F / 1SCC303002M0206
Contents
1. Introduction ....................................................................................................................... 4
1.1 Use of symbols ............................................................................................................................4
1.2 Explanations of abbreviations and terms ...................................................................................4
2. Product overview .............................................................................................................. 5
3. Quick start ......................................................................................................................... 6
3.1 Operating the motorized change-over switch electrically; remote control ...............................6
3.1.1 Locking electrical operation ........................................................................................................6
3.2 Operating the motorized change-over switch manually; local operation .................................7
4. Installation ......................................................................................................................... 8
4.1 Mounting the motorized change-over switch ............................................................................8
4.2 Dimensional drawings ...............................................................................................................10
4.3 Connections ...............................................................................................................................17
4.4 Mounting positions ....................................................................................................................18
4.5 Labelling .....................................................................................................................................18
5. Connecting ...................................................................................................................... 19
5.1 Control circuit.............................................................................................................................19
6. Operating ......................................................................................................................... 20
6.1 Electrical operation ....................................................................................................................20
6.1.1 Impulse control ..........................................................................................................................21
6.1.2 Continuous control ....................................................................................................................22
6.2 Manual operation by using the handle .....................................................................................23
6.3 Locking .......................................................................................................................................24
6.3.1 Locking the electrical operation................................................................................................24
6.3.2 Locking the manual operation ..................................................................................................23
7. Technical data ................................................................................................................. 26
8. Accessories ..................................................................................................................... 28
8.1 Terminal clamp sets ...................................................................................................................28
8.2 Bridging bars..............................................................................................................................29
8.3 Terminal shrouds........................................................................................................................33
8.4 Auxiliary contacts ......................................................................................................................36
8.5 Dual power source .....................................................................................................................36
8.6 Voltage sensing connectors ......................................................................................................38
8.7 Handle and spare fuse storage .................................................................................................39
9. UL standard switches..................................................................................................... 40
9.1 Phase barriers ............................................................................................................................41
ON
Operation
OTM_C 0 I 0 II 0
Switch II Close
OFF
Open
Close
ON
Switch I Open
ON Operation
OTM_CL O
N
I II I
Close
Switch II Open
ON
Close
Switch I Open
ON Operation
OTM_CF O
FF 0 I 0 II 0
Close
Switch II Open
ON
A06102
Close
Switch I Open
1. Introduction
This manual describes the installation and the basic operation of the motorized change-over
and transfer switches, types OTM_C. The instructive part is followed by a section on available
accessories.
General warning: warns about a situation where something other than electrical
equipment may cause physical injury to a person or damage to equipment.
OZXB_ and OZXA_: Terminal clamp sets, the type name, accessories
2. Product overview
Motorized change-over switches (type OTM_C) are suitable for remote control. You can operate the
motorized change-over switches either electrically by using the motor operator or manually by using
the handle. The operation, either electrical or manual, can be chosen by the selector switch “Motor/
Manual” on the motor operator. Motorized change-over switches consist of the change-over switch
and the motor operator.
11 1
I 12
II
5
M
M
2
an..
Man
M
4
A04120
8 6 7 9 4 10 10
3. Quick start
This is a quick guide only meant for those who need a reminder of how to operate the unit. For more
detailed instructions, see chapter 6.
I
II
M
Man.
M
M
an..
Man
M
A04122
Figure 3.1 Operating the motorized change-over switch electrically; remote control
I
II
A04136
M
M
an..
Man
M
2
1
I
II
M
1
2
Man.
ICK!
M
CL
Man.
A04123
I
II
A04137
M
M
an..
Man
M
4. Installation
4.1 Mounting the motorized change-over switch
OMD
I
A04126
M
M
an..
Man
M
A2
I
II
A1
M
M
an..
Man
M
A04127
M5 M6 M10
3,5...4Nm 31...35.4 lb.in
Figure 4.2 Motorized change-over switches, drilling hole distances / screw-mounting, [mm/in]
mm 66
A2
134,5 65 87,5
20 83
9,0 23 3
127
100 122
14
A1 130
130 150
65
25 20
48,5 72
162 A 25
160 37
B
M00111 / OTM160-250E_C_M D
OTM160-250_C_M
E2 E3 E4
A 35 35 35
A1 116 116 116
A2 223 258 293
B 238 273 308
mm
A2 66
87,5
134,5 65 20 23 3 83
127 9,0
25
100 122 14
A1 130
130 150
170 65
170 A 25
48,5 72 20
D
B
160 37
M00115 / OTM160-250E_WC_M
OTM160-250_WC_M
E2 E3 E4
A 43 43 43
A1 116 116 116
A2 239 282 325
B 254 297 340
mm 66
in A2 87,5 2.6
134,5 65 20 23 3.44
0.91 3
5.30 2.56 9,0 0.79 0.12 83/35,5
127 0.35 3.27/1.40
5.00 25
0.98
130 14
100 5.12 0.55
3.94
A1 150
130 5.91
5.12 122 65
4.80 170 2.56
6.69
20
170 A 25 0.79
6.69 0.98 48,5 72
B 19.09 2.83
160 37
M00112 / OTM200U_C_M D
6.30 1.46
OTM200_C_M
U2 U3 U4
A 43 / 1.69 43 / 1.69 43 / 1.69
A1 116 / 4.57 116 / 4.57 116 / 4.57
A2 239 / 9.40 282 / 11.10 325 / 12.80
B 254 / 10 297 / 11.69 340 / 13.39
A2 81
mm
146 95 11 25 56 4 126
137,25 25 87
32,5
156 150 17
A1
120 160
185
95
20,5
185,25 A
192 43
31,25
B
M00113 / OTM315-400E_C_M E
OTM315-400_C_M
E2 E3 E4
A 44 44 44
A1 142 142 142
A2 261 305 349
B 280 323 367
mm 56 4
A2
137,25 95 11 25 126/51,5
87
32,5
17
150
120
160
A1
156 185
220 95
B
195,25 A 20,5
31,25
M00116 / OTM315-400E3-4WCM
B 192 43
OTM 315-400_WC_M
E3 E4
A 54 54
A1 142 142
A2 334,5 388,5
B 353 407
81
A2 3.19
mm 56 4
in 146 11 2.20 0.16 126 / 51,5
5.75 25
137,25 95 0.43 0.98 4.96 / 2.03
5.40 3.74 25/ 87
0.98 3.43 32,5
1.28
150 17
120 5.91 0.67
4.72
160
A1 6.30
156 185
6.14 7.28 95
220 3.74
8.66
OTM400_C_M
U2 U3 U4
A 54 / 2.13 54 / 2.13 54 / 2.13
A1 142 / 5.59 142 / 5.59 142 / 5.59
A2 281 / 11.06 335 / 13.19 389 / 15.31
B 299 / 11.77 353 / 13.90 407 / 16.02
A2 110,5
mm
158
5 138,6
147,5 39 64,1 132,6
13,5 61,5 45
145
200 198
A1 210
160 250 17
20,5
OTM630-800E_C_M
E2 E3 E4
A 65 65 65
A1 180 180 180
A2 325 390 455
B 346 411 476
mm A2
in
158 5 132,6
6.22 39 13,5 0.20
1.54 5.22
147,5 0.53
64,1
5.81 2.52 45
1.77 145
198 5.71
200 7.80
7.87 210 400
160 8.27 15.75
6.30 250 17
A1 9.84 0.67
509
20.04
20,5
0.8
212,5 A 47,5
8.37 1.87 43
B 1.69
M00139/ OTM600U_C_M B
256
OTM600_C_M
10.08
U2 U3 U4
A 65/2.56 65/2.56 65/2.56
A1 180/7.09 180/7.09 180/7.09
A2 325/12.8 390/15.35 455/17.91
B 346/13.62 411/16.18 476/18.74
mm
335
A2 167
80
158,5
13,5 50
186 127
74,5 15
200 50
171
136 100
306 272
A1 400
260 250
M
206
Man.
19
A
253 63
296,5
M00256/OTM1000-1250E_C_M B
OTM1000-1250_C_M
E2 E3 E4 75
A 80 80 80
230 230
15
A1 230
A2 396,5 476,5 556,5
B 426,5 506,5 586,5
mm
335
A2
186 200 158,5 167
Ø13,5 50 127
74,5 15
171 136
100 83
372 258
M
206
Man.
19
253 A 63
B 296,5
M00258/OTM1600E_C_M B
15
75
OTM1600_C_M
E2 E3 E4
A 80 80 80
A1 230 230 230
A2 396,6 476,5 556,5
B 426,5 506,5 586,5
335
mm 13.19
in 167
6.58
A2 136 / 5.36
200 74,5
7.88 13,5 / 0.53 15
50 / 1.97 2.93 0.59
186 / 7.33
171 /6.74
1
1
2
2
83
3.27
338
13.32 400
260 206 372 246 326 15.76
10.24 8.12 14.65 9.69 12.84
A1 258 405
546 10.16 15.96
21.51
M
Man.
19
0.75
1
1
253 / 9.97 A
63
2.48
15
0.59
B 296,5 75
M00257/OTM1200U_C_M B
11.68 2.95
OTM800-1200_C_M
U2 U3 U4
A 80/3.15 80/3.15 80/3.15
A1 230/9.06 230/9.06 230/9.06
A2 396,5/15.62 476,5/18.77 556,5/21.92
B 426,5/16.8 506,5/19.96 586,5/23.11
mm
A2 335
200
167
158,5
127
Ø 13,5 100 136
15
186 74,5
171 100
85
376,4
400
260 262,4
342,4
A1
330,4 206
M
19
276 A
86 296,5
M00259/OTM2000-2500E_C_M B
15
B 75
OTM2000-2500_C_M
E2 E3 E4
A 126 126 126
A1 230 230 230
A2 488,5 614,5 740,5
B 518,5 644,5 770,5
mm A2 429
245
200
141
100
Ø 13,5
223
156,5 15
63 191
186 85
171
400
284
A1 296 376
240
280 364 410
206
100,5 4,8
170,5
73 15
61
258 A 325
377
B 424
M00432/OTM3200_C_M B
OTM3200_C_M
E2 E3 E4
A 140 140 140
A1 250 250 250
A2 521,5 661,5 801,5
B 551,5 691,5 831,5
4.3 Connections
II
50 mm
10 mm
II
A06272
10 mm
50 mm
Figure 4.16 Mounting the connections to the motorized change-over switches OTM3200_C_M
Do not install the motorized change-over switches in any other position than those
described above.
4.5 Labelling
1 2
I
II
A04128
M
M
Man.
Ma n.
5. Connecting
3 LINE LINE
11 14 12 23 24
3
24
12
14 23
11
M
I
II
PE N L
A04129
F2
2 M
M
1 24 vdc
Man.
Ma n.
A B C
2
1
F2
L I 0
PE N- + C II
Do not couple power for the control terminal. See the correct terminal for the
power supply in Figure 5.1
The control voltage (output C = 24Vdc) on the control terminal is non-isolated, see
box 2 in Figure 5.1
When relay outputs are used with inductive loads (such as relays, contactors and
motors), they must be protected from voltage spikes using varistors, RC-protectors
(AC current) or DC current diodes (DC current).
6. Operating
Never open any covers on the product. There may be dangerous external control
voltages inside the motorized change-over switch even if the voltage is turned off.
Never handle control cables when the voltage of the motorized change-over switch
or external control circuits are connected.
I
II
A04131
M
M
an..
Man
M
2. Turn the Motor/Manual selection switch to the Motor (M) position, see Figure 6.2.
M
M
A04132
Man.
Man.
I
0
II
The motor operator is protected from overloading by a fuse (F1) under the motor
operator. Only use the same type of fuse that is described on the label close to
the fuse.
If a new command is given before the switch has reached the position of the
previous command, the fuse (F1) may operate.
I II 0
I+II (_CL)
I - position
0 - position
I+II (_CL)
A04130
II -position
The continuous control command can be given with push buttons, cam switches
or with relays incorporated in PLC equipment or with other suitable contacts.
0 - command
I+II (_CL)
I - position
0 - position
I+II (_CL)
A04133
II - position
M
M
Man.
A04134
I
II
A04135
ICK!
M
M
CL
an..
Man
M
Electrical operation is prevented when the handle is attached to the switch panel.
6.3 Locking
You can lock the motorized change-over switch to a specific position.
I
II
A04136
M
M
an..
Man
M
2
1
I
II
A04137
M
M
an..
Man
M
The following chart shows the locking state information (the voltage on motor operator supply
needed).
M Man.
M M
Man. Man.
Man
14 12 14 12 14 12 14 12 14 12
12
14
11 11 11 11 11 11
24 24 24 24 24
24
A04144
23 23 23 23 23 23
7. Technical data
Motor operator, control circuit Value Cabling
Rated operational voltage U [V] 220-240 Vac 50-60 Hz
110-125 Vac/dc 50-60 Hz
48 Vdc
24 Vdc
Operating voltage range 0.85... 1.1 x U
Operating angle 90° 0-I, I-0, 0-II, II-0; 180° I-0-II
Operating time See the Table 7.2
Protection degree IP 20, front panel
Rated impulse withstand voltage 4 kV
Uimp
Voltage supply PE N L 1,5 -2,5 mm2
F2 Max. MCB 16 A
Cable of the push-buttons (no SELV) C II I 0 1,5 -2,5 mm2
Maximum cable length 100 m
State information of locking (no SELV)
Handle attached or motor operator locked 11-12-14 (C/O) 1,5 -2,5 mm2
Locking motor operator 23-24 (NO) 1,5 -2,5 mm2
Operating temperature -25... +55 °C
Transportation and storage temperature -40... +70 °C
Altitude Max. 2000 m
a)
Under nominal conditions
Table 7.2 Specified technical data of motor operators
Measurement Value
Handle attached or motor operator locked 11-12-14 (C/O): 5 A AC-1 / 250 V
Locking motor operator 23-24 (NO): 5 A AC-1 / 250 V
SCPD Max. MCB C2A
8. Accessories
8.1 Terminal clamp sets
OTM2000-2500E_C_
OTM3200E_C_
OZXB3
OZXB4
OZXB5
OZXB6
OZXB7L
OTM1000-1600E_C_ OTM800-1200U_C_
OZXB3 OZXA-1200_
OZXB4 OZXA-1206_
OZXB5 * max. 1 pcs/side
OZXB6*
OZXB7L
OTM630-OTM800E_C_ OTM600U_C_
OZXB3 OZXA-800_
OZXB4 OZXA-806_
OZXB5
OZXB6* * max. 1 pcs/side
OZXB7L
OTM315-OTM400E_C_ OTM400U_C_
OZXB2L OZXA-400_
OZXB3 OZXA-406_
OZXB7
OZXB7L
OZXB8
OZXB9
OTM160-OTM250E_C_ OTM200U_C_
OZXB1L OZXA-200_
OZXB2 OZXA-206_
OZXB2L
OZXB8
OZXB9
A04138
Figure 8.1 Mounting of the terminal clamp sets, types OZXB_ and OZXA_
3
II
630A
800A
OTZC_
2
A04139
Figure 8.2 Mounting of the bridging bars (type OTZC_) to the motorized change-over switches
OTM160-800E_C_
3
II
1
OTZC_
OTM1600E_C
OTM1000-1250E_C OTZC43, OTZC44 OTZC53, OTZC54
OTM800-1200U_C
2
A04189
Figure 8.3 Mounting of the bridging bars (type OTZC_) to the motorized change-over switches
OTM1000-1600E_C_ and OTM800-1200U_C_
II
I
3
1
OTZC_
2
A04190
Figure 8.4 Mounting of the bridging bars (type OTZC_) to the motorized change-over switches
OTM2000-2500E_C_
II
3
1
OTZC_
2
A06273
Figure 8.5 Mounting of the bridging bars (type OTZC_) to the motorized change-over switches
OTM3200E_C_
G M M
OTS250 T1S
OTM160-250_C_ OTS250_ M8 15...22Nm 5/6DIA IN. 133-195LB.IN.
G
OTS400 T1S OTM315-400_C_ OTS400_ M10 30...44Nm 266-390LB.IN.
G
OTS800 T1S OTM600-800_C_ OTS800_ M12 50...75Nm 433-664LB.IN.
1 M
G G
OTS_ T 1S OTS_ T 1L
2
M
OTS250G
T
1L 4 3
OTS400G
T
1L
OTS800G
T
1L
I
1 II
2
A04140
Figure 8.6 Mounting of the terminal shrouds (type OTS_ ) to the motorized change-over switches
OTM160-800E_C_
G
OTS1600 T 1S
3
4
2 I
II
G
OTS1600 T 1L
OTM1000-1600E_C_
OTM800-1200U_C
2
M
A04198
Figure 8.7 Mounting of the terminal shrouds (type OTS_ ) to the motorized change-over switches
OTM1000-1600E_C_ and OTM800-1200U_C_
G G
OTS2500 T 1S, OTS4000 T 1S
1 3
4
I
II
G G
OTS2500 T 1L, OTS4000 T 1L OTM2000-2500E_C_
OTM3200E_C_
M
2
A04213
Figure 8.8 Mounting of the terminal shrouds (type OTS_ ) to the motorized change-over switches
OTM2000-2500_C_ , OTM3200_C_
21
OTM_C max 2+2
37 I OTM_CF max 2+2
OA 1G10 OA 3G01
I
11
0
13
II
I 13
II 13
14 23
24
23 11
14 21
24 12
11 22
M
12 21
Man. 22
2 I
OA 1G10 OA 3G01
0
II
XXXXXX
II
I 13
14 23
24
II 13
14 23
11
12 21
24 22
11
12 21
M
22
Man.
A04141
OA 1G10 OA 3G01
3 I
I+II
II
L N L N
LN1 LN2
Fuse
ODPS230 OTM_C
Fuse
L N C II I 0 PE N L C II I 0
A06289
Figure 8.10 The dual power source, type ODPS230. Connection diagram ODPS230.
L1 L2 N L1 L2 N
ODPSE230C
ODPS F1 F2
X 11
X 13
2 1
2 1
A06290
X 12
1 2
L N PE
OTM_C
Figure 8.11 The dual power source, type ODPSE230C. Connection diagram ODPSE230C.
1 2 3
6,3x0,8
OTM630-800E_C_ 2
OMZB3_
OTM600U_C_
1
a
3 4
b 6,3x0,8
2 3
OTM1000-2500E_C_
6,3x0,8
OMZB4_ OTM800U_C_
!
OTM3200E_C_ ICK
CL
1 4
I
A06124
II
Figure 8.12 Mounting of the voltage sensing connectors, type OMZB_
M
M
B an..
Man
M
Sp
are
Fu
Sp se
are
80 Fu
se
Sp
are
Fus
Sp e
are
Fus
I
e
3
M
M
Man.
Ma n.
Sp
M
are
Fus
Sp e
are
Fus Man
Ma n..
e
M
M
Man.
Ma n.
Sp
are
Fus
Sp e
are
Fus
e
Sp
are
Fus
e
Spare Fuse
Sp
are
xxxxA xxxV
Fuse
Fus
e
FUSE
OTVS0 OTM160-250_C
20 1
A B
580
1365 3
I
II
2
A04261
M an.
Figure 8.13 Handle and spare fuses can be stored on the motorized change-over switch by mounting
the accessory OTVS_
9. UL standard switches
A B D
OTM200-1200U_C 0 13 mm/0.5 in 13 mm/0.5 in
OTM200U_C OTM400U_C
Cable size Cable size Cable size Cable size
AWG C MCM C AWG C MCM C
4-3 100 mm/4 in 250 200 mm/8 in 2 100 mm/4 in 250 250 mm/8 in
2 100 mm/4 in 300 250 mm/10 in 1 100 mm/4 in 300 250 mm/10 in
1 100 mm/4 in 1/0 125 mm/5 in 350 350 mm/12 in
1/0 125 mm/5 in 2/0 150 mm/6 in
2/0 150 mm/6 in 3/0-4/0 175 mm/7 in
3/0-4/0 175 mm/7 in
OTM600-1200U_C
Cable size Cable size
AWG C MCM C
2 100 mm/4 in 250 200 mm/8 in
1 100 mm/4 in 300 250 mm/10 in
1/0 125 mm/5 in 350 300 mm/12 in
2/0 150 mm/6 in 400 330 mm/13 in
3/0-4/0 175 mm/7 in 500 356 mm/14 in
600 381 mm/15 in
Figure 9.1 Clearances per UL 98, minimum enclosure size or equivalent volume
1 4
2
5
I
II I
II
M
M
an..
Man
M
110 21
,5
110
Phase barrier
type 68838 on:
OTM600U_C
173
118
I
II
M
M
Man..
Man
127 21
,5
Phase barrier 167
type 68912 on: 127
OTM800U_C_
OTM1000-1600E_C_
OTM2000-2500E_C_
170
100
I
II
Man.
21
14 ,5
1 2
Phase barrier 19 40
2
type CXBY69470 on:
OTM3200E_C_
170
I 100
II
A06274
ABB Oy
Protection and Connection
P.O Box 622, FI-65101 Vaasa, Finland
www.abb.com/lowvoltage