Control Cable: 1 Executive Standards
Control Cable: 1 Executive Standards
2 Application
%&'=>?@A、B、CDEFGFHIJKLM:N(Uo/U)450/750VOPQRSTU、
VWRX$YZ、[\]^_。
It is used for the signal transmission controlling and measuring system of the electric apparatus
and the power distribute apparatus in the field of metallurgy,power and petrochemistry. Its rated
voltage (Uo/U)is up to including 450/750V.
3
Type and Designation
#$ Model ! " Designation
KVV
PVC insulated PVC sheathed control cable
KYY
PE insulated PE sheathed control cable
KYV
PE insulated PVC sheathed control cable
KVVP
PVC insulated PVC sheathed copper wire braided screen control cable
KYYP PE insulated PE sheathed copper wire braided screen control cable
KYVP PE insulated PVC sheathed copper wire braided screen control cable
KYJVP
XLPE insulated PVC sheathed copper wire braided screen control cable
KVVP2
PVC insulated PVC sheathed copper tape wrapped screen control cable
KYVP2 PE insulated PVC sheathed copper tape wrapped screen control cable
KYV22 PE insulated PVC sheathed double steel tape armoured control cable
KYJV22 XLPE insulated PVC sheathed double steel tape armoured control cable
KYJVR XLPE insulated PVC sheathed flexible control cable
KVVRP PVC insulated PVC sheathed copper wire braided screen flexible control cable
KYYRP PE insulated PE sheathed copper wire braided screen flexible control cable
KYVRP
PE insulated PVC sheathed copper wire braided screen flexible control cable
KYJVRP
XLPE insulated PVC sheathed copper wire braided screen flexible control cable
45
Z-KVV
PVC insulated PVC sheathed control cable flame retardant
45
Z-KYJV
XLPE insulated PVC sheathed control cable flame retardant
45
Z-KVVP PVC insulated PVC sheathed copper wire braided screen control cable flame retardant
45
Z-KYVP PE insulated PVC sheathed copper wire braided screen control cable flame retardant
45
Z-KYJVP
XLPE insulated PVC sheathed copper wire braided screen control cable flame retardant
45
Z-KVVP2
PVC insulated PVC sheathed,copper tape wrapped screen control cable flame retardant
45
Z-KYJVP2 XLPE insulated PVC sheathed copper tape wrapped screen control cable flame retardant
45
Z-KVV22 PVC insulated PVC sheathed double steel tape armoured control cable flame retardant
45
Z-KYV22 PE insulated PVC sheathed double steel tape armoured control cable flame retardant
45
Z-KYJV22 XLPE insulated PVC sheathed double steel tape armoured control cable flame retardant
Model Designation
Z-KVVR PVC insulated PVC sheathed flexible control cable flame retardant
Z-KYVR PE insulated PVC sheathed flexible control cable flame retardant
Z-KYJVR XLPE insulated PVC sheathed flexible control cable flame retardant
Z-KVVRP PVC insulated PVC sheathed copper wire braided screen flexible control cable flame retardant
Z-KYVRP PE insulated PVC sheathed copper wire braided screen flexible control cable flame retardant
Z-KYJVRP XLPE insulated PVC sheathed copper wire braided screen flexible control cable flame retardant
DDZ-KVV PVC insulated PVC sheathed control cable low-smoking low-halogen flame retardant
DDZ-KYV PE insulated PVC sheathed control cable low-smoking low-halogen flame retardant
DDZ-KYJV XLPE insulated PVC sheathed control cable low-smoking low-halogen flame retardant
DDZ-KVVP PVC insulated PVC sheathed control wire braided common shield control cable low-smoking low-halogen flame retardant
DDZ-KYVP
PE insulated PVC sheathed control wire braided common shield control cable low-smoking low-halogen flame retardant
DDZ-KYJVP
XLPE insulated PVC sheathed control wire braided common shield control cable low-smoking low-halogen flame retardant
!
DDZ-KVVP2
PVC insulated.PVC.sheathed copper tape wrapped common shield control cable low-smoking low-halogen flame retardant
!
DDZ-KYJVP2
XLPE insulated PVC sheathed copper tape wrapped common shield control cable low-smoking low-halogen flame retardant
"#$%
DDZ-KVVP22
PVC insulated PVC sheathed double steel tape armoured control cable low-smoking low-halogen flame retardant
"#$%
DDZ-KYJVP22 XLPE insulated PVC sheathed double steel tape armoured control cable low-smoking low-halogen flame retardant
DDZ-KYVR PE insulated PVC sheathed flexible control cable low-smoking low-halogen flame retardant
DDZ-KYJVR XLPE insulated PVC sheathed flexible control cable low-smoking low-halogen flame retardant
DDZ-KVVRP PVC insulated PVC sheathed copper wire braided common shield flexible control cable low-smoking low-halogen flame retardant
DDZ-KYVRP PE insulated PVC sheathed copper wire braided common shield flexible control cable low-smoking low-halogen flame retardant
ELECTRIC WIRES & CABLE
Model Designation
DDZ-KYJVRP XLPE insulated PVC sheathed copper wire braided common shield flexible control cable low-smoking low-halogen flame retardant
* +
WDZ-KYJY XLPE insulated PO sheathed control cable low-smoking halogen-free flame retardant
** +
WDZ-KYY PO insulated PO sheathed control cable low-smoking halogen-free flame retardant
* +
WDZ-KYJYP XLPE insulated PO sheathed copper wire braided common shield control cable low-smoking halogen-free flame retardant
** +
WDZ-KYYP PO insulated PO sheathed copper wire braided common shield control cable low-smoking halogen-free flame retardant
* !+
WDZ-KYJYP2 XLPE insulated PO sheathed copper tape wrapped common shield control cable low-smoking halogen-free flame retardant
** !+
WDZ-KYYP2 PO insulated PO sheathed copper tape wrapped common shield control cable low-smoking halogen-free flame retardant
* "#$%+
WDZ-KYJY23 XLPE insulated PO sheathed double steel tape armoured control cable low-smoking halogen-free flame retardant
** "#$%+
WDZ-KYY23
PO insulated PO sheathed double steel tape armoured control cable low-smoking halogenfree flame retardant
、* 、+
WDZ-KYJYR
XLPE insulated, PO sheathed flexible control cable, low-smoking halogen-free flame retardant
*、* 、+
WDZ-KYYR
PO insulated, PO sheathed flexible control cable, low-smoking halogen-free flame retardant
、* 、+
WDZ-KYJYRP
XLPE insulated, PO sheathed, copper wire braided common shield flexible control cable, low-smoking halogen-free flame retardant
** +
WDZ-KYYRP PO insulated, PO sheathed ,copper wire braided common shield flexible control cable, low-smoking halogen-free flame retardant
4
Explanation of the code in the type
Items Code Designation
K control cable
Y PE
Insulation V PVC
YJ XLPE
Y PO
Y PE/PO
sheathed
V PVC
class of conductor R Muti-strands flexible conductor
(Omitted) !"# No shield
P $%&' copper wire braided
"# shield
P2 $()* copper tape wrapped
P3 +,-.()* Al/plastic wrapped
(Omitted) !/0 No armour
/0 Armor
2 12(/0 double steel tape armour
2 PVC
3
Over sheathed
3 PE
89,70℃;<=!>45 ?70℃
/ ;;89 ?90℃;。
MJN; 70℃ for PE, 70℃ PVC Or HFPO insulation cable, 90℃ for XLPE insulation cable
Heat-resistance grade
90 BCDEFGHIJKL90℃
The max. long-term operating temperature of conductor is 90℃
(Omitted) !OP No requirement
4567 Z QR45 Bundle Flame-retardant
Flame-retardant characteristics DDZ <=<>45 low-smoking&low-halogen flame retardant
WDZ !><=45 low-smoking&Halogen-free flame retardant
5
Model Explanation
□□ □□□ □□ □□□ □
TU Nominal sectional area(mm2)
VW Core No.
MJN; Heat-resistance grade
3X Over sheath
/0 Armor
"# shield
kind of conductor
sheathed
Insulation
YZ senes code
45 Flame-retardant code
[:( ) ]^TU_`10mm abcd efg,A]^hi,j
,B-k.。
2
Remarks:( ) means the class conductor when its nominal area is less than 10mm ,A means solid conductor,
2
6
Indication Examples
,l mn,VWpgqTU]^。rstuvwxgyrefc,
z (B)]^,`w{|q}。~b:
The indication of plastic insulated control cable consists of type,number of cores,nominal sectional
area of conductor,When the same type product is made of different class of conductor,the more
flexible one is indicated with (B) following the specitication.For exampies :
7
Using feature &Main Technical Performances
7.1 x(UO/U):450/750V Rated voitage(UO/U): 450/750V;
7.2 gBCFGDEHIJK:
L:70℃ L:90℃
The Max. long-term operating temperature of conductor:
PEinsulated cable:70℃ XLPE insulated cable:90℃
L:70℃、90℃(i
ngMJN;x);
PVC insulated cable: 70℃、90℃(according to the grade of heat proof after the type)
!><=45 L: 70℃,90℃(i
n|gMJN;x);
low-smoking halogen-free flame retardant PO insulated cable:70℃、90℃(according to the
grade of heat proof after the type)
7.4 DE:
/0$()*"#efgy<93g12;efy<93g6。
The permitted bending radius:
No less than 12 times of the overall diameter of the cable for which has armor or copper tape
wrapped shield.No less than 6 times of the overall diameter of the cable for the others.
7.6
3;
4。
The D.C resistance of conductor is show in table 3 and the insulation resistance is show in table 4.
3 table 3
20℃
D.C. resistance of conductor at 20℃ ≤Ω/km
Nominal
section area
2
Untinned Tinned
mm
A Kind A B Kind B Flexible A Kind A B Kind B Flexible
0.5 36.0 36.0 39.0 36.7 36.7 40.1
0.75 24.5 24.5 26.0 24.8 24.8 26.7
1.0 18.1 18.1 19.5 18.2 18.2 20.0
1.5 12.1 12.1 13.3 12.2 12.2 13.7
2.5 7.41 7.41 7.98 7.56 7.56 8.21
4 4.61 4.61 — 4.70 4.70 —
6 3.08 3.08 — 3.11 3.11 —
10 — 1.83 — — 1.84 —
4 table 4
70℃90℃
Insulation resistance at 70℃ or 90℃ ≥MΩ km
Nominal
section area
2
!"#$ !" PEor XLPE insulated %!"&'()* "+ PVCorHFPO insulated
mm
A Kind A B Kind B Flexible A Kind A B Kind B Flexible
0.5 0.1400 0.1300 0.1300 0.014 0.014 0.013
0.75 0.1200 0.1100 0.1100 0.012 0.014 0.011
1.0 0.1100 0.1000 0.1000 0.011 0.013 0.010
1.5 0.1100 0.1000 0.1000 0.011 0.010 0.010
2.5 0.1000 0.0900 0.0900 0.010 0.009 0.009
4 0.0850 0.0700 — 0.0085 0.0077 —
6 0.0700 0.0650 — 0.0070 0.0065 —
10 — 0.0650 — — 0.0065 —
KVV、KYY、KYJV、KYV、Z-KVV、Z-KYV、Z-KYJV、DDZ-KVV、
DDZ-KYV、DDZ-KYJV、WDZ-KYY、WDZ-KYJY、KYYP、KVVP、 2~14 2~10
—— 2~61
KYJVP、KYVP、Z-KVVP、Z-KYJVP、Z-KYVP、DDZ-KVVP、
Z-KYVP、Z-KYJVP、WDZ-KYYP、WDZ-KYJYP
KVVP2、KVVP3、KYYP2、KYYP3、KYVP2、KYVP3、KYJVP2、
KYJVP3、Z-KVVP2、Z-KVVP3、Z-KYVP2、Z-KYVP3、Z-KYJVP2、
Z-KYJVP3、DDZ-KVVP2、DDZ-KVVP3、DDZ-KYVP2、DDZ-KYVP3
—、— 4~61 4~14 4~10
DDZ-KYJVP2、DDZ-KYJVP3、WDZ-KYYP3、WDZ-KYYP2、
WDZ-KYJYP2、WDZ-KYJYP3
KVVR、KYYR、KYJVR、KYVR、Z-KVVR、Z-KYJVR、WDZ-KYVR、61
4~ —— ——
WDZ-KYYR、WDZ-KYJYR
KVVRP、KYYRP、KYVRP、KYJVRP、Z-KVVRP、Z-KYVRP、
Z-KYJVRP、Z-KVVRP、DDZ-KYVRP、DDZ-KYJVRP、 4~61 4~48 —— ——
WDZ-KYYRP、WDZ-KYJYRP