Design Criteria: File Path: D:/Perodua/Drainage Calc/Drain/Msma/Drain
Design Criteria: File Path: D:/Perodua/Drainage Calc/Drain/Msma/Drain
Design Criteria: File Path: D:/Perodua/Drainage Calc/Drain/Msma/Drain
File No.:
Description: Perodua Tampoi Designer: Aini Checker:
_OSD Date: August 28, 2019 Date:
Reference Calculation Output
1. Design Criteria
Design Manual = MSMA 2nd Edition
Method = Simplified Method
Type of OSD = Below Ground
2. Proposed Development
Figure Location = Johor - Johor Bahru
5.A1 Region = Region 5 - Southern
Project Area = 1.138 ha
Impervious Area = 0.900 ha
Pervious Area = 0.238 ha
Percentage of Impervious Area = 79.09%
Terrain = Mild
Inlet Pipe
Table Inlet pipe diameter = 558 mm
5A3
Table Inlet/ha = 236.73 1/s/ha
5A2 For area of 1.138 ha, Inlet Flow = 1.138 x 236.7/1000 = 0.269m3/s
Primary Outlet
Primary outlet discharge should not exceed the lesser PSD flow.
Ho = Depth - Diameter/2 - H
Ho = 0.90 - 0.200/2 - 0.000
Ho = 0.800 m
Secondary Outlet
Table Required overflow pipe diameter = 526 mm
5A3
Ao = π × (D/2)2
= π × (0.526/2)2
= 0.217 m2