FROM 33 kV HT PANEL
AT MCR

19/33, kV1RX3CX185 Sq mm
XLPE Al. Arm.CABLE
A A

AUX. TRAFO.
75kVA,33/415V
Z=4% Dyn11,ONAN
OCTC,±5%
@ STEPS OF 2.5%

1R x 3.5C x 50SQMM
AL. ARM. XLPE LT CABLE

MCR ACDB PANEL


INDOOR TYPE TP MCB
(FLOOR MOUNTED)
TYPE-2 SPD,
40KA

6A, SP MCB
R Y B
B B

CT MFM CL-1.0
125/5A WITH
RS485
CL.0.5, 10VA PORT

125A, 25KA
4P,MICROPROCESSOR ON OFF TRIP
BASED MCCB WITH
LSIG

415V ±10%, 50HZ ±5%, 125A, 3Ph, 4WIRE 10kA FOR 1 Sec., Al.BUS BAR,TPN

25A 25A 16A 10A 16A 16A 16A 10A 20A 10A 6A 25A 6A
DP 25A 25A 25A 10A 10A 10A 10A 6A 10A 10A 16A 25A 6A 25A
FP FP DP DP DP DP FP FP FP DP DP DP FP FP FP FP FP FP FP DP DP FP DP DP FP FP
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
C-CURVE C-CURVE D-CURVE D-CURVE C-CURVE D-CURVE D-CURVE C-CURVE C-CURVE C-CURVE C-CURVE C-CURVE C-CURVE
C D-CURVE D-CURVE D-CURVE D-CURVE D-CURVE D-CURVE D-CURVE D-CURVE C-CURVE D-CURVE D-CURVE C-CURVE C-CURVE D-CURVE C

MODULE CLEANING SYSTEM - 4 kW


WATER TREATMENT SYSTEM 5 kW
3Ph. INDUSTRIAL SOCKET - 1 kW

PERIPHERY LIGHTING - 1.65 kW

DBCR MOTORIZED ISOLATOR 1

DBCR MOTORIZED ISOLATOR 2

DBCR MOTORIZED ISOLATOR 3

DBCR MOTORIZED ISOLATOR 4


MARSHALLING BOX - 0.15 kW
EXHAUST FAN (OTHER AREA)
EXHAUST FAN (SWITCHGEAR

MARSHALLING BOX - 0.1kW


AUXILIARY TRANSFORMER
HT PANEL SPACE HEATER,
INVERTER TRANSFORMER
BATTERY CHARGER - 5 kW

SECURITY ROOM - 0.5 kW

TO LIGHTING PANEL - 5 kW
AC (SCADA ROOM) - 1 kW
AC (CONF. ROOM) - 1 kW

BOREWELL PUMP - 5 kW
3C X 2.5 SQ.MM CU AR.

3C X 2.5 SQ.MM CU AR.


3C X 2.5 SQ.MM CU. FL.

3C X 2.5 SQ.MM CU. FL.


3C X 2.5 SQ.MM CU. FL.
3C X 2.5 SQ.MM CU. FL.

4C X 10 SQ.MM AL AR.
4C X 10 SQ.MM AL AR.

4C X 10 SQ.MM AL AR.
4C X 4 SQ.MM CU AR.
3C X 10 SQ.MM Al. AR.

4C X 10 SQ.MM AL AR.
4C X 4 SQ.MM CU. AR.

LAMP, SOCKET - 3 kW
4C X 10 SQ.MM AL AR.

4C X 4 SQ.MM AL AR.

4C X 4 SQ.MM AL AR.

4C X 4 SQ.MM AL AR.

4C X 4 SQ.MM AL AR.
4C X 4 SQ.MM CU AR.

4C X 4 SQ.MM AL. AR.


ROOM) - 0.5 kW
UPS - 5 kVA

- 0.2 kW

- 0.2 kW

- 0.2 kW

- 0.2 kW

SPARE

SPARE

SPARE

SPARE

SPARE
SPARE

SPARE
0.3 kW
ALL DIMENSIONS ARE IN mm & WEIGHTS ARE IN kg UNLESS OTHERWISE SPECIFIED.

D D
UPS-5kVA
3PH-415V TO
1PH-230V

4C x 4SQ.MM CU. AR.

INDOOR PANEL UPS DB PANEL INDOOR PANEL LDB PANEL


(WALL MOUNTED) ON OFF LOCATION:MCR (WALL MOUNTED) LOCATION:MCR
40A 4A SP MCB
DP R Y B
MCB
C-CURVE
20A FROM MCR AND ICR ACDB PANEL
230V ±10%, 50HZ ±3%, 40A,1Ph, 2WIRE FP ON OFF
MCB
C-CURVE 1R X 4C X 10 sq. mm.
CU Cable
10A 10A 6A 6A 6A 6A 6A 6A 6A 6A 6A 6A 10A
E DP DP DP DP DP DP DP DP DP DP DP DP DP 415V ±10%, 50HZ ±3%, 25A,3Ph, 4WIRE E
OUTDOOR PANEL PERIPHERY LIGHTING DB
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB 4A SP MCB
STAND MOUNTED LOCATION: FIELD
R Y B
6A 6A 20A 6A 6A 6A 6A 6A 6A 6A 6A 20A
(MARSHALLING BOX) - 0.2 kW

DP DP DP DP DP DP DP DP DP DP DP DP
MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB
SCADA EWS + OWS+Printer

FAS PANEL + DETECTOR +


TRANSFORMER CCU UNIT

ALARM SYSTEM - 0.25 kW

+ELCB +ELCB +ELCB +ELCB +ELCB +ELCB +ELCB +ELCB +ELCB +ELCB +ELCB +ELCB MCB
SOCKET FOR ETHERNET
SCADA PANEL - 0.75 kW

EMERGENCY LIGHTING

415V
3C x 2.5 Sq.mm CU. AR.

3C x 2.5 Sq.mm CU. AR.


3C x 2.5 Sq.mm CU. AR.

CCTV DVR & MONITOR


3C x 2.5 Sq.mm CU. AR.

3C x 2.5 Sq.mm CU. FL.


3C x 2.5 Sq.mm CU. FL.

3C x 2.5 Sq.mm CU. FL.

3C x 2.5 Sq.mm CU. FL.

3C x 2.5 Sq.mm CU. FL.

3CX2.5sqmm. CU. AR.

FP, 10A NEUTRAL LINK


HT PANEL ROOM LIGHTING

BATTERY ROOM LIGHTING


AUTO MAN
10 A POWER

STORE ROOM LIGHTING

SCADA ROOM LIGHTING


PANTRY LIGHTING AND
WMS - 0.25 kW

WASHROOM LIGHTING
CCTV - 0.2 kW

CCTV - 0.2 kW

LIGHTING AND OTHER

TRANSFORMER YARD
CONTACT

CONFERENCE ROOM
OFF ON

METERING YARD
INVERTER AREA
SPARE

SPARE

SPARE

415V ±10%, 50HZ ±3%, 10A, 3Ph, 4WIRE


0.25 kW

0.1 kW
0.4 kW

OTHER LOAD
1 kW

AND FAN

AND FAN

SPARE

SPARE
LOAD
R1 Y1 B1 R2 Y2 B2 R3 Y3 B3

MCB+ELCB MCB+ELCB MCB+ELCB


F SP 6A SP 6A SP 6A
F

1R X 4C X 4 sq. mm.
CU Ar. Cable

C1 C1 C1 C2 C2 C2 C3 C3 C3
STREET
LIGHT QTY.
TOTAL WATT

CKT-1 CKT-2 CKT-3


ALL INFORMATION CONTAINED IN THIS DOCUMENT IS CONFIDENTIAL &

1. ACDB PANEL SHALL BE FIXED TYPE, SINGLE/DOUBLE FRONT, FLOOR MOUNTED AND
LEGEND DISCRIPTION
UPSDB SHALL BE SINGLE FRONT WALL MOUNTED TYPE.
2. ALL FRAMES & LOAD BEARING MEMBERS SHALL BE FABRICATED OF COLD ROLLED
TWO WINDING TRANSFORMER Engineering, Procurement and Construction (EPC) Contractor for designing,
SHEET STEEL OF THICKNESS 2.0MM. THE NON LOAD BEARING & COVERS SHALL BE engineering, procuring, supplying, constructing, erecting, testing and
SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF

MOULDED CASE CIRCUIT BREAKER commissioning of 50 MWAC (2*10 MWAC + 2*15 MWAC) solar photovoltaic (PV)
OF CRCA SHEET OF STEEL OF THICKNESS 1.6MM AND REMOVABLE GLAND PLATE
G power plant with associated transmission system and comprehensive Operation & G
OF THICKNESS 3.0MM.
3. CABLE ENTRY SHALL BE FROM BOTTOM. MINIATURE CIRCUIT BREAKER Maintenance (O&M) for 10 (ten) years at Pavagada Ultra Mega Solar Park of
4. NEOPRENE RUBBER GASKET SHALL BE PROVIDED TO MAKE DUST & VERMIN Tumakuru District in Karnataka.
AMARARAJA POWER SYSTEMS LIMITED.

PROOF. EARTH LEAKAGE CIRCUIT BREAKER


5. QUANTITY RATING OF MODULE MOUNTING SYSTEM MOTORS & LOADS SHALL BE
CONFIRMED IN MODULE CLEANING SYSTEM DRAWINGS &DOCUMENT. MFM MULTI FUNCTION METER
6. MFM AT ACDB INCOMER SHALL BE WITH RS485 PORT FOR SCADA COMMUNICATION.
7. FOR PUMPS, WATER TREATMENT PLANTS, COMPLETE STARTER / CONTROL/ CURRENT TRANSFORMER
REFERENCE DRAWING:-
PROTECTION IS LOCALIZED. ONLY POWER FEEDER IS CONSIDERED AT ACDB.
INDICATION LAMP
1. ARPSL-KREDL-E-02-010-008 - AUXLILIARY TRANSFORMER SIZING CALCULATION
8. FOR PERIPHERY LIGHTING CIRCUIT FEEDERS, MCB ALONG WITH TIMER
CONTACTOR AUTO/MANUAL SELECTION SWITCH SHALL BE PROVIDED. CONTACTOR 2. ARPSL-KREDL-E-01-051-008 - UPS SIZING CALCULATION
SHALL BE PROVIDED WITH ON/OFF PUSH BUTTONS, ON/OFF INDICATION LAMP. 3. ARPSL-KREDL-E-02-006-027 - AUXILIARY CABLE SCHEDULE
TC WINDING TEMP. CONTROLLER
9. QUANTITY / RATING OF MODULE CLEANING SYSTEM MOTORS & LOADS SHALL BE
CONFIRMED IN MODULE CLEANING SYSTEM DRAWINGS & DOCUMENTS. CBCT ELR
CORE BALANCED CURRENT TRANSFORMER
H WITH EARTH LEAKAGE RELAY H

SURGE PROTECTION DEVICE

T TIMER

1 2 3 4 5 6 7 8 9 10 11 12
DATE: