Vent-O-Mat Catt Program: Version: 3.0.0

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

VENT-O-MAT

CATT PROGRAM
EXAMPLE 3 - DEEP WELL

Designer : Anonymous
Filename : C:\My Programs\VENT-O-MAT CATT\Projects\Vent-O-Mat Example 3 (Deep wel
l system).vdw
Date : Sunday, 1 June 2008
Description : An example of a deep well sizing
Printed: 1 Jun 2008 Page 1

DEEP WELL ANALYSES:

Input Data:
Pump maximum flow rate - 22.5 l/s
Pump operating head - 70 m
Ground level - 1508 m
Rest water level - 1495 m
Minimum operating level - 1480 m
Pump intake level - 1475 m
Deep well diameter - 150 mm
Fluid type - Water
Installation - Vertical turbine pump

Calculated results:
Air valve -
RBXb Double Acting air valve - 80 mm
Optimum collector dimensions:
Collector dimensions - A = 625 mm
Collector dimensions - B = 150 mm
Collector dimensions - C = 225 mm

The software program was developed for the convenience of its users. Although every reasonable effort has been made to ensure that the results are
correct and accurate, neither Vent-O-Mat, DFC nor the program developers, assumes any responsibility for any results, interpretation thereof or any use
made of the results obtained with this program. This program is not presented nor is it intended to be used as a complete study and the use of this
software program or output shall be made under the direction of trained engineers exercising their independent judgement regarding the proposed design.

VENT-O-MAT CATT PROGRAM : VERSION: 3.0.0


Copyright (C) 2008 by Sinotech CC. Vent-O-Mat, P.O. Box 5064, Benoni South, 1502, South Africa
TEL: 027 11 748 0200, FAX: 027 11 421 2749, E-MAIL: ventomat@dfc.co.za, WEBSITE: www.ventomat.com