Professional Documents
Culture Documents
Relay Setting Phojal Substation
Relay Setting Phojal Substation
CUSTOMER: HPPTCL
LINE PROTECTION
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 1/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Note: Settings for Power swing blocking, Phase selection, SOTF, Week end infeed, and Fault
locator are added in Distance protection settings.
CT ratio – 600/1A
PT ratio – 220kV/110V
R1 = 0.0667Ÿ/km
X1 = 0.4114Ÿ/km
R0 = 0.2403Ÿ/km
X0 = 1.2279Ÿ/km
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 2/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
The fault resistive reach setting is minimum of below 2 values for zone-1.
= 11.38Ÿ at 80.79°
= 34.16Ÿ at 78.93°
= 73.5Ÿ at 80.79°
= 220.66Ÿ at 78.93°
As per given connectivity diagram, Line-OUT is connected to local end bus where Line-IN is connected.
Hence Line-OUT is considered as Shortest Reverse line for reverse zone settings.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 3/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
= 14.86Ÿ at 80.79°
= 44.61Ÿ at 78.93°
As per TASK FORCE guidelines, Zone-1 is set to 80% of unit line impedance i.e 80% of Protected Line
Impedance. The system particulars like line length, per KM impedance and % reach in each zone are
Above values are high, hence by normal practice RFPP is set to 30Ÿ and RFPE is retained with
40.43Ÿ.
As per TASK FORCE guidelines, Zone-2 is set to 150% of protected line impedance for double
circuited lines. In present case, protected line is considered as double circuited line.
Trip Delay is 350ms. Zone-2 should not enter next voltage level with the consideration of infeed effect.
If it is entering, kindly adjust zone-2 tripping delay with respect to adjacent transformer LV backup
protection.
Zone-3 is set to 120% of (100% of protected line impedance + 100% of longest line impedance at
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 4/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Trip Delay is 1s. Zone-3 should not enter next voltage level with the consideration of infeed effect. If it is
entering, kindly adjust zone-3 tripping delay with respect to adjacent transformer LV backup protection.
Zone-4 reverse setting is 50% of shortest line impedance (reverse line) connected to the local bus.
Trip Delay is 0.35s. Trip Delay should be coordinated with bus bar main protection fault clearance and
SOTF settings:
IBase: Set the Base current for the SOTF function in primary Ampere. This parameter is set to 600A
UBase: Setting of the Base voltage level on which the Dead line voltage is based. This parameter is set
Mode: The operation of ZCVPSOF has three modes for defining the criteria for trip. When Mode is set
to Impedance, the operation criteria is based on the start of overeaching zone from impedance zone
measurement (Normally zone-2). A non-directional output signal should be used from an overreaching
zone. The selection of Impedance mode gives increased security. Impedance mode is selected in
present case.
AutoInit: Automatic activating of the ZCVPSOF function is by default set to Off. If automatic activation
Deadline detection is required, set the parameter Autoinit to On. Otherwise the logic will be activated by
an external BC input. It is set to OFF in present case and the logic has to be activated by an external
BC input.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 5/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
If Autoinit mode=OFF, only Breaker Close (BC) input is used to detect dead line condition.
If Autoinit mode=ON, either UI Level detection of internal function or Breaker Close (BC) input is used
It has been assumed that in the present case CB close command input is available to the relay
tSOTF: Time of SOTF function active status after breaker closed in impedance mode. This is normally
set to 0.2 s. It means, till 0.2s, SOTF function will be active after breaker closed.
IPh<: Setting of under current. This setting is applicable only if mode=UILevel or UILv&Imp and Autoinit
UPh<: Setting of the U< voltage. This setting is applicable only if mode=UILevel or UILv&Imp and
tDuration: Set the required duration of low UI check to achieve operation (to ensure dead line
condition). This setting is applicable only if mode=UILevel or UILv&Imp. In present case, this parameter
is not applicable.
tDLD: Set the required time for all currents and all voltages to be low to Auto Initiate the SOTF function.
This setting is applicable only if Autoinit mode=ON. In present case, this parameter is not applicable.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 6/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Following are the characteristics for Phase selector and load encroachment:
Figure: Relation between distance protection ZMQPDIS and FDPSPDIS for phase-to-earth fault
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 7/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Figure: Relation between distance protection (ZMQPDIS) and FDPSPDIS characteristic for
1-FDPSPDIS (red line), 2-ZMQPDIS, 3-0.5 x RFRvPP PHS, 4- X1PHS/ tan (60°), 5-0.5 x RFFwPPPHS,
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 8/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
With the extended Zone-3 reach settings, that may be required to address the many under reaching
factors already considered, load impedance encroachment is a significant risk to long lines of an
interconnected power system. Not only the minimum load impedance under expected modes of system
operation be considered in risk assessment, but also the minimum impedance that might be sustained
for seconds or minutes during abnormal or emergency system conditions. Failure to do so could
For high resistive earth fault where impedance locus lies in the Blinder zone, fault clearance shall be
INBlockPP: Setting of phase-phase blocking current element for other phases at an earth fault. It is 3I0
INReleasePE: Setting of Neutral release current (shall be set below minimum neutral current expected
at earth faults) here. It is the setting for the minimum residual current needed to enable operation in the
3I0 residual current must fulfill the conditions according to the equations given below
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 9/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
where:
Conditions that have to be fulfilled in order to release the phase-to-phase loop are:
where:
Load encroachment:
The minimum load impedance can be calculated on the basis of maximum permitted power flow of
229MVA over the protected line and minimum permitted system voltage. Minimum permitted system
For setting angle for load blinder, a value of 30° is set which is adequate.
Phase selection:
Reactive reach
The reactive reach in forward direction must as minimum be set to cover the measuring zone used in
where:
X1Zm is the reactive reach for the zone to be covered by FDPSPDIS, and the constant 1.44 is a safety
margin
X0Zm is the zero-sequence reactive reach for the zone to be covered by FDPSPDIS
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 10/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
The reactive reach in reverse direction is automatically set to the same reach as for forward direction.
The resistive reach must cover RFPE for the overreaching zone to be covered, mostly zone 2.
where:
RFPEZm is the setting RFPE for the longest overreaching zone to be covered by FDPSPDIS.
Reactive reach
The reactive reach in reverse direction is the same as for forward so no additional setting is required.
Resistive reach
The resistive reach in reverse direction must be set longer than the longest reverse zones. In blocking
schemes it must be set longer than the overreaching zone at remote end that is used in the
communication scheme.
Reactive reach
Resistive reach
In the same way as for phase-to-earth fault, the reach is automatically calculated based on setting X1.
The fault resistance reaches in forward direction RFFwPP, must cover RFPPZm with at least 25%
margin. RFPPZm is the setting of fault resistance for phase to phase fault for the longest overreaching
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 11/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
where:
RFPPZm is the setting of the longest reach of the overreaching zones that must be covered by
FDPSPDIS .
The proposed margin of 25% will cater for the risk of cut off of the zone measuring characteristic that
might occur at three-phase fault when FDPSPDIS characteristic angle is changed from 60° to 90°.
IMinOpPP: Setting of minimum sensitivity for zone Phase-Phase elements. Measures IL-IL for each
loop. This is the minimum current required in phase to phase fault for zone measurement. To be set to
20% of IBase.
IMinOpPE: Setting of minimum operating current for Phase faults. Measures ILx. This is the minimum
current required in phase to earth fault for zone measurement. To be set to 20% of IBase.
= 171.2Ÿ
RLdFw = 118.61Ÿ
It is important to adjust the setting of load encroachment resistance RLdFw in Phase selection with load
encroachment (FDPSPDIS) to the value equal to or less than the calculated value of RLdInFw in power
swing.
RLdInFw = RLdFw = 0.8 x RLdOutFw = 0.8x 148.26 = 118.61Ÿ need to be set in relay for RLdFw.
It is at the same time necessary to adjust the load angle in FDPSPDIS to follow the condition presented
in equation below
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 12/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
୲ୟ୬(ௗುೄವ)
݀ܮ݃ݎܣுௌ • arc tanቂ ቃ
ௗோி௪
ArgLdPHS = 30°
Hence by using above equation ArgLdPSD = 24.79° need to be set in relay, where kLdRFw is set to 0.8.
Power swing detection function (ZMRPSB) comprises an inner and outer quadrilateral measurement
characteristic as shown in figure below. Its principle is based on the measurement of time it takes for a
power swing transient impedance to pass through the impedance area between the inner and outer
characteristics. Power swings are identified by transition times longer than a transition set time on
corresponding timers. The impedance measuring principle is same as that used for distance protection
zones. The impedance and the characteristics passing times are measured in all three phases
separately.
The various settings for power swing detection are shown in below figure.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 13/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
explained below.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 14/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
RLdInFw = RLdInRv = KL * RLdOutFw where KL is multiplication factor (0.8 for lines <80KM).
RLdOutFw = RLdOutRv = K L * RLMin where RLMin is minimum load resistance at minimum voltage
tH: System studies should determine the settings for the hold timer tH. The purpose of this timer is, to
secure continuous output signal from Power swing detection function (ZMRPSB) during the power
swing, even after the transient impedance leaves ZMRPSB operating characteristic and is expected to
return within a certain time due to continuous swinging. Consider the minimum possible speed of power
tP1 and tP2: The tP1 timer serve as detection of initial power swings, which are usually not as fast as
the later swings are. The tP2 timer become activated for the detection of the consecutive swings, if the
measured impedance exit the operate area and returns within the time delay, set on the tW waiting
timer.
When initial swing comes, its speed should be more than tP1, once it leaves the characteristics timer
tW starts. If swing comes again within tW, its speed shall be more than tP2. Otherwise if it comes again
tR1, tR2 and tEF timers are Inhibit timers. These timers are used to release PSB blocking under certain
conditions.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 15/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
tEF: The setting of the tEF timer must cover, with sufficient margin, the opening time of a circuit breaker
and the dead-time of a single-phase autoreclosing together with the breaker closing time.
tEF is used to release PSB blocking when the circuit breaker closes onto persistent single-phase fault
after single-phase auto reclosing dead time. This parameter is not applicable in present case.
tR1: The tR1 inhibit timer delays the influence of the detected residual current on the inhibit criteria for
ZMRPSB. It prevents operation of the function for short transients in the residual current measured by
the IED.
tR1 is used to release PSB blocking if an earth-fault appears during the power swing (input IOCHECK
is high) and the power swing has been detected before the earth-fault (activation of the signal
I0CHECK). If residual current persist for more than tR1 set delay, PSB allows Distance protection to
trip. Otherwise Directional Earth fault protection has to issue trip under this condition.
Above two timers tR1 and tEF requires a binary start input from a Directional Earth fault function. This
has to be configured during IED engineering. Normally timer tR1 is recommended to be set to 0.3s and
tR2: The tR2 inhibit timer disables the output START signal from ZMRPSB function, if the measured
impedance remains within ZMRPSB operating area for a time longer than the set tR2 value. This time
delay was usually set to approximately two seconds in older power-swing devices.
tR2 is used to release PSB blocking if the power swing has been detected and measured impedance
remains within its PSB operate characteristic for the set time delay tR2.
Setting of the positive sequence reactance for PSB function to operate in Forward direction
X1lnFw = X1lnRv = 1.1 * maximum of all zone’s X1 (In present case, it is zone-3)
Setting of the line resistance for the characteristic angle of the characteristic
R1FlnFw = R1FlnRv = 1.1 * maximum of all zone’s RFPP (In present case, it is zone-3)
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 16/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Setting of the positive sequence reactance for PSB function to operate in reverse direction is same as
Setting of the resistance for PSB function to operate in reverse direction is same as that of forward
direction.
OperationLdCh = On
Setting of the Outer Load resistance in forward direction for the Load enchroachment function, when
utilized
RLdOutFw = KL × RLmin, where RLmin = 148.26Ÿ and K L = 0.8 for the lines less
Since this factor is already consider in arriving at maximum load MVA same is not considered again
RLdOutFw = 148.26Ÿ
Setting of the Outer Load resistance in Reverse direction for the Load enchroachment function, when
utilized
RLdOutRv = 148.26Ÿ
Zero sequence
The fuse failure supervision (SDDRFUF) function can be set in five different modes by setting the
parameter OpMode. The zero sequence function continuously measures the internal currents and
The measured signals are compared with their respective set values 3U0< and 3I0>. The function
enable the internal signal fuseFailDetected if the measured zero sequence voltage is higher than the
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 17/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
set value 3U0>, the measured zero sequence current is below the set value 3I0< and the operation
mode selector (OpMode is set to 2 (zero sequence mode). This will activate the output signal BLKU,
Negative sequence
The negative sequence operates in the same way as the zero sequence, but it calculates the negative
The function enable the internal signal fuseFailDetected if the measured negative sequence voltage is
higher than the set value 3U2>, the measured negative sequence current is below the value 3I2< and
Setting for OpMode: Setting of the operating mode for the Fuse failure supervision. Zero sequence
based fuse fail detection is enabled and settings for the same are given based on below
recommendations.
3U0> and 3I0<: The setting of 3U0> should not be set lower than maximal zero sequence voltage
during normal operation condition. The setting of 3I0< must be higher than maximal zero sequence
current during normal operating condition. In present case, 3U0> is set to 30% of UBase and 3I0< is set
to 10% of IBase.
3U2> and 3I2<: These parameters are not applicable if OpMode is selected to UZsIZs.
DUDI: This is another philosophy for detecting fusefail like Zero sequence based and Negative
sequence based algorithm. If OpMode is set to UZsIZs and OpDUDI is kept ON, fusefail detection will
DU> and DI<: DUDI method will measure the difference in voltage (should be more than set in DU>)
and difference in current (should be less than set in DI<). DU> is recommended to set 60% of UBase
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 18/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
UPh> and IPh>: For DUDI mode, voltage in the corresponding phase shall be more than set value in
UPh> for 1.5cycles before actual fuse fail condition and current should be more than set value in IPh>
before fuse fail. UPh> is recommended to set 70% of UBase and IPh> is recommended to set 10% of
IBase.
A criterion based on delta current and delta voltage measurements can be added to the fuse failure
supervision function in order to detect a three phase fuse failure, which in practice is more associated
with voltage transformer switching during station operations. In present case, this parameter is set ON.
SealIn: Setting of the seal-in function On-Off giving seal-in of alarm until voltages are symmetrical and
high. If sealin is ON and fusefail persists for more than 5s, outputs blockz and blocku will get sealin
(means latched) until any one phase voltage is less than USealIn< setting. It will release when all three
voltages goes above USealIn< setting. In present case, this parameter is made ON and recommended
Dead line detection: If any phase voltage is less than UDLD< set value and corresponding current is
less than IDLD< set value, this will consider as dead line and it will block Z only, it will not block U.
During real fuse fail condition, FF function will block both Z and U. UDLD< is recommended to set to
UBase: Setting of the Base voltage level on which the voltage setting is based. In present case this
IBase: Set the Base current for the function on which the current levels are based. In present case this
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 19/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
EF4PTOC function is used for “IDMT Directional E/F protection-67N”. Protection shall be looking
IBase: Set the Base current for the function on which the current levels are based. This parameter is
UBase: Setting of the Base voltage level on which the directional polarizing voltage is based. This
DirMode1: Setting of the operating direction for the stage or switch it off. This parameter is set to
Characteristic1: Setting of the operating characteristic. This parameter is set to “IEC Norm. Inv.” in
present case.
IN1>: Setting of the operating current level in primary values. This parameter is set to 10% of base
t1: When definite time characteristic has been selected, set the definite time delay. This parameter
k1: Set the back-up trip time delay multiplier for inverse characteristic. Kindly refer below setting
t1Min: Set the Minimum operating time for inverse characteristic. Hence this parameter is set to 0.1s in
present case.
HarmRestrain1: Set the release of Harmonic restraint blocking for the stage. This parameter is kept
polMethod: Set the method of directional polarizing to be used. If it is set as “Voltage”, it will measure
3U0 from 3 phase voltages and -3U0 is reference. If it is set “Current”, it will measure 3I0 from I3PPOL
input and calculate 3U0 using RNPol and XNPol values. If it is set “Dual”, it will consider sum of above
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 20/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
UPolMin: Setting of the minimum neutral point polarizing voltage level for the directional function.
IPolMin, RNPol, XNPol: These parameters are not applicable if polMethod is set to “Voltage”.
AngleRCA: Set the relay characteristic angle, i.e. the angle between the neutral point voltage and
I>Dir: Minimum current required for directionality. This should be lower than pickup of earth fault
protection. This parameter is normally recommended to be set to 10% of the base current.
2ndHarmStab: Setting of the harmonic content in IN current blocking level. This is to block earth fault
protection during inrush conditions. Setting is in percentage of I2/I1. This parameter is normally
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 21/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Setting Calculations:
Maximum local end fault current (3-ph) = 14.109kA (As per given inputs)
220kV Maximum Bus fault current at local end (1-ph) = 14.109kA (Considered same as that of 3-ph)
Operating time at this fault current = 0.6s (Assumed more than zone-2 time delay)
Operating time is assumed, this shall be coordinated with the downstream settings to avoid mal-
operations.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 22/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
The relationship between current and time on the standard curves complies with the standard IEC
IEC normal inverse characteristic is set for 67N (Directional E/F protection). For IEC normal inverse Į =
t = 0.6s
Į = 0.02
ȕ = 0.14
IN1> = 0.1 times the full load current (Assumed 10% of the full load current)
I = 14.109kA
Earth Fault protection (67N) is set to 10% of base current with a TMS of 0.49(IEC Normal inverse);
Note: IEC Normal inverse curve characteristics is set, TMS (k1) should be coordinated with
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 23/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
SchemeType: Scheme type, Mode of Operation. This parameter can be set to Off, Intertrip, Permissive
UR, Permissive OR or Blocking. In present case, this parameter is set to Permissive OR since
tCoord: Received communication signal is combined with the output from an overreaching zone till the
set duration in tCoord. There is less concern about false signal causing an incorrect trip.
tSendMin: To assure a sufficient duration of the received signal (CR) at the remote end, the send
signal (CS) at local end can be prolonged by a tSendMin reset timer. The recommended setting of
UBase: Setting of the Base voltage level on which the voltage settings are based. This parameter is set
U1>: Setting of the U> voltage. This parameter is recommended set 110% of the base voltage in
OpMode1: Setting of the Overvoltage function measuring mode for involved voltages. Normally this
Characterist1: Setting of the characteristic for the time delay, inverse or definite time. Normally this
t1: Setting of the definite time delay, when selected. This parameter is recommended to be set to 5s in
present case.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 24/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
k1: Set the time delay multiplier for inverse characteristic, when selected. This parameter is not
t1Min: Setting of the definite minimum operating time for the inverse characteristic. This parameter is
ResetTypeCrv1: Set the reset time curve for inverse characteristic. This parameter is normally
t1Reset: Setting of the definite time reset time. This parameter is not applicable if ResetTypeCrv1 is set
to Instantaneous.
HystAbsn1: Absolute hysteresis is set in % of UBase. The setting of this parameter is highly
dependent of the application. In OV2PTOV, this can be set as low as 0.5%. Which means drop-off to
U2>: Setting of the U>> voltage. This parameter is recommended to be set to 140% of the base voltage
OpMode2: Setting of the Overvoltage function measuring mode for involved voltages. Normally this
Characterist2: Setting of the characteristic for the time delay, inverse or definite time. Normally this
t2: Setting of the definite time delay, when selected. This parameter is recommended to be set to 0.1s
in present case.
k2: Set the time delay multiplier for inverse characteristic, when selected. This parameter is not
t2Min: Setting of the definite minimum operating time for the inverse characteristic. This parameter is
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 25/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
DPHLPDOC1 function is used for “Directional O/C protection-67-IDMT”. Protection shall be looking
Maximum local end fault current (3-ph) = 14.109kA (As per given inputs)
Operating time at this fault current = 0.6s (Assumed operating time more than zone-2 time delay)
Operating time is assumed, this shall be coordinated with the downstream settings to avoid mal-
operations.
The relationship between current and time on the standard curves complies with the standard IEC
IEC normal inverse is set for 67 (Directional O/C protection). For IEC normal inverse Į = 0.02 and ȕ =
0.14
t = 0.6s (Assumed)
Į = 0.02
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 26/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
ȕ = 0.14
I1> = 1.1 times the rated current (Considered 110% of full load current)
= 1.1 x 600 = 660A, 660/600 = 1.1xIn need to be set in relay, where 600A is CT ratio.
I = 14.109kA
Over current protection (67) is set to 1.1xIn with TMS of 0.27(IEC Normal inverse); TMS has to be
Note: IEC Normal inverse curve characteristics is set, TMS (k1) should be coordinated with
DEFLPDEF1 function is used for “IDMT Directional E/F protection-67N”. Protection shall be looking
Maximum local end fault current (3-ph) = 14.109kA (As per given inputs)
220kV Maximum Bus fault current at local end (1-ph) = 14.109kA (Considered same as that of 3-ph)
Operating time at this fault current = 0.6s (Assumed more than zone-2 time delay)
Operating time is assumed, this shall be coordinated with the downstream settings to avoid mal-
operations.
The relationship between current and time on the standard curves complies with the standard IEC
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 27/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
IEC normal inverse characteristic is set for 67N (Directional E/F protection). For IEC normal inverse Į =
t = 0.6s
Į = 0.02
ȕ = 0.14
IN1> = 0.1 times the full load current (Assumed 10% of the full load current)
= 0.1 x 600 = 60A, 60/600 = 0.1xIn need to be set in relay, where 600A is CT ratio.
I = 14.109kA
Earth Fault protection (67N) is set to 0.1xIn with a TMS of 0.49(IEC Normal inverse); TMS has to be
Note: IEC Normal inverse curve characteristics is set, TMS (k1) should be coordinated with
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 28/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
CT Starpoint (0201): In address 201 CT Starpoint, the polarity of the wye-connected current
transformers is specified (the following figure also goes for only two current transformers). The setting
determines the measuring direction of the device (forward = line direction). A change in this setting also
results in a polarity reversal of the earth current inputs IE or IEE. In present case, this parameter is set
to “towards Line”.
Unom PRIMARY (0203) and Unom SECONDARY (0204): In addresses 203 Unom PRIMARY and 204
Unom SECONDARY the device obtains information on the primary and secondary rated voltage
(phase-to-phase voltage) of the voltage transformers. In present case, Unom PRIMARY is set to 220kV
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 29/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
CT PRIMARY (0205) and CT SECONDARY (0206): In address 205 CT PRIMARY and 206 CT
SECONDARY the primary and secondary rated current transformers need to be set. In present case,
U4 transformer (0210): The device features four voltage measuring inputs, three of which are
connected to the set of voltage transformers, Address 2010 is to indicate fourth input. If the input U4 is
not required, set: Address 210 U4 transformer = Not connected. In present case, this parameter is set
to Not connected.
Uph / Udelta (0211): Matching ratio Phase-VT to Open-Delta-VT. Since U4 input is not used and set to
Usy1/Usy2 ratio (0215): Matching ratio Usy1 / Usy2. Since U4 input is not used and set to Not
I4 transformer (0220): If the input I4 is not required, set: Address 220 I4 transformer = Not connected.
As per available scheme, Neutral Current of the parallel line is not connected to I4 in present case.
Hence I4 transformer is set to Not connected. Kindly change this setting if Neutral Current of the
I4/Iph CT (0221): Matching ratio I4/Iph for CT's. Since I4 input is not used and set to Not connected,
SystemStarpoint (0207): The manner in which the system starpoint is earthed must be considered for
the correct processing of earth faults and double earth faults. Accordingly, set for address 207
SystemStarpoint = Solid Earthed, Peterson-Coil or Isolated. For low-resistant earthed systems set Solid
Rated Frequency (0230): The rated frequency of the power system is set under address 230 Rated
Frequency. The factory presetting according to the ordering code (MLFB) only needs to be changed if
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 30/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
the device is applied in a region different from the one indicated when ordering. In present case, this
PHASE SEQ. (0235): Use address 235 PHASE SEQ. to change the default setting (L1 L2 L3 for
clockwise rotation) if your power system has a permanent anti-clockwise phase sequence (L1 L3 L2). In
Distance Unit (0236): Address 236 Distance Unit determines the distance unit (km or Miles) for the
fault location indications. If the compounding function of the voltage protection is used, the overall line
capacitance is calculated from the line length and the capacitance per unit length. In present case, this
Format Z0/Z1 (0237): Matching of the earth to line impedance is an essential prerequisite for the
accurate measurement of the fault distance (distance protection, fault locator) during earth faults. In
address 237 Format Z0/Z1 the format for entering the residual compensation is determined. It is
possible to use either the ratio RE/RL, XE/XL or to enter the complex earth (residual) impedance factor
K0. In present case, this parameter is set to Zero seq. comp. factor K0 and angle(K0).
EarthFltO/C 1p (0238A): Earth Fault O/C: setting for 1pole AR. Address 238EarthFltO/C 1p specifies
whether the earth-fault settings for single-pole tripping and blocking in the single-pole dead time are
accomplished together for all stages (setting stages together) or separately (setting stages separate.).
TMin TRIP CMD (0240A): Minimum TRIP Command Duration. In address 240 the minimum trip
command duration TMin TRIP CMD is set. It applies to all protection and control functions which may
issue a trip command. It also determines the duration of the trip pulse when a circuit breaker test is
initiated via the device. In present case, this parameter is set to 0.2s.
TMax CLOSE CMD (0241A): Maximum Close Command Duration. In address 241 the maximum close
command duration TMax CLOSE CMD is set. It applies to all close commands issued by the device. It
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 31/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
also determines the length of the close command pulse when a circuit breaker test cycle is issued via
the device. It must be long enough to ensure that the circuit breaker has securely closed. In present
T-CBtest-dead (0242): Dead Time for CB test-autoreclosure. The 7SA522 allows a circuit breaker test
during operation by means of a tripping and a closing command entered on the front panel or using
DIGSI. The duration of the trip command is set as explained above. Address 242 T-CBtest-dead
determines the duration from the end of the trip command until the start of the close command for this
test. It should not be less than 0.1s. In present case, this parameter is set to 1s.
FullScaleVolt. (1103) and FullScaleCurr. (1104): Measurement Full Scale Voltage (100%) and
Measurement Full Scale Current (100%). The rated primary voltage (phase-to-phase) and rated primary
current (phases) of the protected equipment are entered in the address 1103 FullScaleVolt. and 1104
FullScaleCurr. These settings are required for indication of operationalmeasured values in percent. In
Line Angle (1105): The line angle (address 1105 Line Angle) may be derived from the line parameters.
Distance Angle (1211): Angle of inclination, distance charact. Address 1211 Distance Angle specifies
the angle of inclination of the R sections of the distance protection polygons. The shape of the tripping
characteristic is among other factors influenced by the inclination angle Distance Angle (address 1211).
Usually, the line angle is set here, i.e. the same value as in address 1105 Line Angle. Hence this
Below figure shows the Polygonal characteristic (setting values are marked by dots).
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 32/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
P,Q sign (1107): P,Q operational measured values sign. It is occasionally desired to define the power
drawn from the line (e.g. as seen from the consumer) positively. Using parameter 1107 P,Q sign the
signs for these components can be inverted. If the setting is not reversed (default), the positive direction
for the power etc. corresponds to the “forward” direction for the protection functions. In present case,
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 33/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
x' (1110): x' - Line Reactance per length unit. The reactance value X' of the protected line is entered as
reference value x' at address 1110 in Ÿ/km if the distance unit was set as kilometers. Kindly refer
Line Length (1111): Line length in km shall be set here. Hence in present case, this parameter is set to
20.35km.
K0 (Z1) (1120) and Angle K0(Z1) (1121): Zero seq. comp. factor K0 for zone Z1. and Zero seq. comp.
angle for zone Z1. Kindly refer setting calculations for this parameter.
K0 (> Z1) (1122) and Angle K0(> Z1) (1123): Zero seq.comp.factor K0,higher zones >Z1 and Zero
seq. comp. angle, higher zones >Z1. Kindly refer setting calculations for this parameter.
RM/RL ParalLine (1126) and XM/XL ParalLine (1127): Mutual Parallel Line comp. ratio RM/RL. and
Mutual Parallel Line comp. ratio XM/XL. If the device is applied to a double circuit line (parallel lines)
and parallel line compensation for the distance and/or fault location function is used, the mutual
coupling of the two lines must be considered. A prerequisite for this is that the earth (residual) current of
the parallel line has been connected to the measuring input I4 of the device and that this was
configured with the power system data by setting the appropriate parameters. Kindly refer setting
RATIO Par. Comp (1128): Neutral current RATIO Parallel Line Comp. For earth faults on the protected
feeder there is in theory no additional distance protection or fault locator measuring error when the
parallel line compensation is used. The setting in address 1128 RATIO Par. Comp is therefore only
relevant for earth faults outside the protected feeder. It provides the current ratio IE/IEP for the earth
current balance of the distance protection, above which compensation should take place. In general, a
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 34/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
PoleOpenCurrent (1130A): Pole Open Current Threshold. In address 1130A the residual current
PoleOpenCurrent is set, which will definitely not be exceeded when the circuit breaker pole is open. If
parasitic currents (e.g. through induction) can be excluded when the circuit breaker is open, this setting
may be very sensitive. Otherwise this setting must be increased. Usually the presetting is sufficient.
Hence in present case, this parameter is left with the default value of 0.1A.
PoleOpenVoltage (1131A): Pole Open Voltage Threshold. The residual voltage PoleOpenVoltage,
which will definitely not be exceeded when the circuit breaker pole is open, is set in address 1131.
Voltage transformers must be on the line side. The setting should not be too sensitive because of
possible parasitic voltages (e.g. due to capacitive coupling). It must in any event be set below the
smallest phase-earth voltage which may be expected during normal operation. In present case, this
SI Time all Cl. (1132A): Seal-in Time after ALL closures. The switch-on-to-fault activation (seal-in) time
SI Time all Cl. (address 1132) determines the activation period of the protection functions enabled
during each energization of the line (e.g. fast tripping high-current stage). This time is started by the
internal circuit breaker switching detection when it recognizes energization of the line or by the circuit
breaker auxiliary contacts, if these are connected to the device via binary input to provide information
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 35/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
that the circuit breaker has closed. The time should therefore be set longer than the circuit breaker
operating time during closing plus the operating time of this protection function plus the circuit breaker
operating time during opening. In present case, this parameter is set to 0.5s.
T DELAY SOTF (1133A): minimal time for line open before SOTF. Before each line energization
detection, the breaker must be recognized as open for the settable time1133 T DELAY SOTF. In
Line Closure (1134): Recognition of Line Closures with. In address 1134 Line Closure the criteria for
the internal recognition of line energization are determined. Only with ManCl means that only the
manual close signal via binary input or the integrated control is evaluated as closure. I OR U or ManCl
means that additionally the measured currents or voltages are used to determine closure of the circuit
breaker, whereas CB OR I or M/C implies that either the currents or the states of the circuit breaker
auxiliary contacts are used to determine closure of the circuit breaker. If the voltage transformers are
not situated on the line side, the setting CB OR I or M/C must be used. In the case of I or Man.Close
only the currents or the manual close signal are used to recognize closing of the circuit breaker. In
present case, this parameter is set to Current flow or Manual close BI.
Reset Trip CMD (1135): RESET of Trip Command. Address 1135 Reset Trip CMD determines under
which conditions a trip command is reset. If CurrentOpenPole is set, the trip command is reset as soon
as the current disappears. In present case, this parameter is set to with Pole Open Current Threshold
only.
OpenPoleDetect. (1136): open pole detector. Address 1136 OpenPoleDetect. defines the criteria for
operating the internal open-pole detector. When using the default setting w/ measurement, all available
data are evaluated that indicate single-pole dead time. The internal trip command and pickup
indications, the current and voltage measured values and the CB auxiliary contacts are used. In present
I-CTsat. Thres. (1140A): CT Saturation Threshold. 7SA522 contains a saturation detector which
largely detects the measuring errors resulting from the saturation of the current transformers and
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 36/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
initiates a change of the measurement method of the distance protection. The threshold above which
the saturation detector picks up can be set in address 1140 I-CTsat. Thres.. This is the current level
above which saturation may be present. The setting ’ disables the saturation detector. In present case,
SI Time Man.Cl (1150A): Seal-in Time after MANUAL closures. SI Time Man.Cl (address 1150) is the
time following manual closure during which special influence of the protection functions is activated
(e.g. increased reach of the distance protection). In present case, this parameter is left with the default
value of 0.3s.
MAN. CLOSE (1151): Manual CLOSE COMMAND generation. For manual closure of the circuit
breaker via binary inputs, it can be specified in address 1151 MAN. CLOSE whether the integrated
manual CLOSE detection checks the synchronism between the busbar voltage and the voltage of the
switched feeder. This setting does not apply for a close command via the integrated control functions.
If the synchronism check is desired, the device must either feature the integrated synchronism check
function or an external device for synchronism check must be connected. In present case, this
Man.Clos. Imp. (1152): MANUAL Closure Impulse after CONTROL. For commands via the integrated
control (on site, DIGSI, serial interface) address 1152 Man.Clos. Imp. determines whether a close
command via the integrated control regarding the MANUAL CLOSE handling for the protection
functions (like instantaneous re-opening when switching onto a fault) is to act like a MANUAL CLOSE
command via binary input. If none is set here, a CLOSE command via the control will not generate a
MANUAL CLOSE impulse for the protection function. In present case, this parameter is left with the
3pole coupling (1155): 3 pole coupling. Address 1155 3pole coupling determines whether any multi-
phase pickup leads to a three-pole tripping command, or whether only multi-pole tripping decisions
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 37/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
result in a three-pole tripping command. This setting is only relevant for versions with single-pole and
three-pole tripping and is only available there. This is possible with setting 1155 3pole coupling = with
TRIP. Each of the four devices detects a single-pole internal fault and can thus trip single-pole.
With the setting 1155 3pole coupling = with PICKUP, the two lines are switched off three-pole, since
each device picks up as with L1-L2-E, i.e. as with a multi-phase fault. In present case, this parameter is
Trip2phFlt (1156A): Trip type with 2phase faults. Address 1156 Trip2phFlt determines that the short-
circuit protection functions perform only a single-pole trip in case of isolated two-phase faults (clear of
This allows a single-pole reclose cycle for this kind of fault. You can specify whether the leading phase
(1pole leading Ø), or the lagging phase (1pole lagging Ø) is tripped. The presetting 3pole is usually
used.
FCT Distance (1201): Distance protection. At address 1201 FCT Distance the distance protection
function can be switched ON or OFF. In present case, this parameter is set to ON.
Minimum Iph> (1202): Phase Current threshold for dist. meas. The minimum current for fault detection
Minimum Iph> (address 1202) is set somewhat (approx. 10 %) below the minimum short-circuit current
that may occur. In present case, this parameter is set to 0.1A (Default value).
Distance Angle (1211): Angle of inclination, distance charact. The shape of the tripping characteristic
is among other factors influenced by the inclination angle Distance Angle (address 1211). Usually, the
line angle is set here, i.e. the same value as in address 1105 Line Angle. Hence this parameter is also
SER-COMP. (1208): Series compensated line. In applications for, or in the proximity of, series-
compensated lines (lines with series capacitors) address 1208 SER-COMP. is set to YES, to ensure
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 38/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
that the direction determination operates correctly in all cases. In present case, this parameter is set to
NO.
Paral.Line Comp (1215): Mutual coupling parall.line compensation. The mutual coupling between the
two lines of a double-circuit configuration is only relevant to the 7SA522 when it is applied on a double-
circuit line and when it is intended to implement parallel line compensation. A prerequisite is that the
earth current of the parallel line is connected to the I4 measuring input of the device and this is entered
in the configuration settings. In this case, address 1215 Paral.Line Comp has to be set to YES (default
setting).
SOTF zone (1232): Instantaneous trip after SwitchOnToFault. To determine the reaction of the
distance protection during closure of the circuit breaker onto a fault, the parameter in address 1232
SOTF zone is used. When setting to Inactive there is no special reaction, i.e. all distance stages
operate according to their preset zone parameters. In present case, this parameter is set to Inactive.
R load (Ø-E) (1241) and R load (Ø-Ø) (1243): R load, minimum Load Impedance (ph-e) and R load,
minimum Load Impedance (ph-ph). The R value R load (Ø-E) (address 1241) refers to the phase-to-
earth loops, R load (Ø-Ø) (address 1243) to the phase-to-phase loops. The values are set somewhat
(approx. 10 %) below the minimum expected load impedance. The minimum load impedance appears
when the maximum load current and minimum operating voltage exist. Kindly refer setting calculations
ĭ load (Ø-E) (1242) and ࢥ load (Ø-Ø) (1244): PHI load, maximum Load Angle (ph-e) and PHI load,
maximum Load Angle (ph-ph). The spread angle of the load trapezoid characteristic ࢥ load (Ø-E)
(address 1242) and ࢥ load (Ø-Ø) (address 1244) must be greater (approx. 5°) than the maximum
arising load angle (corresponding to the minimum power factor cosࢥ). In present case, these
Trip 1pole Z2 (1317A): Single pole trip for faults in Z2. This may also be selected for the second zone
with address 1317 Trip 1pole Z2. Single pole tripping in zone 2 is only possible if this address is set to
YES. The default setting is NO. In present case, this parameter is set to NO.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 39/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
1st AR -> Z1B (1357): Z1B enabled before 1st AR (int. or ext.). If the distance protection is used in
conjunction with an external automatic recloser, it can be determined in address 1357 1st AR -> Z1B
which distance zone is released prior to starting the AR. Usually, the overreaching zone Z1B is used for
the first cycle (1st AR -> Z1B = YES). This may be suppressed by changing the setting of 1st AR ->
3I0> Threshold (1203): 3I0 threshold for neutral current pickup. In systems with earthed starpoint, the
setting 3I0> Threshold (address 1203) is set somewhat below the minimum expected earth fault
3U0> Threshold (1204): 3U0 threshold zero seq. voltage pickup. When setting 3U0> Threshold
(address 1204), care must be taken that operational asymmetries do not cause a pickup. If the U0
criterion is not required, the address 1204 is set to ’. In present case, this parameter is set to 15V.
3I0>/ Iphmax (1207A): 3I0>-pickup-stabilisation (3I0> /Iphmax). The preset value 3I0>/ Iphmax = 0.10
(address 1207) is usually recommended for the slope of the 3I0 characteristic.
E/F recognition (1209A): criterion of earth fault recognition. In earthed power systems the earth fault
detection can be complemented by a zero sequence voltage detection function. You can determine
whether an earth fault is detected when a zero sequence current or a zero sequence voltage threshold
is exceeded or when both criteria are met. 3I0> OR 3U0> (default setting) applies at address 1209 E/F
recognition if only one of the two criteria is valid. In present case, this parameter is set to 3I0> OR
3U0>.
2Ph-E faults (1221A): Loop selection with 2Ph-E faults. The loop selection for double earth faults is set
at address 1221 2Ph-E faults (Phase-to-Phase Earth fault detection). In most cases, Block leading Ø
(blocking of the leading phase, default setting) is favorable because the leading phase-to-earth loop
tends to overreach, especially in conjunction with large earth fault resistance. Hence in present case
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 40/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Start Timers (1210): The delay times for the distance zones can be started either all together on
general fault detection by the distance protection function, or individually at the moment the fault enters
the respective distance zone. Parameter Start Timers (address 1210) is set by default to on Dis.
Pickup. This setting ensures that all delay times continue to run together even if the type of fault or the
selected measuring loop changes, e.g. because an intermediate infeed is switched off. Hence in
T1-1phase (1305): T1-1phase, delay for single phase faults. The first zone is normally set to operate
T1-multi-phase (1306): T1multi-ph, delay for multi-phase faults. Different delay times can be set for
single- and multiple-phase faults in the first zone. But in present case, this parameter is also set to 0s.
T2-1phase (1315): T2-1phase, delay for single phase faults. For the second zone, it is also possible to
set separate delay times for single-phase and multi-phase faults. In general, the delay times are set the
same. If stability problems are expected during multi-phase faults, a shorter delay time could be
considered for T2-multi-phase (address 1316) while tolerating a longer delay time for single-phase
faults with T2-1phase (address 1315). This parameter is set to 0.35s in present case to match this
T2-multi-phase (1316): T2multi-ph, delay for multi-phase faults. This parameter is also set to 0.35s in
T3 DELAY (1325): The zone timers for zone-3 are set with the parameter T3 DELAY (address 1325).
This parameter is set to 1s in present case to match this setting with Main-I relay setting.
T4 DELAY (1335): The zone timers for zone-4 are set with the parameter T4 DELAY (address 1335).
This parameter is set to 0.35s in present case to match this setting with Main-I relay setting.
T5 DELAY (1345): The zone timers for zone-5 are set with the parameter T5 DELAY (address 1345).
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 41/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
T1B-1phase (1355): T1B-1phase, delay for single ph. Faults. This parameter is set to oo(infinite) in
T1B-multi-phase (1356): T1B-multi-ph, delay for multi ph. Faults. This parameter is set to oo(infinite) in
Op. mode Z1 (1301): Operating mode Z1. By means of the parameter MODE = Forward or Reverse or
Non-Directional can be set for zone-1. This parameter is set to Forward in present case.
R(Z1) Ø-Ø (1302): R(Z1), Resistance for ph-ph-faults. For the first zone these are the parameters
R(Z1) Ø-Ø (address 1302) for the R intersection of the polygon applicable to phase-to-phase faults.
X(Z1) (1303): X(Z1), Reactance. Kindly refer setting calculations for this parameter.
RE(Z1) Ø-E (1304): RE(Z1), Resistance for ph-e faults. Kindly refer setting calculations for this
parameter. For the first zone these are the parameters R(Z1) Ø-Ø (address 1302) for the R intersection
of the polygon applicable to phase-to-phase faults, X(Z1) (address 1303) for the X intersection (reach),
RE(Z1) Ø-E (address 1304) for the R intersection applicable to phase-to-earth faults and delay time
settings.
T1-1phase (1305): T1-1phase, delay for single phase faults. The first zone is normally set to operate
T1-multi-phase (1306): T1multi-ph, delay for multi-phase faults. Different delay times can be set for
single- and multiple-phase faults in the first zone. But in present case, this parameter is also set to 0s.
Zone Reduction (1307): Zone Reduction Angle (load compensation). If a fault resistance at the fault
location (arc, tower footing etc.) causes a voltage drop in the measured impedance loop, the phase
angle difference between this voltage and the measured loop current may shift the determined fault
location in X direction. Parameter 1307 Zone Reduction allows an inclination of the upper limit of zone
Z1 in the 1st quadrant. This prevents spurious pickup of zone Z1 in the presence of faults outside the
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 42/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
protected area. To disable this feature, this parameter shall be set to 0°. In present case, this parameter
is set to 0°.
Op. mode Z1B (1351): Operating mode Z1B (overrreach zone). Since this zone is not used, this
parameter is set to Inactive. Since Inactive is set at address 1351, settings parameters from 1352 to
Op. mode Z2 (1311): Operating mode Z2. By means of the parameter MODE = Forward or Reverse or
Non-Directional can be set for zone-2. This parameter is set to Forward in present case. By means of
the parameter MODE = Forward or Reverse or Non-Directional, each zone can be set (address 1301
Op. mode Z1, 1311 Op. mode Z2, 1321 Op. mode Z3, 1331 Op. mode Z4, 1341 Op. mode Z5 and 1361
R(Z2) Ø-Ø (1312): R(Z2), Resistance for ph-ph-faults. For the second zone these are the parameters
R(Z2) Ø-Ø (address 1312) for the R intersection of the polygon applicable to phase-to-phase faults.
X(Z2) (1313): X(Z2), Reactance. Kindly refer setting calculations for this parameter.
RE(Z2) Ø-E (1314): RE(Z2), Resistance for ph-e faults. Kindly refer setting calculations for this
parameter.
T2-1phase (1315): T2-1phase, delay for single phase faults. For the second zone, it is also possible to
set separate delay times for single-phase and multi-phase faults. In general, the delay times are set the
same. If stability problems are expected during multi-phase faults, a shorter delay time could be
considered for T2-multi-phase (address 1316) while tolerating a longer delay time for single-phase
faults with T2-1phase (address 1315). This parameter is set to 0.35s in present case to match this
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 43/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
T2-multi-phase (1316): T2multi-ph, delay for multi-phase faults. This parameter is also set to 0.35s in
Trip 1pole Z2 (1317A): Single pole trip for faults in Z2. single-pole tripping usually applies to single-
phase faults in Z1 (if the remaining conditions for single-pole tripping are satisfied), this may also be
selected for the second zone with address 1317 Trip 1pole Z2. Single pole tripping in zone 2 is only
possible if this address is set to YES. The default setting is NO. In present case also, this parameter is
set to NO.
Op. mode Z3 (1321): Operating mode Z3. By means of the parameter MODE = Forward or Reverse or
Non-Directional can be set for zone-3. This parameter is set to Forward in present case.
R(Z3) Ø-Ø (1322): R(Z3), Resistance for ph-ph-faults. For the third zone these are the parameters
R(Z3) Ø-Ø (address 1322) for the R intersection of the polygon applicable to phase-to-phase faults.
X(Z3) (1323): X(Z3), Reactance. Kindly refer setting calculations for this parameter.
RE(Z3) Ø-E (1324): RE(Z3), Resistance for ph-e faults. Kindly refer setting calculations for this
parameter.
T3 DELAY (1325): The zone timers for zone-3 are set with the parameter T3 DELAY (address 1325).
This parameter is set to 1s in present case to match this setting with Main-I relay setting.
Op. mode Z4 (1331): Operating mode Z4. By means of the parameter MODE = Forward or Reverse or
Non-Directional can be set for zone-4. This parameter is set to Reverse in present case.
R(Z4) Ø-Ø (1332): R(Z4), Resistance for ph-ph-faults. For the fourth zone these are the parameters
R(Z4) Ø-Ø (address 1332) for the R intersection of the polygon applicable to phase-to-phase faults.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 44/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
X(Z4) (1333): X(Z4), Reactance. Kindly refer setting calculations for this parameter.
RE(Z4) Ø-E (1334): RE(Z4), Resistance for ph-e faults. Kindly refer setting calculations for this
parameter.
T4 DELAY (1335): The zone timers for zone-4 are set with the parameter T4 DELAY (address 1335).
This parameter is set to 0.35s in present case to match this setting with Main-I relay setting.
Op. mode Z5 (1341): Operating mode Z5. By means of the parameter MODE = Forward or Reverse or
Non-Directional can be set for zone-5. This parameter is set to Inactive in present case. Since Inactive
is set at address 1341, settings parameters from 1342 to 1346 are not applicable in present case.
P/S Op. mode (2002): Power Swing Operating mode. The power swing blocking function blocks the
tripping of the distance protection for specific zones (which are set under address 2002 P/S Op. mode)
phase-selectively:
• Blocking of the trip command for all zones (All zones block): The trip command of the distance
• Blocking of the trip command for the first zone only (Z1/Z1B block): Only the trip command of the
first zone and of the overreaching zone (Z1 and Z1B) are blocked during a power swing. A pickup in
a different zone (Z2 and higher) can lead to a trip command in the case of a power swing after the
• Blocking of the trip command for the higher zones only (>= Z2 block): Z2 and the higher zones are
blocked for the tripping during a power swing. Only a pickup in the first zone or the overreach zone
• Blocking of the first two zones (Z1, Z1B, Z2 block): The trip commands of the first and second zone
(Z1 and Z2) and the overreaching zone (Z1B) are blocked during a power swing. A pickup in a
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 45/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
different zone (Z3 and higher) can lead to a trip command in the case of a power swing after the
PowerSwing trip (2006): Additionally the tripping function for unstable power swings (asynchronism)
can be set with parameter PowerSwing trip (address 2006), which should be set to YES if required
(presetting is NO). In the event of power swing tripping it is sensible to set P/S Op. mode = All zones
block for the power swing blocking to avoid premature tripping by the distance protection.
In present case, this parameter is left with the default setting of NO.
FCT SOTF-O/C (2401): Inst. High Speed SOTF-O/C is ON/OFF. A prerequisite for the operation of the
switch-onto-fault protection is that in address 124 SOTF Overcurr. = Enabled was set during the
configuration of the device scope of functions. At address 2401 FCT SOTF-O/C it can also be switched
I>>> (2404): I>>> Pickup. The magnitude of the current which causes pick-up of the switch-onto-fault
function is set as I>>> in address 2404. The setting value should be selected large enough to ensure
that the protection does not under any circumstances pick up due to a line overload or due to a current
increase e.g. resulting from an automatic reclosure dead time on a parallel feeder. It is recommended to
set at least 2.5 times the rated current of the feeder. In present case, this parameter is set to 3A.
START (3802): Start fault locator with. If the fault location calculation is to be started by the trip
command of the protection, set address 3802 START = TRIP. In this case a fault location is only output
if the device has also issued a trip. The fault location calculation can however also be started with each
fault detection of the device (address 3802 START = Pickup). In this case the fault location is also
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 46/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Paral.Line Comp (3805): Mutual coupling parall.line compensation. If the parallel line compensation is
used, set address 3805 Paral.Line Comp to YES (presetting for devices with parallel line
compensation). Kindly check this at site whether parallel line neutral current is connected to this relay
Load Compensat. (3806): Load Compensation. If load compensation is applied to single-phase faults
in double-fed lines of an earthed system, set YES in address 3806 Load Compensat.. If high fault
resistances are expected for single-phase faults, e.g. at overhead lines without overhead earth wire or
unfavourable earthing conditions of the towers, this will improve the accuracy of the distance
Setting Calculations:
CT ratio – 600/1A
PT ratio – 220kV/110V
R1 = 0.0667 Ÿ/km
X1 = 0.4114 Ÿ/km
R0 = 0.2403 Ÿ/km
X0 = 1.2279 Ÿ/km
ଡ଼ై
Line angle ĭ = arctanቀ ቁ.
ୖై
By using above formula, ĭ=80.79° need to be set in address 1105 and 1211.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 47/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
ి
X’sec = x X’prim = 0.3 x 0.4114 = 0.1234Ÿ/km, need to be set in address 1110.
K0 (Z1) (1120) and Angle K0(Z1) (1121): earth impedance compensation factors are defined with their
magnitude and angle which may be calculated with the line data using the following equation:
ు ଵ
K0 =
ై
=
ଷ
x ቀబ െ 1ቁ
భ
Where
By using above equation and line impedance parameters, K0 (Z1) and Angle K0(Z1) are calculated.
Since impedance values/km are same for all zones, K0 and Angle K0 are same for all the zones. Hence
K0 (> Z1) and Angle K0(> Z1) are set to 0.67 and -2.79 respectively at addresses 1120 and 1121.
RM/RL ParalLine (1126) and XM/XL ParalLine (1127): The coupling factors may be determined using
ୖ ଵ ୖబ
ୖై
=ଷx ୖభ
Where
R0M = Mutual zero sequence resistance (coupling resistance) of the line = 0.049Ÿ
ୖ
By using above formula = 0.793.
ୖై
ଡ଼ ଵ ଡ଼బ
= x
ଡ଼ై ଷ ଡ଼భ
Where
X0M = Mutual zero sequence reactance (coupling reactance) of the line= 0.30Ÿ
ଡ଼
By using above formula = 0.727.
ଡ଼ై
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 48/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
= 171.2Ÿ
RLoad prim = 118.61Ÿ (considered 0.8 factor, which is already considered in REL670 setting calculations)
ి
RLoad sec = x RLoad prim
ి
Where = 0.3
Hence RLoad sec = 118.61 x 0.3 = 35.58Ÿ needs to be set in the address of 1241 and 1243.
R(Z1) Ø-Ø (1302): This parameter is set to 30Ÿ (primary value) to match with the Main-I relay settings.
ి
R(Z1) Ø-Ø (secondary) = R(Z1) Ø-Ø (primary) x = 30 x 0.3/2 = 4.5Ÿ needs to be set in the address
X(Z1) (1303): This parameter is set to 8.98Ÿ (primary value) to match with the Main-I relay settings.
ి
X(Z1) Ø-Ø (secondary) = X(Z1) Ø-Ø (primary) x = 8.98 x 0.3 = 2.695Ÿ needs to be set in the
address of 1303.
RE(Z1) Ø-E (1304): This parameter is set to 40.43Ÿ (primary value) to match with the Main-I relay
settings.
ి
R(Z1) Ø-E (secondary) = R(Z1) Ø-E (primary) x = 40.43 x 0.3 = 12.13Ÿ needs to be set in the
address of 1304.
R(Z2) Ø-Ø (1312): This parameter is set to 60Ÿ (primary value) to match with the Main-I relay settings.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 49/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
ి
R(Z2) Ø-Ø (secondary) = R(Z2) Ø-Ø (primary) x = 60 x 0.3/2 = 9Ÿ needs to be set in the address
X(Z2) (1313): This parameter is set to 16.85Ÿ (primary value) to match with the Main-I relay settings.
ి
X(Z2) Ø-Ø (secondary) = X(Z2) Ø-Ø (primary) x = 16.85 x 0.3 = 5.054Ÿ needs to be set in the
address of 1313.
RE(Z2) Ø-E (1314): This parameter is set to 75Ÿ (primary value) to match with the Main-I relay
settings.
ి
R(Z2) Ø-E (secondary) = R(Z2) Ø-E (primary) x = 75 x 0.3 = 22.5Ÿ needs to be set in the address
of 1314.
R(Z3) Ø-Ø (1322): This parameter is set to 75Ÿ (primary value) to match with the Main-I relay settings.
ి
R(Z3) Ø-Ø (secondary) = R(Z3) Ø-Ø (primary) x = 75 x 0.3/2 = 11.25Ÿ needs to be set in the
X(Z3) (1323): This parameter is set to 100.54Ÿ (primary value) to match with the Main-I relay settings.
ి
X(Z3) Ø-Ø (secondary) = X(Z3) Ø-Ø (primary) x = 100.54 x 0.3 = 30.162Ÿ needs to be set in the
address of 1323.
RE(Z3) Ø-E (1324): This parameter is set to 125Ÿ (primary value) to match with the Main-I relay
settings.
ి
R(Z3) Ø-E (secondary) = R(Z3) Ø-E (primary) x = 125 x 0.3 = 37.5Ÿ needs to be set in the address
of 1324.
R(Z4) Ø-Ø (1332): This parameter is set to 75Ÿ (primary value) to match with the Main-I relay settings.
ి
R(Z4) Ø-Ø (secondary) = R(Z4) Ø-Ø (primary) x = 75 x 0.3/2 = 11.25Ÿ needs to be set in the
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 50/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
X(Z4) (1333): This parameter is set to 7.33Ÿ (primary value) to match with the Main-I relay settings.
ి
X(Z4) Ø-Ø (secondary) = X(Z4) Ø-Ø (primary) x = 7.33 x 0.3 = 2.2Ÿ needs to be set in the address
of 1333.
RE(Z4) Ø-E (1334): This parameter is set to 125Ÿ (primary value) to match with the Main-I relay
settings.
ి
R(Z4) Ø-E (secondary) = R(Z4) Ø-E (primary) x = 125 x 0.3 = 37.5Ÿ needs to be set in the address
of 1334.
FUSE FAIL MON. (2910): Fuse Failure Monitor. In present case, this parameter is set ON. In address
2910 FUSE FAIL MON., the “Fuse Failure Monitor”, e.g. during asymmetrical testing, can be switched
OFF.
FFM U>(min) (2911A): Minimum Voltage Threshold U>. The asymmetry of the voltage is detected by
the fact that either the zero sequence voltage or the negative sequence voltage exceed a settable value
FFM U>(min) (address 2911). If the zero-sequence voltage or the negative-sequence voltage exceed
the presettable value FFM U>(min) (address 2911) for more than 10s, the signal “VT FuseFail>10s”
The settings for the “fuse failure monitor” for non-symmetrical measuring voltage failure must be
selected such that on the one hand it is reliably activated if a phase voltage fails (address 2911 FFM
U>(min)), but does not pick up on earth faults in an earthed network on the other hand.
FFM I< (max) (2912A): Maximum Current Threshold I<. Address 2912 FFM I< (max) must be set
sufficiently sensitive (below the smallest fault current during earth faults).
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 51/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
The current is assumed to be sufficiently symmetrical if both the zero sequence as well as the negative
sequence current are below the settable threshold FFM I< (max) (address 2912).
FFM U<max (3ph) (2913A): Maximum Voltage Threshold U< (3phase). In address 2913 FFM U<max
(3ph) the minimum voltage threshold is set. In present case, this parameter is set 15V.
FFM Idelta (3p) (2914A): Delta Current Threshold (3phase). If the measured voltage drops below this
threshold and a simultaneous current jump which exceeds the limits according to address 2914 FFM
Idelta (3p) is not detected while all three phase currents are greater than the minimum current required
for the impedance measurement by the distance protection according to address 1202 Minimum Iph>, a
• All 3 phase-to-earth voltages are smaller than the threshold FFM U<max (3ph) (address 2913),
• The current differential in all 3 phases is smaller than the threshold FFM Idelta (3p) (address 2914).
• All 3 phase current amplitudes are larger than the minimum current Iph> (address 1202) for
V-Supervision (2915): Voltage Failure Supervision. In address 2915 V-Supervision, the measured
voltage supervision can be switched to w/ CURR.SUP, w/ I> & CBaux or OFF. In present case, this
T V-Supervision (2916A): Delay Voltage Failure Supervision. Address 2916 T V-Supervision is used to
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 52/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
FCT EarthFltO/C (3101): Earth Fault overcurrent function. Parameter 3101 FCT EarthFltO/C can be
used to switch the earth fault protection ON or OFF. This refers to all stages of the earth fault
protection. If not required, each of the four stages can be deactivated by setting its MODE... to Inactive.
BLOCK for Dist. (3102): Block E/F for Distance protection. The earth fault protection can be blocked
by the distance protection to give preference to the selective fault clearance by the distance protection
over tripping by the earth fault protection. In address 3102 BLOCK for Dist. it is determined whether
blocking is performed during each fault detection of the distance protection (every PICKUP) or only
during single-phase fault detection by the distance protection (1phase PICKUP) or only during multiple-
phase fault detection by the distance protection (multiph. PICKUP). If blocking is not desired, set NO.
BLK for DisZone (3174): Block E/F for Distance Protection Pickup. It is also possible to block the
earth fault protection trip only for pickup of the distance protection on the protected line section. To
block the earth fault protection for faults occurring within zone Z1, set address 3174 BLK for DisZone to
in zone Z1. To block the earth fault protection for faults occurring within zone Z1 or Z1B, set address
3174 BLK for DisZone to in zone Z1/Z1B. If, however, blocking of the earth fault protection by the
distance protection is to take effect regardless of the fault location, set address 3174 BLK for DisZone
to in each zone.
Address 3102 thus refers to the fault type and address 3174 to the fault location. The two blocking
options create an AND condition. To block the earth fault protection only for single-phase faults
occurring in zone Z1, set address 3102 BLOCK for Dist. = 1phase PICKUP and 3174 BLK for DisZone
= in zone Z1. To block the earth fault protection for any fault type (any distance protection pickup)
occurring within zone Z1, the setting 3102 BLOCK for Dist. = every PICKUP and 3174 BLK for DisZone
= in zone Z1 applies.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 53/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
BLOCK 1pDeadTim (3103): Block E/F for 1pole Dead time. Setting parameter 3103 BLOCK
1pDeadTim to YES completely blocks the earth fault protection if the Open Pole Detector has
recognized a single-pole dead time. If no single-pole tripping is carried out in the protected network, this
Regardless of how parameter address 3103 BLOCK 1pDeadTim is set, the earth fault protection will
always be blocked during the single-pole dead time, if it has issued a trip command itself. This is
necessary because otherwise the picked up earth fault protection cannot drop out if the fault current
Iph-STAB. Slope (3104A): Stabilisation Slope with Iphase. Asymmetrical load conditions in multiple-
earthed systems or different current transformer errors can result in a zero-sequence current. This zero-
sequence current could cause faulty pickup of the earth current stages if low pickup thresholds are set.
To avoid this, the earth current stages are stabilized by the phase current: as the phase currents
increase, the pickup thresholds are increased. The stabilization factor (= slope) can be changed with
Trip 1pole E/F (3109): Single pole trip with earth flt.prot. Address 3109 Trip 1pole E/F specifies that the
earth fault protection trips single-pole, provided that the faulted phase can be determined with certainty.
This address is only valid for devices that have the option to trip single-pole. If you are using single-pole
automatic reclosure, the setting YES (default setting) remains valid. Otherwise set NO.
2nd InrushRest (3170): 2nd harmonic ratio for inrush restraint. For the recognition of the inrush
current, the portion of second harmonic current content referred to the fundamental current component
can be set in address 3170 2nd InrushRest. Above this threshold the inrush blocking is effective. The
Hence in present case, this parameter is left with the default value of 15%.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 54/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
feeders or lines that are terminated on transformers it may be assumed that, if very large currents
occur, a short-circuit has occurred before the transformer. In the event of such large currents, the inrush
restraint is inhibited. This threshold value which is set in the address 3171 Imax InrushRest, should be
In present case, this parameter is also left with the default value of 7.5A.
SOTF Op. Mode (3172): Instantaneous mode after SwitchOnToFault. With the parameter SOTF Op.
Mode (address 3172) it is finally possible to determine whether the fault direction must be checked
setting for each stage that applies for this direction check.
SOTF Time DELAY (3173): Trip time delay after SOTF. To avoid a spurious pickup due to transient
overcurrents, the delay SOTF Time DELAY (address 3173) can be set. Usually, the default setting 0
can be retained. In the case of long cables, where large peak inrush currents can occur, a short delay
may be useful.
Hence in present case, this parameter is left with the default value of 0s.
Op. mode 3I0> (3130): 3130 Operating mode. First of all, the mode for each stage is set: address 3110
Op. mode 3I0>>>, address 3120 Op. mode 3I0>> and address 3130 Op. mode 3I0>. Each stage can
be set to operate Forward (usually towards line), Reverse (usually towards busbar) or Non-Directional
(in both directions). If a single stage is not required, set its mode to Inactive.
3I0> (3131): 3I0> Pickup. Pickup value for earth fault protection. In present case, this parameter is set
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 55/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
3I0p Time Dial (3143): Calculations for this parameter are given in Main-I relay setting calculations. By
3I0> Telep/BI (3133): Instantaneous trip via Teleprot./BI. For the 3I0> stage this means that address
3133 3I0> Telep/BI is set to YES. The time delay T 3I0> set for this stage (address 3132) then functions
3I0> SOTF-Trip (3134): Instantaneous trip after SwitchOnToFault. It is possible to determine with a
setting which stage trips without delay following closure onto a dead fault. 3I0> SOTF-Trip (address
3134) stage can be set to YES or NO for this purpose. In present case, this parameter is set to YES.
3I0> InrushBlk (3135): Inrush Blocking. To enable this feature, in present case, this parameter is set to
YES.
IEC Curve (3151): To match with the Main-I relay settings, this parameter is set to Normal Inverse in
present case.
FCT Telep. Dis. (2101): Teleprotection for Distance protection. At address 2101 FCT Telep. Dis. the
use of a teleprotection scheme can be turned ON or OFF. Possible selection options for this parameter
are ON, PUTT (Z1B), POTT, OFF. In present case, this parameter is set to POTT, since protected line
is short in length.
Type of Line (2102): If the teleprotection has to be applied to a three terminal line the setting in
address 2102 must be Type of Line = Three terminals, if not, the setting remains Two Terminals. In
Send Prolong. (2103A): Time for send signal prolongation. The send signal prolongation Send
Prolong. (address 2103) must ensure that the send signal reliably reaches the opposite line end, even if
there is very fast tripping at the sending line end and/or the signal transmission time is relatively long. In
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 56/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
the case of the permissive overreaching schemes POTT and UNBLOCKING this signal prolongation
time is only effective if the device has already issued a trip command. In present case, this parameter is
set to 0.05s.
DIS TRANSBLK EF (2112A): DIS transient block by EF. Where the teleprotection schemes of the
distance protection and earth fault protection share the same channel, DIS TRANSBLK EF (address
2112) should be set to YES. In present case, this parameter is set to NO.
FCT Direct Trip (2201): Direct Transfer Trip (DTT). A prerequisite for the application of the direct and
remote tripping functions is that during the configuration of the scope of functions in address 122 DTT
Direct Trip = Enabled was applied. At address 2201 FCT Direct Trip it can also be switched ON or OFF.
Trip Time DELAY (2202): Trip Time Delay. It is possible to set a trip delay for both the local external
trip and the receive side of the remote trip in address 2202 Trip Time DELAY. This can be used as a
security time margin, especially in the case of local trip. In present case, this parameter is set to 0.01s.
Uph-e>(>) (3701): Operating mode Uph-e overvoltage prot. The phase voltage stages can be switched
ON or OFF in address 3701 Uph-e>(>). In addition to this, you can set Alarm Only, i.e. these stages
operate and send alarms but do not generate any trip command. The setting U>Alarm U>>Trip creates
in addition also a trip command only for the U>> stage. In present case, this parameter is set to ON.
Uph-e> (3702): Uph-e> Pickup. To match with the Main-I relay settings, this parameter is set to
T Uph-e> (3703): T Uph-e> Time Delay. To match with the Main-I relay settings, this parameter is set
to 5s in present case.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 57/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Uph-e>> (3704): Uph-e>> Pickup. To match with the Main-I relay settings, this parameter is set to
T Uph-e>> (3705): T Uph-e>> Time Delay. To match with the Main-I relay settings, this parameter is
Uph-e>(>) RESET (3709A): Uph-e>(>) Reset ratio. Reset ratio is set to 0.98 in present case.
Fast simultaneous tripping of the breakers at both ends of a faulty line is essential for successful auto-
Some protections start auto-reclosing and others block. Protections which start A/R are Main-I and
— O/V Protection
— Busbar Protection
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 58/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
When a reclosing relay receives start and block A/R impulse simultaneously, block signal dominates.
Similarly, if it receives 'start' for 1-phase fault immediately followed by multi-phase fault the later one
Operation: If it is set ON, Autorecloser will be ON always but initiation is required to START input from
trip relay to start the timers in Autorecloser. If External ctrl is selected, on or off of Autorecloser function
will be using an external switch via IO or communication ports. In present case, this parameter is set to
ON.
ARMode: This parameter is set to 1/2ph in present case. If 2 phase fault occurs, it is converted to 3-ph
3 phase: If 3 phase is selected, Autorecloser all shots will be 3-ph for all faults.
1/2/3ph: If 1/2/3ph is selected, Autorecloser first shot will be 1ph for 1ph fault, 2-ph for 2-ph fault and 3-
ph for 3-ph fault. If first shot fails, next shots will be 3-ph for all faults.
1/2ph: If 1/2ph is selected, Autorecloser will be 1ph for 1ph fault and 2-ph for 2-ph fault. For 3-ph faults,
Autorecloser will not work and it will not close the breaker after dead time. If first shot fails, next shots
TR2P and TR3P inputs required if 2ph and 3ph Autorecloser is needed.
1ph+1*2ph: If 1ph+1*2ph is selected, Autorecloser first shot will be 1ph for 1ph fault and 2-ph for 2-ph.
If first shot fails, next shots will be 3-ph for 1ph faults. For 2ph faults, first shot will be 2ph and no next
shots, only 3ph trip, if it fails. For 3ph fault, Autorecloser will not work and it will not close the breaker
If 1ph fault occurred, Autorecloser will go for 1ph reclose after a 1ph trip. If Autorecloser fails to close, it
will go for 3ph trip and next Autorecloser will 3ph and it will continue based on no of shots setting.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 59/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
If 2ph fault occurred, Autorecloser will go for 2ph reclose after a 2ph trip. If Autorecloser fails to close, it
will go for 3ph trip and there will not be next Autorecloser cycle even if set more number of shots in
setting.
1/2ph+1*3ph: If 1ph+1*3ph is selected, Autorecloser first shot will be 1ph for 1ph fault, 2-ph for 2-ph
fault and 3-ph for 3-ph fault. If first shot fails, next shots will be 3-ph for 1ph and 2ph faults. For 3ph
faults, first shot will be 3ph and no next shots, only 3ph trip.
1ph+1*2/3ph: If 1ph+1*2/3ph is selected, Autorecloser first shot will be 1ph for 1ph fault, 2-ph for 2-ph
fault and 3-ph for 3-ph fault. If first shot fails, next shots will be 3-ph only for 1ph. For 2ph or 3ph faults,
first shot will be 2ph or 3ph respectively and no next shots, only 3ph trip.
t1 1ph, t1 2ph and t1 3ph are the first shot dead times for 1ph, 2ph and 3ph faults. t1 2ph and t1 3ph
t2 3Ph, t3 3Ph, t4 3Ph and t5 3Ph are not applicable if NoOfShots is set to 1.
Single phase dead time of 1.0 s. is recommended for both 400 kV and 220 kV systems.
t1 3PhHS: This timer is applicable if STARTHS input is used. This can be used where tripping by
different protection stages is needed. For this case, dead timer shall be normally in the range of 400ms.
This is a high speed auto recloser without synchrocheck. Hence this should be set to a low value. It
may be used when one wants to use two different dead times in different protection trip operations. This
input starts the dead time t1 3PhHS. This parameter is not applicable in present case.
tReclaim: After closing command to breaker, this timer will start, if fault occurred during this timer, auto
recloser will go for second shot or will issue 3ph trip based on setting.
According to IEC Publication 56.2, a breaker must be capable of withstanding the following operating
0 + 0.3 s + CO + 3 min + CO
The recommended operating cycle at 400 kV and 220 kV is as per the IEC standard. Therefore, reclaim
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 60/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
tSync: Maximum time for Synchro check condition to be fulfilled (Not applicable for 1-ph A/R). This is
tTrip: If trip command and start auto-reclosing signal persist for more than tTrip time, Autorecloser will
be either blocked or extend the auto-reclosing dead time based on Extended t1 setting. It will block if
Extended t1=OFF and it will extend auto-reclosing dead time if Extended t1=ON. A trip pulse longer
At a setting somewhat longer than the auto-reclosing open time, this facility will not influence the
tPulse: It is just closing pulse width of CB closing command from Autorecloser. This parameter in
tCBClosedMin: If either main or tie CB is kept open prior to the occurrence of fault, the Autoreclose
Setting tCBClosedMin is the minimum time the CB shall be kept closed prior to occurrence of a fault to
get an AR attempt. If the CB has not been closed for at least this minimum time, a reclosing start will
tUnsucCl: CB check time before unsuccessful alarm. Normally the signal UNSUCCL appears when a
new trip and start is received after the last reclosing shot has been made and the auto-reclosing
function is blocked.
The signal resets once the reclaim time has elapsed. The “unsuccessful” signal can also be made to
depend on CB position input. The parameter UnsucClByCBChk should then be set to CBCheck, and a
timer tUnsucCl should also be set. If the CB does not respond to the closing command and does not
close, but remains open, the output UNSUCCL becomes high after time tUnsucCl.
The Unsuccessful output can for example, be used in Multi-Breaker arrangement to cancel the auto-
reclosing function for the second breaker, if the first breaker closed onto a persistent fault. It can also be
used to generate a Lock-out of manual closing until the operator has reset the Lock-out. Normally this
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 61/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
Priority: In a multi-C.B. arrangement one C.B. can be taken out of operation and the line still be kept in
service. After a line fault, only those C.Bs which were closed before the fault shall be reclosed.
the breakers in case of a permanent fault. This will help in avoiding unnecessary wear and tear. In this
case, the breaker selected as priority High is reclosed first and only if it is successful, the other breaker
A natural priority is that the C.B. near the busbar is reclosed first. In case of faults on two lines on both
sides of a tie C.B. the tie C.B. is reclosed after the outer C.Bs. The outer C.Bs. do not need a prioriting
In a single breaker arrangement the setting is Priority = None. In a multi-breaker arrangement the
setting for the first CB, the Master, is Priority = High and for the other CB Priority = Low.
While the reclosing of the master is in progress, it issues the signal WFMASTER.
A reset delay of one second ensures that the WAIT signal is kept high for the duration of the breaker
closing time. In the slave unit, the signal WAIT holds back a reclosing operation. When the WAIT signal
is reset at the time of a successful reclosing of the first CB, the slave unit is released to continue the
reclosing sequence.
tWaitForMaster: Setting of the maximum wait time for Master to be ready. In single CB applications,
one sets Priority = None. At sequential reclosing the function of the first CB, e.g. near the busbar, is set
Priority = High and for the second CB Priority = Low. The maximum waiting time, tWaitForMaster of the
second CB is set longer than the “auto-reclosing open time” and a margin for synchrocheck at the first
Whenever Zone1 Trips TIE CB as well as BUS CB Opens and First Dead time of Main CB starts and in
the mean time tWaitForMaster (TIE CB) starts elapsing. If WFMASTER does not deactivate with in
tWaitForMaster then TIE CB AR get deactivated. If WFMASTER deactivate before tWaitForMaster then
TIE CB Dead Time starts and at the end of Dead time TIE CB Reclose will happen.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 62/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
NoOfShots: The maximum number of reclosing shots in an auto-reclosing cycle is selected by the
CB position Open instead of from protection trip signals, one has to configure the CB Open position
signal to inputs CBPOS and START and set a parameter StartByCBOpen = On and CBAuxContType =
NormClosed (normally closed). One also has to configure and connect signals from manual trip
CBAuxContType: Select the type of contact used for the CB Position input.
connected to inputs CBPOS and START. When the signal changes from “CB closed” to “CB open”, an
auto-reclosing start pulse is generated and latched in the function, subject to the usual checks. Here it
needs to be set whether NC or NO auxiliary contact of the CB is connected to the relay. Normally NO
contact is used.
CBReadyType: The selection depends on the type of performance available from the CB operating
gear. At setting OCO (CB ready for an Open – Close – Open cycle), the condition is checked only at the
start of the reclosing cycle. The signal will disappear after tripping, but the CB will still be able to
perform the C-O sequence. For the selection CO (CB ready for a Close – Open cycle) the condition is
also checked after the set auto-reclosing dead time. This selection has a value first of all at multishot
reclosing to ensure that the CB is ready for a C-O sequence at shot 2 and further shots. During single-
shot reclosing, the OCO selection can be used. A breaker shall according to its duty cycle always have
storing energy for a CO operation after the first trip. (IEC 56 duty cycle is O-0.3s CO-3minCO).
Extended t1: Extended t1 for PLC failure activated or not. An auto-reclosing open time extension
delay, tExtended t1, can be added to the normal shot 1 delay. It is intended to come into use if the
communication channel for permissive line protection is lost. In such a case there can be a significant
time difference in fault clearance at the two ends of the line. A longer “auto-reclosing open time” can
then be useful. This extension time is controlled by setting parameter Extended t1=On and the input
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 63/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
PLCLOST. Typical setting in such a case: Extended t1 = On and tExtended t1 = 0.8 s. In present case
tInhibit: A typical setting is tInhibit = 5.0s to ensure reliable interruption and temporary blocking of the
function. Function will be blocked during this time after the tinhibit has been activated.
CutPulse: The CB closing command, CLOSECB is given as a pulse with a duration set by parameter
tPulse. For circuit-breakers without an anti-pumping function, close pulse cutting can be used. It is
selected by parameter CutPulse=On. In case of a new trip pulse (start), the closing command pulse is
then cut (interrupted). The minimum closing pulse length is always 50 ms.
If CB is with anti-pumping relay, this CutPulse can be set OFF. In present case, this parameter is set to
OFF.
Follow CB: Select if the multi-shot cycle to advance to next shot at a new fault if CB has been closed
during dead time. The usual setting is Follow CB = Off. The setting On can be used for delayed
reclosing with long delay, to cover the case when a CB is being manually closed during the “auto-
reclosing open time” before the auto-reclosing function has issued its CB closing command.
AutoCont: Setting of the operating mode for next AR attempt (continue if CB does not close). This is
applicable only if multi-shots are selected. The normal setting is AutoCont = Off.
UnsucClByCBChk: Setting of the signal mode at Unsuccessful reclosing. The “unsuccessful” signal
can also be made to depend on CB position input using UnsucClByCBChk setting. 3ph trip is issued if
breaker has not been closed even if there is no trip output from distance relay.
BlockByUnsucCl: Blocking of the Auto reclose program at unsuccessful auto reclosing. If this is made
ON, Autorecloser will be blocked for unsuccessful Autorecloser and it must be unblocked by using the
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 64/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
SelPhaseBus1: Setting of the input phase for Bus 1 voltage reference. This parameter has to be set
based on the corresponding phase PT/CVT input connected to this function. Present case, this
SelPhaseLine1: Setting of the phase or line 1 voltage measurement. This parameter has to be set
based on the corresponding phase PT/CVT input connected to this function. Present case, this
SelPhaseBus2: Setting of the input phase for Bus 2 voltage reference (used in multi breaker schemes
only). This parameter has to be set based on the corresponding phase PT/CVT input connected to this
SelPhaseLine2: Setting of the phase or line 2 voltage reference (used in multi breaker schemes only).
This parameter has to be set based on the corresponding phase PT/CVT input connected to this
UBase: Setting of the Base voltage level on which the voltage settings are based. This parameter is set
PhaseShift: This setting is used to compensate for a phase shift caused by a transformer between the
two measurement points for bus voltage and line voltage, or by a use of different voltages as a
reference for the bus and line voltages. The set value is added to the measured line phase angle. The
bus voltage is the reference voltage. This parameter is set to 0° in present case.
URatio: The URatio is defined as URatio = bus voltage/line voltage. This setting scales up the line
voltage to an equal level with the bus voltage. This parameter is set to 1 in present case.
CBConfig: Set available bus configuration here if external PT selection for sync is not available. If No
voltage sel. is set, the default voltages used will be U-Line1 and U-Bus1. This is also the case when
external voltage selection is provided. Fuse failure supervision for the used inputs must also be
connected. In present case this parameter is set to No voltage. Kindly adjust this parameter if voltage
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 65/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
To allow closing of breakers between asynchronous networks a synchronizing function is provided. The
systems are defined to be asynchronous when the frequency difference between bus and line is larger
OperationSC: This decides whether Synchrocheck function is OFF or ON. In present case this
UHighBusSC and UHighLineSC: Set the operating level for the Bus high voltage and Line high
voltage at Line synchronism check. The voltage level settings must be chosen in relation to the bus or
line network voltage. The threshold voltages UHighBusSC and UHighLineSC have to be set lower than
the value at which the breaker is expected to close with the synchronism check. A typical value can be
UDiffSC: Setting of the allowed voltage difference for Manual and Auto synchronism check. The setting
for voltage difference between line and bus in p.u, defined as (U-Bus/ UBaseBus) - (U-
FreqDiffM and FreqDiffA: The frequency difference level settings for Manual and Auto sync. A typical
value for FreqDiffM can be100mHz for a connected system, and a typical value for FreqDiffA can be
PhaseDiffM and PhaseDiffA: The phase angle difference level settings for Manual and Auto sync.
PhaseDiffM is normally recommended to set 30°. PhaseDiffA is also set to 30° in present case.
tSCM and tSCA: Setting of the time delay for Manual and Auto synchronism check. Circuit breaker
closing is thus not permitted until the synchrocheck situation has remained constant throughout the set
delay setting time. Typical values for tSCM and tSCA can be 0.1s.
Auto related settings are applicable since this function block is used for 3-ph Autorecloser operation
AutoEnerg and ManEnerg: Setting of the energizing check directions to be activated for AutoEnerg.
Setting of the manual Dead line/bus and Dead/Dead switching conditions to be allowed for ManEnerg.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 66/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
DLLB, Dead Line Live Bus, the line voltage is below set value of ULowLineEnerg and the bus voltage is
above set value of UHighBusEnerg. DBLL, Dead Bus Live Line, the bus voltage is below set value of
AutoEnerg and ManEnerg are set to Both of the above DLLB, DBLL.
ManEnergDBDL: This need to be made OFF to avoid manual closing of the breaker if both Bus and
UHighBusEnerg and UHighLineEnerg: Set the operating level for the Bus high voltage at Line
energizing for UHighBusEnerg. Set the operating level for the Line high voltage at Bus energizing for
UHighLineEnerg.
The threshold voltages UHighBusEnerg and UHighLineEnerg have to be set lower than the value at
which the network is considered to be energized. A typical value can be 80% of the base voltages. If
system voltages are above the set values here, relay will consider it as Live condition.
ULowBusEnerg and ULowLineEnerg: Setting of the operating voltage level for the low Bus voltage
level at Bus energizing for ULowBusEnerg. Setting of the operating voltage level for the low line voltage
The threshold voltages ULowBusEnerg and ULowLineEnerg, have to be set to a value greater than the
value where the network is considered not to be energized. A typical value can be 40% of the base
voltages. If system voltages are below the set values here, relay will consider it as Dead condition.
UMaxEnerg: Setting of the maximum live voltage level at which energizing is allowed. This setting is
used to block the closing when the voltage on the live side is above the set value of UMaxEnerg. In
tAutoEnerg and tManEnerg: Set the time delay for the Auto Energizing and Manual Energizing. The
purpose of the timer delay settings, tAutoEnerg and tManEnerg, is to ensure that the dead side remains
de-energized and that the condition is not due to a temporary interference. If the conditions do not
persist for the specified time, the delay timer is reset and the procedure is restarted when the conditions
are fulfilled again. Circuit breaker closing is thus not permitted until the energizing condition has
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 67/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
220kV Phojal Line-IN Protection Relay Setting Calculations, HPPTCL
remained constant throughout the set delay setting time. Normally tManEnerg and tAutoEnerg are
OperationSynch: Operation for synchronizing function Off/ On. This parameter is recommended to set
OFF.
tBreaker, tMinSynch and tMaxSynch: These parameters are not applicable if OperationSynch is set
to OFF.
Description
220kV Phojal Line-IN Protection Relay Setting
Reviewed By RK
Calculations, HPPTCL
Order Ref Rev Sheet
Prepared by Nadeem
3100048543 01 68/68
Issued by Dept. Yr. Wk Doc. No. Yr. Wk
INPS-SAS 14 49 YN1M302203-ZAA 16 22
REL670 Settings-Main-I
REL670 Analog Input Settings-Main-I
Line Distance Protection, 21L-Main-I
Phase Selection and Load encroachment Settings-Main-I
Directional Impedance Settings-Main-I
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
MLFB: 7SA52216DB904QR4
Parameter set version: V04.70.07
Device path: C:\Data\Relay settings\HPPTCL-PHOZAL\from SAS\7SA522
\HPPTCL_P\P7DI\GV\SD\00000014
Author:
Creation date: 12.02.14 16:24:03
Last modified: 26.05.16 15:17:15
Operating mode: Offline
Comment:
Setting values in: Secondary value description
PRINT - CONTENTS
1 Device Configuration ...................................................................................................................................................… 3
2 Power System Data 1 ..................................................................................................................................................... 4
2.1 Group Power System Data 1; Group Transformers ....................................................................................................… 4
2.2 Group Power System Data 1; Group Power System ..................................................................................................… 4
2.3 Group Power System Data 1; Group Breaker .............................................................................................................… 4
3 Settings groups ...........................................................................................................................................................… 5
3.1 Group Power System Data 2; Group Power System ..................................................................................................… 5
3.2 Group Power System Data 2; Group Line Status ........................................................................................................... 5
3.3 Group Power System Data 2; Group Trip 1-/3-pole ....................................................................................................… 6
3.4 Group Distance protection, general settings; Group General .....................................................................................… 6
3.5 Group Distance protection, general settings; Group Earth faults ...............................................................................… 6
3.6 Group Distance protection, general settings; Group Time Delays ..............................................................................… 7
3.7 Group Distance zones (quadrilateral); Group Zone Z1 ...............................................................................................… 7
3.8 Group Distance zones (quadrilateral); Group Zone Z1B-exten. .................................................................................… 7
3.9 Group Distance zones (quadrilateral); Group Zone Z2 ...............................................................................................… 8
3.10 Group Distance zones (quadrilateral); Group Zone Z3 ...............................................................................................… 8
3.11 Group Distance zones (quadrilateral); Group Zone Z4 ...............................................................................................… 8
3.12 Group Distance zones (quadrilateral); Group Zone Z5 ...............................................................................................… 9
3.13 Group Distance zones (quadrilateral); Group Zone Z6 ...............................................................................................… 9
3.14 Group Power Swing ....................................................................................................................................................… 9
3.15 Group Teleprotection for Distance prot. ....................................................................................................................… 10
3.16 Group DTT Direct Transfer Trip ................................................................................................................................… 10
3.17 Group Instantaneous HighSpeed SOTF Overcurrent ...............................................................................................… 10
3.18 Group Weak Infeed (Trip and/or Echo) .....................................................................................................................… 10
3.19 Group Measurement Supervision; Group Balance / Summ. .....................................................................................… 11
3.20 Group Measurement Supervision; Group Fuse Fail. Mon. .......................................................................................… 11
3.21 Group Measurement Supervision; Group VT mcb ....................................................................................................… 12
3.22 Group Measurement Supervision; Group Load Angle ..............................................................................................… 12
3.23 Group Earth fault overcurrent; Group General ..........................................................................................................… 12
3.24 Group Earth fault overcurrent; Group 3I0>>> ............................................................................................................... 13
3.25 Group Earth fault overcurrent; Group 3I0>> ................................................................................................................. 13
3.26 Group Earth fault overcurrent; Group 3I0> ...............................................................................................................… 13
Page 1 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 2 of 17
Device Configuration Settings
AA1D1Q01FP2_prn
Device Configuration
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
1 Device Configuration
Page 3 of 17
Power System Data
AA1D1Q01FP2_prn
Power System Data 1
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 4 of 17
AA1D1Q01FP2_prn
Settings groups
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
3 Settings groups
Page 5 of 17
AA1D1Q01FP2_prn
Group Power System Data 2; Group Trip 1-/3-pole
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 6 of 17
AA1D1Q01FP2_prn
Group Distance protection, general settings; Group Time Delays
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 7 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 8 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 9 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 10 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 11 of 17
AA1D1Q01FP2_prn
Group Measurement Supervision; Group VT mcb
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 12 of 17
AA1D1Q01FP2_prn
Group Earth fault overcurrent; Group 3I0>>>
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 13 of 17
AA1D1Q01FP2_prn
Group Earth fault overcurrent; Group 3I0 InverseTime
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 14 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 15 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 16 of 17
AA1D1Q01FP2_prn
HPPTCL_Phozal / C1 / Q01 /
SIMATIC AA1D1Q01FP2/7SA522 26.05.16 15:30:51
Page 17 of 17
REC670 Settings
REC670 Analog Input Settings
Autorecloser Settings, 79
Synchrocheck Settings, 25