COOLING LOAD ESTIMATION SHEET (E-20)

Project Name: EVER GREEN BUILDING @ CARIO Doc No:


Air System Name: Rev: 0
Equipment Type: Date: 6-Sep-13
Space used for: GENERAL MANAGER Sheet No:
Floor: 12TH Reference: Client:
SPACE SIZE CONDITIONS 0
FDB 0
FWB %RH 0
FDP gr / lb
Area
Length (ft) Width (ft) Height (ft) Size (cu.ft) Outside 101 69 19.8 51.5 56.8
(sq.ft)
1 389 389 11.5 4474 Room 76 63.3 50 56 67.2

SOLAR GAIN-GLASS (Q = U x A x ∆T) Difference 25 xxx xxx xxx 10.4


ITEM Area (sq.ft) Temp. Difference Factor BTU / HR VENTILLATION

N Glass 0 5 People 5 CFM/Per 25

NE Glass 0 389 sq.ft 0.06 CFM/ sq.ft 23

E Glass 107.5 164 0.56 9872.8 4474 cu.ft 0.00 0.00

SE Glass 0 * No of Fersh Air Charges per Hour

S Glass 0 CFM VENTILATION: 48


SW Glass 0 INFILTRATION

W Glass 0 Swinging /Revolving Doors People CFM/Per 0

NW Glass 0 Open Door Door CFM/Door 0

Skylight 0 Exhaust Fan 0

SOLAR & TRANS GAIN WALLS & ROOF (Q = U x A x ∆T) Crack 59.05 Feet 0.37 CFM/ft.

ITEM Area (sq.ft) Temp. Difference Factor BTU / HR CFM INFILTRATION: 22

Wall - North 229.5 15 0.45 1549.125 CMF OUTSIDE AIR THROUGH APPARATUS

Wall - West 0 SENSIBLE HEAT FACTOR & APPARATUS DEWPOINT

Wall - East 117 35 0.45 1842.75 Room Sense, Ht 21726.17


0.9442986186 Sens heat factor
Partition 0 Room total heat 23007.74

Roof Sun 0 Indicated ADP 0F 53 Selected ADP 53

Roof Shaded 0 DEHUMIDIFIED AIR RISE (CFM=SH/1.08 X Dehumidified Air Rise temp)

TRANS GAIN - EXCEPT WALLS & ROOF (Q = U x A x ∆T) (1-BF) RM Temp. ADP Dehumidified Air Rise
ITEM Area (sq.ft) Temp. Difference Factor BTU / HR 0.88 76 53 20.24

All Glass 0 21726.17


= 987.55 Dehum air CFM
Partition 0 1.08 20.24

Ceiling 0 TOTAL AIR CFM

Floor 0 987.55 20.24


1110.45
INFILTRATION AND OUTSIDE AIR (Qs = 1.08 x CFM x ∆T) 76 58

ITEM Air flow (CFM) Temp. Difference Factor BTU / HR * 1.08 factor used only for normal air conditioning applied adjust for dehumidified

INFILTRATION 21.8 25 1.08 589.9095


** To be compensated for temperature rise due to fan motor duct heat gain to first outlet.
ITEM Air flow (CFM) Temp. Difference Factor BTU / HR

Outside Air 48 25 0.12 1.08 156.62 NOTES


INTERNAL HEAT
Internal
ITEM No. of Peoples BTU / HR
heat
People 5 245 1225
Internal
ITEM Total hp
heat
HP 0

ITEM Total Power(Watts) Watts/sq ft Factor BTU / HR

Light 428 3.4 1454.86


Internal
ITEM Total BTU / HR
heat
Appliances etc 900 3.4 3060

ROOM SENSIBLE HEAT SUB TOTAL 19751.07

Duct Heat Gain Duct Leak Loss Fan H.P Safety Factor 10% 1975.11

ROOM SENSIBLE HEAT 21726.17


ROOM LATENT HEAT(Qs = 0.68 x CFM x ∆W)
ITEM CFM gr/lb Factor BTU / HR
Infiltration 22 10.4 0.68 154.5

Out Side Air 48 10.4 0.12 0.68 41.02

ITEM lb/hr Factor BTU / HR

Steam 0

Internal
ITEM No. of Peoples BTU / HR
heat

people 5 205 1025


ROOM LATENT HEAT SUB TOTAL 1220.54
Supply Duct Leakage Loss Safety Factor % 5% 61.03
ROOM LATENT HEAT 1281.56
ROOM TOTAL HEAT 23007.74
OUT SIDE AIR HEAT
ITEM CFM F Factor
Sensible 48 25 0.88 1.08 1148.56
ITEM CFM gr/lb Factor
Latent 48 10.4 0.88 0.68 300.84
TONS 2.04 Grand total heat 24457.13
COOLING L

Project Name:
Air System Name:
Equipment Type:
Space used for:
Floor: Reference:
SPACE SIZE
Length (ft) Width (ft) Area (sq.ft) Height (ft) Size (cu.f
0 0
SOLAR GAIN-GLASS (Q = U x A x ∆T)
ITEM Area (sq.ft) Temp. Difference Factor
N Glass

NE Glass

E Glass

SE Glass

S Glass

SW Glass

W Glass

NW Glass

Skylight

SOLAR & TRANS GAIN WALLS & ROOF (Q = U x A x ∆T)


ITEM Area (sq.ft) Temp. Difference Factor
Wall - North

Wall - West

Wall - East
Partition

Roof Sun

Roof Shaded

TRANS GAIN - EXCEPT WALLS & ROOF (Q = U x A x ∆T)


ITEM Area (sq.ft) Temp. Difference Factor
All Glass

Partition

Ceiling

Floor

INFILTRATION AND OUTSIDE AIR (Qs = 1.08 x CFM x ∆T)


ITEM Air flow (CFM) Temp. Difference Factor
INFILTRATION 0 1.08
ITEM Air flow (CFM) Temp. Difference Factor
Outside Air 0 0.12 1.08
INTERNAL HEAT
Internal
ITEM No. of Peoples
heat
People
Internal
ITEM Total hp
heat
HP
Total
ITEM Watts/sq ft Factor
Power(Watts)
Light 0 3.4
Internal
ITEM Total
heat
Appliances etc 3.4
ROOM SENSIBLE HEAT SUB TOTAL
Duct Leak
Duct Heat Gain Fan H.P Safety Factor 10%
Loss
ROOM SENSIBLE HEAT
ROOM LATENT HEAT(Qs = 0.68 x CFM x ∆W)
ITEM CFM gr/lb Factor
Infiltration 0 0.68
Out Side Air 0 0.12 0.68

ITEM lb/hr Factor


Steam
Internal
ITEM No. of Peoples
heat
people
ROOM LATENT HEAT SUB TOTAL
Supply Duct Leakage Loss Safety Factor % 5%
ROOM LATENT HEAT
ROOM TOTAL HEAT
OUT SIDE AIR HEAT
ITEM CFM F Factor

Sensible 0 0 0.88 1.08

ITEM CFM gr/lb Factor

Latent 0 0 0.88 0.68

TONS 0.00 Grand total heat


OLING LOAD ESTIMATION SHEET (E-20)

Doc No:
Rev:
Date:
Sheet No:
Client:
CONDITIONS 0
FDB 0
FWB %RH
Size (cu.ft) Outside
0 Room
Difference 0 xxx xxx
BTU / HR VENTILLATION
0 0 People CFM/Per

0 0 sq.ft 0 CFM/ sq.ft

0 0 cu.ft 0.00

0 * No of Fersh Air Charges per Hour

0 CFM VENTILATION:

0 INFILTRATION

0 Swinging /Revolving Doors People

0 Open Door Door

0 Exhaust Fan

T) Crack Feet 0
BTU / HR CFM INFILTRATION:
0 CMF OUTSIDE AIR THROUGH APPARATUS

0 SENSIBLE HEAT FACTOR & APPARATUS DEWPO

0 Room Sense, Ht 0.00


0 Room total heat 0.00

0 Indicated ADP 0F Selected ADP

0 DEHUMIDIFIED AIR RISE

T) (1-BF) RM Temp. ADP De


BTU / HR 0.88 0
0 0.00
=
0 1.08 0

0 TOTAL AIR CFM

0 0.00 0

T) 0 8
BTU / HR * 1.08 factor used only for normal air conditioning applied adjust for dehumidified
0
** To be compensated for temperature rise due to fan motor duct heat gain to first outl
BTU / HR
0.00 NOTES

BTU / HR
0

0
BTU / HR
0.00
BTU / HR
0
0.00
0.00
0.00

BTU / HR
0
0.00

BTU / HR
0

BTU / HR

0
0.00
0.00
0.00
0.00

0.00

0.00

0.00
0
FDP gr / lb

xxx 0
VENTILLATION
0

0.00

Fersh Air Charges per Hour

INFILTRATION

CFM/Per 0

CFM/Door 0

CFM/ft.
0
DE AIR THROUGH APPARATUS

FACTOR & APPARATUS DEWPOINT

Sens heat factor


Sens heat factor

HUMIDIFIED AIR RISE

Dehumidified Air Rise


0

Dehum air CFM

TOTAL AIR CFM

0.00

ng applied adjust for dehumidified

o fan motor duct heat gain to first outlet.

NOTES