SEL-751A Feeder Protection

• Overcurrent
• Voltage
• Power factor
• Frequency and rate of change of frequency
• Breaker failure
• Arc-flash detection (AFD) and protection
• Thermal – with RTDs
SEL-751A
Feeder Protection and Much More!

• Autoreclosing control
• Synchronism check
• Synchrophasor measurements
• Breaker monitor
• Station dc battery monitor
• Demand, peak demand metering
Bus

SEL-751A
27*
P
59*GQ
O
81 UR* Protection
3 Undervoltage Overvoltage
Phase
Frequency Elements
Ground
Neg-Seq

50 P
50 GQ
P
51 GQ
3 AF*
Arc-Flash Overcurrent Time-Overcurrent
Overcurrent Phase Phase
Ground Ground
Neg-Seq Neg-Seq

50
NAF* 50N 51N 25*
1
Arc-Flash Neutral Neutral Neutral Time-
Synchronism
Overcurrent Overcurrent Overcurrent
Check
Breaker

52 AFD* Arc-Flash Detector


79*
Autoreclosing
27* 59*

1 Undervoltage Overvoltage
Line *Optional Feature
Current-Based Protection
• Instantaneous overcurrent (50P, 50Q, 50G, 50N)
♦ 4 independent set points for each type
♦ Provides 50P1 phase identification

• Time overcurrent (51P, 51G, 51N, 51Q)


♦ 2 independent set points (51P, 51G, 51N)
♦ 1 per-phase set point (51A, 52B, 51C)
♦ 1 set point for 51Q

• Underfrequency / overfrequency (81):


6 independent set points either underfrequency
or overfrequency
Instantaneous / Definite-Time
Overcurrent Elements

4 Levels (1–4) for


Each Element Type
Time-Overcurrent Elements

• Set each element with 1-cycle


or electromechanical reset
• Select from 5 U.S. curves
or 5 IEC curves
5 U.S. Curves

• Moderate
• Inverse
• Very
• Extreme
• Short time
5 IEC Curves

• Class A (standard)
• Class B (very)
• Class C (extreme)
• Long time
• Short time
Adaptive Phase Overcurrent Elements

Perform reliably in presence of:


• CT saturation
• DC offset
• Off-frequency harmonics
CT Saturation

Secondary
Current
Primary
Current
CT

Saturated Signal
Traditional Filter Performance

Trip Threshold

Saturated
Signal Nonsaturated Signal

Traditional
Filter Signal
Fast Operation With CT Saturation

300 Bi-Polar Peak Traditional Instantaneous


Detector Filter Element Pickup
Secondary Current (A)

200

100

-100

-200

0 1 2 3 4 5 6
Cycles
Voltage-Based Protection

• Undervoltage (27, 27S):


2 independent set points each
• Overvoltage (59, 59G, 59Q, 59S):
2 independent set points each
• 20 to 70 Hz frequency tracking