Controller
0:30 3.93 9:00 3.22
1:00 3.46 9:30 3.39
1:30 3.41 10:00 3.34 With the integral controller in cascade to the forward loop
2:00 3.39 10:30 3.37 gain of the closed-loop system, the overall transfer function
2:30 3.34 11:00 3.26 can be computed as follows:
3:00 3.20 11:30 3.29
3:30 3.24 12:00 3.29
4:00 3.22 12:30 3.17
4:30 3.22 13:00 3.15
5:00 3.2 13:30 3.12
5:30 3.23 14:00 3.11
6:00 3.21 14:30 3.11
6:30 3.20 15:00 3.12
7:00 3.25 15:30 3.13
R (s )
0.055 1 E ( s )=
)( 1 0.055
1 s 1+( )( )
s+ s 1
Vtemp Gc ( s ) G( s) 144.155 s+
= = 144.155
Vdesired 1+Gc ( s ) G(s) 1 0.055 s( s+ 0.0069) 3.6
1+ ( ) E ( s )= 2 ∙
s 1 s +0.0069 s +0.055 s
s+
144.155
0.055 0.055 At steady-state:
¿ =
1 1
(
s s+
144.155 ) 2
+ 0.055 s +
144.155
s+ 0.055
e ss =lim sE ( s ) =lim
s ( s ( s+0.0069 ))
3.6
=
0
∙ =0
s→0 s →0
2
s +0.0069 s +0.055 s 0.055
The system is now second-order and type 1 with a transfer
function shown in Fig.11. Due to the increase in system type,
overshoot can be observed in the output step response.
Oscillations are present in the output that decrease and reach
steady-state at a value equal to Vdesired. This implies that the
steady-state error can be computed to be 0.
III. CONCLUSION
The goal of the experiment was to modify the previously
constructed fully functional plant of a temperature-controlled
system into a closed-loop system. This was implemented
using a unity feedback gain, designed using a difference
amplifier. An additional forward gain was also introduced
using a proportional controller (a non-inverting amplifier) and
an integral controller (cascade of integrator and inverting
amplifiers). The latter one increases the type of the system
from 0 to 1, and hence decreasing the steady state error,
theoretically to 0, given a step input. Some significant
deviations from the theoretical computations were obtained in
the integral controller most likely because of the change in the
behavior of the original open loop system. This may be caused
by non-idealities, defective components, and/or the change in
ambient conditions.
REFERENCES
[1] (2018) Electronics Tutorials Closed-loop Control Systems [Online].
Available: https://www.electronics-tutorials.ws/systems/closed-loop-
system.html
[2] (2018) Electronics Tutorials Op-Amp [Online]. Available:
https://www.electronics-tutorials.ws/opamp/opamp_6.html
[3] (2018) Electronics Tutorials Op-Amp [Online]. Available:
https://www.electronics-tutorials.ws/opamp/opamp_8.html