TECHNOTE
R O O F I N G

DATE
11
98
Ballast Design Guide for
IRMA Roofs
Introduction Wind Design Guide for the stone ballast, as well as
This document has been Ballasted Single-Ply Roofing the anticipated live loads.
developed for those who Systems published by the
design, specify, or install Single Ply Roofing Institute. Slope
IRMA roofing systems, by The SPRI data was utilized for The roof slope should not
helping them select the the mechanically-attached exceed 2" in 12".
appropriate stone or paver and loose-laid systems.
ballast design for each job. Design Wind Speed
IRMA, remember, places This document first presents The design wind speed for
STYROFOAM* brand insula- some General Design the building location should
tion above the roofing mem- Considerations, then a series be determined from the ANSI
brane, protecting it from of tables from which the 58.1-1982 wind speed map,
both physical abuse and the proper ballast design can be Figure 1, or from the local
stress of temperature selected. The final section code authority.
extremes. The function of the describes the requirements
roof ballast, then, is to keep and alternatives of the four Roof Height
the insulation secure during Ballast Designs that are rec- The roof height from the
wind and rain storms. ommended. ground level to the top of the
new roofing system may be
IRMA roofing systems which General Design different on different sides of
are installed in accordance Considerations the building. Therefore, the
with these recommendations The following factors should height should be based on
qualify for Dow’s 10-year be considered when designing the worst-case elevation.
limited warranty, covering a ballasted IRMA roofing
both the thermal resistance system: Parapet Height
of STYROFOAM and the The parapet wall height
wind resistance of the ballast Roof Structure should be measured from the
design. See the IRMA war- The building structure (either top of the ballast to the top
ranty certificate for details. new or retrofit) must be of the parapet. If the height
strong enough to support the varies, the shortest parapet
The information presented is present and future dead height should be used. For
based on extensive wind test- loads on the roof, including special cases contact your
ing of ballasted roofing sys- Dow Technical Service
tems at the National Representative
Research Council of Canada (1-800-441-4369).
and from portions of the

TechNote 508a *Trademark of The Dow Chemical Company


TECHNOTE

Gravel Stop Building Exposure check with a Dow TS&D


If a gravel stop is used at the The surrounding terrain has an representative.
building perimeter, its height effect on the overall wind
above the ballast should be a exposure of the building. The This air space is not required if
minimum of 2 inches when exposure can be categorized the pavers are covering only a
necessary to contain the as (P) Somewhat Protected or limited area, such as corners of
ballast. (E) Full Exposure to Winds. the roof or narrow roof walk-
ways.
Areas of Extra Ballasting P = Buildings located in pro-
Certain areas of the roof insu- tected areas such as wooded Paver Strapping
lation require additional bal- areas or where buildings Strapping of pavers should be
lasting to overcome high wind nearby are taller and offer accomplished with 22 gauge,
loads and to restrain the foam some wind resistance. 3" wide x 12' long galvanized
from floating during heavy rain E = Buildings located on or stainless steel straps, strap-
storms. This assures that indi- plains or shorelines which ping should be mechanically
vidual stones cannot migrate offer little or no protection fastened to each paver with
to below the foam and abrade from winds. minimum 1/4" x 1-1/4" corro-
the membrane. Areas needing sion-resistant metal anchors,
such additional ballasting are: Concrete Pavers expanded in predrilled holes,
Concrete pavers should be such as the Zamac Nailin
Perimeter Edge of manufactured from minimum #2820 by the Rawlplug
Insulation, which is a four- 3000 lb/in2 concrete and Company.
foot-wide swath running should weigh a minimum of
along the perimeter edge of 18 lb/ft2. Interlocking Pavers
the roof insulation (and Proprietary interlocking pavers
which includes any insulation Paver Venting can be used as an optional
adjacent to higher walls). When pavers cover over 90% ballast system. They are avail-
of the insulation surface, a able from paver manufacturers
Penetrations Through 3/16" ventilating air space is such as Hanover Prest-Paving
Insulation, which are usually required between the Company, IDR Division of The
two-foot-wide swaths run- foam and the pavers to pre- National Concrete Masonry
ning around any roof insula- vent freeze-thaw spalling of Association, RoofBlok Limited,
tion penetrations which the concrete and moisture and Westile.
exceed 4 feet in any direc- vapor build-up in the insula-
tion, such as skylights, tion. This air space can be These pavers are lighter in
expansion joints, equipment achieved with paver pedestals, weight than the noninterlock-
pads, etc. with ribbed STYROFOAM ing pavers described above.
ROOFMATE* brand roof insu- The wind resistance of propri-
Corners, where arrays of lation, or with ribbed or footed etary interlocking pavers is not
concrete pavers are required concrete pavers. For roof covered by the Dow warranty,
in IRMA Ballast Designs #2 construction in the South, but it is covered by the paver
and #3. manufacturer’s warranty.

*Trademark of The Dow Chemical Company


TechNote 508a-2
TECHNOTE

Ballast Design Options Table B: Adhered Membranes, (Adhered or not)


Selection of the Proper IRMA heights from 45-70 2. Building height
Ballast Design feet 3. Design wind speed
A designer of IRMA roofing Table C: Adhered Membranes, 4. Parapet height
systems has four Ballast heights from 70 to 5. Building site exposure
Designs to chose from: 500 feet Find the proper Ballast Design.
Standard, #1, #2, and #3. Table D: Mechanically- If paver ballast is to be used
These Designs vary with build- attached or Ballasted and will cover over 90% of the
ing height, parapet height, Membranes, heights insulation, determine if paver
membrane attachment, and to 150 feet, maximum venting is needed and, if so,
wind speed. The tables below how it will be accomplished.
are organized by membrane To select the Ballast Design
attachment method and build- which is required for your roof, Then, after you have deter-
ing height. And they list the work through one of these mined the appropriate Ballast
Ballast Design which is required four tables according to the Design, move on to page 7 to
for each roof condition. following steps. learn the requirements of that
Design.
Table A: Adhered Membranes, Select the appropriate:
heights to 45 feet 1. Roof membrane attachment

Table A Membrane: Adhered Roof Heights: 12 to 45 feet

A-1. For 2" high gravel stops to 36" high parapets


Design Wind Speed, mph 70 80 90 100 110
Site Exposure P&E P&E P&E P&E P&E
Ballast Design Standard 1 1 1 1

A-2. For parapet heights above 36"


Design Wind Speed, mph 70 80 90 100 110
Site Exposure P&E P&E P&E P&E P&E
Ballast Design Standard Standard Standard Standard Standard

Table B Membrane: Adhered Roof Heights: 45 to 70 feet

B-1. For 6" high gravel stops to 36" high parapets


Design Wind Speed, mph 70 80 90 100 110
Site Exposure P&E P&E P&E P&E P&E
Ballast Design Standard 1 1 1 1

B-2. For parapet heights above 36"


Design Wind Speed, mph 70 80 90 100 110
Site Exposure P&E P&E P&E P&E P&E
Ballast Design Standard Standard Standard Standard Standard

*Trademark of The Dow Chemical Company


TechNote 508a-3
TECHNOTE

Table C Membrane: Adhered Roof Heights: 70 to 500 feet

C-1. For parapet heights 18" to 36" (for lower parapets, contact TS&D)
Design Wind Speed, mph 70 80 90 100 110
Site Exposure P&E P&E P&E P&E P&E
Ballast Design
>70 - 100 feet 1 1 2 2 2
>100 - 200 feet 1 1 2 2 3
>200 - 300 feet 1 2 2 3 3
>300 - 400 feet 1 2 2 3 NR
>400 - 500 feet 1 2 2 3 NR

C-2. For parapet heights above 36"


Design Wind Speed, mph 70 80 90 100 110
Site Exposure P&E P&E P&E P&E P&E
Ballast Design
>70 - 100 feet Standard 1 1 1 1
>100 - 200 feet Standard 1 1 1 2
>200 - 300 feet 1 1 1 1 2
>300 - 400 feet 1 1 1 2 2
>400 - 500 feet 1 1 1 2 2

NR = Not Recommended

*Trademark of The Dow Chemical Company


TechNote 508a-4
TECHNOTE

Table D Membrane: Loose-Laid Ballasted or Mechanically-Attached


Roof Heights: up to 150 feet, maximum

NOTE! For roofs above 150 feet, contact Dow TS&D for individual building analysis (800-441-4369).

NOTE! These tables assume that you have specified proper provisions for sealing off openings in
the roof deck and any perimeter blocking, so as to prevent air from getting immediately below the
roofing membrane and exerting a “billowing” force on the membrane. For further information, see
Dow Technical Data Sheet No. 179-5285.

D-1. From 2-inch high gravel stops to 5.9-inch high parapets


Design Wind Speed, mph 70 80 90 100 110
Site Exposure E P E P E P E P E P
Ballast Design
0 - 15 feet 1 1 1 1 2 1 2 2 3 3
>15 - 30 feet 1 1 1 1 2 1 2 2 3 3
>30 - 60 feet 1 1 2 1 2 2 3 2 3 3
>60 - 90 feet 2 2 2 2 2 2 3 3 NR NR
>90 - 120 feet 2 2 2 2 3 3 NR NR NR NR
>120 - 150 feet 2 2 2 2 3 3 NR NR NR NR

D-2. For parapet heights from 6.0 to 11.9 inches


Design Wind Speed, mph 70 80 90 100 110
Site Exposure E P E P E P E P E P
Ballast Design
0 - 15 feet 1 1 1 1 1 1 2 2 3 3
>15 - 30 feet 1 1 1 1 2 1 2 2 3 3
>30 - 60 feet 1 1 2 1 2 2 3 2 3 3
>60 - 90 feet 2 2 2 2 2 2 3 3 3 3
>90 - 120 feet 2 2 2 2 3 3 3 3 3 3
>120 - 150 feet 2 2 2 2 3 3 3 3 NR NR

D-3. For parapet heights from 12.0 to 17.9 inches


Design Wind Speed, mph 70 80 90 100 110
Site Exposure E P E P E P E P E P
Ballast Design
0 - 15 feet 1 1 1 1 1 1 2 2 3 3
>15 - 30 feet 1 1 1 1 2 1 2 2 3 3
>30 - 60 feet 1 1 2 1 2 2 3 2 3 3
>60 - 90 feet 1 1 2 2 2 2 3 3 3 3
>90 - 120 feet 2 2 2 2 3 3 3 3 3 3
>120 - 150 feet 2 2 2 2 3 3 3 3 3 3

NR = Not Recommended

*Trademark of The Dow Chemical Company


TechNote 508a-5
TECHNOTE

Table D (cont.) Membrane: Loose-Laid Ballasted or Mechanically-Attached


Roof Heights: up to 150 feet, maximum

D-4. For parapet heights from 18.0 to 23.9 inches


Design Wind Speed, mph 70 80 90 100 110
Site Exposure E P E P E P E P E P
Ballast Design
0 - 15 feet 1 1 1 1 1 1 2 2 3 3
>15 - 30 feet 1 1 1 1 2 1 2 2 3 3
>30 - 60 feet 1 1 2 1 2 2 2 2 3 3
>60 - 90 feet 1 1 2 2 2 2 3 3 3 3
>90 - 120 feet 2 2 2 2 2 2 3 3 3 3
>120 - 150 feet 2 2 2 2 3 3 3 3 3 3

D-5. For parapet heights from 24.0 to 35.9 inches


Design Wind Speed, mph 70 80 90 100 110
Site Exposure E P E P E P E P E P
Ballast Design
0 - 15 feet 1 1 1 1 1 1 2 2 3 3
>15 - 30 feet 1 1 1 1 1 1 2 2 3 3
>30 - 60 feet 1 1 2 1 2 1 2 2 3 3
>60 - 90 feet 1 1 2 2 2 2 3 3 3 3
>90 - 120 feet 2 2 2 2 2 2 3 3 3 3
>120 - 150 feet 2 2 2 2 3 3 3 3 3 3

D-6. For parapet heights from 36.0 to 71.9 inches


Design Wind Speed, mph 70 80 90 100 110
Site Exposure E P E P E P E P E P
Ballast Design
0 - 15 feet 1 1 1 1 1 1 2 2 3 3
>15 - 30 feet 1 1 1 1 1 1 2 2 3 3
>30 - 60 feet 1 1 1 1 2 1 2 2 3 3
>60 - 90 feet 1 1 2 2 2 2 2 2 3 3
>90 - 120 feet 1 1 2 2 2 2 3 3 3 3
>120 - 150 feet 1 1 2 2 2 2 3 3 3 3

D-7. For parapet heights from 72 to 96 inches


Design Wind Speed, mph 70 80 90 100 110
Site Exposure E P E P E P E P E P
Ballast Design
0 - 15 feet 1 1 1 1 1 1 2 2 3 3
>15 - 30 feet 1 1 1 1 1 1 2 2 3 3
>30 - 60 feet 1 1 1 1 2 1 2 2 3 3
>60 - 90 feet 1 1 1 1 2 2 2 2 3 3
>90 - 120 feet 1 1 2 2 2 2 2 2 3 3
>120 - 150 feet 1 1 2 2 2 2 3 3 3 3

*Trademark of The Dow Chemical Company


TechNote 508a-6
TECHNOTE

Requirements of IRMA Ballast Designs


Stone Ballast
All references to stone ballast herein are references to ASTM D 448. The sizes and sieve analyses of
the aggregates recommended in this TechNote are listed below.

ASTM D 448: Standard Sizes of Coarse Aggregate


Weight Percent Finer Than Sieve Openings

Nominal Size
Size Square
Number Openings 3" 2-1/2" 2" 1-1/2" 1" 3/4" 1/2" 3/8"

2 2-1/2 to 1-1/2" 100 90 to 100 35 to 70 0 to 15 0 to 5

4 1-1/2 to 3/4" 100 90 to 100 20 to 55 0 to 15 0 to 5

5 1 to 1/2" 100 90 to 100 20 to 55 0 to 10 0 to 5

The following tables describe the requirements for each of the four IRMA Ballast Designs identified
in Tables A, B, C, and D, including alternate Designs and corner paver arrays.

IRMA Ballast Design: Standard

Field Install 10 lb/ft2 of #5 aggregate (1" stone).


It may be crushed stone or rounded riverbed stone.
Perimeter & Install 15 lb/ft2 of #5 aggregate.
Penetrations If the foam is 3" or more in thickness, install 20 lb/ft2.
As an alternate to either the 15 or 20 lb/ft2 of stone ballast, one row of
8"x16"x2" concrete pavers may be installed along the perimeter edge of
the insulation and around penetrations of the insulation. The balance of
the area should be covered with 10 lb/ft2 of #5 aggregate.
Corners Same as Perimeter & Penetrations.
Options to above: A minimum of 18 lb/ft2 of concrete pavers may be installed over the
entire roof.
or: A minimum of 11 lb/ft2 of proprietary interlocking concrete pavers (warranted
by others) may be installed over the entire roof.

*Trademark of The Dow Chemical Company


TechNote 508a-7
TECHNOTE

IRMA Ballast Design: #1

Field Install 12 lb/ft2 of #4 aggregate (1-1/2" stone).


It may be crushed stone or rounded riverbed stone.
Perimeter & Install 15 lb/ft2 of #4 aggregate.
Penetrations If the foam is 3" or more in thickness, install 20 lb/ft2.
As an alternate to either the 15 or 20 lb/ft2 of stone ballast, two rows (four
feet) of 24"x24"x2" concrete pavers may be installed along the perimeter
edge of the insulation and around penetrations of the insulation.
Corners Same as Perimeter & Penetrations.
Options to above: A minimum of 22 lb/ft2 of concrete pavers may be installed over the
entire roof.
or: A minimum of 11 lb/ft2 of proprietary interlocking concrete pavers
(warranted by others) may be installed over the entire roof.

*Trademark of The Dow Chemical Company


TechNote 508a-8
TECHNOTE

IRMA Ballast Design: #2

Field Install 13 lb/ft2 of #2 aggregate (2-1/2" stone).


It may be crushed stone or rounded riverbed stone.
Perimeter &
Penetrations Install 15 lb/ft2 of #2 aggregate.
If the foam is 3" or more in thickness, install 20 lb/ft2.
As an alternate to either the 15 or 20 lb/ft2 of stone ballast, three rows
(six feet) of 24"x24"x2" concrete pavers may be installed along the
perimeter edge of the insulation and around penetrations of the insula-
tion, with the first row of perimeter edge pavers being strapped together,
straps running parallel to the parapets.
Corners Install Paver Array 1.
Options to above: A minimum of 22 lb/ft2 of concrete pavers may be installed over the entire
roof, with the first row of perimeter edge pavers being strapped together,
straps running parallel to the parapets.
or: A minimum of 11 lb/ft2 of proprietary interlocking concrete pavers (war-
ranted by others) may be installed over the entire roof.

IRMA Ballast Design: #3

Field Install 13 lb/ft2 of #2 aggregate (2-1/2" stone).


It may be crushed stone or rounded riverbed stone.
Perimeter Adhere the membrane to the roof deck for four feet in from the para-
pets. Install four rows (eight feet) of 24"x24"x2" concrete pavers along
the perimeter edge and strap the first two rows together, straps running
parallel to the parapets.
Penetrations Install 15 lb/ft2 of #2 aggregate.
If the foam is 3" or more in thickness, install 20 lb/ft2.
Corners Install Paver Array 2.
Options to above: Minimum of 22 lb/ft2 of concrete pavers may be installed over the entire
roof, with the two rows of pavers nearest the parapets being strapped
together, straps running parallel to the parapets.
or: Minimum of 11 lb/ft2 of proprietary interlocking concrete pavers (war-
ranted by others) may be installed over the entire roof.

*Trademark of The Dow Chemical Company


TechNote 508a-9
TECHNOTE

*Trademark of The Dow Chemical Company


TechNote 508a-10
TECHNOTE

NOTICE: No freedom from any patent owned by Dow Seller or others is to be inferred. Because use conditions and applicable laws may differ from one loca-
tion to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for
Customer’s use and for ensuring that Customer’s workplace and disposal practices are in compliance with applicable laws and other government enactments.
Dow Seller assumes no obligation or liability for the information in this document. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.

WARNING: STYROFOAM brand insulation products are combustible and may constitute a fire hazard if improperly used or installed. Consult Dow for further
information. The material contains a flame retardant additive to inhibit accidental ignition from small fire sources. During shipping, storage, installation and use,
these products should not be exposed to open flame or other ignition sources.

For technical information, call 1-800-441-4369

The Dow Chemical Company


200 Larkin Center
1605 Joseph Drive
Midland, MI 48674

*Trademark of The Dow Chemical Company Printed in U.S.A.


TechNote 508a-11 Form No. 179-5481-1198QRP