Professional Documents
Culture Documents
DIP Manual
DIP Manual
Teleprotection
Version A
User's Manual
DIP5K/EN U/A11
User's Manual DIP5K/EN U/A22
DIP5000
Teleprotection
CONTENT
BLANK PAGE
Overview DIP5K/EN OS/A22
DIP 5000
OVERVIEW
Overview DIP5K/EN OS/A22
CONTENTS
1. OVERVIEW 5
1.1 Safety Section 5
1.2 Main Characteristics 5
1.3 Installation 5
1.4 Human machine Interface DIP5000 DIGITAL 5
1.5 Human machine Interface DIP5000 ANALOG SINGLE TONE 5
1.6 Human machine Interface DIP5000 ANALOG DUAL TONE 5
1.7 Commissioning 5
1.8 Maintenance 5
2. DEFINITIONS 6
DIP5K/EN OS/A22 Overview
BLANK PAGE
Overview DIP5K/EN OS/A22
MODIFICATIONS PAGE
BLANK PAGE
Overview DIP5K/EN OS/A22
1. OVERVIEW
The DIP5000 User manual includes eight sections:
• Safety section,
• Presentation,
• Installation,
• Commissioning,
• Maintenance.
1.1 Safety Section
The Safety Section provides full information on safe handling, commissioning and testing of
this equipment. This Safety Section also includes reference to typical equipment label
markings.
1.2 Main Characteristics
The Presentation Section provides full information on DIP5000 DIGITAL and ANALOG
features, equipment description, main characteristics and performances.
1.3 Installation
The Installation Section provides full information on equipment description, shipment,
environmental conditions, boards installation, power supply boards and VDC range,
equipment connection.
1.4 Human machine Interface DIP5000 DIGITAL
The Human Machine Interface Section provides full information on HMI software installation,
system requirement, operating the Password manager, HMI interface description, operating
the HMI.
1.5 Human machine Interface DIP5000 ANALOG SINGLE TONE /DUAL TONE CODED
The Human Machine Interface Section provides full information on HMI software installation,
system requirements, operating the Password manager, HMI interface description, operating
the HMI (Single tone and dual tone modes).
1.6 Commissioning
The Commissioning Section provides full information on DIP5000 commissioning,
configuring hardware, testing and fault isolation during commissioning, checks.
1.7 Maintenance
The Maintenance Section provides full information on DIP5000 Maintenance, Testing and
Fault isolation, firmware upgrade.
DIP5K/EN OS/A22 Overview
2. DEFINITIONS
Summary of some of the terms and acronyms used in this manual
• Nominal transmission time - The time elapsed between the moment of a change of
state at the transmitter input and the moment of the corresponding change of state at
the receiver output when there is no interference or noise. This time does not include
propagation time.
• Guard - The guard signal is a signal that is transmitted to monitor the integrity of the
teleprotection system and it effectively supervises the channel in terms of the signal
quality. Other monitoring is also employed. When present, the guard signal inhibits
any command output of the teleprotection receiver.
• Permissive trip - Protection schemes where the received command initiates tripping
without qualification by local protection. Intertrip channels utilize similar principles to
permissive trip channels, however, security against unwanted operation and
dependability of correct operation are prime requirements. Speed of operation is
usually sacrificed to meet security and dependability requirements, particularly in
analogue systems.
• Direct trip / Inter-trip - Protective schemes where the received command initiates
tripping without qualification that are similar in operation to permissive trip with the
exception that security against unwanted operation and dependability of correct
operation are prime requirements. Speed of operation is usually sacrificed to meet
security and dependability requirements.
• Blocking - Protective schemes where the received command blocks the operation of
local protection. These channels utilise similar principles to permissive trip channels;
however dependability of operation and speed are prime requirements. . VF - Voice
Frequency.
• LF (AF) - Low Frequency. Signals transmitted in the 0-4 kHz base band. Also called
Audio Frequency.
• FV - Guard Frequency.
• FC - Command Frequency.
DIP 5000
SAFETY SECTION
Safety Section DIP5K/EN SS/A22
1. INTRODUCTION 3
BLANK PAGE
Safety Section DIP5K/EN SS/A22
1. INTRODUCTION
This Safety Section and the relevant equipment documentation provide full information on
safe handling, commissioning, and testing of this equipment. This Safety Section also
includes references to typical equipment label markings.
The technical data in this Safety Section is typical only, see the technical data section of the
relevant equipment documentation for data specific to a particular equipment.
Before carrying out any work on the equipment the user should be familiar with
the contents of this Safety Section and the ratings on the equipment’s rating
label.
Reference should be made to the external connection diagram before the equipment is
installed, commissioned, or serviced.
Language specific, self-adhesive User Interface labels are provided in a bag for some
equipment.
• Are familiar with the installation, commissioning, and operation of the equipment and
of the system to which it is being connected;
• Are able to perform safely switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and
to isolate, ground, and label it;
• Are trained in the care and use of safety apparatus in accordance with safety
engineering practices;
Disposal
It is recommended that incineration and disposal to water courses be avoided.
The equipment should be disposed of in a safe manner. Any equipment
containing batteries should have them removed before disposal, taking
precautions to avoid short circuits. Particular regulations within the country of
operation may apply to the disposal of the equipment.
Safety Section DIP5K/EN SS/A22
6.4 Environment
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be mounted in a specific cabinet or housing which will
enable it to meet the requirements of IEC 60529 with the classification of degree of
protection IP54 (dust and splashing water protected).
Pollution Degree - Pollution Degree 2 Compliance is demonstrated by reference to safety
Altitude - Operation up to 2000m standards.
IEC 60255-27:2005
EN 60255-27: 2005
DIP5K/EN SS/A22 Safety Section
Personnel qualification: authorized and properly trained personnel only are admitted to carry out
installing, programming, commissioning, maintenance, troubleshooting, and operation of the
equipment.
Technical specifications: the equipment must be operated within the technical specifications. Failure
to do so may result in personal injuries or equipment damage.
Insertion and removal of plug-in modules: neither removal nor insertion of modules, except for
redundant power supply units, is permitted. Before inserting or removing modules, the power supply of
the equipment has to be switched OFF.
ESD protection: the modules in this equipment contain devices which can be damaged by
electrostatic discharges. Appropriate measures must be taken before unpacking modules or removing
them from equipment racks. Grounding straps for technical personnel and the provision of anti-static
workbenches are essential precautions to prevent ESD damage when handling or working on
modules. Modules may only be shipped either in their original packing or installed in equipment racks.
Cabinets which are not secured to the floor tip forwards when the hinged frame is opened. Do not
open the hinged frame without precautions.
Electrical installation: this is Class I equipment as defined in EN 60255-27. The equipment and
cubicle/cabinet shall be solidly bonded to the protective (earth) conductor for both safety and
electromagnetic compatibility reasons. The equipment must be protected by circuit breakers or fuses
with a maximum rating of 16 Amps.
All circuit breakers in the cabinet must be switch OFF before working on the equipment.
The isolating terminals of the external cables must be kept open during installation, maintenance and
before storage, decommissioning, and disposal.
Ensure that all supply inputs have been isolated/switched off before installing the equipment.
When an analog DIP 5000 is connected to cables, pilot wires, or leased circuits, the equipment must
only be used in conjunction with barrier transformers withstanding a 15kVrms or 20kVrms test voltage
at 50Hz/60Hz for 1 mn, according to national regulations or electric utilities’ practice.
DIP5K/EN SS/A22 Safety Section
Fibre optic installation: Optical connectors: clean all optical connectors by an approved method
before making any optical connection; do not rotate the optical connector unnecessarily when making
an optical connection. When not connected, fit all optical plugs and couplings with protective caps.
Damage to optical fibres: when dressing fibres, take care not to exceed the minimum bend radius
(typically 35mm) and do not over tighten binders used for dressing as damage may result.
Back cover: hazardous voltages and/or hazardous energy levels behind the back cover.
Working on the equipment: do not work on the system or connect or disconnect cables during
periods of lightning.
Electrical strength test: do not repeat any electrical tests. Improper test methods can cause severe
damage to the equipment. Electric strength and earth continuity tests have been performed in the
factory.
EMC: this is class A equipment. In a domestic environment, this equipment may cause radio
interference. In this case, the user may be required to take appropriate measures.
Power supply for alarm: this shall be protected against overcurrents and short circuit conditions.
Safety Section DIP5K/EN SS/A22
Common interface UT148: hazardous voltages and/or hazardous energy levels on the module and
the cable. Do not touch the module and the cable leads.
Relay interface SRxxx: hazardous voltages and/or hazardous energy levels on the module and the
cable. Do not touch the module and the cable leads.
Laser / LED: take care using optical cards IR182/IR185, class I Laser/LED product.
Using HMI DIP 5000: the teleprotection link can be disturbed while using certain maintenance
functions of the DIP 5000 HMI (e.g. forcing commands).
During routine tests with the DIP 5000 in operation, “Reset device” in the menu should not be
activated, as this causes the DIP 5000 to be re-initialized and thus be blocked for approximately 5
seconds. During this time no commands can be transmitted.
Commissioning: do not close/establish any connections to protection devices until the DIP 5000 is
properly commissioned.
DIP5K/EN SS/A22 Safety Section
BLANK PAGE
Main Characteristics DIP5K/EN IT/A22
DIP 5000
MAIN CHARACTERISTICS
Main Characteristics DIP5K/EN IT/A22
CONTENTS
1. SAFETY INSTRUCTIONS 7
2. DEFINITIONS 8
3. OVERVIEW 9
5. DIGITAL MODE 14
5.1 Digital Transmission Principle 14
5.2 Available Digital Interfaces 14
5.2.1 Digital Interfaces Supported 15
5.2.2 Opto-electrical Redundancy 16
5.3 Optimization of the Transmission Medium 16
5.4 Number of Commands 16
5.5 Applications 16
5.6 Link Check 16
5.7 Maintenance and Loopback 17
6. ANALOG MODE 18
6.1 Frequency Coding in the 0 - 4 kHz band Single Tone . 18
6.2 Frequency Coding in the 0 - 4 kHz band Dual Tone . 18
6.3 Analog Mode Specific Features 19
6.3.1 Transmission Medium (all versions) 19
6.3.2 Optimization of the Medium - Single Tone 19
6.3.3 Number of Commands - Single Tone 20
6.3.4 Link Test 21
6.3.5 Unblocking Function 21
6.3.6 Alive Output 21
6.3.7 External Alarm Input 21
6.3.8 DIP 5000 Connected to a Power Line Carrier (PLC) 22
DIP5K/EN IT/A22 Main Characteristics
7. UNIT DESCRIPTION 24
8. MAIN CHARACTERISTICS 26
8.1 Mechanical Characteristics 26
8.2 Environmental Characteristics 27
8.3 Power Supply Electrical Characteristics 28
8.4 Operational Characteristics 29
8.5 Digital Transmission Characteristics 31
8.6 Voice Frequency Transmission Characteristics 32
8.6.1 General characteristics 32
8.6.2 Band sharing single tone 32
8.6.3 Band sharing dual tone 33
9. PERFORMANCE 34
9.1 Digital interfaces 34
9.1.1 Transfer time as a function of transmission speed (digital and IR 182 boards) 34
9.1.2 Transfer time as a function of transmission speed (IR 185 board) 34
9.1.3 Security 34
9.1.4 Dependability 35
9.2 Analog Interface Single Tone Version 35
9.2.1 Transmission time 35
9.2.2 Security (bandwidth 300-3400 Hz) 35
9.2.3 Dependability (bandwidth 300-3400 Hz) 35
9.3 Analog Interface Dual Tone 36
9.3.1 Transmission time 36
9.3.2 Security (bandwidth 300 1900 Hz) 36
9.3.3 Dependability (bandwidth 300 1900 HZ) 36
Main Characteristics DIP5K/EN IT/A22
LIST OF FIGURES
FIGURE 1 - DIP 5000 ENVIRONMENT 10
FIGURE 2 - EXAMPLE OF NETWORK CONFIGURATION 13
FIGURE 3 - DIGITAL INTERFACES 15
FIGURE 4 - REDUNDANCY SCHEME 16
FIGURE 5 - LOOPBACK 17
FIGURE 6 - TRANSMISSION - VOICE FREQUENCY BAND ST 18
FIGURE 7 - TRANSMISSION - VOICE FREQUENCY BAND DUAL TONE 18
FIGURE 8 - LINK TEST - ANALOG MODE 21
FIGURE 9 - THE DIAGRAM SHOWS AN EXAMPLE OF THE AUTOMATIC POWER PROCESS22
FIGURE 10 - VOICE FREQUENCY INTERFACE 23
FIGURE 11 - DIP 5000 RACK 24
LIST OF TABLES
TABLE 1 - INPUT COMMAND FREQUENCY CODING 19
TABLE 2 - DIP 5000 BOARDS 25
TABLE 3 - MECHANICAL CHARACTERISTICS 26
TABLE 4 - ENVIRONMENTAL CHARACTERISTICS 27
TABLE 5 - POWER SUPPLY CHARACTERISTICS 28
TABLE 6 – OPERATIONALS CHARACTERISTICS 30
TABLE 7 – DIGITAL TRANSMISSION CHARACTERISTICS 31
TABLE 8 – VOICE FREQUENCY GENERAL CHARACTERISTICS 32
TABLE 9 - BAND SHARING SINGLE TONE 32
TABLE 10 - FREQUENCIES DUAL TONE 33
TABLE 11 – FREQUENCIES AND BANDWIDTH (DUAL TONE ) 33
TABLE 12: TRANSMISSION TIME MEASUREMENTS FOR ELECTRICAL AND IR182 CARDS 34
TABLE 13 - TRANSMISSION TIME MEASUREMENTS FOR IR185 CARD INCLUDING MUX 34
TABLE 14 – TRANSMISSION TIME SINGLE TONE 35
TABLE 15 – TRANSMISSION TIME DUAL TONE 36
DIP5K/EN IT/A22 Main Characteristics
BLANK PAGE
Main Characteristics DIP5K/EN IT/A22
MODIFICATIONS PAGE
NOTE: From revision C, the numbering system of the document has changed
according to the AREVA standards, on the other hand the index of the
document has been incremented for a better follow-up.
DIP5K/EN IT/A22 Main Characteristics
BLANK PAGE
Main Characteristics DIP5K/EN IT/A22
1. SAFETY INSTRUCTIONS
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE USER
SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
SECTION DIP5K/EN SS/A11 OR LATER ISSUE, THE TECHNICAL DATA
SECTION AND THE EQUIMENT RATING LABEL.
2. DEFINITIONS
Summary of some of the terms and acronyms used in this manual
• Nominal transmission time - The time elapsed between the moment of a change of
state at the transmitter input and the moment of the corresponding change of state at
the receiver output when there is no interference or noise. This time excludes
propagation time.
• Guard - The guard signal is a signal that is transmitted to monitor the integrity of the
teleprotection system and it effectively supervises the channel in terms of signal
quality. Other monitoring is also employed. When present, the guard signal inhibits
any command output of the teleprotection receiver.
• Permissive trip - Protection schemes where the received command initiates tripping
without qualification by local protection. Intertrip channels utilize similar principles to
permissive trip channels, however, security against unwanted operation and
dependability of correct operation are prime requirements. Speed of operation is
usually sacrificed to meet security and dependability requirements, particularly in
analog systems.
• Blocking - Protective schemes where the received command blocks the operation of
local protection. These channels use similar principles to permissive trip channels.
However, dependability of operation and speed are the prime requirements.
• VF - Voice Frequency.
• LF (AF) - Low Frequency. Signals transmitted in the 0-4 kHz base band. Also called
Audio Frequency.
• FV - Guard Frequency ()
• FC - Command Frequency
3. OVERVIEW
The AREVA DIP 5000 is maintenance-free equipment, easy to commission, and offers a
high level of flexibility for installation.
The DIP 5000 can be supervised and managed through a telecom network.
The DIP 5000 Teleprotection unit is designed to work in hostile environmental conditions that
can be found in buildings housing very high voltage relay equipment.
To this end, it is fitted with protection devices against electromagnetic interference
(induced or radiated).
Although initially designed for power applications, DIP 5000 Teleprotection unit is also used
in all applications where the following criteria are essential:
• Decoding and advanced processing of the signals received, enabling faithful return of
the information transmitted.
DIP5K/EN IT/A22 Main Characteristics
»Mux »Mux
Optical fibres
Optical fibres
OPGW
OPGW
SDH network
SDH network
Microwave
Microwave
…..
…..
Digital network
C37.94 V11 V11 C37.94
Optical fibres G703 G703 Optical fibres
Optical fibres
Protection Protection
relay Pilot cables
relay
Leased line
Pilot cables
Analogie
Leased Muxline
…..
…..
» HV Line
»
D0047ENc
• Real-time measurement and display of the transfer time and BER when using the
Human Machine Interface software (Digital mode only)
• Local and remote DIP 5000 entirely programmable using HMI software running on PC
computer (remote only available in digital mode)
• Permissive tripping,
• Blocking,
• Direct tripping.
• Reinforced blocking
• IRIG-B interface for synchronizing event logging on both sides. The IRIG-B format is:
B12x interface (modulated), standard 200-04, input impedance 4.7kΩ at 1000Hz,
modulation ratio: 3:1 to 6:1, input signal peak to peak: 100mv to 10v.
• Auxiliary power supply, either the same or a different voltage, 2 separate connectors
to increase dependability and availability.
• Adding an I/O board module provides combinatorial logic on inputs and outputs.
• Local and remote (digital mode) teleprotection identity and address definition
• Setting the time and date of local and remote (digital mode) teleprotection
• Definition of the alarm activation bit error rate or SNR (digital mode)
• Alarm status
• Inhibition status
• Operating commands
• Line locking
• Remote loopback
• Opto-electrical redundancy
Converter COM 1
DIP5000a
I.P.
TMS5000 System 1 port
COM 2
DIP5000d
HMI Demon Optical
LAN
DIP5000d
I.P.
Converter COM 3
DIP5000d
8 ports
Electrical
DB
DIP5000d
COM 4
DIP5000a
D0486ENb
5. DIGITAL MODE
5.1 Digital Transmission Principle
The transmission principle used is that of constant transmission of a digital frame
corresponding to the standby state. Closing one or more contacts modifies this frame and
transmits a command message. The length of the messages depends on the Teleprotection
variant chosen. They are encoded by means of 4, 8 or 16 words selected in a code. The
code is calculated to provide maximum security and dependability.
5.2 Available Digital Interfaces
The architecture and principles used enable the DIP 5000 Digital/Analog Teleprotection unit
to adapt to various transmission media:
• Interface for 4-wire voice frequency transmission support (Leased Line, Pilot cable,
PLC).
Main Characteristics DIP5K/EN IT/A22
V11/X24
T
DCE
R
LINE
DIP5000 S (Clock)
S'
G703.1 Codirectional
T
Tx DCE
LINE
Clock
R Clock
Rx
DIP5000
G703.6
T
Tx DCE
LINE
Clock
R Clock
Rx
DIP5000
OPTICAL FIBER
Data Optical Fiber R Data
Tx
x
Clock Clock
DIP5000 DIP5000
Data Optical Fiber Data
Rx Tx
Clock Clock
Clock LINE
Optical Fiber Clock
Rx
DIP5000
D0045ENb
»Mux »Mux
Optical fibres
Optical fibres
OPGW
OPGW
SDH network
SDH network
Microwave
Microwave
…..
Alternate ….. Alternate
Path Path
V11 Digital network V11
G703 G703
• the local loopback can be carried out while transmitting to the remote,
• commands can be forced using the HMI while in local or remote mode.
Tx
LOCAL REMOTE
LOOPBACK Rx LOOPBACK
Transmitter
blocked or not
LOCAL REMOTE
FIGURE 5 - LOOPBACK
This feature allows the checking of the entire transmission link.
DIP5K/EN IT/A22 Main Characteristics
6. ANALOG MODE
6.1 Frequency Coding in the 0 - 4 kHz band Analog Single Tone
As part of this principle, the standby state (all the contacts whose position is to be
transmitted are open) corresponds to the continuous transmission of a guard frequency FV.
If one or more contacts close, transmission of the guard frequency stops and one or more
command frequencies FC are transmitted (via closed contact or transmitted command).
Standby state
Guard Frequency
Transmission of
2 commands
FC1 FC2
D0048ENa
DF
F1 F2 F3 F4 F5 F6 F7 F8
D0485ENa
• Bandwidth optimization
In the absence of a command, the link can transmit other signals (for example, telephony or
data). In this particular case, the guard frequency FV can be the telephone signalling
frequency of the telecommunication system and hence can be generated by the latter. When
a command is transmitted, the transmission of telephony, calling, and, as appropriate, higher
frequency signals is interrupted for the benefit of the command frequencies.
DIP5K/EN IT/A22 Main Characteristics
• Power optimization
A specific exploitation mode, called Enhanced Mode, allows the use of all the available
power of the PLC equipment to transmit the teleprotection commands.
In this scheme, the level of the transmitted command towards the PLC depends on the
number of simultaneous commands to transmit, in order to obtain a P.E.P. level, on the R.F.
medium, equivalent to the level of the maximum power of the PLC.
6.3.3 Number of Commands - Single Tone
The architecture of the DIP 5000 unit is such that standard boards can be used to provide 2
or 4 command versions.
Two variants are available:
• normal mode
In this mode, the commands are fully independent and can be transmitted simultaneously.
The output level is shared between the command signals. Due to the simultaneous
transmission aspect, the level of each command signal is limited so that the sum is equal or
less than the admissible transmitted level.
• enhanced mode
This mode, defined by a particular algorithm coding mode, forces the command output signal
to the max output available power. This solution is particularly suited to the PLC medium and
sensitive links where the optimized SNR is reached.
In the command state, the DIP 5000 transmits its command signal at the maximum output
reference. In the case of two simultaneous commands, the level of each signal is reduced in
order not to exceed the maximum output reference.
This arrangement is automatically set back to the initial setting (max reference) as soon as
the simultaneous condition is cancelled.
The DIP 5000 with its 4 commands is arranged in a 2+2 operating mode. The 4 commands
are shared into 2 groups combined with a priority rule.
Each group keeps to the automatic max reference concept. The 2+2 priority rule is designed
for optimized signal transmission.
Priority rule
Test T
T
CPU CPU
R Test R
• Trip threshold: adjustable from 10 to 20 dB under the guard nominal level by 0.1 dB
steps.
6.3.6 Alive Output
The voice frequency interface module provides an output contact (solid state relay) which is
closed as long as the DIP 5000 teleprotection is powered. This feature allows the
communication equipment or the protection automation system to be aware of the powering-
off of the teleprotection unit when the guard frequency is emitted by the communication
equipment.
The circuit for this contact is located in the communication interface connector.
6.3.7 External Alarm Input
The voice frequency interface board has an opto-electronic input circuit that is activated by
voltage (48V nominal). This input can be configured by the HMI to trigger an alarm on the
teleprotection unit. This alarm can be minor or major, and is activated after a delay selected
by the user (from 0 to 2.5 seconds with 100 ms step).
This feature allows, for example, the DIP 5000 teleprotection to take into account the
powering-off or the absence of power, as well as a dedicated alarm issued by the
communication unit.
The circuit for this input is located in the communication interface connector.
DIP5K/EN IT/A22 Main Characteristics
Input commands
ON
R.F Output
(PLC)
• 8 frequency tones
• Interface for 4 wires voice frequency transmission support (Leased Line, pilot cable,
PLC).
ANALOGUE
Tx
DIP5000 Rx DCE
DCE ALARM
LINE
BLE / BOOST
BLR
ALIVE
D0046ENc
7. UNIT DESCRIPTION
The DIP 5000 Teleprotection unit is made up of a EUROPE type rack 19" wide and 3 units
high, in which the printed circuit boards holding the components (6-unit format, 220-mm
deep) are housed.
The modules are connected by a motherboard which also holds the sockets to which are
fitted the connectors to the power supply, the transmission medium and the operating
system.
37,7 mm
3
(3U)
57,1 mm 2 132,5 mm
4 5 6
1 300 mm
or
316 mm
37,7 mm
D0051XXb
* In order to increase dependability, two power supply modules can be used, with the same
or different input voltage.
** In addition to communication interface
*** France only
DIP5K/EN IT/A22 Main Characteristics
8. MAIN CHARACTERISTICS
8.1 Mechanical Characteristics
Dimensions
Height 132 mm (3U)
Width 483 mm (19")
Depth 307 mm or 323 mm
Mass 7.6 kg
Conductor cross-section section on medium AWG 20 to 22 (0.324 to 0.519 mm²)
connector
Allowable cable diameter on medium access 8.2 mm maximum
connector
Cable for plug in terminal (I/O commands) 0.08 < Section < 2.5 mm²
Protection index IP30
Climatic aspect
Nominal operation range
Temperature -10°C to +55°C
Relative humidity 90% at 23 °C
Operating limits
Temperature -40°C to +70°C
Relative humidity 95% at 40 °C
Storage limits conditions
Temperature -40°C to +85°C
Relative humidity 100% at 23 °C with no condensation
Product Safety
Generic standard EN 60255-5 (2000)/EN60255-27(2005)
Teleprotection Standard IEC 60834-1 (1999)/EN 60834-1 (2000)
Insulation resistance > 30.104 MΩ/500 VDC
Dielectric tests at 50Hz 2.5 kV on I/O commands
1kV on communication link
Impulse xxxwithstand level ± 5 kV on I/O commands
Earth continuity < 22 mΩ
EMC Requirements
Compliance with IEC Recommendations
Teleprotection Standard IEC 60834-1 (1999)/EN 60834-1 (2000)
Generic immunity (industrial) IEC 61000-6-2 (2005)
Generic emission (industrial) IEC 61000-6-4 (2006)
Generic immunity (station and substation IEC/TS 61000-6-5 (2001)
environment)
EMC (Testing)
Electrostatic discharges IEC 61000-4-2(2001) Class 4/
IEC 60255-22-2 (1996)
Radiated electromagnetic field IEC 61000-4-3 (2006) Class 3
Fast transient bursts IEC 61000-4-4 (2004) Class 4/
IEC 60255-22-4 (2002) Class B
Surge immunity IEC 61000-4-5 (2005) Class 3/
IEC 60255-22-5 (2002)
Conducted electromagnetic field IEC 61000-4-6(2006) Class 3/
IEC 60255-22-6 (2001)
Magnetic field IEC 61000-4-8(2001) Class 5
Pulsed magnetic field IEC 61000-4-9(2001) Class 5
Voltage dips, short interruptions and voltage IEC 61000-4-29 (2000)
variations
Oscillatory waves IEC 61000-4-12(2006) Class 3/
IEC 60255-22-1 (2007)
xxxConducted common mode disturbances IEC 61000-4-16(2002) Class 4/
IEC 60255-22-7 (2003)
TABLE 4 - ENVIRONMENTAL CHARACTERISTICS
DIP5K/EN IT/A22 Main Characteristics
General
Number of commands transmitted 2 or 4 with one I/O board, up to 8 with a second
board
Particularity All commands are independent and can be used
simultaneously.
Command inputs
Physical input 4 per I/O board up to 8 with 2 boards
Mode By voltage 24 to 250 V DC
Decoupling Opto-electronic
Input Filter 1 to 100 ms selectable by HMI, 1 ms step
Minimum closure time Digital version: 1 ms
Analog version: from 1 ms to 5 ms (1 ms step)
selectable by HMI
Logical input combination Possibility of AND, OR, LOG between 2 inputs
Possible transmission extension
(minimum duration)
For digital transmission 0 up to 250 ms by 1 ms steps from HMI
For analog transmission 0 up to 500 ms by 1 ms steps from HMI
Command outputs
Mode By contacts (solid-state relay)
Number of contacts 4 working contacts, up to 8 with two I/O boards
Contacts working by pairs when logical input
combination is used
Maximum voltage 290 VDC
Maximum current 2 A (protected against over current 100A/30ms)
Cut-off power 120 W
Short circuit current 100A/30 ms
Contact closure time Equal to the duration of command signal received
Possible output extension (minimum
duration)
For digital output 0 up to 20 ms by 1 ms steps and 200 ms up to 3s by
10 ms steps from HMI
For analog output Coded Dual tone 0 up to 200 ms by 2 ms steps and 200 ms up to 3s
by 20 ms steps from HMI
For analog output Single tone 0 up to 500 ms by 1 ms steps
DIP5K/EN IT/A22 Main Characteristics
Auxiliary relays
Mode By contacts (solid-state relay)
Number of contacts 1 Working contact
At least 2 aux. contacts by command (1 TX & 1 RX)
Up to 4 aux. contacts by command (2 TX & 2 RX)
Same characteristics as command
outputs
Alarm Functions
Interface Indicator lights and relays
Number of contacts 2 x 2 neutral contacts (NC)
Maximum voltage 290 VDC
Maximum current 5 A (protected against over current 100A/30ms)
Cut-off power 100 W
Short circuit current 100A/30 ms
Delay on alarm relay command 0s/2.5s/5s/10s selectable from HMI
Operator assistance
Operations Indicator lights and alarm loops
Maintenance PC to handle all start-up and maintenance operations
History More than1750 time-stamped events and more
than1750 time-stamped alarms
Resolution = 1 ms between 2 events or alarms
Medium access
Line impedance 600 Ω or high impedance (selected by
jumper)
Return loss 20 dB minimum on 600 Ω
Galvanic insulation Translator
Sender
Precision of transmitted frequencies 1 Hz
Transmission level From –30 dBm to +6 dBm
Maximum overall output level (4 commands) +6 dBm
Preaccentuation Up to 14 dB between two signals
Spurious signals outside band < 50 dB of transmitted signal
Receiver
Permissible levels From –40 dBm to 0 dBm
Adjustment 1 for guard frequency and 1 for commands
Acceptable difference between guard and 0 to 14 dB
command frequency
2 commands
Channel bandwidth 300 - 3400 Hz 300 - 2400 Hz 300 - 2000 Hz 300 - 2000 Hz
Guard frequency band (Rx) 3500/3800 Hz 2400/2650 Hz 2000/2300 Hz 3600/3800 Hz
Guard frequency (Tx) 3600 Hz 2600 Hz 2240 Hz 3680 Hz
Command 1 frequency 900 Hz 400 Hz 480 Hz 480 Hz
Command 2 frequency 2100 Hz 1200 Hz 1120 Hz 1120 Hz
4 commands
Channel bandwidth 300 - 3400 Hz 300 - 2400 Hz 300 - 2000 Hz 300 - 2000 Hz
Guard frequency band (Rx) 3500/3800 Hz 2400/2650 Hz 2000/2300 Hz 3600/3800 Hz
Guard frequency (Tx) 3680 Hz 2600 Hz 2240 Hz 3680 Hz
Command 1 frequency 640 Hz 400 Hz 480 Hz 480 Hz
Command 2 frequency 1280 Hz 800 Hz 800 Hz 800 Hz
Command 3 frequency 1920 Hz 1200 Hz 1120 Hz 1120 Hz
Command 4 frequency 2560 Hz 1600 Hz 1440 Hz 1440 Hz
Band F8 Bandwidth
1 1741 300-1900
2 1820 400-2000
3 2110 670-2260
4 2295 850-2450
5 2479 1040-2630
6 2664 1220-2810
7 2848 1400-3000
8 3033 1590-3180
9 3429 1990-3580
Frequencies
(Hz) Band 1 Band 2 Band 3 Band 4 Band 5 Band 6 Band 7 Band 8 Band 9
F1 448 527 818 1002 1187 1371 1556 1741 2136
F2 633 712 1002 1187 1371 1556 1741 1925 2321
F3 818 897 1187 1371 1556 1741 1925 2110 2505
F4 1002 1081 1371 1556 1741 1925 2110 2294 2690
F5 1187 1266 1556 1741 1925 2110 2294 2479 2875
F6 1371 1451 1741 1925 2110 2295 2479 2664 3059
F7 1556 1635 1925 2110 2294 2479 2664 2848 3244
F8 1741 1820 2110 2294 2479 2664 2848 3033 3429
Link test F3+F7 F3+F7 F3+F7 F3+F7 F3+F7 F3+F7 F3+F7 F3+F7 F3+F7
9. PERFORMANCE
9.1 Digital interfaces
9.1.1 Transfer time as a function of transmission speed (digital and IR 182 boards)
OPERATION
DATA
Blocking Permissive Tripping Direct Tripping
RATE
2 cmds 4 cmds 8 cmds 2 cmds 4 cmds 8 cmds 2 cmds 4 cmds 8 cmds
32 Kbps 4.5 ms 6.5 ms 10.5 ms 6 ms 8.5 ms 15 ms 7.5 ms 11.5 ms 19.5 ms
64 Kbps 3 ms 4 ms 6 ms 3.5 ms 5 ms 8 ms 4.5 ms 6.5 ms 10.5 ms
128 Kbps 2 ms 2.5 ms 3.5 ms 2 ms 3 ms 4.5 ms 2.5 ms 3.5 ms 5.5 ms
256 Kbps 1.5 ms 1.5 ms 2 ms 1.5 ms 2 ms 2.5 ms 2 ms 2.5 ms 3.5 ms
2048 Kbps 1 ms 1 ms 1 ms 1 ms 1 ms 1 ms 1.5 ms 1.5 ms 1.5 ms
TABLE 12: TRANSMISSION TIME MEASUREMENTS FOR ELECTRICAL AND IR182 CARDS
NOTE: The times given correspond to a configuration with the input filter
disabled.
9.1.2 Transfer time as a function of transmission speed (IR 185 board)
The IR-185 board, short haul multimode fibres, is used to connect a DIP 5000 unit to any
transmission equipment (e.g Mux) with the IEEE C37.94 optical protocol.
Standard IEEE C37.94 runs at a maximum of 2.048Mbits/sec, with as many as twelve slots
of 64Kbits/sec each available for maximum data flow. The DIP 5000 has eight slots selected
with a rotary switch.
9.1.4 Dependability
Blocking 1E-30
Permissive 1E-35
Direct Tripping 1E-19
BANDWIDTH OPERATION
300-2400 2540 Hz 10 - 10 11 - 12 13 - 13 13 - 14 18 - 18 19 - 20
300-2000 2240 Hz 10 - 10 11 - 12 13 - 13 14 - 15 18 - 18 19 - 20
300-2000 3680 Hz 10 - 10 11 - 12 13 - 13 14 - 15 18 - 18 19 - 20
BANDWIDTH OPERATION
Blocking Permissive Direct tripping
Command channel 4 commands 4 commands 4 commands
300-1900 Hz 8 ms 9 ms 10 ms
OPERATION
Blocking Permissive Direct tripping
-4 -6
<3.10 <6.10 <10-11
OPERATION
Blocking Permissive Direct tripping
-4 -4
<6.10 <8.10 <8.10-4
Permissive
1,00E+00
11
1,00E-01 13
15
1,00E-02
17
Pmc 19
1,00E-03
21
1,00E-04
23
1,00E-05
<1,00E-06
3 4 5 6 7 8 9
SNR
D0615ENb
Main Characteristics DIP5K/EN IT/A22
Blocking
1,00E+00
1,00E-01
1,00E-02 11ms
13ms
Pmc
1,00E-03 15ms
25ms
1,00E-04
1,00E-05
1,00E-06
0 2 4 6 8 10
SNR
D0616ENb
Direct tripping
1,00E+00
1,00E-01
1,00E-02 1,1T0
1,3To
Pmc
1,00E-03 1,5To
2,1To
1,00E-04 3,1To
37ms
1,00E-05
1,00E-06
3 5 7 9 11
SNR
D0617ENb
DIP5K/EN IT/A22 Main Characteristics
BLANK PAGE
Installation DIP5K/EN IN/A22
DIP 5000
INSTALLATION
Installation DIP5K/EN IN/A22
CONTENTS
1. SAFETY INSTRUCTIONS 7
2. SHIPMENT 8
2.1 Packaging 8
2.2 Storage 8
2.3 Parts list 8
3. ENVIRONMENTAL CONDITIONS 10
4. INSTALLATION 11
4.1 Description 11
4.2 Plug-in Board Rack Position 11
4.3 Board Modular implementation 11
4.3.1 Minimal Board Rack implementation 12
4.3.2 Complementary Board Rack implementation 12
4.3.3 Optional Boards 13
6. CONNECTION 15
6.1 Rear Connectors 15
6.2 Terminal block Wiring 16
6.2.1 Plug-in terminal block description 16
6.2.2 Input /Output Terminal Block Pin-Out 17
6.2.3 Recommendation 18
6.2.4 Input Logic Command allocation 18
6.2.5 Wiring Examples 20
6.3 Alarm and Output copy Terminal Block Wiring 20
6.3.1 Plug-in terminal blocks description 20
6.3.2 Alarm and Output copy terminal block Pin Out 21
6.3.3 Output Copy Allocation 21
6.4 Power supply wiring 23
6.4.1 Plug-in terminal blocks description 23
6.4.2 Power supply connector Pin Out with standard CORTEC subrack 23
6.4.3 Power supply connector Pin Out with dual power supply version 23
DIP5K/EN IN/A22 Installation
7. INSTALLATION PROCEDURE 30
8. APPENDIX 31
8.1 Terminal block location 31
8.2 Terminal block location dual power supply version 32
8.3 2 commands version connections 33
8.4 4 commands - 1 I/O board version – connections 33
8.5 4 commands - 2 I/O boards version – connections 34
8.6 8 commands connections 34
8.7 Selecting type of configuration 35
LIST OF FIGURES
LIST OF TABLES
BLANK PAGE
Installation DIP5K/EN IN/A22
MODIFICATIONS PAGE
NOTE: From the revision C, the numbering system of the document has
changed according to the AREVA standards, on the other hand the
index of the document has been incremented for a better follow-up.
DIP5K/EN IN/A22 Installation
BLANK PAGE
Installation DIP5K/EN IN/A22
1. SAFETY INSTRUCTIONS
BEFORE CARRYING OUT ANY WORK ON THE UNIT, THE USER
SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
SECTION DIP5K/EN SS/A11 OR LATER ISSUE, THE TECHNICAL DATA
SECTION AND THE RATING ON THE EQUIMENT RATING LABEL.
2. SHIPMENT
2.1 Packaging
DIP 5000 packaging includes:
• A set of connectors, including small tools (x5) to insert a cable on wago connectors
UNIT COMPONENTS
2 or 4 Commands Variant (3) 8 Commands Variant
3U rack AM170/AM170D 1
UT 148 CPU Board 1
Terminal blocks 9
Line connection 1
(15 pin female socket)
PC connection 1
(9 pin female socket)
ALxxx PSU card (1) 1 or 2 (2)
SRxxx card (1) 1 or 2 (3) 2
IRxxx digital interface board (1) 1 (DIP 5000 Digital version)
IR182/185 optical interface board 1 (DIP 5000 Optical Fibre version)
IR183 Voice Frequency interface 1 (DIP 5000 Analog version)
IR184 IRIG_B interface board 1 (optional)
FI002 filter board 1 for 2 or 4 commands variant only (optional)
* For 220 VDC and higher voltages refer also to application note document n° PTC–DIP5K-TS-E-
005.pdf.
DIP5K/EN IN/A22 Installation
3. ENVIRONMENTAL CONDITIONS
Operating temperature limits: -40°C to + 70°C
Maximum relative humidity at 23°C: 90 %
This unit is to be installed in rooms sheltered from the rain.
Installation DIP5K/EN IN/A22
4. INSTALLATION
4.1 Description
Rack dimensions comply with the standard EUROPE 19 inches type, which are 3 units high
in compliance with standard DIN 41494.
The rack is designed to be installed in frames or cabinets. The only fastening and support
points on these racks are situated on the front panel of the frame, on perforated brackets.
4.2 Plug-in Board Rack Position
The UT 148 and I/O boards, which are 220 mm long and 6U wide, are plugged in and locked
horizontally on the left part of the rack.
• One SRxxx card (SR114, SR115, SR116) for commands 1 to 4 must be located in
slot 3
37,7 mm
3
(3U)
57,1 mm 2 4 5 6 132,5 mm
1 300 mm
or
316 mm
37,7 mm
Optical Interface
optional
• The Power Supply boards are plugged in and locked vertically in slots 5 and 6 after the
unit has been installed in the rack and the connecting cables fed through.
Main PSU
Aux PSU
IR182
2 commands variant
UT 148 Board
IRxxx interface
Aux PSU
IR182
FI002 optional
4 commands variant
UT 148 Board
IRxxx interface
Aux PSU
IR182
D0494ENa
• 1 I/O board in slot 2 for the 8 command version (Digital only) or 1 FI002 for filtering.
• 1 I/O board in slot 2 can be added in the 4 command version to extend the number of
outputs or to provide combinatorial logic on inputs.
IR xxx
V7 communication interface board
V5
V3
V2
IR184
V4
Optional IRIG-B interface board
V6
V1
MAX MAX
3000 U13 3000 U14
V8
V9
EEPROM
FLASH
Timer
U8
DSP
2189 U2
S1 M
S2 3,3V
– D0053ENa
⇒ ± 20 V max. amplitude
⇒ 10 ms max. duration
6. CONNECTION
To comply with safety requirements and EMC specifications, the protective (earth) conductor
terminal on the rear of the DIP 5000 unit shall be connected to a ground bar via a flat braid
made of tinned copper with a cross section of at least 12 mm X 1 mm. This braid must be
reliably connected to one of the two M5 threaded studs located on the back of the DIP 5000
unit.
P14 P11
P16 Tx 1 1
1
Rx P10
P15
P17 Optical Fiber 1
P12
- BAT 1
- BAT Access P20
+BAT P19
+BAT P13
1
P18
D0058ENa
P14 P11
P16 Tx 1 1
1
Rx P10
P15
AUX MAIN P12
Optical Fiber 1
1
- BAT
Access P20
- BAT
+BAT P19
+BAT P13
1
P18
D0492ENb
• P12 Terminal block reserved for command inputs 5 to 8, or 1 to 4 with optional FI002.
• P18 15-pin female socket connector for access to the communication line (copper
wire).
• P19 9-pin female socket connector for RS 232C link with the interface PC for
maintenance/operation or access to the supervision network (TMN).
• FC/PC connector for optical fibre connection, only if the unit is fitted with the IR182
option.
6.2 Terminal block Wiring
The I/O commands to and from the protection relay are wired on terminal blocks P10, P11,
P12 and P13, located at the rear of the unit. The connector references and Pin 1 position are
labelled on the rear panel (see Appendix - Figure 15).
All the input and output connexions of these blocks are isolated.
6.2.1 Plug-in terminal block description
Terminal blocks are equipped with an index slot to prevent reversed connection.
The Input Output wires, whose cross-section must be in the range 0.08 - 2.5mm², are
connected to these terminal blocks by means of 10 self-locking connection points.
1
2
3
4
5
6
7
8
9
10
D0055XXa
1
Lever
D0054ENa
TABLE 4 - P10, P11, P12, AND P13 TERMINAL BLOCK CIRCUITS LOCATIONS
Pins 1 and 2 must be strapped on connectors P10, P11, P12 and P13 (see Figure 5). This
configuration enables the terminal block presence to be checked. If the terminal block is
removed, the strap is no longer detected and an alarm is set. The strap must be located on
the terminal block connector and must not be removed.
DIP5K/EN IN/A22 Installation
6.2.3 Recommendation
All the relays connected to the output contacts should have a free-wheeling diode.xxx
6.2.4 Input Logic Command allocation
Depending on the DIP 5000 hardware configuration, a combinatorial logic operator can be
applied to inputs and then allocated to commands sent to another DIP.
Input logic allows a logical operator to be affected to board input and to be allocated to a
command.
Permitted combinations are
OR: logical OR of two inputs
AND: Logical AND of two inputs
LOG: logical function ()
A command can thus be activated by the result of the logical OR, AND or LOG applied to
two inputs coming from different sources even with different voltage levels. This feature is
accessible when the number of available inputs is higher than the number of commands as
follows:
(1) (1)
TERMINAL COMMAND 2 COMMANDS VERSION 4 COMMANDS VERSION 4 COMMANDS VERSION 8 COMMANDS VERSION
BLOCK ALLOCATION 1 I/O BOARD 1 I/O BOARD 2 I/O BOARDS 2 I/O BOARDS
DIGITAL ONLY
IN5 or IN6
IN5 and IN6
(2)
LOG (IN5, IN6)
IN7 or IN8
COMMAND 5 IN5
Acquisition
COMMAND 6 IN6
Acquisition
P12
COMMAND 7 IN7
Acquisition
COMMAND 8 IN8
Acquisition
COMMAND 5 OUT5
Output
COMMAND 6 OUT6
Output
P13
COMMAND 7 OUT7
Output
COMMAND 8 OUT8
Output
1
2
3
4
5
6
7
8
9
10
11
D0056XXa
PINS TERMINAL BLOCK P14 TERMINAL BLOCK P15 TERMINAL BLOCK P16
1 T COPYT1 T COPYT9 C
Minor Alarm 1 Output
2 T COPYT2 T COPYT10 R
4 T COPYT4 T COPYT12 C
Minor Alarm 2 Output
5* C COPYC 1 to 4 C COPYC 9 to 12 R
7 T COPYT5 T COPYT13 C
Major Alarm 1 Output
8 T COPYT6 T COPYT14 R
10 T COPYT8 T COPYT16 C
Major Alarm 2 Output
11** C COPYC 5 to 8 C COPYC 13 to 16 R
Allocation of the Output copy relays depends on the configuration (see table below)
COMMAND 5
COPYT9
Acquisition COPY
COMMAND 6
COPYT10
Acquisition COPY
P15
COMMAND 7
COPYT11
Acquisition COPY
COMMAND 8
COPYT12
Acquisition COPY
COMMAND 5 Output
COPYT13
COPY
COMMAND 6 Output
COPYT14
COPY
P15
COMMAND 7 Output
COPYT15
COPY
COMMAND 8 Output
COPYT16
COPY
4 Functional Earth
V11/X24 Interface
(ISO 4903)
1
9 T(B)
2 T(A)
10
3 R(B)
11
R(A)
4
12
5 S(B)
13
S(A)
6 S'(B)
14
7 S'(A)
15
8
G703.1 Interface
codirectional
1
9 T(B)
2 T(A)
10
3 R(B)
11
R(A)
4
12
5
13
6
14
7
15
8
D0608ENa
G703.6 Interface
2Mbit/s
1
9
2 Tx +
10
Tx -
3
11
4 Rx +
12
5 Rx -
13
6
14
7
15
8
D0609ENa
Analog Interface
1
9 Tx(B)
2 Tx(A)
10 TBB(B)
3 TBB(A)
11 Rx(B)
4 Rx(A)
12 RB(B)
5 RB(A)
13 EA(B)
6 EA(A)
14 AL(B)
7 AL(A)
15
8
D0610ENa
EMC protection
When not used, the rack connector must be covered with an EMC protection
plate.
0V Rx
DTR Tx
5 4 3 2 1
9 8 7 6
DSR
D0618ENa
0V Tx
DTR Rx
5 4 3 2 1
9 8 7 6
CTS DSR
RTS
D0619ENa
1 10
P11
P10
P12
P13
+ + + +
Cmd 1
Cmd 2
Cmd 3
D0489ENa
7. INSTALLATION PROCEDURE
Installation of the unit includes the following steps:
1. Install casing (rack, cabinet, or box).
2. Insert cables for subsystems and operation (power supply, earthing, transmission
medium, and protection equipment).
3. Mount rack in casing. Fasten in place using the screws on the front panel.
4. Connect rack to earth circuit.
5. Before installing the cards in the racks, make sure apparatus is switched off (plugs
removed or switch open).
6. Install cards in rack.
NOTE: The optical interface card must be mounted and tied to the rack before
mounting the rack in the frame.
Installation DIP5K/EN IN/A22
8. APPENDIX
8.1 Terminal block location
P14 P11
P16 Tx 1 1
1
Rx P10
P15
P17 Optical Fiber 1
P12
- BAT 1
- BAT Access P20
+BAT P19
+BAT P13
1
P18
D0058ENa
P14 P11
P16 Tx 1 1
1
Rx P10
P15
AUX MAIN P12
Optical Fiber 1
1
- BAT
Access P20
- BAT
+BAT P19
+BAT P13
1
P18
D0492ENb
{
P14 P11
Group 1 Group 2
{
IN1 IN2 IN3 IN4
Command 1 Command 2
Acquisition Acquisition
D0059ENa
{
P14 P11
Common of Command
Acquisition Copy
Common of Command
Output Copy
P10 - + - + - + - +
{
{
IN1 IN2 IN3 IN4
Command 1 Command 2 Command 3 Command 4
Acquisition Acquisition Acquisition Acquisition
D0060ENa
{
P14 P11
Group 1 Group 2
Command 1 Command 2
Group 1 Copy Common
Acquisition Acquisition
Group 2 Copy Common
Group 3 Copy Common IN1 IN2 IN3 IN4
{
Group 4 Copy Common
Group 3 Group 4 P10 - + - + - + - +
P15
P12 - + - + - + - +
{
Command 4 Output Copy IN5 IN6 IN7 IN8
Command 3 Command 4
Command 3 Output Copy Acquisition Acquisition
{
OUT5 OUT6 OUT7 OUT8
Command 3 Command 4
Restitution Restitution
D0061ENa
P14 P11
Group 1 Group 2
Command 1 Command 2 Command 3 Command 4
Group 1 Copy Common Acquisition Acquisition Acquisition Acquisition
Group 2 Copy Common
IN1 IN2 IN3 IN4
Group 4 Copy Common
{
P15
P12 - + - + - + - +
{
ACQUISITION
Input Selection
Input 1
SIMPLE MODE
MMI Choice
Input 2
ACQUISITION
OR Function
Input 1+ Input 2
COMBINED MODE
LOG Function
Function Selection
MMI Choice
D0063ENb
BLANK PAGE
Commissioning DIP5K/EN CM/A22
DIP 5000
COMMISSIONING
Commissioning DIP5K/EN CM/A22
CONTENTS
1. SAFETY INSTRUCTIONS 7
2. FOREWORD 8
2.1 Step by Step procedure 8
2.1.1 Reminder of Installation procedure final status 8
3. CHECKING PREREQUISITES 9
4. CONFIGURING HARDWARE 10
4.1 Initial Status 10
4.2 Configuring Input/Output board jumpers 10
4.3 Configuring the IR185 Optical Communication interface (if used) 11
4.4 Final Status 11
5. POWERING UP 12
5.1 Powering up initial step 12
5.2 Prerequisite 12
5.3 Powering up procedure 12
5.4 Powering up step final status 12
6. CONFIGURING SOFTWARE 13
6.1 Introduction 13
6.2 Prerequisite 13
6.3 Initial status 13
6.4 Configuring DIP 5000 DIGITAL 13
6.4.1 Creating User Password(s) 13
6.4.2 Configuring General Parameters 14
6.4.3 Configuring Input/Ouput Parameters 14
6.4.4 Configuring Application Parameters 15
6.4.5 Configuring Alarms Parameters 16
6.4.6 Entering Comments 17
6.4.7 Configuring Backup Interface 17
6.4.8 Saving the Configuration 17
6.5 Configuring DIP 5000 Analog Single tone 17
6.5.1 Creating User Password 18
6.5.2 Configuring General Parameters 18
6.5.3 Configuring Sender Parameters 19
6.5.4 Configuring Receiver Parameters 20
6.5.5 Configuring Input/Output Parameters 22
6.5.6 Alarm Parameters Single Tone 23
DIP5K/EN CM/A22 Commissioning
8. OPERATIONAL CHECKS 32
8.1 Initial Status 32
8.2 Procedure 32
8.3 Standalone Checks 33
8.3.1 Forcing alarms 33
8.3.2 Maintenance Forcing commands 33
8.3.3 PLC forcing commands 33
8.4 Final status 33
8.5 In line Checks 33
8.6 Final Status 33
9. APPENDIX A 34
9.1 UT148 card layout 34
9.2 SR11x card layout and jumper settings 35
9.3 AL137 card layout 36
9.4 AL139 card layout 36
9.5 IR183 card layout 37
9.6 IR184 card layout 38
9.7 FI002 card layout and jumpers settings 39
9.7.1 FI002 board layout 39
9.8 IR-185 BOARD 40
Commissioning DIP5K/EN CM/A22
LIST OF FIGURES
LIST OF TABLES
BLANK PAGE
Commissioning DIP5K/EN CM/A22
MODIFICATIONS PAGE
BLANK PAGE
Commissioning DIP5K/EN CM/A22
1. SAFETY INSTRUCTIONS
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE USER
SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
SECTION DIP5K/EN SS/A11 OR LATER ISSUE, THE TECHNICAL DATA
SECTION AND THE RATING ON THE EQUIMENT RATING LABEL.
2. FOREWORD
DIP 5000 teleprotection commissioning is performed following the Step by Step
commissioning procedure described in the following paragraphs.
Rigorously following these procedures will prevent malfunctions and damage to the
equipment.
Proceeding in this manner guarantees optimal link configuration, and better performance in
the minimum time in compliance with security rules.
Commissioning procedures and checks requires the user to be familiar with Human-Machine
Interface software use, refer to the Human-Machine Interface Chapter for complementary
information.
Only a PC supporting the Human Machine Interface software is needed to perform
commissioning, no other measuring device or multimeter is required.
2.1 Step by Step procedure
2.1.1 Reminder of Installation procedure final status
The initial step of the commissioning procedure corresponds to the final status of the
Installation procedure:
Start
Checking Prerequisite
Configuring Hardware
Powering up
Configuring Software
Operational Checks
End
D0611ENa
3. CHECKING PREREQUISITES
Before Commissioning the following points MUST be checked:
• Installation is complete,
• Installed DIP 5000 must be earth grounded (see § Connection in Installation chapter),
• Terminal block Power Supply connection (see § Power supply wiring in Installation
Chapter),
• Compliance of the power supply board with the available DC input voltage (see
§ Power Supply Boards VDC range values in Installation Chapter),
• Pins 1 and 2 of connectors P10, P11, P12, and P13 must be connected with a jumper
(See § Terminal Block Input/Output Wiring in Installation Chapter), otherwise an alarm
is set.
• Prerequisite about qualification: Only authorized and trained technicians can carry out
installing, programming, commissioning, maintenance, testing, and repair.
• Be careful:
Warning labels: precaution and indications of hazardous voltages and hazardous energy
level must be strictly observed.
DIP5K/EN CM/A22 Commissioning
4. CONFIGURING HARDWARE
4.1 Initial Status
Prerequisites have been checked.
No changes should be made to the link positions unless the supply input voltage
has been isolated.
4.2 Configuring Input/Output board jumpers
In this step you have to work on Boards. Security reminder:
ESD protection: the modules in this equipment contain devices which can be damaged by
electrostatic discharges. Appropriate measures must be taken before unpacking modules or
withdrawing them from equipment racks. Essential precautions to prevent ESD damage
when handling or working on modules are grounding straps for technical personnel and the
provision of anti-static workbenches. Modules may only be shipped either in their original
packing or installed in equipment racks.
Input/output boards SR11x are equipped with jumpers S2 S3 S4 S5.
S5
S4
S3
S2
3
2
1
3
2
1
3
2
1
3
2
1
D0127XXa
Jumpers on Input/output boards SR11x must be configured according to the DC value of the
input command.
The following table gives the correspondence between input commands and Input/Output
SR 11x board location in the rack for a two board installation.
S2 S3 S4 S5
SR11x Input 1 Input 2 Input 3 Input 4
Top position in the rack
SR11x Input 5 Input 6 Input 7 Input 8
Bottom position in the rack
Laser/LED: take care using optical cards IR182/IR185, class I Laser/LED product.
The IR185 Optical Communication interface has a rotary switch to be set in compliance with
the DIP 5000 frequency clocks.
Select rotary switch position using the following table
5. POWERING UP
5.1 Powering up initial step
• For more information about boards’ Switch and LEDs location see Appendix A.
• For more information about LEDs’ status indicators see § Maintenance in the
Maintenance chapter.
5.3 Powering up procedure
Power up the DIP 5000 applying the following procedure:
Start
Switch ON
(AL13x/AL14x cards)
? No
Yes
? No
Yes
Repair
(see § Testing
and Fault
Isolation)
End
D0612ENa
Once the DIP 5000 is powered, check the LEDs’ correct status, they must be green.
• In case a LED indicates a fault, see the § Testing and fault isolation in Maintenance
chapter.
5.4 Powering up step final status
At the end of the Powering up step the DIP 5000 is powered up and ready to receive the
configuration files.
Commissioning DIP5K/EN CM/A22
6. CONFIGURING SOFTWARE
6.1 Introduction
DIP 5000 DIGITAL, DIP 5000 ANALOG Single tone, DIP 5000 ANALOG Dual Tone software
configurations are independently described in the following paragraphs
Depending of your DIP 5000 version DIGITAL or ANALOG, refer to the appropriate
paragraphs below.
6.2 Prerequisite
The DIP 5000 software configuration requires a PC equipped with an H version compatible
with your DIP 5000 firmware.
Configuring requires the user to be familiar with the use of the Human Machine interface
Software.
6.3 Initial status
DIP 5000 is powered on.
Security Reminder
Using HMI DIP 5000: teleprotection link gets disturbed while using certain functions offered
by the HMI DIP 5000 for maintenance (e.g. forcing commands).
6.4 Configuring DIP 5000 DIGITAL
For more details about DIP 5000 DIGITAL configuration procedures,refer to the HUMAN
MACHINE INTERFACE DIP 5000 DIGITAL CHAPTER. To each procedure step there is a
corresponding paragraph in the HMI chapter.
The configuration procedure is the following:
• Creating password,
• Send the configuration file to the DIP 5000, the DIP 5000 resets.
For HMI DIGITAL see § Sending a configuration file in the Human Machine Interface DIP
5000 Digital chapter.
For HMI ANALOG see § Sending a configuration file in the Human Machine Interface DIP
5000 Analog chapter.
• Check the correct status of LEDs after the reset and that there are no alarms.
In case of alarm status of LEDs
• Read alarms
For HMI DIGITAL see § Reading Alarms in the Human Machine Interface DIP 5000 Digital
chapter.
For HMI ANALOG see § Reading Alarms in the Human Machine Interface DIP 5000 Analog
chapter.
Once the alarm is identified, apply the corresponding resolution procedure of the §TESTING
AND FAULT ISOLATION in the MAINTENANCE CHAPTER.
Commissioning DIP5K/EN CM/A22
Start
Send the
configuration
Checks alarms
status OK
after reset ?
? No
Yes
Check hardware
alarms status OK ?
? No
Repair
see § Testing and
Fault Isolation
End
D0613ENa
8. OPERATIONAL CHECKS
8.1 Initial Status
The DIP 5000 is in pre-operational state, medium not connected.
8.2 Procedure
This procedure involves:
− Checking the user connections (rear sockets) and the “Terminal Block Presence” 1-2
jumpers
− Standalone Checks
− In-line Checks
Start
Ch e ck t h e "u se r "
c on n e ctio n s (r e a r
so ck e ts)
S e t th e tim e o n th e
e q uip m e n t
< Da te / Wr ite / Lo ca l>
Me n u
Sa ve t h e co n fig u r a tio n
in a b a ck - u p file < Re a d / Loc a l> Me n u < File > Me n u
< Co n fig ur a t ion > < File / Sa ve >
Co m m a n d
St a nd a lo n e c h e ck s
In line ch e ck s
End
D0614ENa
9. APPENDIX A
9.1 UT148 card layout
UT148
P 10
P2
P9 IR 1xx P 11
V7 communication interface card
V5
V3
V2
P8
P5 Optionnal IR184
P7 IRIG-B place P6
V4
V6
P 12
V1 P4 MAX MAX
3000 U13 3000 U14
V8
V9
P1
E E P R OM
FLAS H
Timer
U8
DS P
U2
S1 2189M
S2 P3 3,3V
D0131ENc
V1 Steady green
V8 Fast flashing green
V7 Off
Commissioning DIP5K/EN CM/A22
SR11x
K4
K3
K2
K1 P1
V5 3
2 S5
1
V6
3
V7 2 S4
1
V8 3
2 S3
1
3
2 S2
1
P3
K12
MAX K11
7000 U4
V1 K10
V2
K9
V3 S1
V4 K8
P2
K7
K6
K5
D0132XXa
Jumper position
The jumper S2 to S5 allows to select the tension value range in function of the level of the
input command.
AL137/AL 140
Power
K2
Fuse
MAJ. AL.
A1
MIN. AL. K3
Power switch S1 P1
K1
K4
+5V
0V Factory setting
D0133ENb
AL139
Fuse
Power
MAJ. AL. K3
Power switch P1
K1
INT.1
C20
+5V 0V K2
POT.1
Factory setting
D0134ENb
Commissioning DIP5K/EN CM/A22
IR183
J2A
J3A P1
J2B
J3B
J2C
J3C
J2D
J3D
D0495ENa
Rotary switch
Test jumper
Power jumper
Tx LED Tx
Rx LED Rx
SPI connector
JTAG connector
GREEN LED power on
D0496ENa
LEDs
The board is equipped with 2 LEDs (diameter 5 mm) on the front side.
The upper led D1 is labelled TX on the front side, the other one D2 is labelled RX
STATE D1 D2 Comment
NORMAL Steady Green Steady Green Normal operation
LOS - Steady Red Loss of signal on RX input
AIS - steady* Receiving AIS (all ones)
Yellow
LOF - blinking Red Loss of Frame (1 ms red when a frame
is bad)
YEL Steady* - Yellow bit received (state 1)
Yellow
TXAL Steady Red - No signal to transmit signal from UT148
RSET Steady Red Steady Red During reset or FPGA programming
Interface to ALXXX
The IR185 module is powered by the ALxxx module with a single voltage: 5V DC. This
voltage crosses the mother board, so it needs filtering at the input of the board.
Take care about powering the optical interface components, as the receiver and transmitter
parts may be disconnected (no return current from TX part on RX ground).
DIP5K/EN CM/A22 Commissioning
BLANK PAGE
Maintenance DIP5K/EN MT/A22
DIP 5000
MAINTENANCE
Maintenance DIP5K/EN MT/A22
CONTENTS
1. SAFETY INSTRUCTIONS 5
2. OVERVIEW 6
3. MONITORING 7
3.1 Monitoring LEDs 7
3.2 Messages 9
3.3 LEDs Relay Information 9
3.4 Push-buttons 9
6. FAULT CLASSIFICATION 37
LIST OF FIGURES
MODIFICATIONS PAGE
BLANK PAGE
Maintenance DIP5K/EN MT/A22
1. SAFETY INSTRUCTIONS
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE USER
SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
SECTION DIP5K/EN SS/A11 OR LATER ISSUE, THE TECHNICAL DATA
SECTION AND THE RATING ON THE EQUIMENT RATING LABEL.
2. OVERVIEW
This section includes two parts:
• Testing and repair: in this part a fault classification is given, maintenance tools
described, and repair procedures given.
3. MONITORING
The monitoring resources available with the DIP5000 equipment are the following:
• Notification messages,
3.1 Monitoring LEDs
LEDs, located on the DIP 5000 front face display supervision information (see TABLE 1 –
LEDS INDICATION).
System operation is monitored by these LEDS and four alarm relays (two dedicated to major
alarm and two to minor alarm).
Alarm requiring a maintenance action are notified by the status of these LEDs and relays.
V7 V5 V3 V2 V4 V6 V1 V8 V9 S1 S2
D0135XXa
TX MAJOR ALARM
RX MINOR ALARM
Optical interface
Power supplies indicator lights
indicator lights D0136ENa
x Signal V6 Off
Missing Red Steady
Guard/Low Level
Transmission of Amber Steady
Link Test Message Test V2 during 2sec
Link test fault Amber Steady
UT148 indicator
UT148 indicator light UT148 indicator light
Teleprotection Status light
V1 (STATUS) V8 (STATUS)
V7 (MTN)
NORMAL OPERATION Steady Green Fast-flashing Green Off
Normal operation after a cold Steady Green Fast-flashing Amber Off
start
Initialisation in progress Steady Green Fast-flashing Red Off
Alarm on power-up test Fast-flashing Red Fast-flashing Red Off
Configuration Write in the Slow-flashing Red Slow-flashing Red Off
Flash EPROM
Storage status Quick switch from Green Quick switch from Green
(Isolated Timer Battery) to Amber then Red to Amber then Red
MAINTENANCE STEADY GREEN FAST-FLASHING GREEN OR STEADY AMBER
FAST-FLASHING AMBER
Remote loopback of STEADY GREEN FAST-FLASHING GREEN OR FAST-FLASHING
equipment FAST-FLASHING AMBER AMBER
Pending code transfer for SLOW-FLASHING YELLOW SLOW-FLASHING YELLOW FAST-FLASHING
Flash memory AMBER
CODE TRANSFER IN PROGRESS Green when timing the Green when timing the Fast-flashing
“0”s of transmitted data “1”s of transmitted data Amber
Writing the code in the Flash SLOW-FLASHING RED SLOW-FLASHING RED Fast-flashing
memory Amber
• Reset.
For more information on using these MAINTENANCE functions see the § Maintenance Menu
in the HMI DIP5000 chapter corresponding to your version DIGITAL or ANALOG.
4.3 Reading Alarms Snapshot DIP 5000 HMI DIGITAL
See § Reading the alarm snapshots in the HMI DIP5000 DIGITAL chapter.
The supervised alarms are the following:
"Power Up” Alarms
• Configuration CRC
• Communication Interface
• Missing SR board
• Remote Minor
• Transmission time
For more information refer to the HMI DIP 5000 DIGITAL CHAPTER.
4.4 Reading Alarm Event DIP5000 DIGITAL
See the § Reading Alarm List in HMI DIP 5000 DIGITAL CHAPTER
4.5 Reading Alarm DIP 5000 HMI ANALOG
See § Reading the alarm snapshots in the HMI DIP5000 ANALOG chapter.
The supervised alarms are the following:
"Power Up” Alarms”
"Communication" Alarms
• Power supply voltage is properly applied to the DIP 5000 (if the power supply LED is
not lit),
• Wiring,
• External connection and circuit to which the DIP5000 is connected (protection side,
transmission medium, power supply, external alarm),
• Motherboard aspect.
If communication between the HMI PC and the DIP5000 cannot be established, check the
cable connection on the DIP5000 side and PC side. Open the front panel of the DIP and
check the internal connection between the RS 232 connector and the UT 148 board.
5.2 Fault Isolation Procedure
Most of the faults are notified to the user by the LEDs status (see § 3.1).
If a LED status notifies an alarm:
1. Determine the alarm cause using the table TABLE 1 – LEDS INDICATION,
2. Connect the PC and launch the HMI,
3. Read the alarm snapshot and notification messages,
4. Apply the repair procedure associated with the alarm (see the next paragraph
Troubleshooting procedure).
Note: In the event of board replacement, apply the commissioning procedure (see
COMMISSIONING chapter).
In the event of a complex fault that cannot be resolved with a repair procedure (several
simultaneous faults or breakdowns with multiple implications), use the maintenance
commands and test tools (see § 4.2) to analyse or deal with the fault (the reset command
can be useful).
5.3 Troubleshooting Procedures
How to use this paragraph:
In the event of an alarm notification, refer to the associated figures:
PRECAUTION
Remove the back panel fastening screws of the IR 182/185 modules, before
carrying any work on the optical interface board
Power up Alarms
MAIN POWER
MAJOR ALARM
MINOR ALARM
Fault:
Flash EPROM
Replace the UT148 module
DSP RAM
Timer RAM
Communication interface
fault see Repair Sheet 1
Configuration checksum
fault see Repair Sheet 4
Is the card No
Put the IRxxx card in position
present ?
Yes
Yes
Th e c o n fig u ra tio n d o e s n o t
SR11x coherence fault m a tc h th e n u m b e r o f c a rd s
p re s e n t.
Yes
D0139ENc
Is the card No
Put the IRIG-B card in position
present ?
Yes
Yes
UT148 card
Failure on one of the modules or
IRIG-B card fault
No
No
Hardware Alarms
Hardware alarms
MAIN POWER
MAJOR ALARM
SR11x test fault
see Repair Sheet 6 MINOR ALARM
AL13x / AL14x
power supply voltage see Repair Sheet 8
MAIN POWER
MAJOR ALARM
MINOR ALARM
MINOR ALARM
D0143ENc
N˚ 1 Card N˚ ? N˚ 2
D0144ENc
Terminal block
presence fault
Y es
UT 148 card
F ailure on one of the modules or S R 11x card fault
or F B motherboard fault
D0145ENc
Is the
"P OW E R " indicator light Yes R eplace the faulty
on the faulty card AL 13x / AL 14x module
lit ?
No
No
Yes
D0146ENc
Timer battery
voltage fault
Check
that the "Power Cap"
is present on the timer
Is the No
See Installation manual
"Power Cap" present ?
Replace the
See appended procedure
timer "Power Cap"
D0147ENa
OR
No
No
NOTE: Before carrying out a diagnosis, use the HMI to reset the local
equipment, then read the alarms again.
Maintenance DIP5K/EN MT/A22
Communication Alarms
(Digital version)
Major or Minor
Remote Alarm see Repair Sheet 13
MAJOR ALARM
Major/Minor Alarm
Programmable by HMI MINOR ALARM
D0149ENc
Synchro Loss
No
Command number
OK ?
Yes
Card number No
OK ?
Yes
Logical Address No
OK ?
Yes
Clock Config. No
OK ?
Yes
Fault located on
Change the configuration
IRxxx or UT148
No
END END
D0151ENa
Menu : <Read>
Make a note of the nature of fault <Remote>
on the remote equipment <Alarms Snapshot>
END
D0152ENa
No
Yes
Lack of timing ?
Lack of timing,
HDB3 code violation, with
only with V11 interface and
G703.6 (2Mbps) interface
G703.1 contradirectional interface
No
Tx Command duration
alarm fault
Local reading of
Input / Output status
Yes
No
D0155ENb
NOTE: Before carrying out a diagnosis, use the HMI to reset the local
equipment, then read the alarms again.
DIP5K/EN MT/A22 Maintenance
Communication Alarms
(Analog version)
MAIN POWER
MAJOR ALARM
Major/Minor Alarm
Programmable by HMI
MINOR ALARM
MAJOR ALARM
Major/Minor Alarm
Programmable by HMI
MINOR ALARM
MAJOR ALARM
Reversible Major Alarm
MINOR ALARM
MAIN POWER
MINOR ALARM
D0156ENc
Command number No
OK ?
Y es
Card number No
OK ?
Y es
F ault located on
Change the configuration
IR 183 or UT 148
Y es
Has the fault disappeared ?
No
E ND E ND
D0157ENb
FIGURE 22 - COMMUNICATION ALARMS ANALOG – MISSING GUARD LOW LEVEL ALARM NOISE
ALARM DT - LOCKING ALARM DT
DIP5K/EN MT/A22 Maintenance
External Alarm
No
No
Miscellaneous messages
or warning
Too many transmission Fault in the V24 dialog. Restart the HMI or
errors manually reset the teleprotection.
Continued
D0159ENa
Miscellaneous messages
or warning
(continued)
OR
OR
END
D0160ENa
6. FAULT CLASSIFICATION
Faults are divided into two classes: Major and Minor
Major Faults
A major fault is a fault whose occurrence inhibits normal operation of the equipment or
entails a risk to operation. In all cases, it involves placing the command output relays in rest
mode. The relays are kept in this mode until the fault disappears.
Minor Faults
A minor fault is a fault whose appearance causes no risk to operation. In this case, normal
operation of the equipment is guaranteed.
The following table summarises the faults classified in categories with class and type
information:
"Hardware" faults
Presence of SR114 modules MAJ REV
AL137/AL139 fault MIN REV
Presence of operating terminal blocks MIN REV
Battery fault (timer) MIN IRREV
Input/Output test MAJ IRREV
UT power supply voltage test MAJ REV
Link Test MAJ IRREV A
"Communication" faults
Transmission time alarm MIN/MAJ* REV D
Lack of received signal MAJ REV D
Lack of Rx timing MAJ REV D
Lack of Tx timing MAJ REV D
Synchro Loss MAJ REV D
Bit Error Rate/MAJ ALARM MAJ REV D
Bit Error Rate/MIN ALARM MIN REV D
Major remote Alarm MAJ REV D
Minor remote Alarm MIN REV D
Tx Command duration Alarm MIN/MAJ* REV
Missing Guard MAJ REV A
Low Level MAJ REV A
Locking MAJ REV A Dual tone***
Noise MAJ REV A Dual tone
External Alarm MIN/MAJ* REV A
* configuration with HMI
** In the Version column, ‘D’ indicates that the fault concerns only the Digital version of the
DIP5000. ‘A’ indicates that the fault concerns only the Analog version. None indicates that
the fault concerns both versions.
Remote equipment faults are indicated locally. They are classed as reversible whatever their
nature. Once the remote fault is removed, the local alarm disappears.
Maintenance DIP5K/EN MT/A22
• Prerequisite,
• Using Winzip extract the files dipsoft.dat and readme.txt in the created directory.
• Copy the dipsoft.dat file to the HMI application PC installation directory (default:
C:\Program Files\AREVA\IHM Dip5000\. If an old dipsoft.dat file is present, a message
will ask you to replace it; answer YES.
DIP5K/EN MT/A22 Maintenance
This window notifies the user of the current DSP and EPLD version and the versions to load.
Maintenance DIP5K/EN MT/A22
When all files have been successfully transferred, the DIP5000 resets.
11. Reset the Event and Alarm logs when upgrading from a digital version earlier than
ZZ339A-05 or an analog version earlier than ZZ350A-03.
12. Check that the DIP5000 version complies with the upgrade version by selecting menu
Read/local/version.
13. Delete the C:/ diptemp directory, and the dipsoft.dat file from the HMI directory
NOTE: In the event of a communication problem beetween the HMI PC and
the DIP5000 the following notification message appears:
BLANK PAGE
Human Machine Interface DIP5K/EN HI/A22
DIP 5000
HUMAN MACHINE
INTERFACE
HUMAN MACHINE
INTERFACE
CONTENTS
1. SAFETY INSTRUCTIONS 8
3. OVERVIEW 10
3.1 Foreword 10
3.2 System Required 10
3.3 Installing the HMI 10
6. INTERFACE DESCRIPTION 16
6.1 Main screen 16
6.2 Header bar 16
6.3 Menu bar 17
6.4 Toolbar 17
6.5 Status bars 17
6.6 Work and dialog zone. 18
7. FUNCTIONALITIES DESCRIPTION 19
7.1 <Tools> Menu 19
7.2 <File> Menu 19
7.3 <DIP> Menu 20
7.4 <History> Menu 20
7.5 <Test> Menu 20
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 2/70 DIP 5000
LIST OF FIGURES
MODIFICATIONS PAGE
VERSION DATE COMMENTS
A11 01/04/2001 ORIGINAL ISSUE
B11 08/23/2004 AREVA LOGO AND ADDITION OF ANALOG
VERSION
C11 07/12/2006 NEW FEATURES AND ADDITIONAL TECHNICAL
EXPLANATIONS
D11 11/14/2007 NEW CHAPTER. TASK ORIENTED WRITING. HMI
CHAPTER SEPARATED IN THREE PARTS DIGITAL,
ANALOG SINGLE TONE, ANALOG DUAL TONE.
E11 02/11/2008 MINOR CORRECTIONS
A22 08/14/2008 PACKAGE RELEASE 2.2
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 6/70 DIP 5000
BLANK PAGE
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 7/70
GENERAL
This manual describes the Human-Machine interface of the DIP 5000, i.e. the software
application which enables commissioning, operational use and maintenance of this
equipment.
DEFINITIONS
HMI tool for using the DIP 5000 (Human-Machine Interface)
Configuration all the characteristics (fixed components) and parameters
(customisation components) of a DIP 5000
Configuration File micro-computer file containing all the configuration components of a
DIP 5000
Input password password for accessing the ‘Password Manager’ utility
User level all the authorised operations corresponding to the level of
responsibility of a given operator
Level password password for accessing a user level
1. SAFETY INSTRUCTIONS
• In the text Menu names are shown between <> example: menu <DIP>
• Window names are shown between <> example: < Input Window >
Answer
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 10/70 DIP 5000
3. OVERVIEW
3.1 Foreword
As it is powerful and easy to use, the DIP 5000 Analog HMI enables local:
• complete commissioning of the unit and control of its levels, without the need for other
tools,
• run the setup.exe file from the <Run> <Menu> in the program manager:
D\:setup.exe,
Menus
Level
Menus 0 2
File new x x
open x x
Tools Identification x x
To user level 0 x x
connect x x
disconnect x x
exit x x
DIP * configuration x x
hardware configuration x x
version x x
Alarms snapshot x x
input/output x x
Reset x
DIP/Date * read x x
write x
DIP/Maintenance * Input level measure x x
Output levels setting, adjustment receiving x
alignment and automatic alignment
switch to maintenance mode x
Unlocking line (security) x
Unlocking relay (security) x
local loop back x
transmitter forcing x
command output forcing x
alarm forcing x
Help x x
• upper case (A to Z)
• lower case (a to z)
• numbers (0 to 9)
3. Enter DIP5000 in upper case in this window (only the first time).
NOTE: Modifying the Password Manager password is recommended after the
first use (see the next paragraph).
3. Enter the new password in compliance with the rules for Password Creation (see § 5.1).
Carefully note the new password. If you lose it the application must be reinstalled.
2. Enter the password to be created while complying with the password creation rules (see
§ 5.1). Enter the password again in the “Confirm password” field.
1. To remove a password, select the password line in the list and click the
button. A confirmation message is then displayed, Answer yes.
5.6 Exiting the Password Manager
To exit the password manager and return to the WINDOWS environment, select Password>
Exit.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 16/70 DIP 5000
6. INTERFACE DESCRIPTION
The HMI has an integrated environment, using standard WINDOWS tools and processes.
As only the operating modes specific to the HMI will be mentioned in the following, it is
recommended that operators not familiar with WINDOWS refer to the user manual for this
environment.
6.1 Main screen
The main screen is composed of functional zones (see the following figures).
FIGURE 4 – TOOLBAR
6.5 Status bars
Depending on the user level and the type of operation in progress, status bars can appear
displaying the following information.
The bottom bar displays:
• any alarm present (clicking in this zone opens a window displaying the faults that
have triggered this alarm)
• tick boxes
• command buttons
• text boxes
• lists
• scroll bars
7. FUNCTIONALITIES DESCRIPTION
7.1 <Tools> Menu
Identification: Opens a pop up window, asking you to enter a password to set your user
level. Access to a higher user level is password protected.
Back to level 0: this will return you to priority level 0.
Disconnect: Disconnects the HMI from the DIP 5000.
Exit: Closes the DIP 5000 HMI application.
7.2 <File> Menu
File>New: Creates a configuration file from a default configuration in a DIP 5000 version
(Single tone or Dual tone). When selected, a pop-up window opens asking you to choose
DIP 5000 version (Single tone or Dual tone).
This menu is used to read the following parameters on the local unit:
• Configuration: Read the configuration file from the DIP 5000and modify all
configuration parameters,
• Hardware configuration: Read hardware configuration parameters,
• Maintenance: Used to launch measurements, adjust levels, force values,
• Alarms snapshot: Provides a view of the current alarm status,
• Input/Output: Read input and output status,
• Version: Read firmware versions,
• Date Setup: Read and write the date and time on the unit,
• Reset: Perform hardware and software resets on the unit.
7.4 <History> Menu
• Erase: Delete the event and alarm logs via two sub menus <Erase Events> and
<Erase Alarms>.
7.5 <Test> Menu
• Create a confirguration
To connect to a DIP 5000, click on the Connect icon or open the <Tools> menu:
and pick <Connect local> which will open the <Connection> window:
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 22/70 DIP 5000
You can pick among the ports automatically detected by the HMI or shortcuts previously
defined. To create a new shortcut, right-click in the desired location of the Favorites tree.
4. You can change the firmware password with this option. Bear in mind that if you lose
the firmware password, the motherboard (UT148) will have to be returned to the
factory.
8.3.3 Returning to level 0
The user level can be reset to 0 at any moment.
To set user level to 0
1. Select Tools> Back to level 0
The HMI has scanned the machine for all RS 232C ports which are listed under "Default".
You can also define names of groups and/or individual ports by right-clicking on elements of
the "Favorites" tree leading to a structure like this:
Answer .
The HMI closes.
8.4 General configuration procedure
The configuration of a new unit or reconfiguration of an existing unit involves creating a
configuration file:
• Select the DIP 5000 Single Tone version in the < Version selection > Window after
clicking File > New,
• Select DIP>Configuration
• General
• Sender
• Receiver
• Input/Output
• Alarms
This configuration window is used to access to the following parameters:
• Number of Commands
• Version (Normal/Enhanced)
• Comments
• HMI Speed
• Link test
• Logical Address
• IRIG-B State
• Sender parameters
• Receiver parameters
• Input/Output parameters
• Alarms
8.5.2 Configuration Window Toolbar
FIGURE 9 – TOOLBAR
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 28/70 DIP 5000
Clicking the button opens a Synthesis Window displaying the DIP 5000 Configuration
parameters in text format:
Select the value corresponding to your configuration by checking the corresponding radio
button.
8.6.2 Configuring Version
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 30/70 DIP 5000
• Normal: in this mode the power available for a signal command is unchanging, and
linked to the number of commands. Total available power is uniformly distributed
between the number of commands.
Select the 600, 1200, 2400, 4800, or 9600 bps values by checking the corresponding radio
button,
8.6.5 Configuring Logical Address
Range 0 to 255. The sender and the receiver units must have the same logical address.
8.6.6 Entering Comments
Enter the Source Station, the Destination Station, and your comments in compliance with
the following rules:
The Link Test feature is used to automatically and periodically check the transmission
medium between the sender and the receiver, by sending a message in a loop.
To schedule transmission tests:
Select test periodicity by checking the corresponding button:
• Daily: in this case, enter the hour and minutes using the scroll-down window
• Hourly: in this case, enter the minutes using the scroll-down window.
• External: The Guard source comes from an external unit (PLC or other).
NOTE: The <LF Band Guard> parameter is Guard Source parameter
dependent. So the Guard source parameter must first be configured.
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 33/70
• 300 - 2000
• 300 - 2400
• 300 - 3400
Select the Guard via the Guard scroll-down window.
Choices of <Guard> parameter are <Bandwidth> parameter dependent:
The Transmission level corresponds to the signal power allocated to a Frequency and to
the Guard.
The value range is -30 dBm to 6 dBm, the display accuracy is 0,1 dBm.
To configure Transmission levels For Guard and Frequency 1 to 4:
Select, using the scrolling button, the Transmission levels in compliance with the following
rule:
The difference between frequency transmission levels must not exceed 16 dBm. If this rule is
not respected, a warning message appears when attempting to save the configuration file.
• Holding Delay
• Protection schemes
8.7.4.1 Configuring Sender Holding Delay
• Input signal commands whose duration is inferior to the Input Valid Delay are
validated and transmitted without any prolongation.
Restitution at the receipt end of input commands sent in such condition is not
guaranteed because the transmission time may be less than the processing time
required by the Protection Scheme.
• Input signal commands whose duration is greater than the Input Valid Delay are
validated and transmitted for a minimum duration corresponding to the Holding Delay
parameter.
When the Holding Delay parameter is greater than the processing reception
duration, reception of input command sent in such condition is guaranteed to be
lossless.
Parameter Values
Parameter values are in ms.
Range value 0 to 5 ms.
Example
E.g. holding delay 50ms, input validation delay 5ms:
1. Input signal command 3ms, duration less than the Input valid Delay, the <Holding
Delay> is not taken into account; the command is sent without any prolongation time.
2. Input signal command 6ms, command input duration greater than the Input Valid Delay.
The <Holding Delay> is taken into account and the command is transmitted for the
Holding Delay: 50 ms.
3. Input signal command 60 ms: command input duration greater than the Input Valid
Delay. Signal Input command greater than the <Holding Delay>. The signal input
command is transmitted for 60 ms.
Procedure
Select the Input Valid Delay for each command by positioning the scrolling button.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 36/70 DIP 5000
Parameter Description
3 protection Schemes are available
Permissive tripping,
Blocking,
Direct tripping.
Permissive tripping commands are always monitored by a protection relay. The circuit
breaker is tripped when receipt of the command coincides with operation of the protection
relay at the receiving end responding to a system fault. The intention of these schemes is to
speed up tripping for faults occurring within the protected zone.
Blocking commands are initiated by a protection element that detects faults external to the
protected zone. Detection of an external fault at the local end of a protected circuit results in
a blocking signal being transmitted to the remote end. At the remote end, receipt of the
blocking signal prevents the remote end protection operating if it had detected the external
fault. The risk of a spurious trip is higher.
Direct tripping, intertrip signals are sent directly to the master trip relay. Receipt of the
command causes circuit breaker operation. The method of communication must be reliable
and secure because any signal detected at the receiving end will cause a trip of the circuit at
that end.
Procedure
For each command select the protection scheme by selecting the value with the scroll down
window.
8.7.5 Sender Transmission parameters configuration procedure
Depending on user needs and of the characteristics of input signals applied to the DIP 5000,
notably their duration, two procedures are available.
8.7.5.1 Procedure Without Input Valid Delay
For each command:
1. Using the scroll-down window select a protection scheme.
Optional:
2. Select a Holding Delay using the scrolling button.
The Bandwidth is a technical characteristic of the medium used corresponding to its signal
transmission capacity.
Depending on the characteristics of the medium, select the appropriate bandwidth via the
Bandwidth scroll-down window.
Possible values are:
• 300-2000,
• 300-400,
• 300-3400.
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 39/70
Guard Signal
This parameter defines the Guard Signal level.
Parameter values are in dBm.
Value Range -40 to 0 dBm.
Select the Guard Signal input level using the scrolling button.
Commands vs Guard
This parameter corresponds to the relative level between signal commands and the Guard
Signal.
Parameter values are in dB.
Depending on the selected version (normal or enhanced) two values ranges are possible:
0 - 6 dB for the normal version,
0 - 16 db for the enhanced version.
Select the Commands vs Guard using the scrolling button.
NOTE: The Receiver Input level, can also be set from the Maintenance window, manually or
automatically (see § 8.13).
8.8.3 Configuring Receiver Protection Scheme
Parameter description
Three protection type values are available: Permissive, Blocking, and Direct tripping.
For each command, select the Type using the scroll-down window.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 40/70 DIP 5000
Parameter description
Idle state: the restitution relay is set to the idle state if an alarm occurs.
Former state: the restitution relay contact stays open or closed, even when an alarm is set.
The alarm has no influence on contact state.
For each command select the Relay State on Alarm using the scroll-down window.
8.8.5 Configuring Receiver Holding Delay
Unblocking
Only command which type is Permissive tripping can be unblocked. Each command can be
unblocked, independently of the others.
For each command to unblock check the corresponding box.
Unblocking Threshold
Parameter values are in dB. The value range is -20 to -10 dB. Display accuracy is ± 0.1dB.
Click the button, give a path for the configuration file and name it.
Select the I/O Boards parameter corresponding to your hardware configuration by checking
the corresponding radio button.
For 2 commands select 1 board,
For more than 2 commands, 1 board or two boards can be selected.
NOTE: If two boards are selected, a Combinatorial Logic on Inputs part is
displayed.
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 43/70
Parameter Description
The Input Filter Delay is a threshold applied to the input command signal. It is used to
exclude high noise-level signals which could be taken as input signal commands.
Signal commands with a duration less than the Input Filter Delay duration are not
transmitted.
Signal commands with a duration greater than the Input Filter Delay duration are validated
and transmitted. The propagation time of the command transmitted via the Input Filter Delay
increases of the Input Filter Delay.
Parameter value
Range 0 to 3 ms in 1 ms steps.
Procedure
Select the value using the scrolling button for each command to which an Input Filter Delay
is to be applied.
8.9.3 Configuring Combinatorial logic on inputs
This panel is only available having configured 4 commands/2 boards.
• IN1: The command is allocated to the input signal connected to the IN1 input (P10
connector)
• IN2: The command is allocated to the input signal connected to the IN2 input (P10
connector)
• IN1 or IN2: The command is allocated to the result of the OR operator applied to the
input signal connected to the IN1 input (P10 connector) and the IN2 input (P10
connector)
• IN1 and IN2: The command is allocated to the result of the AND operator applied to
the input signal connected to the IN1 input (P10 connector) and the IN2 input (P10
connector)
For command 2 same explanation replacing IN1 by IN3 and IN2 by IN4.
For command 3 same explanation replacing IN1 by IN5 IN2 by IN6 and P10 connector by
P12 connector.
For command 4 same explanation replacing IN1 by IN7 IN2 by IN8 and P10 connector by
P12 connector.
8.9.4 Sending Input/Output Configuration
When you have completed Input/Output Parameters configuration as described above:
Click the button, give a path for the configuration file and name it.
The External alarm input comes from an external device, PLC or other.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 46/70 DIP 5000
The external unit and the DIP 5000 must be interconnected with a special connection cable
supporting alarm wires.
Parameter values are in seconds. The value range is 0 to 2.5 s. The display accuracy is
± 0.1s.
This alarm occurs if the Signal level, measured through internal digital filter, is under a
Threshold during a Delay.
Threshold
Defines the level under which an alarm is set.
Parameter values are in dBr. The value range is -16 to -6 dBr. Display accuracy is ± 0.1 dBr
Delay
Defines the low level signal delay from which an alarm is set.
Parameter values are in seconds. The value range is 1 to 10 s. The display accuracy is
± 0.1s.
Click the button, give a path for the configuration file and name it.
Save: This menu opens a standard dialog box of Windows® allowing the displayed
configuration to be saved in a file.
To save a configuration file:
Select File > Save
Give a path and a name to the configuration file.
8.11.3 Sending a configuration file
Send: This menu, accessible from user level 2, with connection established, is used to send
the displayed configuration to the unit. After receiving the configuration file, the unit resets.
When the unit restarts the sent configuration is taken into account.
A window configuration is opened in the HMI using the menus <File><New> or
<File><Open> or <DIP><Configuration>.
Once modified, the configuration file can be sent to the unit by the menu <File><Send> or
the <Send> button.
To send a configuration file:
• Configuration,
• Hardware configuration,
• Maintenance
• Alarms Snapshot
• Input/Output
• Versions
• Date Setup
The DIP Menu also allows the <Reset> command to be launched (from user level 2).
8.12.1 Reading the Configuration
To read the configuration parameters of the connected DIP 5000:
Select DIP> Configuration and the DIP 5000 Configuration is displayed:
When the configuration window is open, the user can modify configuration parameters (see
§ 8.6 and following).
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 51/70
• local loopback,
This Panel, accessible from user level 2, shows the Input level graphically, as well as
numerically in the top part of the panel.
The range of displayed values is -45 to 15 dBr, 0 dBr is the nominal receiver alignment
value. Display accuracy is ± 0.1 dBr.
This Panel, accessible from user level 2, is used to set the DIP 5000 frequencies and guards
output levels.
The value range is -30 dBm to 6 dBm with an accuracy of ± 0.1 dBm accuracy.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 56/70 DIP 5000
Procedure
For the Guard frequency and Frequencies 1 to 4:
Select the output level by positioning the scrolling button.
This panel, accessible from user level 2 is used to adjust receiver level.
Guard Frequency
The received level of the guard frequencies is directly given in dBm.
This level can be adjusted to between - 45 dBm and +15dBm.
Display accuracy is ± 0.1 dBm.
The settings for Guard and Relative Level Commands Guards are independent and the
settings values must be sent separately.
Procedure
Using the scrolling button windows, select the Guard Receive level.
Answer .
A message informing the user of DIP 5000 reset is displayed.
The settings are now stored in the flash memory and will be active after a reset.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 58/70 DIP 5000
Loop
In this mode, transmission is looped on reception even if the transmission media access is
locked.
Procedure
To activate/deactivate the loop:
Select Active or Inactive by checking the corresponding radio button.
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 59/70
Unlock
The states for line AF and contact relay are:
• Unlocked
• Locked
Unlocking Line AF: This state is used to connect the DIP 5000 transmitter to the
transmission line. This operating mode introduces some risks of unwanted commands since
the operator can simulate the acquisition of a command.
Locking Line AF: This state is used to disconnect the DIP 5000 transmitter from the
transmission line. The operator can then simulate command acquisition without any risk.
Unlocking Contact relay: When this state is activated, the output command relays states
comply with the command conditions present on the reception line. This operating mode
introduces some risks of local unwanted commands in the event of loopback.
Locking Contact Relay: When this state is activated, the output command relays are forced
to the idle state, whatever the command conditions present on the reception line.
Procedure
To unlock Line AF:
Check the Line AF box
To lock Line AF
Un-check the line AF box
To unlock Contact Relay
Check the Contact Relay box
To lock Contact relay
Un-check the Contact Relay box
Once the Loop and Unlock parameters are configured:
This panel is used to force the state of the output command relays on the local unit,. The
output command relays will be activated only if the relays are unlocked. The recopy relays
must be always unlocked.
To force an Output Relay:
Check the corresponding Command box
To force alarms:
Check the box for the Alarms to be forced, Major, Minor or both.
Click on the button to copy PC Time Date settings in the DIP 5000 part.
NOTE: Viewing and date setup is also possible clicking on the button
from the top toolbar.
8.15 Resetting the DIP
To reset the DIP 5000 from the DIP menu:
Select DIP> Reset
A confirmation message pop-up window is displayed:
Answer .
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 64/70 DIP 5000
The following window appears to inform the user that a reset is being performed.
After restarting of the DIP 5000, check the correct status of the LEDS and that there are no
alarms.
8.16 Operating <History> Menu
• undated (counters)
• Counters
The <History> menu also allows the events and alarms buffers to be erased.
WARNING: AFTER CLEARING THE BUFFERS THE INFORMATION CANNOT BE
RECOVERED
8.16.1 Reading Events
To read Events:
Select History>Events the following message is displayed while events are being loaded:
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 65/70
The record and print buttons respectively allow files to be recorded and printed.
Internal time-stamped events, are recorded in a stack limited to 1785 events. When the stack
is full, any further event replaces the oldest one.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 66/70 DIP 5000
The record and print buttons respectively save and print alarm files.
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 67/70
The record and print buttons respectively allow files to be recorded and printed.
Counter files (*.cnter) can be opened using the File menu of the Main window:
Answer
Check the event file is empty by selecting History> Events.
8.16.5 Erasing Alarms
The Erase Alarms option will delete all entries from in the alarm list.
NOTE: Erasing alarms completely removes them from the system, and the
action cannot be undone. If you might need to view the alarms at a
later date, use the File>Save option to save a copy of the alarm list
before using Erase>Events.
To delete the currently displayed alarm list.
Select History > Erase> Erase Alarms
Human Machine Interface DIP5K/EN HI/A22
SINGLE TONE
DIP 5000 Page 69/70
Answer
Check the Alarm file is empty by selecting History> Alarms
8.17 Operating <Test> Menu
Link test is used to check the ability of the DIP 5000 link to send and receive bidirectional
commands.
Launching Link Test automatically can also be scheduled daily or Hourly see § 8.6.7 for
settings.
Command processing has priority on Link Test.
To launch Link Test:
Select Test> Link Test
In case of bad test results, a DIP 5000 failure is declared.
8.18 Help Menu
This menu allows the Help file to be accessed and the HMI software version to be read.
DIP5K/EN HI/A22 Human Machine Interface
SINGLE TONE
Page 70/70 DIP 5000
HUMAN MACHINE
INTERFACE
CONTENTS
1. SAFETY INSTRUCTIONS 8
3. OVERVIEW 10
3.1 Foreword 10
3.2 System Required 10
3.3 Installing the HMI 10
6. INTERFACE DESCRIPTION 16
6.1 Main screen 16
6.2 Header bar 16
6.3 Menu bar 17
6.4 Toolbar 17
6.5 Status bars 17
6.6 Work and dialog zone 18
7. FUNCTIONALITIES DESCRIPTION 19
7.1 <Tools> Menu 19
7.2 <File> Menu 19
7.3 <DIP> Menu 20
7.4 <History> Menu 20
7.5 <Test> Menu 20
LIST OF FIGURES
MODIFICATIONS PAGE
BLANK PAGE
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 7/68
GENERAL
This manual describes the Human-Machine interface of the DIP 5000 teleprotection, i.e. the
software application which enables commissioning, operational use and maintenance of this
unit.
DEFINITIONS
HMI tool for using the DIP 5000 teleprotection (Human-Machine Interface)
Configuration all the characteristics (fixed components) and parameters
(customisation components) of a teleprotection
Configuration File micro-computer file containing all the configuration components of a
teleprotection
Input password password for accessing the ‘Password Manager’ utility
User level all the authorised operations corresponding to the level of
responsibility of a given operator
Level password password for accessing a user level
1. SAFETY INSTRUCTIONS
• In the text Menu name are between <> example: menu <DIP>
Answer
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 10/68 DIP 5000
3. OVERVIEW
3.1 Foreword
As it is powerful and easy to use, the DIP 5000 Analogic teleprotection HMI enables local:
• complete commissioning of the unit and control of its levels, without the need for other
tools,
• The HMI runs on PCs fitted equipped with PIII microprocessors and higher, operating
under WINDOWS 2000 or XP. They must have at least 40 Mb free on the hard disk.
3.3 Installing the HMI
• run the setup.exe file from the <Run> <Menu> in the program manager: D\:set up,
4.2 Menus
Level
Menus 0 2
File new x x
open x x
Tools Identification x x
To user level 0 x x
connect x x
disconnect x x
exit x x
DIP * configuration x x
hardware configuration x x
version x x
Alarms snapshot x x
input/output x x
Reset x
DIP/Date * read x x
write x
DIP/Maintenance * Input level measure x x
Output levels setting, adjustment receiving x
alignment and automatic alignment
switch to maintenance mode x
Unlocking line (security) x
Unlocking relay (security) x
local loop back x
transmitter forcing x
commands output forcing x
alarms forcing x
Help x x
• upper case (A to Z)
• lower case (a to z)
• numbers (0 to 9)
2. Select Password > Input, the following < Password Input> window opens:
3. Enter DIP5000 in upper case in this window (only the first time).
NOTE: Modifying the Password Manager password is recommended after the
first use (see the next paragraph).
3. Enter the new password in compliance with the rules for Password Creation (see § 5.1).
Carefully note the new password. If you lose it the application must be reinstalled.
2. Enter the password to be created while complying with the password creation rules (see
§ 5.1). Enter the password again in the “Confirm password” field.
1. To Remove a password, select the password line in the list and click the
button. A confirmation message is then displayed, Answer yes.
5.6 Exiting the Password Manager
To exit the password manager and return to the WINDOWS environment select
Password>Exit.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 16/68 DIP 5000
6. INTERFACE DESCRIPTION
The HMI has an integrated environment, using standard WINDOWS tools and processes.
As only the operating modes specific to the HMI will be mentioned in the following, it is
recommended that operators not familiar with WINDOWS refer to the user manual for this
environment.
6.1 Main screen
The main screen is composed of functional zones (see the following figures)
FIGURE 4 – TOOLBAR
6.5 Status bars
Depending on the user level and the type of operation in progress, status bars can appear
displaying the following information:
The bottom bar displays:
• Any alarm present (clicking in this zone opens a window displaying the faults that
have triggered this alarm)
• tick boxes
• command buttons
• text boxes
• lists
• scroll bars
7. FUNCTIONALITIES DESCRIPTION
7.1 <Tools> Menu
Identification: Opens a pop up window, asking you to enter a password to set your user
level. Access to a higher user level is password protected.
Back to level 0: this will return you to priority level 0.
Disconnect: Selecting this menu disconnects the HMI from the DIP 5000.
Exit: Closes the DIP 5000 HMI application.
7.2 <File> Menu
File>New: Creates a configuration file from a default configuration in a DIP 5000 version
(Single tone or Dual tone). When selected a pop-up window opens asking you to choose
DIP 5000 version (Single tone or Dual tone)
This menu enables you to read the following parameters on the local unit:
• Date Setup: Read and write the date and time on the unit.
• Erase: Via two sub menus Erase Events and Erase Alarms, allows event and alarm
logs to be deleted from the unit.
7.5 <Test> Menu
You can change the firmware password with this option. Bear in mind that if you lose the
firmware password, the motherboard (UT148) will have to be returned to the factory.
8.2.3 Returning to level 0
At any moment, user level can be set to 0.
To set user level to 0
1. Select Tools> Back to level 0
The HMI has scanned the machine for all RS 232C ports which are listed under "Default".
You can also define names of groups and/or individual ports by right-clicking on elements of
the "Favorites" tree leading to a structure like this:
Answer .
The HMI closes.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 24/68 DIP 5000
• *.rtf -> existing configuration file, this selection will open a window (see Figure 10 for
the window display)
• *.alarms -> alarm list file for consultation (see Figure 27 for the window display)
• *.events -> event list file for consultation (see Figure 26 for the window display)
• *.cnter -> counter statement for consultation ( see Figure 28 for the window display)
• Select the DIP 5000 Dual Tone version in the <version selection> window after
clicking File>New,
• Select DIP>Configuration
• General
• Sender
• Receiver
• Input/Output
• Alarms
This configuration window is used access to the following parameters:
• Comments
• HMI Speed
• Link test
• Logical address
• IRIG-B State
• Sender parameters
• Receiver parameters
• Input/Output parameters
• Alarms
8.5.2 Configuration window toolbar
FIGURE 11 – TOOLBAR
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 27/68
Clicking the button opens a Synthesis Window displaying the DIP 5000 Configuration
parameters in text format:
Select the 600, 1200, 2400, 4800 or 9600 bps value by checking the corresponding button,
8.6.2 Configuring Logical Adress
Range 0 to 255. The sender and the receiver units must have the same logical address.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 28/68 DIP 5000
Enter the Source Station, the Destination Station, and your comments in compliance with the
following rules:
• Daily: in this case enter the hour and minutes using the scroll-down window
• Hourly: in this case enter the minutes using the scroll-down window.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 29/68
• 300-1900
• 400-2000
• 300-1900
• 670-2260
• 850-2450
• 1040-2630
• 1220-2810
• 1400-3000
• 1590-3180
• 2000-3600
8.7.2 Configuring Sender Transmission levels
The transmission level corresponds to the signal power allocated to a Frequency and to the
Guard.
The value range is -30 dBm to 6 dBm, the display accuracy is 0,1 dBm.
To configure Transmission levels For Guard and Frequency 1 to 8:
Select, using the scrolling button, the transmission level in compliance with the following rule:
The difference between frequency transmission levels must not exceed 16 dBm. If this rule is
not respected, a warning message appears when attempting to save the configuration file.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 31/68
• Holding Delay
• Protection schemes
8.7.3.1 Configuring Sender Holding Delay
• Input signal command 3ms, duration less than the Input valid Delay, the Holding
Delay is not taken into account, the command is sent without any prolongation time.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 33/68
• Input signal command 6ms, command input duration greater than the Input Valid
Delay (5ms). The Holding delay is taken into account and the command is
transmitted for the Holding Delay: 50 ms.
• Input signal command 60 ms: command input duration greater than the Input Valid
Delay. Signal Input command greater than the Holding Delay. The signal input
command is transmitted for 60 ms.
Procedure
Select the Input Valid Delay for each command by positioning the scrolling button.
8.7.3.3 Configuring Sender Protection Scheme
Parameter Description
6 protection Schemes are available. There are three basic schemes, Permissive tripping,
Blocking, and Direct tripping.. Each of these, in turn, has a more secure version, but which is
slower
Permissive tripping commands are always monitored by a protection relay. The circuit
breaker is tripped when receipt of the command coincides with operation of the protection
relay at the receiving end responding to a system fault. The intention of these schemes is to
speed up tripping for faults occurring within the protected zone.
Blocking commands are initiated by a protection element that detects faults external to the
protected zone. Detection of an external fault at the local end of a protected circuit results in
a blocking signal being transmitted to the remote end. At the remote end, receipt of the
blocking signal prevents the remote end protection operating if it had detected the external
fault. The risk of a spurious trip is higher.
Direct tripping, intertrip signals are sent directly to the master trip relay. Receipt of the
command causes circuit breaker operation. The method of communication must be reliable
and secure because any signal detected at the receiving end will cause a trip of the circuit at
that end.
Procedure
For each command select the protection scheme by selecting the value with the scroll down
window.
8.7.4 Sender Transmission parameter configuration procedure
Depending on user needs and of the characteristics of input signals applied to the DIP 5000,
notably their duration, two procedures are available.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 34/68 DIP 5000
The Bandwidth is a technical characteristic of the medium used corresponding to its signal
transmission capacity.
Depending on the characteristics of the medium, select the appropriate bandwidth via the
Bandwidth scroll-down window.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 36/68 DIP 5000
• 300-1900
• 400-2000
• 670-2260
• 850-2450
• 1040-2630
• 1220-2810
• 1400-3000
• 1590-3180
• 2000-3600
8.8.2 Configuring Receiver Input Level
Guard Signal
This parameter defines the Guard Signal level.
Parameter values are in dBm.
Value Range -40 to 0 dBm.
Select the Guard Signal input level using the scrolling button.
Commands vs Guard
This parameter corresponds to the relative level between signal commands level and Guard
Signal.
Parameter values are in dB.
Value Range -6 + 6 dB
Select the Commands vs Guard using the scrolling button.
NOTE: The Receiver Input level can also be set from the Maintenance
window, manually or automatically.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 37/68
Parameter description
These are the same protection schemes described in Configuring Sender Protection
Scheme on page 33.
When assigning type to commands make sure that receiver and sender are both using the
same protection scheme.
Procedure
For each command:
Select the Type using the scroll-down window.
NOTE: Make sure that the selected type belongs to the same type range
values.
8.8.4 Configuring Relay State on AI
Parameter description
Idle state: the restitution relay is set to the idle state if an alarm occurs.
Former state: the restitution relay contact keeps, open or closed, even an alarm is set. The
alarm has no influence on contact state.
For each command:
Select the Relay State on AI using the scroll-down window.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 38/68 DIP 5000
Unblocking
Only command which type is Permissive tripping can be unblocked. Each command can be
unblocked, independently of the others.
For each command to unblock, check the corresponding box.
Unblocking Threshold
Parameter values are in dB. The value range is -20 to -10 dB. Display accuracy is ± 0.1dB.
Parameter values are in ms. The value range is 5 to 80 ms. Display accuracy is ± 1 ms.
Click the button, give a path for the configuration file and name it.
• IN1: The command is allocated to the input signal connected to the INT1 input (P10
connector)
• IN2: The command is allocated to the input signal connected to the INT2 input (P10
connector)
• IN1 or IN2: The command is allocated to the result of the OR operator applied to the
input signal connected on the INT1 input (P10 connector) and the INT2 input (P10
connector)
• IN1 and IN2: The command is allocated to the result of the AND operator applied to
the input signal connected to the INT1 input (P10 connector) and the INT2 input (P10
connector)
For command 2 same explanation replacing IN1 by IN3 and IN2 by IN4.
For command 3 same explanation replacing IN1 by IN5 IN2 by IN6 and P10 connector by
P12 connector.
For command 4 same explanation replacing IN1 by IN7 IN2 by IN8 and P10 connector by
P12 connector.
8.9.4 Sending Input/Output Configuration
When you have completed Input/Output Parameters configuration as described above:
Click the button, give a path for the configuration file and name it.
The External alarm input comes from an external unit, PLC or other.
The external unit and the DIP 5000 must be interconnected with a special connection cable
supporting alarm wires.
Parameter values are in seconds. The value range is 0 to 2.5 s. The display accuracy is
± 0.1s.
To configure Alarm on External Input
1. Check the Alarm on external input box,
2. Check the alarm level Minor or Major button.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 43/68
This alarm is set if the input command signal duration is more than the parameter value.
Parameter values are in seconds. The values range 0.5 to 10 s. The display accuracy is
± 0.1s.
Delay
Defines the low level signal delay from which an alarm is set.
Parameter values are in seconds. The value range is 1 to 10 s. The display accuracy is
± 0.1s.
Noise alarm
This alarm occurs if the noise level, measured through internal digital filter, is above a
Threshold during a Delay.
Alarms are displayed in the Snapshot window.
Threshold
Parameter values are in dBr. The value range is -12 to -6 dBr. The display accuracy is
± 0.1 dBr.
Delay
Parameter values are in s. The value range is 1 to 10 s. The display accuracy is ± 0.1s.
The Link test can be periodical (Daily or Hourly) launched (for settings see § 8.6.4).
An instantaneous Link test can also be launched from the toolbar (Menu Test > Link Test).
In case of test failure, an alarm is set. An alarm status is displayed in the Alarm Snapshot
window.
To configure Alarm on link test failure select the level of alarm by checking the
corresponding button.
8.10.6 Configuring Locking alarm
This alarm occurs in case of medium transmission default during a specified period.
Parameter values are 1 to 10 s. in steps of 1 s.
To configure Locking alarm check the Locking alarm box and select the duration by
positioning the scrolling button the Locking Alarm.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 45/68
Click the button, give a path for the configuration file and name it.
Save: This menu opens a standard Windows®dialog box allowing the displayed
configuration to be saved in a file.
To save a configuration file:
Select File > Save
Give a path and a name to the configuration file.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 47/68
the button.
To send a configuration file:
• Configuration,
• Hardware configuration,
• Alarms Snapshot
• Input/Output
• versions
Date Setup See § 8.14 for more details. The DIP menu can also be used to launch the
<Reset> command.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 48/68 DIP 5000
The user can now modify configuration parameters (see § 8.6 and following).
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 49/68
• local loopback,
This Panel, accessible from user level 0, show the Input level graphically.
Numerical values are also displayed in the top part of the panel.
The range of displayed values is -45 to 15 dBr, 0 dBr is the nominal value of receiver
alignment. The display accuracy is ± 0.1 dBr.
This Panel, accessible from user level 1 and higher, is used to set the DIP 5000 frequencies
and guards output levels.
The value range is -30 dBm to 6 dBm with an accuracy of ± 0.1 dBm
Procedure
For the Guard frequency and Frequency 1 to 7 select the output level by positioning the
scrolling button.
This panel, accessible at user level 2 allows the receiver level to be adjusted.
Guard Frequency
The receiver level of the guard frequencies is directly given in dBm.
This level can be adjusted to between - 45 dBm and +15dBm.
The display accuracy is ± 0.1 dBm.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 55/68
Answer .
A message confirming DIP 5000 reset is displayed.
The settings are now stored in the flash memory and will be active after any reset of the
DIP 5000.
8.13.7 Configuring Maintenance Force loopback
This tab is accessible from user level 2 and in maintenance mode.
To access the Force/Lock/Loop window, open the Maintenance window and select the
<Force/Lock/Loop> tab.
Loop
In this mode, transmission is looped on reception even if the transmission media access is
locked.
Procedure
To activate the loop, select Active by checking the corresponding button.
To deactivate the loop, select Inactive by checking the corresponding button.
Unlock
The states for line AF and contact relay are:
• Unlocked
• Locked
Unlocking Line AF: This state is used to connect the teleprotection transmitter to the
transmission line. This operating mode introduces some risks of unwanted commands since
the operator can simulate the acquisition of a command.
Locking Line AF: This state is used to disconnect the teleprotection transmitter from the
transmission line. The operator can then simulate a command acquisition without any risk.
Unlocking Contact relay: When this state is activated, the output commands relays states
comply with the command conditions present on the reception line. This operating mode
introduces some risks of local unwanted commands in the event of loop back.
Locking Contact Relay: When this state is activated, the output commands relays are forced
to the idle state, whatever the command conditions present on the reception line.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 58/68 DIP 5000
Procedure
To unlock Line AF:
Check the Line AF box
To lock Line AF
Un –Check the line AF box
To unlock Contact Relay
Check the Contact Relay box
To lock Contact relay
Un –Check the Contact Relay box
Once the Loop and Unlock parameters are configured:
Freq 8 corresponds to the frequency guard, Freq 1 to Freq 7 are used to encode signal
commands.
As two frequencies are required to encode signal commands, and the frequencies are forced
separately; there is no risk of sending a command by forcing frequency.
This panel is used to send frequencies on unlocked lines referring to various states; standby,
command or test message. To use the feature, the recopy relays must always be unlocked.
To force a frequency, check the corresponding button.
This panel is used to force the state of the output commands relays on the local unit. The
output command relays will be activated only if the relays are unlocked. The recopy relays
must be always unlocked.
To force an Output Relay check the corresponding Command box,
To force alarms:
Check the boxes of the type of Alarm(s) to be forced, Major, Minor or both.
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 61/68
Click on the button to copy PC Time Date settings in the DIP 5000 Time/date
part.
Answer .
The following window appears to inform the user that reset is being performed.
After restarting of the DIP 5000, check the correct status of the LEDS and that there are no
alarms. After any reset, in particular after sending a configuration file to the DIP 5000 unit,
the user will have to renter a password for the HMI.
8.16 Operating the < History> Menu
• undated (counters)
• Events files
• Alarms file
• Counters
The <History> menu allows also the events and alarms buffers to be erased.
WARNING: AFTER CLEARING BUFFERS, THE INFORMATION CANNOT BE
RECOVERED
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 63/68
The record and print buttons respectively allow files to be recorded and printed.
Use the File menu in the Main window to read event files (*.event).
Internal timestamped events are recorded in a stack limited to 1785 events. When the stack
is full, any further event replaces the oldest one recorded.
8.16.2 Reading Alarms Window
To read Alarms, select History>Events and the following message pop-up window
confirming events are being loaded:
The record and print button respectively allow files to be recorded and printed.
The File menu of the Main window allows counters files (*.cnter) to be opened:
Answer
8.16.5 Erasing Alarms
The Erase Alarms option allows the deletion of all alarms displayed in the alarm list.
NOTE: Erasing alarms completely removes them from the system, and the
action cannot be undone. If you might need to view the alarms at a
later date, use the File>Save option to save a copy of the alarm list
before using Erase>Events.
To delete the currently displayed alarm list select History > Erase> Erase Alarms
Human Machine Interface DIP5K/EN HI/A22
DUAL TONE
DIP 5000 Page 67/68
Answer
8.17 <Test> Menu
Link test is used to check the ability of the DIP 5000 link to send and receive bidirectional
commands.
Launching Link Test automatically can also be scheduled Daily or Hourly (see § 8.6.4 for
settings).
Command processing has priority over Link Test.
To launch Link Test, select Test> Link Test
In case of bad test results, a DIP 5000 failure is declared.
A minor or major alarm is set, depending on the alarm configuration (see § 8.10.5).
8.18 <Help> menu
This menu allows the Help file to be accessed and the HMI software version to be read.
DIP5K/EN HI/A22 Human Machine Interface
DUAL TONE
Page 68/68 DIP 5000
HUMAN MACHINE
INTERFACE
CONTENTS
1. SAFETY INSTRUCTIONS 8
3. OVERVIEW 10
3.1 Foreword 10
3.2 System Required 10
3.3 Installing the HMI 10
6. INTERFACE DESCRIPTION 17
6.1 Main screen description 17
6.2 Header bar 18
6.3 Menu bar 18
6.4 Toolbar 18
6.5 Pop-up menus 18
6.6 Status bars. 18
6.7 Work and dialogue zone. 20
7. FUNCTIONALITIES DESCRIPTION 21
7.1 <File> Menu 21
7.2 <Tools> Menu 21
7.3 <Read> Menu 22
7.4 <Date> Menu 22
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 2/58 DIP 5000
LIST OF FIGURES
MODIFICATIONS PAGE
VERSION DATE COMMENTS
A11 01/04/2001 ORIGINAL ISSUE
B11 08/23/2004 AREVA LOGO AND ADDITION OF ANALOG
VERSION
C11 07/12/2006 NEW FEATURES AND ADDITIONAL TECHNICAL
EXPLANATIONS
D11 11/14/2007 NEW CHAPTER. TASK ORIENTED WRITING. HMI
CHAPTER SEPARATED IN THREE PARTS DIGITAL,
ANALOG SINGLE TONE ,ANALOG DUAL TONE.
E11 02/11/2008 MINOR CORRECTIONS
A22 08/14/2008 PACKAGE RELEASE 2.2
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 6/58 DIP 5000
BLANK PAGE
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 7/58
GENERAL
This manual describes the Human-Machine interface of the DIP 5000 teleprotection, i.e. the
microcomputer application which enables commissioning, operational use and maintenance
of this equipment.
DEFINITIONS
HMI tool for using the DIP 5000 teleprotection (Human-Machine Interface)
Configuration all the characteristics (fixed components) and parameters
(customisation components) of a teleprotection
Configuration File micro-computer file containing all the configuration components of a
teleprotection
Input password password for accessing the ‘Password Manager’ utility
User level all the authorised operations corresponding to the level of
responsibility of a given operator
Level password password for accessing a user level
1. SAFETY INSTRUCTIONS
• In the text Menu name are between <> example: <DIP> menu
3. OVERVIEW
3.1 Foreword
As it is powerful and easy to use, the DIP 5000 teleprotection HMI enables local or remote:
• complete commissioning of the equipment and control of its levels, without the need
for other tools,
• run setup.exe file from the <Run> <Menu> in the program manager: D:\setup,
4.2 Menus
Level
Menus 0 2
File new x x
open x x
exit x x
Tools password x x
to user level 0 x x
connect x x
disconnect x x
Read (local/remote) * configuration x x
hardware configuration x x
version x x
comment x x
event list x x
alarm list x x
counter x x
alarms snapshot x x
input/output x x
Date (local/remote) * read x x
write x x
Maintenance * switch to maintenance mode x
unlocking line (security) x
unlocking relay (security) x
local loopback x
remote loopback x
transmitter forcing x
commands output forcing x
alarms forcing x
clear event file (local/remote) x
Interface forcing x
clear alarm file (local/remote) x
local reset x
• upper case (A to Z)
• lower case (a to z)
• numbers (0 to 9)
1. Select Password > Input, the following <Password Input> window opens:
2. Enter DIP 5000 in upper case in this window (only the first time).
NOTE: Modifying the Password Manager password is recommended after the
first use (see the next paragraph).
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 14/58 DIP 5000
3. Enter the new password in compliance with the rules for Password Creation (see § 5.1).
Carefully note the new password. If you lose it the application must be reinstalled.
2. Confirm the new password by re-entering it. The following message is then displayed:
2. Enter the password to be created in the <Password Entry> Window while complyting
with the password creation rules (see § 5.1).
6. When you have finished click the button. Check the Password listing
(see the next paragraph).
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 16/58 DIP 5000
1. To Remove a password, select the password line in the list and click the
button. A confirmation message is then displayed, Answer yes.
5.6 Exiting the Password Manager
To exit from the password manager and return to the WINDOWS environment select
Password Exit.
5.7 Viewing the Software Password Manager Version
Select ?>About, the following window appears:
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 17/58
6. INTERFACE DESCRIPTION
The HMI is an integrated environment, using standard WINDOWS tools and processes.
As only the operating modes specific to the HMI will be mentioned in the following, operators
not familiar with WINDOWS must refer to the user manual for this environment.
6.1 Main screen description
The main screen is composed of 5 functional zones (figure 1 and figure 2 below):
FIGURE 4 – TOOLBAR
6.5 Pop-up menus
By right-clicking on the work space, with connection to the equipment established, a pop-up
menu appears enabling you to carry out all the read operations on local or remote
equipment.
6.6 Status bars.
Depending on user level and the type of operation in progress, status bars display the
following information:
With the HMI connected to the DIP 5000 in maintenance mode, the top bar displays:
• Link address
• Transmission time
• Alarm presence (clicking in this zone opens a window displaying the faults that have
triggered this alarm)
• User level (0 or 2)
• Tick boxes
• Command buttons
• Text boxes
• Lists
• Cursors
7. FUNCTIONALITIES DESCRIPTION
7.1 <File> Menu
The <File> menu elements are used create, modify, and send configuration files, as well as
opening saved alarm (*.Ala) and event (*.Evt) files.
• *.Cfg -> existing configuration file, this selection will open the window (see figure 8)
• *.Ala -> alarm list file for consultation (see figure 13 for the window display
• *.Evt -> event list file for consultation (see figure 11 for the window display)
Exit File: Closes the HMI program.
7.2 <Tools> Menu
Password: This menu enables you to modify the user level. The move to a higher level is
protected and requires input of a password.
To user level 0: This menu enables you to return to the lowest priority 0 level.
Disconnect: This menu enables you to remove the connection between the DIP 5000 and
the PC.
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 22/58 DIP 5000
• Write: Writes the date and time of local or remote equipment, either by recopying the
date and time from the PC, or by sending a date and time selected by the user.
7.5 <Maintenance> Menu
This menu enables all the following maintenance actions:
• Locking: Locks or unlocks the communication line and the command output relays,
• Loop: Carries out a loopback either on the local equipment or on the remote
equipment,
• Forcing: Forces transmission or reception commands and also forces alarm relays.
• Clear buffers: Deletes event and alarm log queues from the local or remote
equipment,
• File menu
• Read menu
8.2.1 File menu Configuration procedure
1. Click on File>New> or File>Open
2. Modify the configuration displayed,
3. Save the changed configuration (<File><Save as ...>).
4. Send the configuration to the equipment.
8.2.2 Read menu Configuration procedure
The configuration on the local or remote equipment can also be modified by reading this
configuration:
1. Click on Read>Local or Remote>Configuration
2. Modify the configuration displayed,
3. Save the changed configuration (<File><Save as ...>).
4. Send the configuration to the equipment.
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 24/58 DIP 5000
The HMI has scanned the machine for all RS 232C ports which are listed under "Default".
You can also define names of groups and/or individual ports by right-clicking on elements of
the "Favorites" tree leading to a structure like this:
Comments
Alarms
Application parameters
Inputs / Outputs
Communication interface
General
Print the configuration
Double click on a significant word from the branch list
on the corresponding configuration window
Save the configuration
D0166ENa
HMI port Speed: select the 600, 1200, 2400, 4800, 9600, 19200 bps value using the scroll
down field,
IRIG-B: select the Off or On value by checking the corresponding circle.
Connect the GPS equipment to the P20 connector.
Synchronize the DIP date to the external source (one synchro top each 30 seconds).
3. Select the Interface Module corresponding to your hardware configuration in the scroll
down field, possible values are:
5. Select the Clock Source value, Received or Internal, by checking the corresponding
circle.
3. Select the digital interface corresponding to your hardware configuration in the scroll-
down window. Possible values:
− IR 180,
− IR 173,
− IR179.
5. Select the clock source, Received or Internal by checking the corresponding circle.
6. Click the Trigger button the following window opens:
7. Select the Time Delay Before Switching parameter value by positioning the cursor.
Possible values are from 5 ms to 100 ms.
8. Click on the Valid button.
9. Check the parameter values are updated in the configuration window:
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 33/58
• OR
• AND
• LOG
When affecting the LOG operator to input signals, a signal command is valid while another
signal command is not sent on the logical associated input.
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 35/58
The following table describes the outputs corresponding to the possible input signal
combination for the LOG operator.
Procedure
To configure the Inputs logic feature:
1. Click on the button from the configuration window, the following window
<Inputs Logic> opens:
The Holding Delay Command Output corresponds to the validity duration of a Command
Output.
1. Check the Command Output to which you want to apply a delay.
2. Adjust the delay positioning the cursor (1 to 3000 ms).
3. Repeat this configuration for each command output to which a delay must be applied.
8.9.3 Configuring Teleprotection Schemes
In the scroll down menu select the receiver teleprotection Scheme to apply to Cmd 1/2 the
possible choices are:
• Permissive
• Direct tripping
• Blocking
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 38/58 DIP 5000
1. In the scroll down menu the Receiver teleprotection Scheme to apply to Cmd 3/4.
1. Check the Bit Error Rate circle corresponding to the Minor Alarm threshold.
2. Check the Bit Error Rate circle corresponding to the Major Alarm threshold.
8.10.2 Configuring Time Overrunning Alarm
If an input signal overruns over the Time Overrunning Input threshold defined, an alarm is
set.
1. Check the box Alarm Time Overrunning Input
2. Position the cursor to define a value time duration (value range 1 to 30 seconds)
3. Affect a level Minor or Major by checking the corresponding circle.
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 40/58 DIP 5000
If the transmission time is over the Transmission time Alarm threshold defined an alarm is
set.
1. Check the Alarm Transmission Time box,
2. Position the Cursor to define a Transmission Time value (range value 3 to 20 ms)
3. Affect a level Minor or Major by checking the corresponding circle.
8.10.4 Configuring Relay Command Delay
Closing of the contact Relay Command can be delayed, possible delay values are the
following
0
2,5 s
5s
10 s
For each Relay 1 and 2, Major and Minor alarm:
Select the delay by positioning the scrolling button.
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 41/58
The <Read> menu is used to display the following information on the local or the remote
teleprotection:
• Configuration
• Hardware configuration
• Comments
• Event list
• Alarms list
• Counters
• Alarms snapshot
• Input/Output status
• Remote bit error rate (the local bit error rate is continually displayed in the lower status
bar)
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 43/58
NOTE: The remote configuration can be read by selecting Read > Remote>
Configuration
8.13.3 Reading Hardware Configuration
To read the local Hardware Configuration select Read > Local> Hardware Configuration
the following window opens:
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 44/58 DIP 5000
Click on the disk tool (or use the File>Save) menu to save the local counter file (*.cpt) which
can be consulted by the File>Open menu on the main screen.
Click on the printer tool (or use the File>Print menu) to print the alarm file.
8.13.9 Reading the alarm snapshots
To read the alarm snapshots select Read > Local> Alarms Snapshots the following
window opens:
NOTE: The alarm snapshot may also be read possible by clicking on the
Alarm entry visible in the bottom bar in case of alarms.
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 49/58
Using the scroll-down menus, select the day month year and time to set.
• <Interface> ( operating mode only) to select the Active Interface (optical or backup°
The HMI does not work like a simulator. In particular, the forcing
transmits real commands output and commands transmission.
Therefore, careless use of these commands may have major
consequences on operation.
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 51/58
8.15.3 Loop
1. Select Loop>Local loop off to unloop
2. Select Loop>Local loop on to loop
3. The type of loopback displayed in the top bar is updated:
DIP5K/EN HI/A22 Human Machine Interface
DIGITAL
Page 52/58 DIP 5000
8.15.4 Forcing
Check the box for the Alarms to be forced, Major, Minor or both.
4. Select the Yes button. The message < Data transmitted> appears.
The DIP 5000 resets.
After reset, check for correct switching by selecting Maintenance> Interface, the active
interface must have switched.
Human Machine Interface DIP5K/EN HI/A22
DIGITAL
DIP 5000 Page 55/58
A warning messages < Are you sure> requests confirmation. Answer Yes.
A message appears to confirm events/alarms deletion.
• Adjust the Time Delay Before Switching to positioning the cursor to 10 ms.
BLANK PAGE
Publication: DIP5K/EN U/A11