Combinations for Variable speed drives

customer assembly Altivar 71


Motor starters: 200…240 V supply voltage
DF526131

Applications
Circuit-breaker/contactor/drive combinations can be used to ensure continuous service of the installation with
optimum safety.
The type of circuit-breaker/contactor coordination selected can reduce maintenance costs in the event of a motor
short-circuit by minimizing the time required to make the necessary repairs and the cost of replacement
equipment. The suggested combinations provide type 1 or type 2 coordination depending on the drive rating.

Type 2 coordination: A motor short-circuit will not damage the device or affect its settings. The motor starter must
be able to operate once the electrical fault has been removed. The electrical isolation provided by the circuit-
breaker will not be affected by the short-circuit. Welding of the contactor contacts is permissible if they can be
DF526153

separated easily.

Type 1 coordination: The electrical isolation provided by the circuit-breaker will not be affected by the incident
and no other elements apart from the contactor are damaged as a result of the motor short-circuit.

The drive controls the motor, provides protection against short-circuits between the drive and the motor and
protects the motor cable against overloads. The overload protection is provided by the drive's motor thermal
protection. If this protection is removed, external thermal protection must be provided.
Before restarting the installation, the cause of the trip must be removed.
PF101002

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power Reference Reference Rating Reference
(1) (2) (3) (4)
kW HP A
Supply voltage 200…240 V 50/60 Hz single phase - Type 2 coordination
0.37 0.5 6.3
0.75 1 10
1.5 2 18
2.2 3 25
3 – 25
4 5 40
GV2 L20
+ 5.5 7.5 50
LC1 D25pp
+ Supply voltage 200…240 V 50/60 Hz single phase - Type 1 coordination
ATV 71HU22M3 0.37 0.5 10
0.75 1 14
1.5 2 18
2.2 3 25
3 – 25
4 5 40
5.5 7.5 50

(1) Standard power ratings for 230 V 50/60 Hz 4-pole motors.


The values expressed in HP conform to the NEC (National Electrical Code).
(2) Breaking capacity of circuit-breakers according to standard IEC 60947-2:
Circuit-breaker Icu (kA) for 240 V
GV2 L 50
GV3 L 100
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
(4) Replace ppwith the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
LC1 D 50 Hz B5 E5 F5 M5 P5 U5
60 Hz B6 E6 F6 M6 – U6
50/60 Hz B7 E7 F7 M7 P7 U7
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.
(5) A line choke must be added, see page 60805/16.

2 60808-EN_Ver1.0.indd
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 200…240 V supply voltage
(continued)
DF526131

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW HP A A
Three-phase supply voltage 200…240 V 50/60 Hz - Type 2 coordination
0.37 0.5 4 –
0.75 1 10 –
1.5 2 10 –
2.2 3 14 –
3 – 18 –
DF526153

4 5 25 –
5.5 7.5 40 –
7.5 10 50 –
11 15 65 –
15 20 80 480
18.5 25 100 600
22 30 100 600
30 40 150 1350
37 50 150 1350
PF101003

45 60 220 1980
55 75 220 1980
75 100 320 1920
Three-phase supply voltage 200…240 V 50/60 Hz - Type 1 coordination
0.37 0.5 4 –
0.75 1 10 –
1.5 2 10 –
2.2 3 14 –
3 – 18 –
4 5 25 –
5.5 7.5 40 –
7.5 10 50 –
GV2 L22 11 15 65 –
+ 15 20 80 480
LC1 D25pp
+ 18.5 25 100 600
ATV 71HU30M3 22 30 100 600
30 40 150 1350
37 50 150 1350
45 60 220 1980
55 75 220 1980
75 100 320 1920

(1) Standard power ratings for 230 V 50/60 Hz 4-pole motors.


The values expressed in HP conform to the NEC (National Electrical Code).
(2) NS80HMA, NSXppp: Products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the
letter corresponding to the circuit-breaker breaking performance (B, F, N, H, S, L).
Breaking capacity of circuit-breakers according to standard IEC 60947-2:
Circuit-breaker Icu (kA) for 240 V
B F N H S L
130 – – – – – –
50 – – – – – –
100 – – – – – –
– 40 85 90 100 120 150
– – 40 85 100 120 150
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and
protection components” catalogue.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
50 Hz
60 Hz
50/60 Hz
50 Hz (LX1 coil)
60 Hz (LX1 coil)
40…400 Hz (LX9 coil)
50 Hz (LX1 coil)
60 Hz (LX1 coil)
40…400 Hz (LX9 coil)
40…400 Hz (LX1 coil)
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

60808-EN_Ver1.0.indd 3
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 380…415 V supply voltage
(continued)
PF095516

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW HP A A
Three-phase supply voltage 380…415 V 50/60 Hz - Type 2 coordination
0.75 1 4 –
1.5 2 6.3 –
2.2 3 10 –
3 – 14 –
4 5 14 –
5.5 7.5 25 –
7.5 10 32 –
11 15 40 –
15 20 50 –
DF526158

18.5 25 50 –
22 30 65 –
30 40 80 480
37 50 100 800
45 60 150 1350
55 75 150 1350
75 100 220 1980
90 125 220 1980
110 150 220 1980
132 200 320 1920
PF107476SE

160 250 320 1920


200 300 320 1920
220 350 500 3000
250 400 500 3000
280 450 500 3000
315 500 NS800L Micrologic 2 or 5 500 3000
355 – NS800L Micrologic 2 or 5 800 1600
400 600 NS800L Micrologic 2 or 5 800 1600
500 700 NS1000L Micrologic 2 or 5 1000 2000

(1) Standard power ratings for 4-pole motors 50/60 Hz 400 V.


The values expressed in HP comply with the NEC (National Electrical Code).
(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.
For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance
(B, F, N, H, S, L).
Breaking capacity of circuit-breakers according to standard IEC 60947-2:
NSX160pMA150 Circuit-breaker Icu (kA) for 400 V
+ B F N H S L
LC1 D115pp 130 – – – – – –
+ 50 – – – – – –
ATV 71HD45N4
70 – – – – – –
– 25 36 50 70 100 150
– – 36 50 70 100 150
– – – – – – 150
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
LC1 Fppp , LC1 B: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control
and protection components” catalogue.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
50 Hz
60 Hz
50/60 Hz
50 Hz (LX1 coil)
60 Hz (LX1 coil)
40…400 Hz (LX9 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
50…400 Hz (WB1 coil)
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

4 60808-EN_Ver1.0.indd
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 380…415 V supply voltage
(continued)
PF095516

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW HP A A
Three-phase supply voltage 380…415 V 50/60 Hz - Type 1 coordination
0.75 1 4 –
1.5 2 6.3 –
2.2 3 10 –
3 – 14 –
4 5 14 –
5.5 7.5 25 –
7.5 10 32 –
11 15 40 –
DF526158

15 20 50 –
18.5 25 50 –
22 30 65 –
30 40 80 480
37 50 100 800
45 60 150 1350
55 75 150 1350
75 100 220 1980
90 125 220 1980
110 150 220 1980
132 200 320 1920
PF107476SE

160 250 320 1920


200 300 320 1920
220 350 500 3000
250 400 500 3000
280 450 500 3000
315 500 NS800L Micrologic 500 3000
2 or 5 (LR OFF)
355 – NS800L Micrologic 800 1600
2 or 5 (LR OFF)
400 600 NS800L Micrologic 800 1600
2 or 5 (LR OFF)
500 700 NS1000L Micrologic 1000 2000
2 or 5 (LR OFF)
(1) Standard power ratings for 4-pole motors 50/60 Hz 400 V.
The values expressed in HP comply with the NEC (National Electrical Code).
(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.
NSX160pMA150 For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance
+ (B, F, N, H, S, L).
LC1 D115pp Breaking capacity of circuit-breakers according to standard IEC 60947-2:
+ Circuit-breaker Icu (kA) for 400 V
ATV 71HD45N4 B F N H S L
130 – – – – – –
50 – – – – – –
70 – – – – – –
– 25 36 50 70 100 150
– – 36 50 70 100 150
– – – – – – 150
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and
protection components” catalogue.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
50 Hz
60 Hz
50/60 Hz
50 Hz (LX1 coil)
60 Hz (LX1 coil)
40…400 Hz (LX9 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
50…400 Hz (WB1 coil)
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

60808-EN_Ver1.0.indd 5
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 440…480 V supply voltage
(continued)
PF095516

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW HP A A
Three-phase supply voltage 440…480 V 50/60 Hz - Type 2 coordination
0.75 1 4 –
1.5 2 6.3 –
2.2 3 10 –
3 – 10 –
4 5 14 –
5.5 7.5 25 –
7.5 10 32 –
11 15 40 –
15 20 50 –
DF526158

18.5 25 50 –
22 30 50 –
30 40 65 –
37 50 100 600
45 60 100 600
55 75 150 1350
75 100 150 1350
90 125 150 1350
110 150 220 1980
132 200 220 1980
160 250 320 1920
PF107476SE

200 300 320 1920


220 350 320 1920
250 400 500 3000
280 450 500 3000
315 500 NS800L Micrologic 2 or 5 500 3000
355 – NS800L Micrologic 2 or 5 500 3000
400 600 NS800L Micrologic 2 or 5 800 1600
500 700 NS1000L Micrologic 2 or 5 1000 2000

(1) Standard power ratings for 400 V 50/60 Hz 4-pole motors.


The values expressed in HP conform to the NEC (National Electrical Code).
(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.
For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance
(B, F, N, H, S, L).
Breaking capacity of circuit-breakers according to standard IEC 60947-2:
Circuit-breaker Icu (kA) for 440 V
NSX160pMA150 B F N H S L
+ 130 – – – – – –
LC1 D115pp 20 – – – – – –
+
ATV 71HD55N4 50 – – – – – –
65 – – – – – –
– 20 35 50 65 90 130
– – 30 42 65 90 130
– – – – – – 130
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and
protection components” catalogue.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
50 Hz
60 Hz
50/60 Hz
50 Hz (LX1 coil)
60 Hz (LX1 coil)
40…400 Hz (LX9 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

6 60808-EN_Ver1.0.indd
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 440…480 V supply voltage
(continued)
PF095516

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW HP A A
Three-phase supply voltage 440…480 V 50/60 Hz - Type 1 coordination
0.75 1 4 –
1.5 2 6.3 –
2.2 3 10 –
3 – 10 –
4 5 14 –
5.5 7.5 25 –
7.5 10 32 –
11 15 40 –
15 20 50 –
DF526158

18.5 25 50 –
22 30 50 –
30 40 65 –
37 50 100 600
45 60 100 600
55 75 150 1350
75 100 150 1350
90 125 150 1350
110 150 220 1980
132 200 220 1980
PF107476SE

160 250 320 1920


200 300 320 1920
220 350 320 1920
250 400 500 3000
280 450 500 3000
315 500 NS800L Micrologic 2 or 5 500 3000
355 – NS800L Micrologic 2 or 5 500 3000
400 600 NS800L Micrologic 2 or 5 800 1600
500 700 NS1000L Micrologic 2 or 5 1000 2000

(1) Standard power ratings for 400 V 50/60 Hz 4-pole motors.


The values expressed in HP conform to the NEC (National Electrical Code).
(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.
For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance
(B, F, N, H, S, L).
Breaking capacity of circuit-breakers according to standard IEC 60947-2:
Circuit-breaker Icu (kA) for 440 V
NSX160pMA150
+ B F N H S L
LC1 D115pp 130 – – – – – –
+ 20 – – – – – –
ATV 71HD55N4
50 – – – – – –
65 – – – – – –
– 20 35 50 65 90 130
– – 30 42 65 90 130
– – – – – – 130
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and
protection components” catalogue.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
50 Hz
60 Hz
50/60 Hz
50 Hz (LX1 coil)
60 Hz (LX1 coil)
40…400 Hz (LX9 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

60808-EN_Ver1.0.indd 7
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 380…480 V supply voltage
(continued)
PF095516

Motor starters for IP 54 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW HP A A
Three-phase supply voltage 380…415 V 50/60 Hz - Type 2 coordination
0.75 1 4 –
1.5 2 6.3 –
2.2 3 10 –
3 – 14 –
4 5 14 –
5.5 7.5 25 –
7.5 10 32 –
11 15 40 –
15 20 50 –
DF526158

18.5 25 50 –
22 30 65 –
30 40 80 480
37 50 100 800
45 60 150 1350
55 75 150 1350
75 100 150 1350

Three-phase supply voltage 440…480 V 50/60 Hz - Type 2 coordination


0.75 1 4 –
1.5 2 6.3 –
2.2 3 10 –
DF5107482

3 – 10 –
4 5 14 –
5.5 7.5 25 –
7.5 10 32 –
11 15 40 –
15 20 50 –
18.5 25 50 –
22 30 65 –
30 40 100 600
37 50 100 600
45 60 100 600
55 75 150 1350
75 100 150 1350

(1) Standard power ratings for 400 V 50/60 Hz 4-pole motors.


The values expressed in HP conform to the NEC (National Electrical Code).
(2) NS80HMA, NSXppp: Products sold under the Merlin Gerin brand.
For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance
(N, H, L).
Breaking capacity of circuit-breakers according to standard IEC 60947-2:
NSX160pMA150
+ Circuit-breaker Icu (kA) for 400 V
LC1 D115pp B F N H S L
+ 100 – – – – – –
ATV 71WD55N4 50 – – – – – –
70 – – – – – –
– 25 36 50 70 100 150
Circuit-breaker Icu (kA) for 440 V
B F N H S L
100 – – – – – –
20 – – – – – –
50 – – – – – –
– 20 35 50 65 90 130
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
50 Hz
60 Hz
50/60 Hz
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

8 60808-EN_Ver1.0.indd
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 380…480 V supply voltage
(continued)
DF526131

Motor starters for IP 20 drives on base plate


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW HP A A
Three-phase supply voltage 380…415 V 50/60 Hz - Type 2 coordination
0.75 1 4 –

1.5 2 6.3 –

2.2 3 10 –

3 – 14 –

4 5 14 –
DF526153

5.5 7.5 25 –

7.5 10 32 –

Three-phase supply voltage 440…480 V 50/60 Hz - Type 2 coordination


0.75 1 4 –

1.5 2 6.3 –

2.2 3 10 –

3 – 10 –

4 5 14 –

5.5 7.5 25 –

7.5 10 32 –

(1) Standard power ratings for 4-pole motors 50/60 Hz 400 V.


The values expressed in HP comply with the NEC (National Electrical Code).
(2) Breaking capacity of circuit-breakers according to standard IEC 60947-2:
Circuit-breaker Icu (kA) for 400 V
100
50
(3) Composition of contactors:
LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
(4) Replace pp with the control circuit voltage reference given in the table below:
GV2 L16
+ Volts a 24 48 110 220 230 240
LC1 D18pp 50 Hz
+ 60 Hz
ATV 71PU40N4Z 50/60 Hz
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

60808-EN_Ver1.0.indd 9
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 690 V supply voltage
(continued)
DF526131

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW A A
Three-phase supply voltage 690 V 50/60 Hz - Type 2 coordination
2.2 6.3 78
3 6.3 78
4 10 138
5.5 10 138
7.5 14 170
11 18 223
15 25 327
18.5 25 350
DF526153

22 32 448
30 40 560
37 50 700
45 65 910
55 100 1100
75 100 1100
90 320 2880
110 320 2880
132 320 2880
160 320 2880
200 320 2880
200 630 5670
101014

250 630 5670


315 630 5670
400 630 5670
500 800 7200

(1) Standard power ratings for 690 V 50 Hz 4-pole motors.


(2) NSppp: Products sold under the Merlin Gerin brand.
Breaking capacity of circuit-breakers according to standard IEC 60947-2:
Circuit-breaker Icu (kA) for 690 V
4
5
75
GV2 L16
+ (3) Composition of contactors:
LC1 D25pp LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.
+ LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and
ATV 71HU75Y protection components” catalogue.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
50 Hz
60 Hz
50/60 Hz
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
40…400 Hz (LX1 coil)
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

10 60808-EN_Ver1.0.indd
Combinations for Variable speed drives
customer assembly Altivar 71
Motor starters: 690 V supply voltage
(continued)
PF103273

Motor starters for IP 20 drives


Motor Drive Circuit-breaker Line contactor
Power (1) Reference Reference (2) Rating Irm Reference (3) (4)
kW A A
Three-phase supply voltage 690 V 50/60 Hz - Type 1 coordination
250 500 –
315 500 –
400 500 –
500 630 –
630 800 –

(1) Standard power ratings for 690 V 50 Hz 4-pole motors.


(2) NSX630LMA, NSppp: Products sold under the Merlin Gerin brand.
Breaking capacity of circuit-breakers according to standard IEC 60947-2:
PF526089

Circuit-breaker Icu (kA) for 690 V


35
75
(3) Composition of contactors:
LC1 Fppp, LC1 BL: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control
and protection components” catalogue.
(4) Replace pp with the control circuit voltage reference given in the table below:
Volts a 24 48 110 220 230 240
40…400 Hz (LX1 coil) –
50…400 Hz (WB1 coil) –
For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.
PF107586SE

NSX630LMA500
+
LC1 F400
+
ATV 71HC25Y

60808-EN_Ver1.0.indd 11