Document Number Rev
POWER CONSUMPTION & HEAT DISSIPATION
P15340-CYD-V013-I-DC-0001 0
POWER CALCULATION
Power
NO. ITEM QTY Unit TOTAL Unit
Consumption
Power
NO. ITEM QTY Unit TOTAL Unit
Consumption
3. FIELD EQUIPMENT
Power
NO. ITEM QTY Unit TOTAL Unit
Consumption
The enclosure is placed free-standing row, ambient temperature being 30°C maximum and 25 °c
Minimum
Emissivity ε = 0.14
Maximum temperature increase which may occur inside the enclosure compared with the ambient is as
Follows:
(TINTERNAL - TU) max = (∆T) max = Qv / (k x A) = 600W/ [5.5(W/ m2°C)] x 6.02 m2] = 18.13 °C
Therefore,
Max Enclosure Internal Temperature that is reachable for this panel
= (18.13 + 30) °C = 48.13°C< 600°C
At 48°C, temperature of the box does not exceed 60°C
Hconv, side = 1.42 (∆T/ L) 0.25 = 1.42 (18.13/ 2)0·25 = 2.46W/ (m2 °C)
Radiation Factor
Qrad = ε Aσ (Ts4-TSurr4) where σ is Stefan Boltzmann Constant
= 0.14 x (11.2m2 + 0.64m2) (5.67 x 10-8 W/m2 K4) x [(60+273)4 - (48.13+273)4] K4
= 156.13W
Required cooling output QE
= Heat Dissipation in Enclosure - Heat Loss by Convection and Radiation
= 600 - (327.04W + 21.88W + 156.13W)
= 94.95W
Conclusion
The result shows that the heat loss by convection and radiation is less than heat dissipated in the
Enclosure. Therefore, cooling is required. In addition, the internal temperature will not exceed 600C
Under current conditions.